APPLICATION GUIDELINES FOR COPELAND COMPLIANT SCROLL COMPRESSORS (ZR*1 Models)

Similar documents
Application Guidelines for Glacier K3 Copeland Scroll Refrigeration Compressors

Application Engineering

Application Guidelines for Low Temperature ZF**KAE 1-2.5HP Copeland Scroll Refrigeration Compressors

September 2016 AE Application Guidelines for Copeland CS**KIE Compressors in Ice Machines AE4-1421

LIQUID REFRIGERANT CONTROL IN REFRIGERATION AND AIR CONDITIONING SYSTEMS

A Series Inertia Compressor Applications. Application Bulletin 115

H29A Series Compressor Applications. Application Bulletin 139

Application Guidelines for ZS**KAE Refrigeration Copeland Scroll Compressors HP

AE ZJ36 to ZJ54KHE R410A Copeland Scroll Compressors

Application Engineering

7 to 15 Ton ZR*KC and ZP*KC Copeland Scroll Compressors

AE R9. AE R9 May Application Guidelines For K4 Refrigeration Copeland Scroll Compressors Horsepower

AE R17 November 2016

KITS COMMON TO HEATING AND COOLING EQUIPMENT 504,652M 03/04. Supersedes 503,249M

AE Application Guidelines for Refrigeration Copeland Discus Compressors with R-410A

Application Guidelines. Scroll Compressors for Air Conditioning ZR18K* to ZR380K*, ZP24K* to ZP485K*

Scroll compressors with vapour injection for Dedicated Heat Pumps. ZH13 KVE & ZH18 KVE Application Guidelines

Contour TM Screw Compressors

AE R1 October to 5 Ton ZPS*K6 Copeland Scroll Two-Stage Compressors

User s Information and Installation Instructions

Scroll Compressors for Heat Pump Applications ZH12K4E to ZH11M4E, ZH06KVE to ZH48KVE

Digital Scroll Compressors for Air Conditioning

Application Guidelines for ZB*KC/ZB*KCE Copeland Scroll Refrigeration Compressors 7 to 15 HP

AE R3. July 2016 AE R3. Replaces AE CR KQ, CR K6, CR_5, CR K7 Hermetic Reciprocating Compressors

2 shp 13 lc 1 36 t - 1 a

AIR TO AIR HEAT PUMP SYSTEM DESIGN

Nominal Capacity 024 = 7 kw (2 tons) 036 = 10.5 kw (3 tons) 048 = 14 kw (4 tons) 060 = 17.5 kw (5 tons)

500 EX Fusion Compressor Series

Application Guidelines

User s Information and Installation Instructions

INTRODUCTION. Special Applications of Package Air Conditioners. Instant Cooling Requirement in Wedding Ceremonies

Liebert Small System MCD and PFH Condensers (1-5 Ton) Warranty Inspection Check Sheet

AE R21 September 2017

APPROVAL SHEET SPECIFICATIONS OF HERMETIC SCROLL COMPRESSOR C-SBR180H16A

Condensing Unit Installation and Operating Instructions

Condensing Unit Installation and Operating Instructions

Bulletin , March Electric Hot Gas Bypass Valves

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2)

3 to 5 Tons. AIR CONDITIONERS 2scu13. Dry Charge Split System - 60 HZ PRODUCT SPECIFICATIONS. 2 scu 13 lc 1 36 t - 1 a MODEL NUMBER IDENTIFICATION

Application Guidelines. Copeland Scroll Summit Series ZB50KCE to ZB114KCE & ZB66K5E to ZB114K5E ZF25K5E to ZF49K5E

Refrigeration Scroll Enhanced Vapour Injection

HS25 SERVICE UNIT INFORMATION

30GT FLOTRONIC AIR-COOLED CHILLERS

SECTION ROTARY-SCREW WATER CHILLERS

AE R1 Application Guidelines for ZB*KAU Copeland R-290. August Scroll Compressors

