LIGHTING CONTROLS

Similar documents
SECTION LIGHTING CONTROL DEVICES AND CONTROL PANELS

Lighting Control Strategies. to meet code requirements save energy and improve building performance

East Central College

UBC Technical Guidelines Section Edition Interior Building Lighting Page 1 of 5

Emery County Senior Center Green River 06/07

A. This Section includes the following lighting control devices:

SECTION LIGHTING CONTROLS

Vive Solutions. Commercial Application Guide Code Compliance Lighting Controls IECC 2012

DIVISION 26 ELECTRICAL SECTION LIGHTING CONTROL SYSTEM

Ceiling Mount Sensors B4-B9. Occupancy and Vacancy Sensors B10-B15 B16-B17. Wall Mount Occupancy Sensors B-1

GE LightSweep Lighting Control System Guideform Specification

A. Furnish and install wiring devices and plates as specified herein and as shown on the Drawings.

1. Division 26 Section Electrical General Requirements. 2. Division 26 Section "Wiring Devices" for wall-box dimmers and manual light switches.

ANSI/ASHRAE/IES

Vive Solutions. Commercial Application Guide Code Compliance Lighting Controls IECC 2015

Vive Solutions. Commercial Application Guide Code Compliance Lighting Controls IECC 2015

ANSI/ASHRAE/IES

Lighting Controls. Energy-Saving Solutions For Efficient Buildings

A Guide for Applicants and Lighting Designers

A. This Section includes the following lighting control devices:

WVU DESIGN GUIDELINES & CONSTRUCTION STANDARDS DIVISION 26 ELECTRICAL

Product Specifications Dialog Room Controller* (*patent pending)

Mini Product Guide.

Applied Lighting Controls

Reduce lighting energy costs with controls

SECTION 26 NX DISTRIBUTED INTELLIGENCE LIGHTING CONTROL SYSTEM HUBBELL CONTROL SOLUTIONS

ASHRAE October 18, 2013

SECTION LIGHTING CONTROL DEVICES

Dissecting Lighting Control Requirements ANSI/ASHRAE/IES Standard & 2013

Education Title Solutions

LIGHTING CONTROLS. Smart Enough to Work Right Out of the Box

CRESTRON: GREEN LIGHT NETWORK LIGHTING CONTROLS 1

M001. Revenue Services ISSUED FOR CONSTRUCTION SEPTEMBER. 2, East State Parkway Schaumburg, Illinois Do Not Scale Drawings

WSA120: New Energy Codes and Lighting Controls

Princeton Joint Unified School District Invitation for Bid Installation of District-Wide Lighting Occupancy Sensors

GARCIA GALUSKA DESOUSA Consulting Engineers

Shannon J Markey LC, LEED AP Legrand BCS / Wattstopper Western Regional Manager. Yesterday, Today & Tomorrow

IN2 Lighting Control Devices

Office Title Solutions

Wireless Lighting Control Made Easy

Code Compliance. Lightcloud. Guides for California Title 24 & ASHRAE

SECTION DIGITAL-NETWORKING LIGHTING CONTROLS ENLIGHTED LIGHT MANAGEMENT SYSTEM

Indoor Controls. SpaceWise SWZG2. Wireless technology

Hospitality Title Solutions

Codes and Controls Commercial Building Energy Code Requirements for Light Control. Michael Jouaneh, CEM, LEED AP September 20, 2012

Technology. Occupancy & Vacancy Sensors & Timers. Technology. Occupancy & Vacancy Sensors & Timers L-2

SENSORS. Vacancy Sensors. Occupancy Sensors A4-A7 A-1

miniz Quick Start Guide

Healthcare Title Solutions

Related Sections: TBD. Effective Date: January 1, 2016

LIGHTING CONTROL DEVICES

MANDATORY MEASURES INDOOR LIGHTING CONTROLS. (Reference: Sub-Chapter 4, Section 130.1)

Stanford University Facilities Design Guidelines SECTION NETWORK LIGHTING CONTROLS

LightSweep. Lighting Control System

California s 2008 Building Energy Efficiency Standards for Residential and Nonresidential Buildings

Sensors and Detectors

Integrated LED Lighting Solution

C. The system shall be capable of turning luminaires on/off (where supported by the luminaire) as well as full range dimming.

