Weekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture

Similar documents
Weekly Testing of Dedicated Stairwell Pressurization Fans- Metasys System Extended Architecture Code No. LIT

Single Story Enclosed Shopping Mall Smoke Control with FSCS Override - Metasys System Extended Architecture

Multi-Story Building Smoke Control with FSCS Override - Metasys System Extended Architecture

DX-9100/9120 Weekly Testing of Dedicated Stairwell Pressurization Fans

Metasys System Extended Architecture Smoke Control UL 864 UUKL Compliance

DX-9100/9120 Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit

Multi-Story Building Floor Above/Floor Below Pressurization and Exhaust Logic

Metasys System Extended Architecture Fire System Integration Using the IFC BACnet Gateway

DX-9100/9120 Local Sonalert Logic

Metasys System Extended Architecture Smoke Control System

York 25-Ton VAV Rooftop Unit

Fire System Objects. Introduction Page *3. Engineering *17. Data Base Generation *43

Fire Operator Workstation (Fire OWS) User s Guide

Warehouse Smoke Exhaust and Reset Logic for a Rooftop Unit

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

TC-9102 Applications

Multistate Alarm. Introduction

P2000 and Metasys System Integration

Simplex Panel Interface Guide

Reciprocating Chiller

P2000 and Metasys System Integration

Metasys Integrator TITUS Application

Using the Room View Window

Avigilon Control Center 5 System Integration Guide

DX-9100 Applications from Engineering Services

Solution Guide. UUKL Smoke Control System. 1/6. UL 864, 9th Edition, UUKL Smoke Control Listing. Overview

Metasys Integrator Compu-Aire Application

Ion Gateway Cellular Gateway and Wireless Sensors

HikCentral Web Client. User Manual

Metasys Integrator Airflow Application

HikCentral Web Client. User Manual

JCI - Smoke Control Systems Overview 10/27/2016

UNT Applications. Using UNT Applications...3. Introduction Key Concepts UNT Controller Applications Fan Coil Units...

i-vu CCN 4.0 Owner s Guide

Raytec Avigilon Integration User Guide Integrating Raytec Network Illuminators with Avigilon Control Center Document Revision 2.0

Avigilon System Integration Guide. Avigilon Control Center with AMAG Symmetry Security Management System 7.0

TEC Networked Multi-Stage Economizer Thermostat

Metasys Integrator Cleaver-Brooks Application

Version 1.03 January-2002 USER S MANUAL

ExactLogic BACnet Communicating Thermostat EXL01625 Sequence Datasheet Fan Coil with Modulatating H/C and PO-PC H/C

Monitoring Operator Guide. Access Control Manager Software Version

IndigoVision Alarm Panel. User Guide

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

LineGuard 2300 Program User Manual (FloBoss 107)

ExactLogic BACnet Communicating Thermostat EXL01622 Sequence Datasheet

Graphics+ Runtime Help Code No. LIT Software Release 1.3 Issued September 10, 2014

Johnson Controls Fan Coil Units and Direct Digital Controls

Feature Summary. I. System

TEC Networked Single-Stage Thermostat

Halton SAFE / 7.14 user guide and installation instructions

Table of Contents. i-vu CCN Standard 4.2

ExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling

DACC - NMDA BUILDINGS

Setting up and Managing Alarms in McAfee ESM 10.x

Instruction manual MTL process alarm equipment. October 2016 CSM 725B rev 2 MTL RTK 725B. Configuration Software Manual

Smoke Control Manual

PolyGard Controller LGC/LG2-04. Multi-Point Controller Serial Number S00 User Manual Preliminary Version. August 11, 2006

MultiSite Manager. Setup Guide

TEC1100 Series Thermostats

ArchestrA Direct Connect

TEC210x-2 Series Networked Thermostats

Oracle Communications Performance Intelligence Center

Yokogawa DX Ethernet Driver Help Kepware Technologies

Verasys System Operation Overview Technical Bulletin

Monitor Alarms and Events

Laptop / PC Programming Manual

HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER

Manual# User s Manual. 200E Series. DCU 210E/208E Diesel Engine Control Unit RP 210E Remote Panel