AE October 1965 Reformatted October Hot Gas Bypass Control Systems

072, 090, 120, 180 & 240 MODELS C SERIES CONDENSING UNITS P SERIES HEAT PUMPS

Scroll compressors with vapour injection for Dedicated Heat Pumps. ZH24 KVE to ZH48 KVE Application Guidelines

PDF Created with deskpdf PDF Writer - Trial ::

SECTION AIR COOLED WATER CHILLERS

30GN FLOTRONIC II AIR-COOLED CHILLERS

A Design for True Performance and Energy Savings In Refrigerated Compressed Air Dryers The Digital Scroll Dryer

Installation Instructions

AIR COOLED PACKAGED CHILLER

Digital. Application Guidelines Digital Scroll Compressors for Refrigeration ZBD21K* to ZBD114K* ZFD13KVE to ZFD25KVE ZFD41K5E

Calhoon MEBA Engineering School. Study Guide for Proficiency Testing Refrigeration

Refrigeration Systems and Accessories

Corp L9 Revised HS27 SERIES UNITS SPECIFICATIONS. Model No. HS HS HS HS27-042

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION

Service Step by Step Trouble-Shooting Check-List

MACH N-407 Heat Pump Air-Cooled Chiller

Commercial High-Efficiency Condensing Units

.2 Section Waste Management and Disposal.

Installation Instructions

Table of Contents. Service Procedures. Service Procedures. Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8)

User s Information and Installation Instructions

4201 Lien Rd Madison, WI Owner s Manual Therma-Stor III Heat Recovery System. Installation, Operation & Service Instructions

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

ORTEC HIGH CAPACITY REFRIGERATED AIR/GAS DRYERS

HNC-120BE-L/R-B HNC-150BE-L/R-B HNC-180BE-L/R-B HNC-210BE-L/R-B COUNTER SHOWCASE MODEL SERVICE MANUAL HOSHIZAKI

SECTION WATER-SOURCE UNITARY HEAT PUMPS

The Digital Scroll Dryer

Visit us at For the latest technical information,

Electrical Problems. Fuse(s) blow or circuit breaker trips. Does the unit use circuit breakers or fuses? Replace with correct fuse(s)

Operation and Maintenance Manual

RecoverX Oil-Filled Hermetic Refrigerant Recovery System. Operation and Maintenance Manual

Danfoss scroll compressors SH- In parallel installation

Danfoss scroll compressors SH - In parallel installation

LONG LINE SET APPLICATION R-410A

Danfoss Scroll for Refrigeration MLM / MLZ

A AD Oil burners fuel unit. deltapumps.com. DE A-AD_en_0709.pdf Page 1/1

Residential Piping and Long Line Guideline

AMERICAN EQUIPMENT SYSTEMS A Division Of Trevor-Martin Corporation th Terrace North Clearwater, Florida 33762

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

AE R8 March 2015

PACKAGE AIR CONDITIONER

November 2006 / BULLETIN ELECTRIC DISCHARGE BYPASS VALVES

User s Information/Installation Instructions

Catalog Air Cooled Split System Condensing Units for Rooftop Systems and Air Handlers

AIR CONDITIONING. Carrier Corporation 2002 Cat. No

DTW Works Master Specification Version 2006 Issued 2006/08/01 Section15621 Packaged Reciprocating Water Chillers Page 1 of 5

Installation Instructions

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

Sporlan Valve Division Parker Hannifan/CIC Group

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

Air-Cooled Split System Condensing Unit for Rooftop Systems and Air Handlers

MAKING MODERN LIVING POSSIBLE. Residential and light commercial scroll compressors Hz R-407C / R-22 / R-410A SELECTION & APPLICATION GUIDELINES

HP13 WARNING WARNING. Service Literature HP13 SERIES UNITS

Application Guidelines. Copeland Scroll Compressors for Refrigeration. ZB15K* to ZB220K*, ZS21K* to ZS11M* ZF06K* to ZF48K*, ZF13KVE to ZF48KVE

Transcription:

4-1280 Application Engineering Bulletin AE-1280R4 Revised April, 1995 APPLICATION GUIDELINES FOR COPELAND COMPLIANT SCROLL COMPRESSORS (ZR*1 Models) Introduction The Compliant Scroll Compressor has been under development at Copeland since 1979 and is the most efficient and durable compressor we have ever developed for residential air conditioning and heat pump applications. Compliant Scroll compressors have fewer moving parts and no dynamic suction or discharge valves. In addition, they offer very low vibration and sound levels and are very tolerant to stresses caused by liquid slugging, flooded starts, and debris commonly found in residential split air conditioning and heat pump systems. Application considerations for ZR*2/ZR*3 models are discussed in a separate bulletin. The operating principles of the Compliant Scroll are described in Figure 1. Application Considerations Since the Compliant Scroll is a new type of compressor, there are a number of application characteristics which are different from the traditional reciprocating compressor. These are detailed below. Accumulators Due to the Compliant Scroll s inherent ability to handle liquid refrigerant in flooded start and defrost cycle operation, no accumulator is required for durability below system charge levels listed in the Scroll Compressor Application Diagram (Figure 4). However, large volumes of liquid refrigerant which repeatedly flood back to the compressor during normal off cycles or excessive liquid refrigerant floodback during steady operation can dilute the oil in any compressor to the point that bearings are inadequately lubricated and wear may occur. To test for these conditions see the section entitled EXCESSIVE LIQUID REFRIGERANT FLOODBACK TESTS at the end of this Bulletin. Crankcase Heat Due to the Compliant Scroll s inherent ability to handle liquid refrigerant in flooded conditions, no crankcase heater is required. Reversing Valves Since Compliant Scroll compressors have very high volumetric efficiency, their displacements are lower than for comparable capacity reciprocating compressors. As a result, Copeland recommends that the capacity rating on reversing valves be no more than 1.5 to 2 times the nominal capacity of the compressor with which it will be used in order to ensure proper operation of the reversing valve under all operating conditions. The reversing valve solenoid should be wired so that the valve does not reverse when the system is shut off by the operating thermostat in the heating or cooling mode. If the valve is allowed to reverse at system shutoff, suction and discharge pressures are reversed to the compressor. This results in a condition of system pressures equalizing through the compressor, which can cause the compressor to slowly rotate until the pressures equalize. This condition does not affect compressor durability but can cause unexpected sound after the compressor is turned off. Discharge (Top Cap) Thermostat Internal discharge temperatures reached under some extreme operating conditions (such as loss of charge or extremely high compression ratio caused by failure of evaporator fan) can cause compressor damage. In order to guarantee positive compressor protection, a thermostat has been designed into the Compliant 1989 Copeland Corporation 1