PSC-ID-x-CM Series Ceiling Mount Occupancy Sensor

Building Automation System (BAS) Design Criteria

IECC. nlight Applications Guide.

B. It is recognized that these standards are updated irregularly and lighting technology is changing rapidly.

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION IBAS LIGHTING CONTROL

Table of Contents. Fast Fact. Sensor Models 2 Advantages of Sensors 3 FAQs 4-5

Specifications Occupancy/Vacancy Sensors CSI ASHRAE AIA Division 16 Section 16950

Hubbell Controls Application Guide to ASHRAE 90.1 A SUPPLEMENTAL GUIDE TO CODE REVISIONS IMPACTING LIGHTING CONTROL

Philips Lighting North America Corporation 200 Franklin Square Drive Somerset, NJ Tel

SECTION LOW VOLTAGE LIGHTING CONTROLS

CS1200 WHT Pir Ceiling Mount Occupancy Sensor

1. When using the COMcheck software, the compliance report submitted by the permit holder shall indicate that the applicable code is.

0ACDT2000MV Ultasonic/Infared Occ Sensor

MANUAL OF DESIGN CRITERIA AND SPECIFICATIONS FOR FIRE DETECTION AND ALARM SYSTEMS PUBLIC SCHOOLS IN NEW MEXICO

VESICA LINEAR SUSPENDED VES L

1. When using the COMcheck software, the compliance report submitted by the permit holder shall indicate that the applicable code is.

1. Section [ Lighting Control Panel Boards:] Lighting panels (switching) controlled by ControlKeeper

Dual Technology Wall Mounted Occupancy Sensor. Manual & Specification

SECTION LIGHTING CONTROL DEVICES EATON S LIGHTING SYSTEMS (FORMERLY COOPER CONTROLS) VACANCY/OCCUPANCY SENSORS

Wireless Plug Load Control

SECTION : CAMPUS CENTRAL METERING SYSTEM DESIGN

H-MoSS. Tomorrow s Technology Today! H-MOSS Occupancy and Vacancy Sensors. Adaptive Technology Dual Technology Ultrasonic Passive Infrared

Lighting Proposal Memo. Lighting Proposal. Angela Nudy Lighting/Electrical Dr. Mistrick Lighting Proposal Memo 1

Advanced Lighting For Office

v3 360 Dual Technology Low Voltage Occupancy Sensor with Light Level, Isolated Relay and Manual On feature

MANDATORY MEASURES MANDATORY LIGHTING CONTROLS (a) Area Controls: Manual controls that control lighting in each area separately

FROM THE WORLD S FIRST GFCI RECEPTACLE TO OUR GAME-CHANGING LINE OF PASS & SEYMOUR PLUGTAIL DEVICES, PASS & SEYMOUR PRODUCTS HAVE A REPUTATION FOR

, ,

MANDATORY MEASURES INDOOR LIGHTING CONTROLS. (Reference: Sub-Chapter 4, Section 130)

Job No A. Submit the following equipment, materials and products, including all fittings and accessories:

Sensors Explained AUTOMATION

Code Compliance Commercial Application Guide

LS-CM Series. Overview. Applications. Features & Benefits. Datasheet. Ceiling mount occupancy sensors

LPCMPIRM65 & LPCMPIRDSI65

Dual Relay Multi-Technology Wall Switch Occupancy Sensors

Lighting Control Relay Panels Lighting Control Solutions

Design and Commissioning of Lighting Control Systems. Rick Miller, PE, LC, LEED AP RNM Engineering, Inc. October 18, 2012

visual environment technologies etcconnect.com

Maestro 0 10 V Dimmer Sensor

Ceiling-Mounted Wireless Occupancy/Vacancy Sensor

2025 Lavoisier, #135 Quebec, Quebec G1N 4L6 T F E. cristalcontrols.

ENERGY EFFICIENCY EXPERTS

Transcription:

260923 LIGHTING CONTROLS PART 1: GENERAL 1.01 SUMMARY COMMENTS A. CU has developed this lighting control guideline to direct design professionals toward standard solutions that meet the University s performance requirements. This document defines typical space functions (i.e. laboratory) and provides lighting control solutions based on the room architecture, desired technology, cost, and performance. B. This document is intended to be used as a reference for design professionals working for CU; and as such should not be used as a technical specification. C. All Lighting Control System (LCS) projects shall meet the energy and control requirements outlined in the most current edition of the Energy Conservation Construction Code of New York State. For LEED projects, comply with the requirements of Credit EQc6.1: Controllability of Systems Lighting and coordinate the design of lighting controls as required for Credit EAp2 Minimum Energy Performance and EAc1 Optimize Energy Performance. D. This document does not define products for replacement or preventative maintenance, and should only be used for renovation and new construction projects. E. Any proposed deviations from this standard shall be submitted in writing to CU Facilities Engineering and Energy & Sustainability departments for approval. 1.02 RELATED SECTIONS A. Section 018110 Green Building Guidelines B. Section 018120 Energy Guidelines C. Section 018130 Energy Modeling Guidelines D. Section 230900 Building Automation Control System (BACS) Guidelines E. Section 265100 Interior Lighting 1.03 APPLICABLE CODES AND RESOURCES A. International Energy Conservation Code, with the New York State Supplement (NYSECCC). DATE: 11/16/17 DATE: 11/16/17 Page 1 of 11

B. ASHRAE 90.1, as referenced as an alternate energy code compliance path by the NYSECCC. C. ANSI A117.1 American National Standard for Accessible and Usable Buildings and Facilities. D. IESNA Lighting Controls for Energy Management (LEM-7-13). E. IESNA The Commissioning Process Applied to Lighting and Control Systems (DG-29-11). 1.04 CORNELL STAKEHOLDERS A. The following list represents the Cornell stakeholders that should be included in all meetings and decisions with regard to the design of the lighting control system: 1. Project Manager 2. Facility Director 3. Building Coordinator 4. Energy & Sustainability (E&S) 5. Facilities Engineering (FE) 6. Facilities Management (FM) 1.05 DESIGN REQUIREMENTS A. Lighting Design Kick-off Meeting: The Cornell Project Manager will initiate and facilitate a pre-design kick-off meeting between the lighting designer, Facilities Engineering, and Energy & Sustainability. The intent of this meeting is to review the project and to determine the appropriate design approach for the lighting control system. 1. In preparation for this meeting, the lighting designer shall review field conditions for existing lighting control systems. A preliminary approach and preferred LCS manufacturer shall then be discussed at the meeting. For example, if there is an existing LCS, should it be modified/expanded or is it preferable to specify a different LCS system. 2. This meeting shall also determine who will provide the LCS (i.e., the Electrical Contractor or the Building Automation and Control System DATE: 11/16/17 DATE: 11/16/17 Page 2 of 11

Contractor), and how the work will be identified in the construction documents. B. Design Development: The lighting designer shall provide the following information as the design of the lighting control system progresses: 1. Data sheets for all proposed control system components. 2. A written narrative detailing the proposed LCS for each space or each type of space. 3. An energy modeling report, when included in the project scope. 4. Life Cycle Cost Analyses (LCCA) when needed to determine a final choice between lighting control options. C. Construction Drawings: The design professional shall ensure all LCS equipment, devices, and associated materials are clearly identified on the contract documents. This information includes, but is not limited to the following: 1. Sequences of operation for each type of space. 2. Lighting zones, which shall be coordinated with the BACS drawings. 3. Lighting control and scene control matrices (samples are included at the end of this document) edited to specific job conditions that includes the following information: a. Schedules of occupancy, coordinated with the BACS. b. Control strategy for switched and dimmed luminaires. c. Special programming instructions for emergency power operation and load shed, where applicable. 4. Single-line diagrams with all wiring and equipment clearly depicted. 5. Installation details. 6. Lighting control schedules, coordinated with the BACS. D. Technical Specifications: The design professional shall ensure the following information is included: 1. A requirement for the Contractor to schedule and conduct a Pre-Installation Conference to review the LCS in accordance with the project General Requirements, Section 013119 Project Meetings. DATE: 11/16/17 DATE: 11/16/17 Page 3 of 11

