PACKAGED UNITS KITS AND ACCESSORIES 10/2009 INSTALLATION INSTRUCTIONS FOR SMOKE DETECTOR KITS USED WITH KC/KG/KH & LCH/LGH UNITS

Similar documents
PACKAGED UNITS KITS AND ACCESSORIES. 7/2011 Supersedes 5/2011

INSTALLATION INSTRUCTIONS

COMMERICAL SPLIT SYSTEM KITS AND ACCESSORIES /2012 Supersedes

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS

Installation Instructions

GENERAL. Model 2SD UAI-A Before installing read all of the manufacturers installation and maintenance instructions.

USER'S INFORMATION MANUAL

Installation in Standard & Variable Speed Indoor Air Handlers IMPORTANT

INSTALLATION INSTRUCTIONS

SLP98UHV WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature

INSTALLATION INSTRUCTIONS

Installation Instructions

BK AND BKT BLOWER ACCESSORY INSTALLATION INSTRUCTIONS

Installation Instructions

G71MPP WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature

SERVICE MANUAL FOR 6636A & 6636B SERIES TWO TON HIGH EFFICIENCY PACKAGED AIR CONDITIONERS

WARNING: ELECTRICAL GROUNDING INSTRUCTIONS

INSTALLATION INSTRUCTIONS FOR 7330*5511 OR 7330*5512 MOUNTING KIT 7330B751 CONTROL BOX KIT (12 VDC COOL ONLY)

Installation Instructions

COMMERCIAL ELECTRIC DRYER

INSTALLATION INSTRUCTIONS FOR 8330*5511 MOUNTING KIT

AMERITROL, INC. INSTALLATION OPERATION MANUAL AND WIRING DIAGRAM LX SERIES LIQUID LEVEL SWITCH. Manual Number: LX-DualSP A

LGH/LCH WARNING. CAUTION Danger of sharp metallic edges. Can cause injury. Take care when servicing unit to avoid accidental contact with sharp edges.

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS FOR 6536 SERIES TWO TON PACKAGED HEAT PUMP

PUREPOWER SERIES CENTRAL VACUUM POWER UNITS PP500, PP600 & PP650

AMERITROL, INC. INSTALLATION OPERATION MANUAL AND WIRING DIAGRAM FX SERIES FLOW SWITCH WITH ADDITIONAL TEMPERATURE SWITCH. Manual Number: FXTX2116-1

Installation Instructions

ACCESSORY INSTALLATION INSTRUCTION ELECTRIC HEAT ACCESSORY 10, 16, 26, 36 & 72

INSTALLATION INSTRUCTIONS FOR 6797A737 HEAT PUMP FLUSH MOUNT CEILING PLENUM

INSTALLATION INSTRUCTIONS

GAS UNITS KITS AND ACCESSORIES 505,172M 08/06

Installation Instructions for Med Touch Master Alarms - Wireless

INSTALLATION INSTRUCTIONS FOR MOUNTING KIT

Model 1820 Dehumidifier

INSTALLATION INSTRUCTIONS

CABINET PARTS For Model: KBFC42FTS03 (Stainless Steel)

INSTALLATION INSTRUCTIONS FOR 7330C740 FLUSH MOUNT CEILING ASSEMBLY

LZP-2 ZONE CONTROL PANEL

Operating and Installation Instructions

GAS DRYER MODELS: WGD8000DW0 (White) 03/30/ Whirlpool Corporation Part No. W Rev. C

COMMERCIAL ELECTRIC DRYER

HEATING AND AIR CONDITIONING

G60UH(X) WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature

Installation Guide for inbiox60 Series Access Control Panel

L SERIES UNITS 504,520M. 10/2001 Supersedes 504,413M

INSTALLATION INSTRUCTIONS FOR 6636 SERIES PACKAGE AIR CONDITIONER

Installation Instructions

KG 092 SHOWN READ ALL INSTRUCTIONS IN THIS MANUAL AND RETAIN FOR FUTURE REFERENCE WARNING

INSTALLATION INSTRUCTIONS FOR SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMP

Engine Block Heater Service Kits (Tank Type) ROZJ 6076T and 6076A (John Deere Powered Standby Generator Sets)

Installation Instructions

INSTALLATION INSTRUCTIONS FOR 7370A736 FLUSH MOUNT CEILING PLENUM

Installation Instruction

MIST MAX MODEL MM800. Important: Installation and Operation Manual

Duct smoke housings, 4-wire D341/D341P and D342/D342P

Installation Instructions

Installation Instructions

AMERITROL, INC. INSTALLATION OPERATION MANUAL AND WIRING DIAGRAM LX SERIES LIQUID LEVEL SWITCH. Manual Number: LX-SPDT A

D343. Installation Instructions. Air Duct Smoke Housing

INSTALLATION INSTRUCTIONS

SEALED ENCLOSURE COOLING

50M56U-843 INSTALLER MUST READ DESCRIPTION PRECAUTIONS WARNING CAUTION

INSTALLATION INSTRUCTIONS

GAS DRYER MODELS: (White) (Chrome Shadow) 01/28/ Sears Brands, LLC Part No. W Rev. A

