SPECIFICATION: Kidde Engineered Fire Suppression System Designed for use with 3M Novec 1230 Fire Protection

Similar documents
SPECIFICATION: ECS SERIES CLEAN AGENT FIRE SUPPRESSION SYSTEM

A. NFPA 2001 Standard for Clean Agent Fire Extinguishing Systems 2004 edition.

SPECIFICATION: ARGONITE Engineered Fire Suppression System

FM-200 In-Cabinet Series

SECTION FM-200 FIRE SUPPRESSION SYSTEM

SPECIFICATION: CARBON DIOXIDE ENGINEERED FIRE SUPPRESSION SYSTEM

NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code

SPECIFICATION: DRY CHEMICAL FIRE SUPPRESSION SYSTEM FOR INDUSTRIAL APPLICATIONS MODEL IND

Kidde Nitrogen Inert Gas Clean Agent Fire Suppression System

ENGINEERING SPECIFICATIONS FOR FM-200 CLEAN AGENT INDIRECT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS

KIDDE WHDR WET CHEMICAL FIRE SUPPRESSION AND INTELLIGENT CONTROL SYSTEM FOR COOKING OPERATIONS WITH ARIES-NET MULTI-LOOP INTELLIGENT CONTROL UNIT

SPECIFICATION: AlarmLine TM INTELLIGENT LINEAR HEAT DETECTION

Hospitals and Major Medical Centers

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE SHP PRO CONTROL PANEL SYSTEM

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE CHEETAH Xi 50 CONTROL PANEL SYSTEM

SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPUSLE VALVE, Fike FK AGENT & SHP PRO CONTROL PANEL

DIVISION 21: FIRE SUPPRESSION SYSTEMS SECTION Fire Protection Systems Protecting Cold Storage and Unheated Warehouses

SECTION TOTAL FLOODING ECARO-25 CLEAN AGENT FIRE EXTINGUISHING SYSTEM

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi 50 CONTROL PANEL

Superior by Design The Kidde ADS TM FM-200 System

June 20, 2011 PARTIES INTERESTED IN FIXED CONDENSED AEROSOL FIRE-EXTINGUISHING SYSTEMS

Capital Projects Group Fire Extinguishers Specification

Technical Data. Approvals The 1-1/2 in. to 8 in. (DN40 to DN200) DV-5 Red-E Cabinets are UL Listed and C-UL Listed with the following system types:

Industrial Dry Chemical Fire Suppression System

DV-5 Red-E Cabinet Integrated Deluge Fire Protection Package. General Description. Technical Data. Page 1 of 6 AUGUST 2018 TFP1300. Worldwide Contacts

SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPULSE VALVE, FK AGENT & CHEETAH Xi 50 CONTROL PANEL

SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPULSE VALVE, FK AGENT & CHEETAH Xi CONTROL PANEL

Product Alert September 20, 2012

Technical Data. Approvals The 1-1/2 thru 8 inch (DN40 thru DN200) DV-5 Red-E Cabinets are UL Listed and C-UL Listed with the following system types:

D. Reference Standards (Utilize latest editions available):

FIRE SUPPRESSION SYSTEM

Technical Data. Working Pressure Range 20 to 250 psi (1,4 to 17,2 bar)

SECTION KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

Linear Heat Detection Engineering Specifications

Worldwide Contacts.

TECHNICAL DATA OBSOLETE

C E R T I F I C A T E O F C O M P L I A N C E

Model DDX Deluge Valve

special request FACTORY ASSEMBLED UPRIGHT WITH SCREW FIELD ASSEMBLED MODEL S2 SHIELD (SEE INSTALLATION SECTION) WRENCH FLATS *

Design & Construction Standards, Revised January

Data/ Specification Sheet

CERTIFICATE OF FIRE APPROVAL

Sinorix Engineered Fire Suppression Systems For use with Novec TM 1230 Fire Protection Fluid and HFC-227ea

Model G5-56 Dry (SIN RA5114) K5.6 (80 metric) Concealed Dry Pendent Sprinkler

ANSUL. Twin-Agent Fire Fighting/Securing Systems Specifications. Models 450/50-B, 450/100-B, 900/100-B INDEX SPECIFICATIONS

KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

Twin-Agent Fire Fighting/Securing Systems Specifications

Model DV-5 Red-E Cabinet 1-1/2 thru 8 Inch (DN40 thru DN200), 250 psi (17,2 bar) Integrated Deluge Fire Protection Package General Description

TECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEUMATIC RELEASE 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3.