2. Allowance for a review of the LCS submittal package by Cornell Stakeholders and the Commissioning Agent prior to acceptance. 3. A requirement for the Contractor to schedule, conduct and provide documentation of Owner training as follows: a. Required attendees for training sessions. b. Training shall be performed by factory trained and certified representatives; minimum number, and hours should be commensurate with the size and complexity of the LCS. c. Post occupancy review: Six months after final acceptance, the manufacturer or manufacturer s representative shall meet with CU to review the function and operation of the LCS and provide all labor and materials to reprogram the LCS as required to meet the technical requirements. 4. Closeout Documents, for example Operation and Maintenance Manuals and As-Built Drawings. 5. The design professional shall include the following Contractor scope of work associated with commissioning efforts: 1.06 COMMISSIONING a. The LCS supplier shall conduct and certify the functional testing. b. When occupancy/vacancy sensors, time switches, programmable schedule controls, or photosensors are designed, the following shall be confirmed: i. Placement, sensitivity, and time-out adjustments for occupancy sensors yield acceptable performance. ii. Proper programming of time switches and programmable schedule controls. iii. Photosensor controls reduce artificial light levels c. LCS supplier to provide 24 hours per day, 7 days per week technical phone support located within the United States. Overseas call centers or call back support are not acceptable. d. A service contract for the LCS. DATE: 11/16/17 DATE: 11/16/17 Page 4 of 11

A. All lighting control equipment shall be integrated and commissioned to ensure that the hardware and software are calibrated, adjusted, programmed, and in proper working condition in accordance with the construction documents and manufacturer s instructions. B. The design professional shall coordinate with the Commissioning Agent to ensure that the contract documents include the scope of work associated with commissioning efforts. C. Refer to the IES DG-29-11 document for additional information. 1.07 GENERAL SYSTEM GUIDELINES A. Interior spaces enclosed by walls or floor-to-ceiling partitions will have at least one accessible lighting control to manually control lighting within the space. Controls may be toggle switches, low-voltage switches, dimming controls, or multi-scene controls. B. Interior spaces that are normally occupied shall allow the occupant to reduce the connected lighting load by at least 50%. Lighting reduction may be achieved by any of the following: dual switching of alternate rows of luminaires, alternate luminaires, or alternate lamps; switching the middle luminaire lamps independently of the outer lamps; switching each luminaire or lamp; luminaire dimming. C. Interior spaces that are required to have manual control will also include automatic controls to automatically turn off the lights when the space is not occupied via a sensor or time based schedule. 1. Vacancy sensors shall be used for all interior, occupied spaces, unless otherwise directed. 2. In lecture spaces, specify occupancy sensors for the first 5 rows of seating only. 3. Ceiling-mounted sensors shall be used for spaces over 100-square feet in area. Sensors will utilize Passive Infrared (PIR); dual-technology sensors are not permitted. 4. Wall-mounted sensors shall be used for spaces under 100-square feet in area. Sensors will utilize Passive Infrared (PIR); dual-technology sensors are not permitted. 5. Ceiling-mounted ultrasonic sensors shall be used for ganged toilet rooms with partitions. DATE: 11/16/17 DATE: 11/16/17 Page 5 of 11