Tebis application software

Ovation Alarm Management System

Avigilon Control Center System Integration Guide

RTO. User guide 05/

Synergis Master Controller 2.2 Integration Guide for Assa Abloy IP Locks

Alarm Coordination Connected Components Building Block. Quick Start

System Galaxy Quick Guide

Getting Started with Live Exceptions

Avigilon Control Center System Integration Guide

Alarm Client. Installation and User Guide. NEC NEC Corporation. May 2009 NDA-30364, Revision 9

Autoclave Operations Manual

Paradox Integration Module Settings Guide

Avigilon Control Center 5 System Integration Guide

Installation, Configuration and User Manual

Challenger Series Users Manual

Niagara4 Technical Certification Program Student Guide DAY 1 DAY 2

TEC Networked Multi-Stage Thermostat

Manual# User s Manual. 200 Series. DCU 210/208 Diesel Engine Control Unit RP 210 Remote Panel

Installation and Operation. Tracer ZN521 Zone Controller CNT-SVX07C-EN

ZX1e ZX2e ZX5e. Document No Issue 01 user manual

Avigilon Control Center 5 System Integration Guide

Section 8 System Operation

Alarm Calendar Version 1.10

WorkstationST* Alarm Viewer

TEC2100 Series Networked Thermostats

CODE ALERT Enterprise Software User Guide

ELT-KLED EliteSuite LED Keypad Installation Manual

BACnet Points List for Single Compressor Water to Water PROSSWWE-01

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

Document # R01

BOSCH GV4 Alarm Panel

Avigilon Control Center System Integration Guide

Transcription:

Weekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture Code No. LIT-1201743 Release 1.2 Issued Date July 30, 2004 Supersedes Document Introduction................................................. 3 Related Documentation................................................. 3 Application Overview.................................................. 4 Smoke Control Command Priorities......................................... 4 Automatic Smoke Control During Weekly Testing.............................. 5 Manual Smoke Control During Testing....................................... 5 Assigning the Fire Object Category to Smoke Control Objects................... 5 Security Administration System............................................. 6 Roles and User Accounts Overview........................................... 6 UUKL Smoke Control Security Administration Details.............................. 6 Security Administration Detailed Procedures..................................... 8 Creating a New Role........................................................... 8 Creating a New User Account.................................................... 8 Configuring User Profiles........................................................ 8 Configuring Role Properties..................................................... 9 Assigning System Access Permissions............................................. 9 Design Considerations................................................. 9 Smoke Control NAE Design Considerations................................... 9 Field Controller Point Design Considerations................................ 10 Field Controller Points................................................ 12 Field Controller Selection................................................. 12 Point List............................................................... 12 Smoke Control NAE Application........................................ 13 Application File Location................................................. 13 Metasys System Extended Architecture Objects.............................. 13 Damper 6-1............................................................ 14 Weekly Dedicated Damper Test............................................ 19 Weekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture 1

Weekly Dedicated Damper Test Alarm Screens............................... 26 Weekly Test Schedule.................................................... 30 2

Weekly Testing of Dedicated Smoke Control Dampers - Metasys System Extended Architecture Document Introduction Smoke control applications issue commands to controlled devices that pressurize or depressurize an area of a building to minimize the spread of smoke. This document describes weekly testing of a dedicated smoke control damper in the Metasys system extended architecture.this application is designed to provide a weekly test of a dedicated smoke control damper automatically. Note: This application note only presents an example of one smoke control strategy. Since every building is unique, details of applying the strategy vary. This application note can assist you to develop an appropriate application for your project. Related Documentation Table 1: Related Documentation For Information On Refer To LIT No./Part No. General smoke control information Specific wiring requirements Logic programming for the DX-9100 controller Single story enclosed shopping mall smoke control Multi-story building smoke control Warehouse smoke control Weekly testing of stairwell pressurization fans UL 864 UUKL Requirements Metasys System Extended Architecture Smoke Control System Technical Bulletin Metasys System Extended Architecture Smoke Control Wiring Technical Bulletin GX-9100 Software Configuration Tool Technical Bulletin Single Story Enclosed Shopping Mall Smoke Control with FSCS Override - Metasys System Extended Architecture Multi-Story Building Smoke Control with FSCS Override - Metasys System Extended Architecture Warehouse Smoke Control with FSCS Override - Metasys System Extended Architecture Weekly Testing of Dedicated Stairwell Pressurization Fans Metasys System Extended Architecture MSEA Smoke Control UL 864 UUKL Compliance Checklist LIT-1201684 LIT-1201753 LIT-6364060 LIT-1201736 LIT-1201737 LIT-1201738 LIT-1201739 LIT-1201754 3