Model DV-5 Red-E Cabinet 1-1/2 thru 8 Inch (DN40 thru DN200), 250 psi (17,2 bar) Integrated Preaction Fire Protection Package General Description

DETECT-A-FIRE Heat Detectors

PRODUCT MANAGEMENT BULLETIN# 171b

CHAPTER THREE SPRINKLER SYSTEM AND FM-200 AGENT SYSTEM

TECHNICAL DATA. 319a. January 27, 2012

Series TY-FRL 2.8, 5.6, and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General Description

SECTION CLEAN AGENT FIRE SUPPRESSION SYSTEMS

FireFlex DUAL Double Interlock, Self-contained system

NITROGEN-GENERATING SPRINKLER CORROSION INHIBITING SYSTEM

Series ELO-231 Upright and Pendent Sprinklers. Standard Response, Standard Coverage, General Description

Badger Universal Control Head

TECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEU-LECTRIC RELEASE

Model JL-14 (SIN RA1812) K14.0 (200 metric) Early Suppression Fast Response Sprinkler

UNIFIED FACILITIES GUIDE SPECIFICATIONS

SECTION FIRE-SUPPRESSION STANDPIPES

Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General Description

Application of BS 8489 to the Protection of Generator Enclosures. IWMA, BRE 22 nd March 2017 Dr Tim Nichols CPhys FIFireE

BOC FS125 The Fire Extinguishing Solution

Model/Sprinkler Identification Numbers

Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K Upright, and Pendent Extended Coverage Light and Ordinary Hazard General Description

WRENCH FLATS NPT 1/2" 7/16" (11,1 mm) NOMINAL MAKE-IN. 1-1/2" (38,1 mm) 2-3/16" (55,6 mm) WRENCH NPT. (12,7 mm) NOMINAL MAKE-IN.

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE

SECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE

WORMALD INTERNATIONAL ELECTRIC VALVE ACTUATOR

PRODUCT LISTING DATA SHEET (Active Fire Protection Equipment)

SECTION COMMERCIAL-KITCHEN HOODS

TECHNICAL DATA OBSOLETE

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions:

Series EC K-factor Extended Coverage (Light Hazard) Pendent and Recessed Pendent Sprinklers General Description

Series ELO-231B 11.2 K-factor Upright and Pendent Sprinklers. Standard Response, Standard Coverage, General Description

Module 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements

Australian Standard. Gaseous fire extinguishing systems AS (Incorporating Amendment No. 1) AS

ESCUTCHEON PLATE SEATING SURFACE. 1-11/16" (42,7 mm) CROSS SECTION

Liberty Township Fire Department Fire Prevention Bureau. Clean Agent Fire Protection Plan Submittal Checklist

O-RING UPRIGHT SHIELD WRENCH FLATS WRENCH FLATS FIGURE 1 SERIES TY-B UPRIGHT (TY3153) AND PENDENT (TY3251) SPRINKLERS

AEGIS FEATURES DESCRIPTION. Conventional Fire Alarm-Suppression Control Unit. Effective: March Programmable Relays

Model MBEC-14. Extended Coverage Ordinary & Extra Hazard Horizontal Sidewall Sprinklers for Metal Building Applications. Model MBEC-14 (SIN R6932)

Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage

Model F3 Dry Sprinklers

Western Michigan University Facilities Management Engineering Division

MSC Guidelines for Watermist Fire Suppression Systems Procedure Number: E1-03 Revision Date: 02/16/2017

CLEAN AGENTS Updates to the NFPA 2001 Standard on Clean Agent Fire Extinguishing Systems 2015 Edition

Firefly II Multi Voltage RELEASE DEVICES. Firefly II & IIB-MV INSTALLATION MANUAL

Model G5 Series Sprinkler Summary. Listings and Approvals. G4/G5 QR Gasket culus QR G4/G5 SR Gasket culus, FM SR G4/G5

Revision May All designs must be submitted to FM Global for review and approval prior to issuing such for bids.

Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K Upright and Pendent Extended Coverage Light and Ordinary Hazard General Description

UFGS (August 2008) UNIFIED FACILITIES GUIDE SPECIFICATIONS

Model F1 Residential Sprinklers for Design Density of.10 gpm/ft 2

Integrated Fire Protection System. Owner's Operation and Maintenance Manual

Transcription:

1. GENERAL SPECIFICATION 1.1 A total flooding, Novec 1230 fluid, fire suppression system, super-pressurized with dry nitrogen shall be installed to meet a minimum design concentration of %, by volume in all designated spaces to be protected. 2. CODES/STANDARDS COMPLIANCE 2.1 The design, installation, testing and maintenance of the above stated Novec 1230 fire protection fluid suppression system, shall be in accordance to the following codes, standards and regulatory bodies: A. NFPA 2001 Standard for Clean Agent Fire Extinguishing Systems 2004 edition. B. NFPA 12A Halon 1301 Fire Extinguishing Systems C. UL 2166 Standard for Halocarbon Clean Agent Extinguishing System Units D. Factory Mutual Approval Guide E. ANSI B1.20.1 Standard for pipe threads, General Purpose, 1992 F. Design and installation practices set forth by system manufacturer G. NFPA 70 - NEC National Electrical Code H. NFPA 72 National Fire Alarm Code I. Requirements of the Local Authorities Having Jurisdiction (AHJ) 2.2 The Fire suppression system must have the following listings and approvals: A. FM Approved Factory Mutual Research Center B. UL 2166 Listed Underwriters Laboratories Inc. 2.3 The manufacturer shall meet ISO 9001 requirements for the design, production and distribution of the Novec 1230 fire suppression systems. 3. SYSTEM DESCRIPTION 3.1 All Novec 1230, fire suppression equipment and accessories must be manufactured by: Kidde Fire Systems: 400 Main Street, Ashland, MA 01721 U.S.A. phone: (508) 881-2000 URL: http://www.kiddefiresystems.com March 2005 1 of 5 www.kiddefiresystems.com

3.2 The manufacturer shall warrant all Novec 1230 fluid, fire suppression system products for 36 months from date of shipment or one (1) full year from the date of installation. 3.3 The system shall be supplied and installed by a factory-authorized, Kidde Fire Systems distributor. The distributor / Installer shall be trained by the manufacturer to calculate / design, install, test and maintain the Novec 1230 fluid fire suppression system and shall be able to produce a certificate stating such on request. 3.4 The systems design can be of a Modular, Central storage and or a combination of both. 3.5 The total flooding system shall consist of a Kidde Agent Storage Cylinder, Kidde actuation hardware and system distribution nozzles attached to a pipe network. 3.6 (OPTIONAL EQUIPMENT) Novec 1230 fluid Cylinders of 125-lb or greater capacity shall have the option of a Liquid level indicator. This device will provide a reliable means other than weighing for determining the agent weight with the storage container during normal routine servicing. 4. COMPONENTS 4.1 Novec 1230 fluid Cylinder and Valve Assembly A. Novec 1230 fluid shall be stored in a Kidde Engineered Cylinder(s) P/N 45-100XXX- XXX. Operating pressure of the Novec 1230 fluid system shall be at 360 psig @ 70 F. B. Novec 1230 fluid storage cylinders shall be provided with a safety rupture disc. An increase in internal pressure due to high temperature shall rupture the safety disc and allow the contents to vent before the rupture pressure of the container is reached. The contents shall not be vented through the discharge piping and nozzles. Novec 1230 fluid containers shall be equipped with a pressure gauge to indicate the internal pressures. The gauge shall be an integral part of the equipment and shall be color-coded for fast referencing of pressure readings. C. A low-pressure switch shall be provided on all the Novec 1230 fluid agent containers. A decrease in pressure will cause the normally open contacts to close, indicating a trouble condition at the CIE. The low pressure switch shall be field removable/replaceable while the container is still fully charged D. The Novec 1230 fluid cylinder shall be provided with a safety rupture disc. March 2005 2 of 5 www.kiddefiresystems.com