ELECTRONIC AIR CLEANER SAFETY AND INSTALLATION MANUAL MODEL 5000 TABLE OF CONTENTS

AMERITROL, INC. INSTALLATION OPERATION MANUAL AND WIRING DIAGRAM LX SERIES LIQUID LEVEL SWITCH WITH ADDITIONAL TEMPERATURE SWITCH

TOP AND CONSOLE PARTS

Commercial Series. Power switch & Nameplate location: NAMEPLATE: Single and Dual Section

GE Monogram. Installation. Instructions. Component Cooktop System. Models ZEW145V ZGW124EN3 ZGW125EN3 ZEW155N ZEW166Y ZEW176Y

INSTALLATION INSTRUCTIONS FOR 8330*633* COOL ONLY A/C 8330*635* HEAT READY A/C 8530*63** HEAT PUMP CHILLGRILLE FLUSH MOUNT CEILING ASSEMBLY

ACT-HSC Series Heat Sink Coolers Sealed Enclosure Cooling Installation Guide

COMMERCIAL ELECTRIC DRYER

INSTALLATION INSTRUCTIONS

Installation Instructions

B24 SERVICE UNIT INFORMATION B24 SERIES ADD-ON BLOWER ECB24 SERIES ELECTRIC HEAT

Installation Instructions

Installation Instructions

Replacement Parts List

Send Via: Direct Fax: Feedback ID: Additional Request: Action: MISSING To: DAN GRIMWOOD

LaserGuard2. Laser Collision Avoidance System. Part Number: R1 April 2015 Copyright 2015 Magnetek Material Handling

Installation Instructions

Model Gas Alarm Panel APPLICABILITY & EFFECTIVITY. This manual provides instructions for the following Sierra Monitor products:

Important Information

Insert Manual. RHT Series WARNING. For Your Safety

INSTALLATION INSTRUCTIONS FOR 8330*63**, 8530*63** CHILLGRILLE FLUSH MOUNT CEILING ASSEMBLY

COMMERCIAL ELECTRIC DRYER MODELS: MLE26PDBZW1 (White) 01/14/ Maytag Part No. W Rev. A

Electric Heat Accessory Installation Instructions

ACCESSORY KIT INSTALLATION INSTRUCTIONS

COMMERCIAL ELECTRIC DRYER MODELS: MLE27PDBYW1 (White) 01/19/ Maytag Part No. W Rev. A

GAS-ON-GLASS COOKTOP

DISHWASHER INSTALLATION GUIDE SPECIFICATIONS, INSTALLATION, AND MORE

INSTALLATION INSTRUCTIONS FOR 9330F4552 FREE DELIVERY PLENUM KITS

INSTALLATION INSTRUCTIONS

Installation Instructions Part No

Advantage Series Bathing System Specifications

DH200PL Intelligent Air Duct Smoke Detector with Extended Air Speed Range

Steam Humidifier Fan Pack Installation & Maintenance Instructions

Transcription:

Litho U.S.A. 2009 PACKAGED UNITS KITS AND ACCESSORIES 506218 01 10/2009 D4P120 & D4S KITS INSTALLATION INSTRUCTIONS FOR KITS USED WITH KC/KG/KH024 090 & LCH/LGH036 072 UNITS Shipping and Packing List 53W78 single sensor kit contains the following: 1 Smoke detector sensor 1 Smoke detector power board 1 Supply bracket 1 Supply brace 1 Return bracket (used on KC, KG & KH units only) 1 Return brace (used on KC, KG & KH units only) 1 Power harness (used on KC, KG & KH units only) 1 Sensor harness (used on KC, KG & KH units only) 1 Jumper harness (used on LCH & LGH units only) 1 Metal sampling tube 1 Plastic exhaust tube 1 Magnet 1 Sensor manufacturer s instructions #10 16 X 3/4" sheet metal screws #8 32 X 1" thread forming screws 53W79 dual sensor kit contains the following: 2 Smoke detector sensors 1 Smoke detector power board 1 Supply bracket 1 Supply brace 1 Return bracket (used on KC, KG & KH units only) 1 Return brace (used on KC, KG & KH units only) 1 Power harness (used on KC, KG & KH units only) 1 Sensor harness (used on KC, KG & KH units only) 2 Metal sampling tubes 2 Plastic exhaust tubes 2 Magnets 1 Sensor manufacturer s instructions #10 16 X 3/4" sheet metal screws #8 32 X 1" thread forming screws Application LCH and LGH Units Smoke detector will send a 24Vac signal to the unit A55 IMC when smoke is sensed. IMC default mode will de energize unit. 10/09 Page 1 KC, KG and KH Units Smoke detector will interrupt the 24Vac signal to the unit control circuit when smoke is sensed. Unit will be de energized. Installation WARNING Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a licensed professional installer, service agency or the gas supplier. CAUTION Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch. CAUTION Danger of sharp metallic edges. Can cause injury. Take care when servicing unit to avoid accidental contact with sharp edges. Smoke detector sensor and power board installation Use manufacturer s instructions provided with smoke detector to install sensor(s) and power board. Refer to figure 1 for location of power board, supply air sensor and return air sensor on units with an economizer. For location of return air sensor on units without an economizer, refer to figure 2 for KC, KG and KH units, and figure 3 for LCH and LGH units. Sampling tube installation 1 Slide metal sampling tube onto the back side of the sensor as shown in figure 4. When sensor is installed in return air applications, slide plastic exhaust tube onto back side of the sensor as shown in figure 4. NOTE Plastic exhaust tube is NOT used in supply air applications and should be discarded. 2 Orient sampling tube so that holes point toward the air stream. 506218 01