Scroll which senses dangerous discharge temperature levels and removes power from the compressor until temperature levels are safe again. See Figure 2 for wiring details. The approximate thermostat cut-out/cutin temperatures are 290/140 F. THIS PROTECTIVE DEVICE SHOULD NEVER BE BYPASSED FOR ANY PURPOSE. The thermostat can be tested for proper operation by the following procedures: To check for low temperature operation, check electrical continuity with the thermostat below 140 F. If the thermostat shows open it should be replaced. To check for high temperature protection, the thermostat should remain closed for increasing discharge line temperatures up to 290 F. and then open as temperature rises above 290 F. If the thermostat is open when temperature is between 140 and 290 F., the thermostat will have to be allowed to cool to 140 F. to close before testing high temperature operation. If the thermostat opens below 290 F. with rising temperature it should be replaced. Should the Top Cap Thermostat fail please observe the following: 24 Volt Control Circuit See bulletin supplied with 998-0243-00, 24 volt Top Cap Thermostat replacement kit. 230 Volt Control Circuit Replace Top Cap Thermostat with a discharge line thermostat, Copeland P/N 995-0071-00. "DO NOT REPLACE THE TOP CAP THERMOSTAT IN THE COMPRESSOR ON 230 VOLT CONTROL CIRCUITS." Motor Protection Conventional inherent internal line break motor protection is provided. Oil Type Conventional white oil (Sontex 200 LT) is used in Copeland Compliant Scroll compressors. White oil is compatible with 3GS, and 3GS oil may be used if the addition of oil in the field is required. See Table 2 for field oil recharge values. Suction and Discharge Mufflers Flow through Compliant Scroll Compressors is continuous and has relatively low pulsations. External mufflers, where they are normally applied to piston compressors today, may not be required for Compliant Scroll. Because of variability between systems, however, individual system tests should be performed to verify acceptability of sound performance. Low Ambient Cut-Out Low ambient cut-outs are not required. Starting Characteristics No start assist devices are ever required, even if a system utilizes non-bleed expansion valves. Due to the inherent design of the Compliant Scroll, the internal compression components always start unloaded even if system pressures are not balanced. In addition, since internal compressor pressures are always balanced at startup, low voltage starting characteristics are excellent for Compliant Scroll compressors. Fusite The orientation of the pins on the Fusite for Compliant Scroll compressors is shown in Figure 3 and is also shown inside the terminal box. Deep Vacuum Operation CAUTION Earlier models of Compliant Scroll compressors with serial number date code of 91I or earlier could quickly achieve low vacuums if the suction side of the compressor was closed or severely restricted. This could cause arcing damage to the Fusite pins. Newer models incorporate internal low vacuum protection, and stop pumping (unload) when the pressure ratio exceeds approximately 10 to 1. Compliant Scroll Compressors (as with any refrigerant compressor) should never be used to evacuate a refrigeration or air conditioning system. (See Application Engineering Bulletin AE 24-1105 for proper system evacuation procedures). Nomenclature The model numbers of Compliant Scroll Compressors have been designed to include the nominal capacity at ARI operating conditions. Please refer to the product literature for details pertaining to other information contained in the model number. Shutoff Since the Compliant Scroll compressor is also an excellent gas expander, the compressor may run backwards for a very brief period at shutoff as the internal pressures equalize. A check valve in the discharge of the compressor prevents the compressor from running backwards for more than a second or two. This momentary reversal of direction of the scrolls has no effect on compressor durability and is entirely normal. Suction and Discharge Tubes Compliant Scroll Compressors have copper plated steel suction tubes. These tubes are far more rugged and less prone to leaks than copper tubes used on other 2

