Instructors: Contact information. Don Reynolds Doug McGee Factory Tech Support

Similar documents
Table of Contents. Service Procedures. Service Procedures. Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8)

Service Step by Step Trouble-Shooting Check-List

Otherwise, you can continue reading the file on the following pages.

SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES 3/22/2012 REFRIGERATION

AIR CONDITIONING. Carrier Corporation 2002 Cat. No

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS UNIT OBJECTIVES

Warm Case Troubleshooting Guide 9/18/2014

To accomplish this, the refrigerant fi tis pumped throughh aclosed looped pipe system.

For an administrative fee of $9.97, you can get an un-locked, printable version of this book.

The Saturation process

Thomas J Kelly. Fundamentals of Refrigeration. Sr. Engineering Instructor Carrier Corporation. August 20, Page number: 1.

Calhoon MEBA Engineering School. Study Guide for Proficiency Testing Refrigeration

SECTION 7 AIR CONDITIONING (COOLING) UNIT 41 TROUBLESHOOTING

Math. The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb.

HEAT PUMPS. Carrier Corporation GT72-01 Cat. No

SECTION 8 AIR SOURCE HEAT PUMPS UNIT 43 AIR SOURCE HEAT PUMPS

Use this Construction/HVAC Glossary to answer the questions below.

Energy Use in Refrigeration Systems

Refrigeration Systems and Accessories

HEAT PUMPS. Carrier Corporation GT72-01A Cat. No

PL Series Premier Indoor Plenum Coils

Class 1: Basic Refrigera0on Cycle. October 7 & 9, 2014

HVAC Systems What the Rater Needs to Know in the Field CALCS-PLUS

Refrigeration and Air Conditioning

Residential Piping and Long Line Guideline

How to Diagnose a TXV Failurek

Mortex INSTALLATION INSTRUCTIONS AIR CONDITIONING & HEAT PUMP INDOOR COILS

Cased Aluminum Coils "Dedicated Upflow / Downflow" Convertible to horizontal with separately purchased kit

Superheat charging curves for technicians

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer

APPLICATION DATA SHEET

Experienced Worker Assessment Blueprint HVAC - Heating, Ventilation and Air Conditioning

Checking the Charge on a Heat Pump in the Winter

Everything You. NEED to KNOW. TXV does this by keeping the coil supplied

Determining Real Time Performance of Residential AC Systems. Presented at the RESNET Conference San Antonio, TX February 28, 2006

INSTALLATION INSTRUCTIONS TXV Horizontal Slab Coils WLSH

INSTALLATION & OPERATING INSTRUCTIONS FOR CEILING MOUNT AIR HANDLERS AC SERIES

SECTION 2 SAFETY, TOOLS AND EQUIPMENT, SHOP PRACTICES UNIT 10 SYSTEM CHARGING

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES UNIT OBJECTIVES 3/22/2012

G Series. G Series Air Coils Installation ti Manual ENCASED/UNCASED AIR COILS. Geothermal/Water Source Heat Pumps R-410A Refrigerant 2-5 Ton

Installation Instructions

Installation Instructions

Air Conditioning Components

Pressure Enthalpy Charts

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

Entry Level Assessment Blueprint Heating, Ventilation and Air Conditioning (HVAC)

HVAC/R Refrigerant Cycle Basics

REFRIGERANT RECOVERY Log Book

Application Guide. Refrigerant Piping Manual for Small Split Cooling and Heat Pump Systems SS-APG006-EN

Sporlan Valve Division Parker Hannifan/CIC Group

Technical Standards for the Air Conditioning and Heat Pump Professional BPI STANDARDS

R Series Cooling Manual

Eclipse Technical Training CME686 CME810 CP686 CP886 CP1086

WineZone Ceiling Mount Ductless Split 15

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

SEVEN STEPS TO EFFECTIVE PRE- SEASON COOLING CHECKUPS

CAUTION. Check Equipment and Job Site. Clearance Requirements. Unpack Unit

Condensing Unit Installation and Operating Instructions

SA Series Start up Report

Some of these procedures need to be performed to conform to requirements of the Clean Air Act.