Application Overview This application is designed to perform a weekly test of a dedicated smoke control damper automatically. A schedule on the smoke control NAE commands the weekly dedicated damper test. A Trouble alarm is issued if the status feedback indicator from the damper does not equal the damper command sent by the NAE. Note: Weekly dedicated damper test commands are issued at a Priority 7. A schedule on the Network Automation Engine (NAE) triggers the test, and the damper is commanded Open for 2 minutes. If the damper does not open on within 75 seconds of the controller s Open command, the damper s Trouble Light- Emitting Diode (LED) on the Firefighter s Smoke Control Station (FSCS) is turned on. After the first 2 minutes has expired the damper is then commanded to Close. If the damper does not close within 75 seconds of the controller s close command, the damper s Trouble LED on the FSCS is turned on. After the 2 minutes has expired, the test is disabled, the damper is restored to its normal state, and the Retry logic will retry the test every 60 minutes until the test passes. Once the weekly test passes, the logic will disable the weekly test until its next scheduled test time. The application contains logic that issues a Priority 7 command to Open the dedicated damper for 2 minutes. After 2 minutes has passed, the logic then issues a Priority 7 command to Close the dedicated damper. After 2 minutes has passed, the Priority 7 command is released. If the damper does not reach the desired feedback within 75 seconds, a Damper Failure BACnet Binary Value object (BV) is latched to true. The Auto Command Retry logic will retry the test every 60 minutes until the test passes. Once the weekly test passes, the logic will disable the weekly test until its next scheduled test time. The Alarm Logic process is triggered if any of the following occurs: a dedicated damper goes into alarm during the pressurization test. An alarm situation would occur if the fan feedback did not equal the fan command. the operator tests the alarm process manually. If the damper is in alarm and it is in the testing schedule and the Reset is false, the Sonalert is energized. Smoke Control Command Priorities All automatic smoke control commands are issued at Priority 3. Fire fighter manual overrides, issued from the FSCS panel to pressurize or depressurize zones, are commanded at Priority 2. Fire fighter manual overrides, issued from the FSCS panel to control individual fans and dampers, are commanded at Priority 1. Priority 3 commands are released when the smoke alarm is reset. Weekly test commands are issued at Priority 7. 4

Automatic Smoke Control During Weekly Testing Automatic smoke control operations that take place during a weekly dedicated damper test always override the weekly dedicated damper test. Manual Smoke Control During Testing Manual Smoke Control logic is initiated when a fire fighter turns the FSCS Panel Enable key from the Auto position to Fire Fighter Control position and changes a point from the Auto setting on the FSCS panel. Manual smoke control operations during a weekly dedicated damper test always override the weekly dedicated damper test. Assigning the Fire Object Category to Smoke Control Objects You must assign every object used specifically for smoke control as a Fire object. This limits the control of smoke control devices and points to authorized Fire operators.use the pull down menu to assign the Fire object category (Figure 1). Figure 1: Assigning the Fire Object to Smoke Control Objects! WARNING: Risk of serious injury or death if a smoke control object is not assigned as a Fire object! In the event of a fire or smoke control event, devices or points used for smoke control that are not assigned as Fire objects allow those devices and points to be controlled by non-fire authorized operators. It is imperative that every smoke control device or point be assigned as a Fire object. 5