6. Sensors shall be placed to provide the most effective coverage area and prevent nuisance operation. 7. Occupancy sensors shall be used in public spaces, corridors, hallways, and stairs to adjust light levels automatically based on occupancy. 8. Multi-scene control systems (i.e., Crestron controlled for a lecture or auditorium space) shall be configured to automatically turn off the lights when the space is not occupied, and interface with the BACS via dry contacts for occupied/unoccupied sensor status to enable HVAC temperature setback and airflow control strategies and lights on/lights off status. 9. Do not use sensors in rooms containing electrical distribution equipment (switchboards, switchgear, motor control centers, and panelboards), mechanical rooms, or in spaces where the sudden loss of illumination may pose a life safety hazard. D. Interior spaces that are normally occupied and with sufficient natural light shall include daylighting and dimming controls. E. Exterior luminaires shall be controlled by photocells, astronomic controls, or the BACS. F. Luminaires used for emergency egress shall not be connected to the LCS. 1.08 BACS INTERFACE A. The requirements in this Section apply to an LCS that integrates with the Building Automation and Control System. B. Integrated and Networked LCS s shall use the BACS interface as the primary method to perform all system programming, control, and monitoring. C. Auxiliary relays shall be used in all occupied spaces to interface the lighting control system to the BACS for occupied/unoccupied HVAC temperature setback and airflow control strategies. D. The BACS interface shall display graphic zones for each lighting zone with the location of all equipment. E. The BACS interface shall include floor plans, and display the status of all luminaires, including room occupancy, lights on/off, and a foot-candle level for dimmed spaces. DATE: 11/16/17 DATE: 11/16/17 Page 6 of 11

F. The schedule for all spaces shall be generated by the BACS and imported into the lighting control system. G. The BACS shall monitor the following points: 1. Lighting status (ON/OFF). 2. Occupancy (OCCUPIED/UNOCCUPIED). 3. Light level in foot-candles (dimmed spaces only). 4. Light power output (%) in dimmed zones only. 5. Low battery alarm (wireless sensors). 6. Controller status alarm (OFFLINE). H. All alarms generated by the LCS shall be monitored by the BACS, but will not be sent as alarms to the CU Energy Management Control System (EMCS). 1.09 INTEGRATED LIGHTING CONTROLS A. An Integrated LCS incorporates proprietary BACS hardware and software to provide time-based or sensor-based, dimming, or manual lighting control. All lighting control devices shall be integrated with the BACS, and shall be capable of wireless, wired, or hybrid wireless/wired architectures. B. Integrated LCS s shall be provided by the BACS Contractor. C. This type of system is suitable for use in the design of new buildings and major renovations. 1.10 NETWORKED LIGHTING CONTROLS SYSTEM A. A networked LCS shall utilize individually addressable devices to provide timebased or sensor-based, dimming, or manual lighting control. All lighting control devices shall be digital and networked together, and shall be capable of wireless, wired, or hybrid wireless/wired architectures. B. The Networked LCS shall be integrated with the BACS. C. This type of system is suitable for use in the design of new buildings and major renovations. 1.11 STANDALONE LIGHTING CONTROLS A. Standalone lighting controls shall utilize devices that are not interconnected to provide sensor-based, dimming, or manual lighting control. Lighting control devices may be capable of wired or wireless operation. DATE: 11/16/17 DATE: 11/16/17 Page 7 of 11

B. Standalone LCS s are typically provided by the Electrical Contractor. C. This type of system is suitable for use in the design of smaller renovations. 1.12 LIGHTING CONTROLS APPLICATION TABLE A. Please use the following table as guidance for determining where to apply occupancy sensors, vacancy sensors, daylight harvesting, scene based dimming, and manual controls. DATE: 11/16/17 DATE: 11/16/17 Page 8 of 11