Data Aire, Inc. reserves the right to make design changes for the purpose of product improvement or to withdraw any design without notice.

HVAC Fundamentals & Refrigeration Cycle

A/C-HEATER SYSTEM - MANUAL

Electrical Problems. Fuse(s) blow or circuit breaker trips. Does the unit use circuit breakers or fuses? Replace with correct fuse(s)

Installation Manual BCS 1000/1500

BASIC HEAT PUMP THEORY By: Lloyd A. Mullen By: Lloyd G. Williams Service Department, York Division, Borg-Warner Corporation

12 In Row. Installation Manual. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc.

Heating, Ventilation & Air Conditioning (HVAC)

REFRIGERATION CYCLE Principles of Mechanical Refrigeration Level 2: Cycle Analysis

RSES Technical Institute Training Manual 2 72 hours, 72 NATE CEHs, 7.2 CEUs

Installation Instructions

UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM

Series 6, Vertical Floor-Mount Units

Motor Vehicle Air Conditioning (MVAC) System operation and the refrigerant cycle

PRESSURE-ENTHALPY CHARTS AND THEIR USE By: Dr. Ralph C. Downing E.I. du Pont de Nemours & Co., Inc. Freon Products Division

Event #1 Brazing. In this event you will demonstrate how to:

REFRIGERANT ON-VEHICLE INSPECTION AC 14

Installation Instructions

Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants

Installation Instructions

10/4/2013. The Changing State of Refrigerants

INSTALLATION GUIDE. 4AC 14* ASA1 SERIES R-410a CONDENSING UNITS R-410A ATTENTION, INSTALLER! ATTENTION, USER!

R Series Cooling Modules

B. A. T. Basic Appliance Training

Product Data PH13(N,P)R FEATURES AND BENEFITS. SPLIT SYSTEM HEAT PUMP For Use With R Refrigerant 1---1/2 TO 5 TONS ( )

MYSTICOOL Max Valve System with Xstream and A.R.M.E.D. Technology Service & Installation Instructions Page 1

INSTALLATION INSTRUCTIONS TXV Coils EDM, EDD, EDA

Installation Instructions

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

Installation Manual for ETI AVS Series and NON-ETI Air Handlers with SC or SD Compressor Units and R-410A Refrigerant

Installation Instructions

XSTREAM Valve System With A.R.M.E.D. Technology Service & Installation Instructions Page 1

Installation Instructions

RTP Technical Bulletin

R Series Cooling Modules

Technical Training Associates Presents. Commercial Refrigeration Equipment Servicing Part 1

Basic Principals of Air conditioning By Dr. Esam Mejbil Abed

INSTALLATION INSTRUCTIONS TXV Coils EBD, EBA

INSTALLATION INSTRUCTIONS TXV Coils EBU, EBA

Transcription:

Contact information Instructors: Don Reynolds 616-560-9903 Doug McGee 517-294-3932 Factory Tech Support 888-593-9988

Product Improvements for 2017

Todays Objectives Job Site Information Sheets Low Ambient Kits Evacuation Air Flow Saturation Temperatures Superheat Sub Cooling Metering Devices Troubleshooting the refrigeration system Why Compressors Fail

118 417 55 120 55 41 14 120 111 9 62 59 110 111 111 54.5 55 270 85 75 63 3/8 3/4 1200 3 ft 32 32 55 242 9.6