Security Administration System The Security Administration system authenticates and authorizes users of Metasys system extended architecture applications. The Security Administrator is a browser-based interface that manages all accounts. Use the Security Administrator System to authenticate and authorize users on the Metasys system extended architecture. The Security Administrator creates User Accounts and Roles, and assigns access permissions to each user of the Metasys system extended architecture. Roles and User Accounts Overview Security is based on User Accounts and Roles. Roles are groups of users with a specific function within the Metasys system. To access the system, an individual provides a user account and the correct password. Use letters, numbers, or symbols to create user account passwords. Use the Login button from the logon prompt to send the user s credentials. A unique Session generates when the user s credentials match the logon requirements. UUKL Smoke Control Security Administration Details UUKL smoke control requires that only operators designated as fire operators be able to control the smoke control system. This required the creation of four new roles: 1. Administrator - This is the highest level of control and allows site control of all HVAC and Fire features.fire Administrator - This role is a fire manager level setting. It allows for full system control, including system modification or configuration. 6

2. Fire Administrator - This role is a fire manager level setting. It allows for full system control, including system modification or configuration. Figure 2: Fire Administrator Access Permissions 3. Fire User - This role is for most fire field technicians and allows system control and alarm acknowledgement, but not system modification or configuration. Figure 3: Fire User Access Permissions 7

4. Fire Limited - This is the lowest of the permissions and only allows the operator to view fire/smoke control devices and alarms. Security Administration Detailed Procedures Creating a New Role To create a new role: 1. From the Security Administration menu bar, select Insert > New Role. The New Role dialog box appears. 2. Fill in the information. 3. Click OK. The New Role appears in the tree. Creating a New User Account To create a new user account: 1. From the Security Administration menu bar, select Insert > New User. The User Properties tab appears. 2. Fill in the information. 3. Click OK. The New User appears in the tree. Configuring User Profiles To configure a user profile: 1. Select the user whom you wish to configure. 2. From the menu bar, select Edit > Properties. The User Properties tab appears. 3. Modify the desired user information. 4. Click OK. Figure 4: Fire Limited Access Permissions 8

Configuring Role Properties To configure role properties: 1. Select the user whom you wish to configure. 2. From the menu bar, select Edit > Properties. The User Properties tab appears. 3. Select the Roles tab, then select an Available Role. 4. Click Add. The selected role appears in the Assigned Role list box. 5. Click OK. Assigning System Access Permissions To assign system access permissions: 1. Select the user whom you wish to assign system access permissions. 2. From the main menu, select Edit > System Access Permissions. The System Access Permission dialog box appears. 3. Select an available privilege. 4. Click Add, then click OK to assign the user s System Access Permissions. Design Considerations This field controller and Smoke Control NAE application, as it exists in the Metasys System Extended Architecture Smoke Control Library, complies with the UL 864 UUKL Smoke Listing. However, you are responsible for ensuring that the application complies with state and local regulations, and is approved by the Authority Having Jurisdiction (AHJ). You are also responsible for configuring all of the smoke control components, as well as the programming of those components, in order to comply with the UL 864 UUKL Smoke Listing as documented herein. Smoke Control NAE Design Considerations Keep the following design considerations in mind when designing a weekly dedicated smoke control damper test. In addition, please refer to the Metasys System Extended Architecture Smoke Control System Technical Bulletin (LIT-1201684). The smoke control NAE reports critical alarms based on the alarm condition, and the alarm can only be cleared by resetting from the Intelligent Fire Controller (IFC) panel or the Firefighter s Smoke Control Station (FSCS). You must define the hardware location for each object You must name each object with a descriptive name that is unique in the system. 9

A Programming In Progress BV point is required. You must set this point to true any time you are making changes to the Smoke Control system. This will turn on the Programming In Progress LED on the FSCS to let a fire fighter know that changes are being made and the system may not be fully functional. The point must be turned off when changes are complete. Response time for individual smoke control components to achieve their desired state of operational mode, exclusive of control system response, should not exceed the following time periods: 75 seconds for completion of damper travel plus 90 seconds to annunciate. (Control system response is the time from automatic detection of a smoke condition to the issuing of an appropriate command to the equipment.) Field Controller Point Design Considerations There are a number of field controller that are UL Listed for Smoke Control that are suitable for use in this Metasys System Extended Architecture smoke control application. This document addresses the field points that must be programmed into the field controller, and does not specify which field controller to use. It is up to design engineer to select the field controller, and up to the installation technician to program these required points into the controller. The following field controllers are UL Listed for Smoke Control for Metasys system extended architecture systems: AP-VMA Series AS-AHU Series AS-UNT Series AS-VAV Series DX 9100 A field controller needs to provide the following BV points.: BV Command point for each damper BV Open feedback point for each damper BV Close feedback point for each damper This application can be expanded for a building with more than one dedicated smoke control damper. For further details, please contact Field Support Services in Milwaukee. You must define tag names for all points. You must define the hardware location for each object You must name each object with a descriptive name that is unique in the system. 10

