Fire Pump Supervision - Part 1 by Dean K. Wilson, P.E.

Similar documents
Fire Pump Supervision - Part 2 by Dean K. Wilson, P.E.

Fire Pump Supervision - Part 3 by Dean K. Wilson, P.E.

Not-So-Dead Air Space

Shut Down The Fan: A Reprise by Dean K. Wilson, P.E.

Can You Hear Me Now?

Surviving the Survivable Cable Crunch

Can You Hear Me Now?

Applying Performance-based Fire Alarm System Design Part 4

Performance-based Fire Alarm System Design Introduction

THE BASICS OF BUILDING FIRE PROTECTION DESIGN. RES Symposium April 18, 2017

Changes in NFPA

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST

1 Exam Prep NFPA 14 Stand Pipe Systems Questions and Answers (Plumbing Contractors)

Chapter 4: Fire Protection Systems

Remote Alarm Panels Features

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot

1.1 REFERENCES.1 American National Standards Institute/National Fire Protection Association (ANSI/NFPA).1 ANSI/NFPA 20, Centrifugal Fire Pumps.

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

SECTION 907 FIRE ALARM AND DETECTION SYSTEMS

rpsa FIRE PROTECTION ENGINEERS

HIGH-RISE RETROFIT ORDINANCES - NO and NO

Florida Building Code 2010

Center for Life Safety Education

Slide 1. Slide 2 Instructor. Slide 3. NFPA 25 The Owner s Manual. Roles & Responsibilities DISCLAIMER

Revision May All designs must be submitted to FM Global for review and approval prior to issuing such for bids.

SCHULTE & ASSOCIATES Building Code Consultants 3500 Creighton Road, K5 Pensacola, FL

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment

El Reno Fire Department Fire Alarm Plan Review Worksheet

COMMERCIAL (IBC) FIRE ALARM SUBMITTAL GUIDE

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Plan Review

Module 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements

FIRE ALARM SYSTEMS & 780 CMR. Dave LeBlanc, PE, FSFPE March 17, 2015

Pumps SELECTION OF A PUMP

CITY OF MADISON FIRE DEPARTMENT (MFD) FIRE PROTECTION SYSTEM PLANS

Fire Protection Coffee Break Training May 2016

CONTENTS. B. System Design and Performance Requirements

DERRY FIRE DEPARTMENT LISTED AGENT CERTIFICATION PROGRAM

DESIGN AND CONSTRUCTION STANDARDS SPECIFICATION GUIDELINES

HHA Lyerly Apartments 75 Lyerly Houston, Texas J. Allen Management Managing Agent

Fire Sprinkler System Design and Installation Requirements

Owner/Operator Guide for Successful Sprinkler and Fire Pump Systems

Slide 2 NFPA 25: 2017

2.07 Permit Application Checklist for Diesel Generators, Diesel Fire Pumps, and Fuel Tanks Serving Generators and Fire Pumps (2016)

A hydronic system controls comfort by delivering heated or cooled fluid to the conditioned space through pipes.

By: Russell Bainbridge March 18th, 2016 FPE 596

TOTALPAC2 Integrated Fire Protection System

HHA Bellerive Apartments 7225 Bellerive Houston, Texas J. Allen Management Managing Agent

Report of Committee on Fire Pumps

The Authoritative Source for Plumbing, Hydronics;

Fire Sprinkler Plan Submittal Form

Water Distribution Study Guide Class III (Made available by: Kansas Rural Water Association)

Global Property. QUARTERLY FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location:

SEMICONDUCTOR FABRICATION FACILITIES

SEMICONDUCTOR FABRICATION FACILITIES

Proposed Changes to NFPA

Irrigation Water Pumps

PHYSICAL FACILITIES Consultant s Handbook Specifications Division 21 Fire Suppression 3000 Fire Pumps

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: HVAC Standards

Electric Pumps. Introduction. W4100, W4200 & W4300 Condensate Pumps. Typical Condensate Pump Features