IO-709F LAKT Low Ambient Kit The following accessories must be installed on all condensers and heat pumps when equipped with low ambient kits. Crankcase heater must be installed if not factory installed. Hard start kit for single phase units. (See Spec Sheet for Accessories) TXV kit installed on indoor evaporator coil, if not factory installed. FSK01A - Freeze protection kit must be installed on indoor coil. Wind buffer must be installed for temperatures below 0 F or areas with high prevailing winds. Wind buffer can be a wall fabricated from wood or masonry material that will prevent the prevailing wind from causing the outdoor fan to rotate. NOTE: When wind buffer is installed, it is necessary to use minimum 4" risers to elevate the unit off of the pad to provide better airflow for moderate and high ambient temperatures. NOTE: These kits are not approved for any 16 and 18 SEER outdoor units that utilize an ECM condenser fan motor. Note: Units equipped with ECM condenser motors are not approved for low ambient installations. 3/17/2017

Brazing

Evacuation 25400 microns between each mark

How Do You Get The Water Out? We Boil It We Lower the System Pressure To A Point That Water Boils At Ambient Temperatures

Pressure VS. Boiling Point Physics 101 As Pressure Decreased - The Boiling Point Decreases

Speed Of Evacuation Size Of System Complexity Of Piping System Components Oil Separators Accumulators Valves Ambient Temperature Size Of Pump How You are Hooked Up To the System High & Low Side Size Of Hoses Access Fitting?

One Very Important Rule No test is valid if the airflow is not Correct No Pressures No temperatures No Current Draws

Things you are going to Learn Today Air Flow

Taking Duct Statics (Checking External Static Pressure) ESP With clean filters in the furnace. Measure the static pressure of the return air at the inlet of the furnace(negative pressure) Measure the static pressure of the supply air duct (positive pressure) Add the two reading together for total external static pressure

Goodman/Amana Blower Chart

Air Flow A properly operating air conditioning system both cools ( a sensible heat process) and dehumidifies ( a latent heat process) the air. For example given a 2 ton unit a percentage of the total capacity of the system is utilized to cool the air while the remaining percentage of the total capacity is used to dehumidify the air. Properly controlling both the temperature (sensible heat) and the humidity (latent heat) will provide the optimum comfort levels.

Adding Up The Numbers 750 cfm 22,400 X 0.78 = 17,472 btu s sensible heat 22,400-17,472 = 4,928 btu s latent heat 900 cfm 23,200 X 0.83 = 19,256 btu s sensible heat 23,200 19256 = 3944 btu s latent heat

Saturation Temperature The temperature of the liquid or vapor, where any heat is add or removed, a change of state takes place

Converting Pressure to Saturation For any given pressure refrigerants have a saturation temperature The suction pressure will convert to the temperature of the refrigerant leaving the metering device The liquid pressure converts to the saturation temperature of the refrigerant condensing in the condenser Temperature

Superheat (Evaporator) The amount of heat added to the refrigerant after it changes to the vapor state is called Super Heat.

Pressure Temperature Chart Suction line temperature 55 degrees #120 = 41 degrees Superheat 14 degrees

Superheat Chart

Sub Cooling (Condenser)

#417 120 Liquid Line Temp 111 Sub Cooling 9

Goodman/Amana/Daikin TXV Systems Should read 8 degrees + / - 1 degree of Sub-cooling for Single Stage Units. Superheat 8 degrees Two Stage systems should read 5 to 7 degrees of subcooling in Low Stage. Superheat 7-9 degrees

Metering Devices Note: Always size the piston to the outdoor condenser ( piston will come attached to the outdoor unit)

TXV Valve Operation 49

Symptoms of a Restricted (Underfeeding)Metering Device Restrictions in the metering device will prevent the evaporator coil from receiving the proper amount of refrigerant Low Suction Pressure High Super Heat High sub cooling

Overfeeding Metering Device When an overfeeding condition is present, the suction side of the system operates in a flooded state. The high side of the system operates in a starved state. The suction pressure will be high The super heat will be low The head pressure will be low The subcooling will be low

Symptoms of Low System Charge Fixed or TXV Metering Device Low System Pressures High Superheat Low sub-cooling Low Amperage on compressor The compressor will also run hot Because of low suction pressure the evaporator may form a coating of ice on it If the system is slightly low on charge the TXV may open enough to maintain adequate suction pressure and superheat, but the head pressure will still be lower than normal and the sub-cooling will also be low If the system charge is very low the system will have the same symptoms as a fixed metering device