Space Occupancy/ Vacancy Daylight Harvesting Scene Based Dimming Manual Control Atriums A (O) A Auditorium A (V) A A A Bedroom A (V) A A Classroom A (V) A A A Conference Rooms A (V) A A A Corridors * A (O) A Dining Halls A (O) A B B Gymnasiums A (V) A A A High-bay A (V) A Kitchens B (O) A A Laboratories A (V) A A Lecture Halls A (V) A A A Libraries A (V) A Lobbies A (O) A Locker Rooms A (O) A A Lounges A (V) A B Mechanical Rooms * A Music Rooms A (V) A A Open Office A (O) A Private Offices A (V) A A Residential A (O) Stairways * B (O) A Storage Areas A (V) Toilets A (O) A Waiting Areas A (O) A Workshops A (V) A Exterior (photo/timer) A (O) KEY *: Where not in conflict with applicable codes A: Required for this space O: Occupancy Mode B: Optional for this space V: Vacancy Mode DATE: 11/16/17 DATE: 11/16/17 Page 9 of 11

PART 2: PRODUCTS 2.01 LIGHTING CONTROL PRODUCTS A. Integrated LCS: Hardware and software compatible with the BACS, include BacNET interface modules. a. Automated Logic Corporation b. Alerton B. Networked LCS: a. AcuityControls nlight b. Lutron Grafik Eye c. Wattstopper C. Standalone Occupancy Sensors, Vacancy Sensors, Daylighting Controls: Includes: ceiling-mounted sensors, wall-mounted sensors, corridor sensors, stair sensors, luminaire integrated sensors, and photocells a. AcuityControls b. Lutron c. Philips d. Wattstopper D. Lighting Control Relay Panels: 32 or 48 relay panel, 120VAC or 277VAC, 32- channel, 365-day/astronomical time clock, networkable utilizing CAT6 cabling. a. AcuityControls b. General Electric c. Wattstopper E. Digital Time Clocks: 8 or 16 relay panel, 120VAC or 277VAC, 32-channel, 365- day/astronomical time clock, networkable utilizing CAT6 cabling. a. AcuityControls b. Wattstopper DATE: 11/16/17 DATE: 11/16/17 Page 10 of 11

F. Toggle Switches: 120VAC or 277VAC; 20A rated; industrial or specification grade; 1-way, 3-way, 4-way key operated, motor rated, and pilot light. a. Cooper Wiring Devices b. Leviton c. Pass & Seymour - Legrand G. Wireless Controls: a. AcuityControls b. Lutron c. Wattstopper H. Dimming Controls: Shall be coordinated with the luminaire manufacturer to ensure they are compatible with the specified luminaire ballast/driver technology. I. Multi-Scene Controls: a. AcuityControls b. Crestron c. Lutron d. Wattstopper J. Emergency Shunt Relays: UL 924 listed, 120VAC or 277VAC a. AcuityControls b. Hubbell K. Lighting Contactors: Electrically held, 30A rated contacts, 2-pole thru 12-pole, coordinate coil voltage during design, provide with appropriate NEMA enclosure for the application. a. Cutler Hammer - Eaton b. Square D c. General Electric DATE: 11/16/17 DATE: 11/16/17 Page 11 of 11

LIGHTING CONTROL MATRIX Cornell University Insert Building Name Control Mode Switched Lights Modulated lights Occupancy Type Schedule Occ hours UnOcc Defcon 1 Defcon2 Occupied Occ Hours; Unoccupied UnOcc Hours; Unoccupied Demand 1 Limit Demand 2 Limit Corridor Occupancy ON; Occupancy ON; 40 fc 20 fc 10 fc 20 fc 10 fc Stairs ON ON ON ON ON ON ON Bathrooms Occupancy ON; Occupancy ON; Mechanical/Electrical Manual OFF Manual OFF Faculty Manual 40 fc; PHD Manual 40 fc; Labs Manual 40 fc; Conference Rooms Manual 40 fc;

SCENE CONTROL MATRIX Cornell University Insert Building Name Switch Programming Occupancy Type Schedule Button-1 Button-2 Button-3 Button-4 Button-5 Faculty ON OFF PHD ON OFF Labs 50% Lighting 100% Lighting OFF Conference Rooms 50% Fluorescent Lighting 100% Fluorescent Lighting Projector Mode; LEDs only ON OFF Projector screen Up/Dn