Course FP100 BACKFLOW PREVENTERS (BFPs) 101 FOR AUTOMATIC FIRE SPRINKLER SYSTEM M. Nabeel Waseem, M.Eng, PE, CFPS 2018

Review of Revisions to NFPA 1, 2015 Edition

Unified Fire Authority - Fire Prevention Bureau

PUMPS & PUMPING SYSTEMS FOR THE CHEMICAL PROCESSING & HEATING & AIR CONDITIONING INDUSTRY

TECHNICAL DATA OBSOLETE

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE, 2000 EDITION SECTIONS

SEMICONDUCTOR FABRICATION FACILITIES

Direct Gas-Fired Make-Up Air

Operational Overview and Controls Guide

GRUNDFOS FIRE PUMP SYSTEMS PEERLESS ENGINEERED SYSTEMS LISTED

Worldwide Contacts. Technical Data

Form 2143 Date: 4/3/03 Repl: 2/1/99 BRYAN STEAM LLC. Installation and Operating Service Manual BOILER FEED SYSTEM


Technical Data. Sizes 2 12 Inch (DN50 DN300)

Addressing Sound Masking Requirements in the National Fire Alarm and Signaling Code and UL Standards

SECTION Fire Pumps

CHAPTER 05 - OFFICE OF STATE FIRE MARSHAL SUBCHAPTER 05A - FIRE AND RESCUE SECTION.0900 PUBLIC PROTECTION CLASSIFICATIONS FOR FIRE DISTRICTS

FIRE & LIFE SAFTEY STANDARD

PRESSURE INDEPENDENT CONTROL VALVE TECHNOLOGY. 3/16/2012 Fred Ferrara 1

STATE OF RHODE ISLAND AND PROVIDENCE PLANTATIONS

NFPA 25 and the Influence of Liability

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant.

New Construction Fire Inspection Process

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD

PROTECTING FIRE SPRINKLER SYSTEM PIPES FROM FREEZING IN CHAPTER FACILITIES

2012 International Fire Code Errata (Portions of text and tables not shown are unaffected by the errata)

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)

FIRE SAFETY PLAN. BUILDING NAME: Pathobiology / AHL BUILDING NUMBER: 089. DATE: 15-August-10 FPO #2

BRINE CIRCULATED ICE THERMAL STORAGE SYSTEM DESIGN - CASE ILLUSTRATION - Partial Ice Storage for Air Conditioning Application

Liebert CSU3000 Chiller

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

AUTOMATIC FIRE SPRINKLER SYSTEM STANDARDS Development Standard #4.1 (Commercial Installations)

CAN/ULC-S1001, INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION & LIFE SAFETY SYSTEMS Simon Crosby, LEL, CET, CFPS October 21, 2015

Balloting Version First Draft NFPA 101 Life Safety Code Proposed 2015 Edition

Finishes Plain Brass Chrome Plated and other Finishes Available Upon Request. For cabinets and other accessories refer to separate sheet.

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline

Backflow Prevention for Fire Sprinkler Systems. State of Illinois Plumbing Code

Transcription:

Fire Alarm Notebook by Dean K. Wilson. P.E. Page 1 Fire Pump Supervision - Part 1 by Dean K. Wilson, P.E. Question: As the Authority Having Jurisdiction in my suburban community, I have largely had to deal with relatively small commercial buildings. And, because our municipality has a very strong public water system, I have not had to deal with private fire pumps. Recently, one of the big box stores has broken ground for a gigantic distribution center. The architect has delivered the plans for me to review. I notice that this facility will have three fire pumps. Two diesel engine-driven 2,000 gpm pumps take suction from individual 300,000 gallon tanks located on the northeast and southwest corners of the property. The tanks have automatic fill from the public water supply. The third fire pump, an electric motor-driven unit rated at 1,500 gpm, takes suction from a 16-inch connection to a 24-inch public water main. Apparently, the fire alarm system will supervise the fire pumps. I don t even know where to begin reviewing the fire alarm portion of this installation. Can you help me? I will certainly try to help you. First of all, from your description it sounds as if you have one booster fire pump and two fire pumps. The difference in the designation comes from the suction source. Booster fire pumps take suction from the public water supply and boost the pressure to a level appropriate for the hazard.