compressors. Due to the different thermal properties of steel and copper, brazing procedures may have to be changed from those commonly used. See Figure 5 for suggestions for assembly line and field brazing procedures. Brief Power Interruptions Brief power interruptions (less than ½ second) can result in powered reverse rotation of single phase compliant scroll compressors. This occurs as a result of the high pressure discharge gas expanding backwards through the scrolls at power interruption, causing the scroll to orbit in the reverse direction. If power is reapplied while reverse rotation is occurring, the compressor may continue to run noisily in the reverse direction for several minutes until the compressor s internal protector trips. This is no effect on durability. When the protector resets the compressor will start and run normally. To avoid the noise and loss of cooling resulting from powered reverse rotation Copeland strongly encourages use of an electronic control which can sense brief power interruptions and will lock the compressor out of operation for five minutes. This control could be incorporated in other system controls (such as defrost or thermostat), or be a stand alone control. Functional specifications for this control as well as a suggested wiring diagram are shown in Figure 2. Assembly Line System Charging Procedure Rapid charging only on the suction side of a scroll equipped system or condensing unit can occasionally result in a temporary no-start condition for the compressor. The reason for this is that if the flanks of the compressor happen to be in a sealed position, rapid pressurization of the low side without opposing high side pressure can cause the scrolls to seal axially. As a result, until the pressures eventually equalize, the scrolls can be held tightly together, preventing rotation. The best way to avoid this situation is to charge on both the high and low side simultaneously at a rate which does not result in axial loading of the scrolls. The maximum charging rate can be determined through simple tests. Unbrazing System Components If the refrigerant charge is removed from a scroll equipped unit by bleeding the high side only, it is sometimes possible for the scrolls to seal, preventing pressure equalization through the compressor. This may leave the low side shell and suction line tubing pressurized. If a brazing torch is then applied to the low side while the low side shell and suction line contains pressure, the pressurized refrigerant and oil mixture could ignite when it escapes and contacts the brazing flame. To prevent this occurrence, it is important to Copeland 4-1280 check both the high and low side with manifold gauges before unbrazing, or in the case of repairing a unit on an assembly line, bleed refrigerant from both the high and low side. Instructions should be provided in appropriate product literature and assembly (line repair) areas. Air Conditioning System Suction Line Noise and Vibration Copeland Compliant Scroll Compressors inherently have low sound and vibration characteristics. However, in some respects, the sound and vibration characteristics differ from reciprocating compressors and, in rare instances, could result in unexpected sound complaints. One difference is that the vibration characteristics of the scroll compressor, although low, includes two very close frequencies, one of which is normally isolated from the shell by the suspension of an internally suspended compressor. These frequencies, which are present in all compressors, may result in a low level beat frequency which can be detected as noise coming along the suction line into a house under some conditions. Elimination of the beat can be achieved by attenuating either of the contributing frequencies. This is easily done by using one of the common combinations of design configurations described in Table 3. A second difference of the Compliant Scroll is that under some conditions the normal starting motion of the compressor can transmit an impact noise along the suction line. This phenomenon, like the one described above, also results from the lack of internal suspension, and can be easily avoided by using standard suction line isolation techniques as described in Table 3. TABLE 3 Recommended Configuration Component Tubing configuration Service valve Suction muffler Alternate Configuration Component Tubing configuration Service valve Suction muffler Description *small shock loop * angled valve fastened to unit *not required Description *small shock loop * straight-through valve fastened to unit *may be required 3

The sound phenomena described above are not usually associated with heat pump systems because of the isolation and attenuation provided by the reversing valve and tubing bends. Hipot Testing Compliant Scroll Compressors are configured with the motor down and the pumping components at the top of the shell. As a result, the motor can be immersed in refrigerant to a greater extent than hermetic reciprocating compressors when liquid refrigerant is present in the shell. In this respect, the scroll is more like semihermetics (which have horizontal motors partially submerged in oil and refrigerant). When Compliant Scroll Compressors are Hipot tested with liquid refrigerant in the shell they can show higher levels of leakage current than compressors with the motor on top because of the higher electrical conductivity of liquid refrigerant than refrigerant vapor and oil. However, this phenomenon can occur with any compressor when the motor is immersed in refrigerant. The levels of current leakage should not present any safety issue. To lower the current leakage reading the system should be operated for a brief period of time to redistribute the refrigerant to a more normal configuration and the system Hipot tested again. Compliant Scroll Functional Check Since Compliant Scroll compressors do not have internal suction valves or dynamic discharge valves which can be damaged it is not necessary to perform functional compressor tests where the compressor is turned on with the suction service valve closed to check how low the compressor will pull suction pressure. In fact this type of test may actually damage a Compliant Scroll Compressor (and other types of compressors, also). (See DEEP VACUUM OPERATION CAUTION, above). Rather, the following diagnostic procedure should be used to evaluate whether a Compliant Scroll compressor is functioning properly. 1. Proper voltage to the unit should be verified. 2. If the compressor will not run, the discharge (top cap) thermostat should be checked for continuity to determine if it has opened and removed power from the compressor. If it is open, the compressor must be allowed to cool sufficiently to reset the thermostat. The normal checks of motor winding continuity and short to ground should be made to determine if the inherent internal overload motor protector has opened or if an internal short to ground has developed. If the protector has opened, the compressor must be allowed to cool sufficiently to allow it to reset. 3. Proper indoor and outdoor fan/blower operation should be verified. 4. With service gauges connected to suction and discharge pressure fittings, energize on the compressor. If suction pressure falls below normal levels the system is either low on charge or there is a flow blockage in the system. 5. If suction pressure does not drop and discharge pressure does not rise to normal levels either the reversing valve (if so equipped) or the compressor is faulty. Use normal diagnostic procedures to check operation of the reversing valve. 6. If the reversing valve (if so equipped) checks out satisfactorily, then the compressor current draw must be compared to published compressor performance curves at the compressor operating conditions (pressures and voltages) and significant deviations (+/-15%) from published values may indicate a faulty compressor. Excessive Liquid Floodback Tests The following test are for those system configurations and charge levels identified in Figure 4 which need special testing to verify exemption from need of an accumulator. To test for excessive continuous liquid refrigerant floodback, it is necessary to operate the system in a test room at conditions where steady state floodback may occur (low ambient heating operation). Thermocouples should be attached to the suction and discharge lines (approximately 6 inches from the shell) of the compressor and insulated. If the system is designed to be field charged it should be overcharged by 10 to 20% in this test to simulate overcharging commonly found in field installations. The system should be operated at an indoor temperature of 70 F. and outdoor temperature extremes (0 F. or lower in heating) which produce floodback conditions. The compressor suction and discharge pressures and temperatures should be recorded. The system should be allowed to frost up for several hours (disabling the defrost control and spraying water on the outdoor coil may be necessary) to cause the saturated suction temperature to fall to -20 F. or below. If the discharge line temperature is lower than 60 F. above saturated discharge temperature, then design changes must be made to reduce the amount of floodback or an accumulator must be used. For example, if discharge pressure is 168 PSIG (90 F.), then discharge temperature should be at least 150 F. (90 + 60 ). To test for repeated excessive liquid floodback during normal system off-cycles perform the Field Application Test. Obtain a sample compressor with a side sight tube to measure liquid level in the compressor. Set the system up in a configuration with the indoor 4