An alarm occurs if the command does not equal the condition for any damper output. Each Binary Output (BO) for pressurization and exhaust outputs must be configured to have its own feedback (proof sensor) input. The FSCS indicates when a command does not equal condition. For UL compliance: Response time for individual smoke control components to achieve their desired state of operational mode, exclusive of control system response, should not exceed the following time periods: 75 seconds for damper operation at the desired state plus 90 seconds to annunciate. (Control system response is the time from automatic detection of a smoke condition to the issuing of an appropriate command to the equipment.) For DX-9100 controllers only: If DX Digital Inputs (DIs) are used for smoke control, then DI8 must be jumpered and mapped to the smoke control NAE as a normal state of On. If DI8 is off, a critical alarm must be issued at the FSCS to indicate a binary input fuse failure that must be fixed immediately, because the DI is no longer accurate. If DX Analog Outputs (AOs) are used for smoke control, then Analog Output 14 (AO14, voltage) must be wired to Analog Input 8 (AI8, voltage) and the AI must be mapped to the smoke control NAE with a low alarm limit of 20%. If the AI goes below this, it indicates the AO has failed because of a blown fuse, which drops the AO to 0V and the AI to 0% (low alarm). The DX is downloaded so that the AO is normally at 5V because its source point is an Analog Constant (ACO) with a default of 50. For specific wiring requirements, refer to Metasys System Extended Architecture Smoke Control System Wiring Technical Bulletin (LIT-1201753). 11

Field Controller Points Field Controller Selection There are a number of field controllers suitable for use in this smoke control application. See the Field Controller Point Design Considerations in the previous section for a list of controllers. This document addresses the field points that must be programmed into the field controller, and does not specify which controller to use. It is up to design engineer to select the appropriate field controller, and up to the installation technician to program these required points into the controller. Point List Table 2 shows the hardware point requirements for the GX configuration. Table 2: Hardware I/O Requirements Input Requirements Hardware Location Name of Module Engineer Units Req? Description AI8 AO-FUSE % Only for AI8 Fuse Check DX-9100 DI4 DMP1OPFB OFF/ON Yes Damper 1 Open Feedback DI5 DMP1CLFB OFF/ON Yes Damper 1 Close Feedback DI8 DI-FUSE OFF/ON Only for DX-9100 Output Requirements DI8 Fuse Check Hardware Location Name of Module Engineer Units Req? Description DO4 DMP1 OPN/CLO Yes Damper 1 12

Smoke Control NAE Application Application File Location The Metasys system extended architecture Weekly Testing of Dedicated Smoke Control Dampers application for the smoke control NAE is located on the Branch Project Package (BPP) CD under the Metasys System Extended Architecture Standard Smoke Control Applications directory. Metasys System Extended Architecture Objects This smoke control application resides on the smoke control NAE. Smoke control logic screens are created with the Logic Connector Tool (LCT). System points, interlocks, MCOs, and alarms are configured with the System Configuration Tool (SCT). The damper used in the weekly test is Damper 6-1. The Damper 6-1 logic screens show the logic for the damper. The Weekly Dedicated Damper Test screens show the logic for the weekly test. The LCT logic is organized into two sections: Damper Control and Weekly Dedicated Damper Test. The Damper Control section controls Damper 6-1 being used in the test. The Weekly Dedicated Damper Test section controls the actual damper test and also includes Damper Alarm message screens and Damper Test Schedule screens. 13

Damper 6-1 The Damper 6-1 main logic in Figure 5 has a Damper system logic block. The Damper block s inputs from the field controller are the Damper Commanded State, Damper Open Present Value, Damper Close Present Value, Zone Pressurize Command, and the Zone Depressurize Command. Inputs from the FSCS are the Open and Close toggle switch, the Fire Fighter Control Key, and a Damper Present Value MCO. Outputs are the Open, Auto, Close, and Trouble LEDs on the FSCS and an MCO that commands the field controller points, including the Auto Command Retry. Figure 5: Damper 6-1 Main Logic 14