Fire Alarm Notebook by Dean K. Wilson. P.E. Page 2 Listed horizontal centrifugal booster fire pumps normally have a rating that specifies 120% of rated pressure at shut-off or when no water flow, 100% of rated pressure at 100% of rated flow, and 65% rated pressure at 150% of rated flow. Such pumps have a design that self-unloads. In other words, the maximum brake horsepower necessary to drive the pump occurs at around 110% to 120% of rated flow. Beyond that point on the pump discharge curve, the brake horsepower drops off or self-unloads. The designer of the fire protection system will choose the pressure rating of the booster fire pump based on the residual pressure of the public water supply at the maximum specific rate of flow, measured in gallons per minute (gpm). In the case of this 1,500 gpm booster fire pump, the public water supply must produce 2,250 gpm at no less than 20 psi residual pressure. You will need to see evidence of a flow test of the public water supply in the immediate area of the facility to determine what the actual residual pressure remains at the 2,250 gpm flow. The booster fire pump will then add to that residual pressure the rated pump pressure to create a specific flow rate at a significantly increase in pressure. Thus, the reliability and capacity of the fire protection system depends completely on the reliability and capacity of the public water supply. Listed horizontal centrifugal fire pumps have a similar rating as the booster fire pumps: 120% of rated pressure at shut-off or when no water flow, 100% of rated pressure at 100% of rated flow, and 65% rated pressure at 150% of rated flow. In contrast to booster fire pumps, fire pumps take suction from some static source of water, such as the two independent 300,000 gallon storage tanks you describe. Typically, fire pumps have a much lower suction pressure than booster fire pumps. In the case in point, the height of the tank above the center line of the fire pump will determine the suction pressure created by the column of water within the tank. For every foot of

Fire Alarm Notebook by Dean K. Wilson. P.E. Page 3 elevation, the column of water will create 0.434 pounds per square inch (psi) of pressure. A fortyfoot tall suction tank will create a suction pressure at the centerline of the pump of 17 psi. The size and location of these particular fire pumps hint that the redundant pair may result from a recommendation from the insurance company issuing the property insurance policy for this facility. The high automatic sprinkler system water demand for large warehouses often motivates the insurance company to require redundant and independent water supplies. The third booster fire pump will likely provide the first-operating-pump to handle the demand for a relatively small fire at the facility. Once sufficient pressure drop occurs, the two fire pumps will start to supply additional flow and pressure. While NFPA 72-2010, National Fire Alarm and Signaling Code, has specific requirements for using a fire alarm system to oversee the operational reliability of fire pumps and their associated water tanks, you should first look at the requirements in NFPA 20-2010, Standard for the Installation of Stationary Pumps for Fire Protection. In order to deal with this subject in an orderly fashion, in this first article I will guide you in looking at the requirements for electric motor-driven fire pumps. NFPA 20-2010, Chapter 10, covers the requirements for Electric Drive Controllers and Accessories. Specific requirements relating to the type of supervision that a fire alarm system might provide include the following: 10.4.7* Fire Pump Alarm and Signal Devices Remote from Controller. A.10.4.7 Where unusual conditions exist whereby pump operation is not certain, a "failed-to-operate" fire pump alarm is recommended. In order to supervise the power source for the fire pump alarm circuit, the controller can be arranged to start upon failure of the supervised alarm circuit power.