SAMPLING (See detail to the right) COMPONENT LOCATIONS (Units with an Economizer) DETAIL pointing into air stream) 0.250 BRACE SAMPLING pointing downward) FIGURE 1 LOCATION LC and LG Units LOCATION KC, KG and KH Units INSTALLATION (KC, KG and KH Units without an Economizer) SIDE MULLION FRONT MULLION FRONT MULLION Align 3 holes on bracket with 3 dimples on outside of mullion. BRACE FLANGE FRONT OF UNIT FIGURE 2 Page 2

COMPONENT LOCATIONS (LCH and LGH Units without an Economizer) pointed into air stream) FACTORY INSTALLED BRACE SAMPLING pointing downward) FIGURE 3 WITH SAMPLING TUBE AND EXHAUST TUBE PLASTIC EXHAUST TUBE (Used in return air applications only) METAL SAMPLING TUBE (Point sampling holes toward air stream) HEAD MAGNET TEST LOCATION FIGURE 4 Page 3

Wiring KC, KG and KH Units 1 Make jack/plug connections as shown in figure 7 when installing return air smoke detector only, figure 8 when installing supply air smoke detector only, and figure 9 when installing both supply and return air smoke detectors. 2 Route harness wires to the top of the unit. Secure to existing bundle of wires and route to control area above compressor. See figure 5. Make sure wires are secured away from other components. NOTE In single sensor applications, the wiring harness is sized for return air applications. There will be excess wiring in supply air applications. Gather excess wire and secure away from other components. WIRE ROUTING KG, KC & KH UNITS ROUTE THROUGH FOAM INSULATION TUBE BETWEEN BLOWER AND COMPRESSOR SECTIONS ROUTE THROUGH PLASTIC CONDUIT OVER FILTER FRAME FIGURE 5 FILTER ACCESS PANEL 3 Locate and disconnect wires labeled and 96 in control area above compressor. See figure 6. 4 Connect wires labeled, 96 and TB1C from the kit harness to wires labeled, 96 and TB1C in unit. KC, KG & KH CONTROLS AREA DISCONNECT WIRES LABELED AND 96 A3 Gas Units CMC1 Heat Pumps T3 TB1 K8 / K72 K10 K58 N L1 K1 FIGURE 6 K3 L2 SEE UNIT WIRING DIAGRAM B SECTION FOR A DESCRIPTION OF COMPONENTS T4 S42 T1 C1 OR C12 LCH and LGH Units Make jack/plug connections as shown in figure 10 when installing return air smoke detector only, figure 11 when installing supply air smoke detector only, and figure 12 when installing both supply and return air smoke detectors. Plugs are located in the unit near the location of the sensor(s) and power board. Test Magnet(s) A test magnet is provided in a bag assembly with each sensor. Remove the magnet from the bag assembly and place it on a metal surface near the sensor. The magnet is used during test procedures. Maintenance and Test Procedure Instructions The sensor manufacturer s instructions, which are provided with each sensor, outline information on maintenance and test procedures. Place these instructions in the literature pouch for future reference. 96 Page 4

KC, KG or KH Unit Application with Single Return Air Smoke Detector 96 TB1C J251 P251/P253 Sensor Harness Power Harness FIGURE 7 KC, KG or KH Unit Application with Single Supply Air Smoke Detector 96 TB1C J251 P251/P253 Sensor Harness Power Harness FIGURE 8 KC, KG or KH Unit Application with Return Air and Supply Air Smoke Detectors (Note: Change power board DIP switch setting to 2) 96 TB1C J251 P251 J253 P253 Power Harness P252 Sensor Harness FIGURE 9 Page 5

LCH or LGH Unit Application with Single Return Air Smoke Detector J251 P251 FIGURE 10 LCH or LGH Unit Application with Single Supply Air Smoke Detector P252 J261 J253 P253 JUMPER HARNESS FIGURE 11 LCH or LGH Unit Application with Return Air and Supply Air Smoke Detectors (Note: Change power board DIP switch setting to 2) J251 P251 J253 P253 P252 FIGURE 12 Page 6