The expanded Damper block logic in Figure 6 consists of two control system blocks: the FSCS block and the VMA Trouble Control block. The FSCS block controls the LEDs on the FSCS panel and commands the field controller. The Fan Trouble Control block sets the damper s Trouble LED on the FSCS. Figure 6: Damper 6-1 FSCS and Damper Trouble Control Main Logic 15

The expanded damper FSCS block logic is shown in Figure 7. The Open LED is lit only if the FSCS is in Fire Fighter Control and the damper is open. The Close LED is lit only if the FSCS is in Fire Fighter Control and the damper is closed. The Auto LED is lit only if the damper toggle switch is not in the Open or Close setting. If the Fire Fighter Control Key is off, FSCS Request is set to 0. If the Fire Fighter Control Key is on, FSCS Request is set to the following values depending on the position of the damper toggle switch: Open 1 Auto 0 Close 2 Figure 7: Damper 6-1 Expanded FSCS Block Logic 16

The expanded Damper Trouble Control block logic is shown in Figure 8. The Trouble LED is lit if the damper is in smoke control and the damper has not reached its desired setpoint within 75 seconds or, if DX-9100 controllers are used, one of the DX fuses has blown. A damper is in smoke control if either the field controller is in pressurize or depressurize mode, or, the Fire Fighter Control Key is on and the FSCS toggle switch is set to Open or Close. Figure 8: Damper 6-1 Expanded Damper Trouble Control Block Logic The Damper 6-1 Trouble Interlock Definition in Figure 9 includes status and reliability of the BI Fuse and AI Fuse, reliability of the exhaust air damper open and close status, a binary point that is set to true if the DX goes offline, and a point that sends an alarm if the damper fails. Note: The BI and AI fuses are only required if you are using a DX-9100. Figure 9: Damper 6-1 Trouble Interlock Definition 17

The Damper 6-1 MCO Action Table is shown in Figure 10. The Damper Auto point is a binary point in the field controller to indicate that the damper is under automatic smoke control. When a fire fighter moves the FSCS Damper 1 toggle switch to Opens or Close, the Damper Auto point is turned off. The Damper Command is a point in the field controller to control the damper. Figure 10: Damper 6-1 MCO Action Table 18

Weekly Dedicated Damper Test The Dedicated Damper Test (Figure 11) system logic block inputs are two binary points that enable the damper Open and Close tests, three points from the field controller and a failure reset. Outputs are a binary point to indicate damper failure, and an MCO that commands the field controller to open or close the damper. Figure 11: Weekly Dedicated Damper Test Main Screen The Dedicated Damper Test block expanded logic is shown in (Figure 12). Figure 12: Dedicated Damper Test Block Expanded Logic 19

The Weekly Damper Test Interlock Definition (Figure 13) has a binary point named Weekly Damper Test Enable that enables the weekly testing process when the schedule date and time is reached. An alarm message is sent to the NAE to notify that the weekly test has been enabled. Figure 13: Weekly Damper Test Interlock Definition 20

The Weekly Damper Test Interlock Action Table in Figure 14 commands the damper open at Priority 7 for 2 minutes. If the damper does not open within 75 seconds, the Damper Failure point is set to true. After 2 minutes have expired, the Weekly Damper Test Interlock commands the damper closed at Priority 7 for 2 minutes. If the damper does not close within 75 seconds, the Damper Failure point is set to true. After 2 minutes have expired, the Weekly Damper Test Interlock releases the Priority 7 commands. The Damper Failure is latched for one hour, then the damper test automatically re-enabled and another damper test is started. This cycle continues until the damper test is completed. Once the test passes, it then resets the logic for the next scheduled damper test.. Figure 14: Weekly Damper Test Interlock Action Table 21