unit elevated several feet above the outdoor unit with twenty-five feet of connecting tubing with no traps between the indoor and outdoor units. If the system is designed to be field charged, the system should be overcharged by 10 to 20% in this test to simulate overcharging commonly found in field installations. Operate the system in the cooling mode at the outdoor Copeland 4-1280 ambients, on/off cycle times, and number of cycles specified in Table 1. Record the height of the liquid in the compressor at the start of each on cycle, any protector trips, or any compressor stalls during each test. Review the results with Copeland Application Engineering to determine if an accumulator is required for the application. Table 1 Field Application Test Operate the system as it would be operated in an actual field installation, cycling the unit on and off for the times indicated at each ambient. Outdoor Ambient ( F) 85 95 105 System On-Time (Minutes) 7 14 54 System Off-Time (Minutes) 13 8 6 Number of On/Off Cycles 5 5 4 Table 2 Field Oil Recharge Values Compressor Model No. Oil Recharge (Fl. Oz.) ZR18K1 20 ZR23K1 24 ZR28K1 24 ZR34K1 30 ZR40K1 34 5

Scroll Gas Flow Figure 1 6

The ZR*1 Compliant Scroll Compressor uses a temperature switch located on the top cap of the compressor shell to sense excessive internal temperatures caused by abnormal system conditions. The switch has these characteristics: Operating temperature: Opens 290 (± 9) F. Electrical Ratings: 24 volt control circuit Closes 140 (± 27) F. 72 VA 230 volt control circuit* 360 VA This switch is normally placed in a control circuit as shown in the following example: FIGURE 2 *For a 230 volt control circuit a special thermostat with 4/64th thick wire insulation rated for 150 C and 600 volt must be used. This is only available on special International bills of material. See page two for replacement. Motor Terminal (Fusite) Connections For ZR*1 Compliant Scroll (Single Phase) Figure 3 7

Note: This figure applies to single phase models only. ZR*1 Scroll Compressor Application Diagram Figure 4 8

9 Copeland 4-1280

Copeland Corporation Sidney, OH 45365-0669 Printed in U.S.A.