Fire Alarm Notebook by Dean K. Wilson. P.E. Page 4 10.4.7.1 Where the pump room is not constantly attended, audible or visible signals powered by a source not exceeding 125 V shall be provided at a point of constant attendance. 10.4.7.2 These fire pump alarms and signals shall indicate the information in 10.4.7.2.1 through 10.4.7.2.4. 10.4.7.2.1 Pump or Motor Running. The signal shall actuate whenever the controller has operated into a motor-running condition. This signal circuit shall be energized by a separate reliable supervised power source or from the pump motor power, reduced to not more than 125 V. 10.4.7.2.2 Loss of Phase. 10.4.7.2.2.1 The fire pump alarm shall actuate whenever any phase at the line terminals of the motor contactor is lost. 10.4.7.2.2.2 All phases shall be monitored. Such monitoring shall detect loss of phase whether the motor is running or at rest. 10.4.7.2.2.3 When power is supplied from multiple power sources, monitoring of each power source for phase loss shall be permitted at any point electrically upstream of the line terminals of the contactor, provided all sources are monitored. 10.4.7.2.3 Phase Reversal. (See 10.4.6.2.) This fire pump alarm circuit shall be energized by a separate reliable supervised power source or from the pump motor power, reduced to not more than 125 V. The fire pump alarm shall actuate whenever the three-phase power at the line terminals of the motor contactor is reversed. 10.4.7.2.4 Controller Connected to Alternate Source. Where two sources of power are supplied to meet the requirements of 9.3.2, this signal shall indicate whenever the alternate source is the source supplying power to the controller. This signal circuit shall be energized by a separate, reliable, supervised power source, reduced to not more than 125 V. 10.4.8 Controller Contacts for Remote Indication. Controllers shall be equipped with contacts (open or closed) to operate circuits for the conditions in 10.4.7.2.1 through 10.4.7.2.3 and when a controller is equipped with a transfer switch in accordance with 10.4.7.2.4. You will note in reading the above paragraphs that these requirements do not specifically require the connection of the remote signal devices to a fire alarm system. However, the use of a properly designed and installed fire alarm system offers the most reliable means of supervising the operational readiness of the fire pump.

Fire Alarm Notebook by Dean K. Wilson. P.E. Page 5 Fortunately, as noted in 10.4.8, listed fire pump controllers come equipped with contacts that permit supervisory initiating device circuits from a fire alarm system to connect and monitor the stated features. An installation contractor must take note of the specific conditions that this Standard requires remote indication: Pump or Motor Running (10.4.7.2.1), Loss of Phase (10.4.7.2.2), Phase Reversal (10.4.7.2.3), and, when an alternate source of power is provided, Controller Connected to Alternate Source of Power (10.4.7.2.4). Each supervised feature from the electric fire pump controller should produce a distinctive supervisory off-normal and supervisory restoration-to-normal signal at the fire alarm system control unit. If the location of the fire alarm system control unit does not have constant attendance, the fire alarm system should transmit distinctive signals to an appropriate supervising station. In the particular case of this installation, the electric motor-driven booster fire pump represents one part of a more complex pumping system. Since the other pumps use diesel engines to drive the pumps, an alternate source of power would not normally be required in accordance with NFPA 20-2010, as follows: 9.3.3 An alternate source of power is not required where a backup engine-driven or backup steam turbine-driven fire pump is installed in accordance with this standard. Naturally, in addition to the items stated above, the fire alarm system needs to monitor the operational status of all control valves associated with the booster fire pump installation. In addition, if the geographic location subjects the facility to freezing temperatures during certain seasons of the year, the fire alarm system should monitor the low temperature in the fire pump room.

Fire Alarm Notebook by Dean K. Wilson. P.E. Page 6 In the next article, I will guide you in looking at the requirements for monitoring the operational readiness of the two diesel engine-driven fire pumps and their associated water tanks. IMSA member Dean K. Wilson, P.E., FSFPE, C.F.P.S., now retired on disability, formerly worked as a Senior Engineer in the Erie (PA.) office of the fire protection engineering and code consulting firm, Hughes Associates, Inc. (www.haifire.com.). The opinions expressed in this article are strictly his own. You may reach him by e-mail at deanwilson@roadrunner.com or by telephone at 814-397-5558.