If the damper test fails, the failure is latched by the damper logic in Figure 12. After correcting the reason the damper failed, you must unlatch the failure. The Damper Failure Reset Interlock Definition is shown in (Figure 15). Ten seconds after Damper Failure Reset is set to true, this interlock will set Damper Failure Reset back to false. The Weekly Dedicated Damper Test will release the latched alarm while Damper Failure Reset is true. The Damper Failure is latched until the Damper Failure Reset is manually set to true. Figure 15: Damper Failure Reset Interlock Definition The Damper Failure Reset Interlock Action Table is shown in Figure 16. When the damper test has finished, the damper reset has to be manually placed in active, it then resets itself to inactive and resets the logic for the next scheduled damper test. Figure 16: Damper Failure Reset Action Table The Terminate Testing Interlock Definition in Figure 17 terminates the test if any of the following conditions happen: automatic smoke mode begins pressurization or depressurization is turned on the damper fails to meet command the FSCS switch for the point is in any position other than Auto 22

Figure 17: Terminate Testing Interlock Definition The Terminate Testing Interlock Action Table is shown in Figure 18. When the damper test has been terminated, the interlock stops the Damper Test Complete message, and then releases the damper test. This triggers the Damper Test Terminated alarm message. The damper failure reset will then rerun the damper test every hour until the test passes. Once the test passes, it resets the logic for the next scheduled damper test. Figure 18: Terminate Testing Interlock Action Table 23

The Damper Auto Status Interlock Definition screen is shown in Figure 19. During a weekly damper test, this interlock prevents a trouble condition, related to a weekly damper test failure, from lighting a Trouble LED when: the damper switch is in any position other than Auto auto smoke control mode is invoked manual smoke control is invoked The Trouble LED will light if any of the above conditions result in a smoke control trouble condition not related to the weekly test. After the Auto condition clears itself, the Trouble LED will relight with the trouble from the Weekly Test Failure. Figure 19: Damper Auto Status Interlock Definition 24

. The Damper Command MCO Action Table is shown in Figure 20. The Damper Auto point is a binary point in the field controller to indicate that the damper is under automatic smoke control. While the test is running, the Damper Auto flag is false. The MCO also sets the Damper Command point in the field controller to the desired value. Figure 20: Damper Command MCO Action Table 25

Weekly Dedicated Damper Test Alarm Screens The True/False Dedicated Weekly Damper Test Alarm screens show the alarm messages that result from various alarm conditions. These messages are generated at the smoke control NAE, and include Damper Failure, Weekly Damper Test Enable, Damper Failure Reset, and Weekly Damper Test Complete. If the damper does not reach the desired feedback within 75 seconds, a Damper Failure BV is latched to true, a Damper Feedback Does Not Match The Command alarm message is generated at the smoke control NAE. The alarm screen is shown in Figure 21. Figure 21: Damper Failure Alarm Screen 26

When the scheduled date and time to execute the weekly test is reached, the weekly test begins. In this example, the Damper 6-1 Dedicated Weekly Test Enabled alarm message is generated at the smoke control NAE. The alarm screen is shown in Figure 22. Figure 22: Weekly Damper Test Enable Alarm Screen 27

If the damper test fails, the damper test interlock is reset and a Damper 6-1 Failure Reset alarm message is generated at the smoke control NAE. The alarm screen is shown in Figure 23. Figure 23: Damper Failure Reset Alarm Screen 28

When the weekly dedicated damper test is complete a Weekly Dedicated Damper Test Completed alarm message is generated at the smoke control NAE. The alarm screen is shown in Figure 24. Figure 24: Weekly Damper Test Complete Alarm Screen 29

Weekly Test Schedule The Weekly Test Schedule, shown in Figure 25, is used to configure the day and time the Weekly Damper Test executes. Figure 25: Weekly Schedule Screen 30

The Weekly Test Schedule Exception Schedule (Figure 26) lists any exceptions to the weekly schedule. The weekly test will not execute on the dates in the Exception Schedule list. Figure 26: Exception Schedule Screen The Weekly Test Schedule Exception Schedule Scheduled Items shows a list of all scheduled weekly tests. Figure 27: Scheduled Items Screen Controls Group 507 E. Michigan Street Milwaukee, WI 53202 Metasys is a registered trademark of Johnson Controls, Inc. All other marks herein are the marks of their respective owners. 2004 Johnson Controls, Inc. Published in U.S.A. 31 www.johnsoncontrols.com