Symptoms of a Over Charged Unit Higher than normal head pressure Higher than normal suction pressure Low Superheat High Subcooling High Amperage on Compressor Liquid Floodback Compressor noise A system with a TXV valve will show the suction pressure and superheat to show normal, because the TXV is trying to throttle back the refrigerant entering the coil. This causes the excess refrigerant to be stored in the condenser which will elevate the head pressures and liquid subcooling levels If the overcharge is severe the suction pressure may increase with low superheat

Liquid Line Restrictions Restrictions in the liquid line will prevent the evaporator from receiving the proper amount of refrigerant. The restriction will cause a large pressure drop between the condenser coil and the metering device Liquid line restrictions can be caused by the following restricted filter drier, restricted TXV screen, kinked liquid line or kinked or bent U bend on lower portion of condenser coil

Symptoms of a Liquid Line Restriction Low Suction Pressure High head pressure High Subcooling High superheat Low compressor amperage Frosting or sweat of the liquid line or liquid line filter drier

Suction Line Restrictions The suction line is a much more sensitive refrigerant line, because vapor instead of liquid flows through it. A restricted suction line will cause low suction pressures and head pressures and a starved compressor and condenser. A starved compressor will lead to low compressor amp draw because of the lightened load..

Restricted Suction Line Since a suction line restriction starves the compressor of refrigerant, causing the flow of refrigerant to decrease through the system. This in turn will cause high superheat. Subcooling will be normal to a bit high, because the refrigerant will not be circulated very fast causing the liquid refrigerant to back up into the condenser

Evaporator Circuit Restrictions Restrictions within the evaporator coil will cause the system to exhibit the same operating characteristics as a restricted metering device

Identifying Evaporator Circuit Restrictions Systems running with a restriction in the evaporator coil will have a low suction pressure along with a high superheat The liquid pressure will initially be low If refrigerant is added at this time, the liquid pressure will rise but the suction pressure will remain low. If subcooling is checked at this time, it will be high. This is because excess refrigerant is being stored in the condenser

Checking For Non Condensables Air, nitrogen, and other foreign gasses present in a refrigerant system are referred to as non condensables since they will not condense into a liquid at pressures encountered in a refrigeration system These gases will accumulate in the condenser coil and take up valuable condenser coil circuits

Identifying Condenser Circuit Restrictions The restriction in the circuit will cause a corresponding drop in refrigerant temperature. Therefore, the circuit with the restriction will have refrigerant leaving the circuit at a temperature much colder than the other circuits

Most compressors fail because of System Problems Compressors

Causes of Mechanical Compressor Failures: Refrigerant Flood back Flooded Starts Slugging Compressor Overheating Loss of Oil

Liquid Flood Back Restricted air flow Plugged filters Dirty evaporator coil Non operating blower motor Ductwork Wrong fan speed Overcharge TXV overfeeding Too large of piston

Liquid Refrigerant Flood back Floodback is defined as liquid refrigerant returning to the compressor during the running cycle. The resulting damage is determined by the type of compressor-- refrigerant cooled or air cooled. We will look at them separately.

Refrigerant Migration Refrigerant migration occurs anytime refrigerant and oil are in contact with each other and the compressor is not operating. Refrigerant vapor in the crankcase condenses and is absorbed by the oil. Liquid refrigerant in the evaporator vaporizes and moves to the crankcase as a vapor.

Slugging Slugging is the result of significant quantities of liquid refrigerant, oil, or both getting into the compressor. The cause is usually refrigerate migration

Overheating High Compression Ratios High Return Gas Temperature Lack of External Cooling

Loss of Oil Failures Poor Piping Improper Traps Loss of Charge Short Cycling Low Loads Pressurized Crankcase in Suction-Cooled Compressors

Questions?