4.2 Kidde Actuation hardware A. The Novec 1230 fluid Cylinder valve assembly shall be actuated using a Kidde electric control head, electric / cable control head or lever operated control head. B. (OPTIONAL EQUIPMENT): pneumatic actuation of the Novec 1230 fluid Cylinder valve can be accomplished by using a nitrogen pilot Cylinder Kidde P/N s 877940 or 06-129773-00X 4.3 Distribution Nozzles A. Engineered discharge nozzles for use with the Novec 1230 fluid system will be made of Brass or Stainless steel, Kidde P/N 45-1947XX-XXX or 45-1946XX-XXX respectively. B. Each nozzle shall be located in the space per the manufacturers guidelines, Nozzles can have either a 180 or a 360-degree discharge pattern. C. Each Nozzle discharge pattern shall be available in sizes ranging from 3/8 NPT to 2 NPT. (1/4 if non-listed systems are requested) 4.4 Pipe Network A. Distribution piping and fittings shall be installed in accordance with NFPA 2001, approved piping standards and system manufacturer s requirements. 5. SUBMITTALS 5.1 Engineered Design Drawings A. The factory-authorized Kidde Fire Systems Distributor shall provide all required installation drawings per NFPA 2001. 5.2 Flow Calculation Reports A. The contractor shall provide the following information in the flow calculation report. 1. Customer Information and Project Data 2. Enclosure Information at a minimum, enclosure information is to include Minimum and adjusted design concentrations, Minimum enclosure temperatures, minimum agent required, volume of enclosures and agent discharged. 3. Agent information at a minimum, agent information is to include Cylinder size and part number, quantity of cylinders, main and / or reserve cylinders and pipe take off direction. March 2005 3 of 5 www.kiddefiresystems.com

4. Pipe network information at a minimum, pipe network information is to include pipe type, pipe diameter, pipe length, change in direction or elevation, and any added accessory equivalent length. In addition, the following nozzle information shall be provided; number of nozzles and identification of enclosure location, flow rate of associated nozzle, nozzle nominal size, nozzle type and nozzle orifice area. 5. Detailed list of all Pipes and Pipe Fittings designed in the pipe network 5.3 Commissioning Equipment List A. The contractor shall provide a commissioning equipment list for each installed Novec 1230 fluid suppression system. The equipment list shall identify all installed equipment and configurations. 5.4 Test Plan A. The contractor / installer shall submit a test plan which describes how the system equipment and room integrity shall be tested. This shall include a step-by-step description of all tests and shall indicate type and location of test apparatus to be used. At a minimum, the tests to be conducted shall be per NFPA 2001 and any additional supplemental tests required by the AHJ. Tests shall not be scheduled or conducted until the engineer of record approves the test plan. 5.5 Installation Drawings A. Four (4) sets of installation drawings for each installed Novec 1230 fluid suppression system and One (1) set of the calculation report, owners manual and product data sheets shall be submitted to the end-user / owner. B. Upon completion of installation and commissioning acceptance, two (2) sets of As- Built installation drawings and One (1) set of the calculation report for each installed Novec 1230 fluid suppression system shall be given to the owner / end-user for use and reference. 5.6 Operation and Maintenance Manuals A. Two (2) copies of the Kidde engineered fire suppression system; Operation and Maintenance Manual shall be submitted after complete installation. 6. SYSTEM INSTALLATION AND COMMISSIONING 6.1 Fire Suppression System Equipment employing Novec 1230 fluid. A. The contractor shall install the system in accordance with the manufacturer s installation, operation and March 2005 4 of 5 www.kiddefiresystems.com

6.2 Training Requirements A. The contractor shall be certified and trained by the manufacturer on installation, design and maintenance of the Kidde Novec 1230, Novec 1230 fire suppression systems. 6.3 Routine Maintenance A. Routine maintenance shall be performed as recommended by the manufacturer s installation, operation and At a minimum the routine maintenance will include the following: 1. Visual Check of Pipe network and distribution nozzles per the operation and 2. Weight and pressure of the Novec 1230 fluid cylinder per the operation and 3. Inspect all cylinders and equipment for damage per the operation and March 2005 5 of 5 www.kiddefiresystems.com