Experimental Investigations on Packed Bed Solar Air Heater

Similar documents
Thermal Performance Enhancement of Inclined Rib Roughness Solar Air Heater

Solar air heater duct having triangular protrusions As roughness elements on absorber plate

Performance Analysis Of Double Inclination Ribbed Solar Air Heater Rectangular Duct By Liquid Crystal Thermography

Raman et al., International Journal of Advanced Engineering Technology E-ISSN

A Review on Comparative Study of Thermal Performance of Artificially Roughened Solar Air Heaters

Assistant Professor),( Professor), Department of Mechanical Engg., B.I.T. Sindri 3. Professor, Department of Mechanical Engg., N.I.T.

THERMOHYDRAULIC PERFORMANCE OF AN EQUILATERAL TRIANGULAR DUCT WITH ARTIFICIAL ROUGHNESS USED IN SOLAR AIR HEATER

Thermo-Hydraulic Performance Evaluation Using W-Discrete Rib in Solar Air Heater

Design and Fabrication of Solar Air Heater to Increase Heat Transfer Rate using Artificial Roughness

EFFECT OF DIVERSE STREAM PATTERNS ON THE PERFORMANCE OF SOLAR AIR HEATER

6340(Print), ISSN (Online) TECHNOLOGY Volume 3, Issue (IJMET) 2, May-August (2012), IAEME

Design and Thermal Analysis of Solar Plate Collector with and Without Porous Medium

EXPERIMENTAL PERFORMANCE ANALYSIS OF SOLAR AIR HEATER WITH THREE DIFFERENT MODIFICATIONS IN ABSORBER PLATE

Performance analysis of overlapped solar air heater using CFD

Performance Evaluation of Hybrid Solar Water Heating System Using Wire Screen Packed Solar Air Heater

Performance Analysis for the Double- Pass Solar Air Collector with and Without Porous Media

DESIGN, FABRICATION & PERFORMANCE ANALYSIS OF SOLAR AIR HEATER

Experimental & Analytical Investigation on Modified Solar Dryer with Recirculation of Air

Experimental study on heat transfer characteristics of horizontal concentric tube using twisted wire brush inserts

Greek Symbol η collector efficiency Rim angle

To investigate the surface properties for increasing efficiency of solar water heater

EXPERIMENTAL STUDY ON DOUBLE PASS SOLAR AIR HEATER WITH MESH LAYERS AS ABSORBER PLATE

Experimental Analysis of Open, Simple and Modified Greenhouse Dryers for Drying Potato Flakes under Forced Convection

EFFECT OF GLOBAL SOLAR RADIATION ON THE HEAT TRANSFER AND PRESSURE DROP CHARACTERISTICS OF DOUBLE FLOW PACKED BED SOLAR AIR HEATER

2. HEAT EXCHANGERS MESA

ENSC 388: Engineering Thermodynamics and Heat Transfer

PERFORMANCE ANALYSIS AND CALCULATION OF DIFFERENT PARAMETERS OF CONDENSER USING ANSYS FLUENT SOFTWARE

INTERNATIONAL JOURNAL OF APPLIED ENGINEERING RESEARCH, DINDIGUL Volume 1, No 4, 2011

Experimental Investigation of Elliptical Tube Bank Cross Flow Heat Exchanger with Inline Arrangement & 45 Angle of Attack

Heat Transfer Enhancement using Herringbone wavy & Smooth Wavy fin Heat Exchanger for Hydraulic Oil Cooling

Experimental study on a solar air heater with various perforated covers

Performance Analysis of Solar Air Heater Using Three Wire Mesh

CHAPTER I INTRODUCTION. In the modern life, electronic equipments have made their way

A COMPARATIVE EXPERIMENTAL INVESTIGATION OF THERMAL PERFORMANCE OF THREE DIFFERENT SOLAR AIR HEATERS

Thermal Performance of a Loop Thermosyphon

FABRICATION AND COMPARISON OF SOLAR WATER HEATER WITH AND WITHOUT SEMI CIRCULAR TROUGH

International Journal of Advance Research in Engineering, Science & Technology SOLAR HUMIDIFIER

Solar Drying Techniques And Performance Analysis: A Review

Design, Development and Experimental Investigation of Volumetric Air Receiver

Experimentation of Heat Pipe Used In Nano-Fluids

Investigation of a Novel Ceiling Panel for Heat and Moisture Control in Buildings

Fabrication & Performance Analysis of Solar Water Heater Using Porous Medium & Agitator

Experimental Comparison of Natural Convection Heat Transfer from a Blackened V-Fin Array

A COMPARATIVE EXPERIMENTAL STUDY OF THERMAL PERFORMANCE OF THREE SOLAR AIR HEATERS HAVING DIFFERENT ABSORBER AREA

An Experimental Study on Evacuated Tube Solar Collector for Heating of Air in India Avadhesh Yadav, V.K. Bajpai

LAB EQUIPMENT DETAILS

Design and Development of Water Cooled Condenser for Domestic Refrigerator

THE PERFORMANCE STUDY OF A SOLAR FLAT PLATE TYPE AIR COLLECTOR WITH NATURAL AND FORCED CONVECTION

Performance Enhancement of Inclined Bubbling Fluidized Bed Paddy Dryer by Design Modification

Experimental Investigation of a Heat Pump Assisted Fluidized Bed Dryer

Conditioning of outdoor air using rotating disk type liquid desiccant-air contacting device

EFFECTS OF VARIABLES ON NATURAL CONVECTIVE HEAT TRANSFER THROUGH V-CORRUGATED VERTICAL PLATES

Performance Study of Triple Concentric Pipe Heat Exchanger

EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM

A Generalized Correlation for Pressure Drop of Refrigerant R-134a through Helical Capillary Tubes

Thermal Analysis of Concentric Tube Heat Exchanger Using Louvered Strip Inserts

DESIGN AND ANALYSIS OF PIPE HEAT EXANGERS WITH INSIDE FINS

American International Journal of Research in Science, Technology, Engineering & Mathematics

Design and Performance Analysis of One Ended Evacuated Tubes at Different Air Flow Rates Nitin Panwar 1

A REVIEW ON HEAT TRANSFER ENHANCEMENT BY PASSIVE METHODS

Effect of Inclination Angle on Temperature Characteristics of Water in- Glass Evacuated Tubes

Natural Convection Heat Transfer Augmentation from Heat Sinks using Perforated Fins: A Review

ijcrr Vol 04 issue 07 Category: Research Received on:06/02/12 Revised on:17/02/12 Accepted on:02/03/12

Global Journal of Engineering Science and Research Management

PERFORMANCE EVALUATION OF A MIXED MODE SOLAR DRYER

THERMAL ENGINEERING LABORATORY II. To train the students with principles and operation of thermal Engineering equipments.

Performance of Water-in-Glass Evacuated Tube Solar Water Heaters

Experimental Studies on Aero Profile Thermosyphon Solar Water Heating System

Experimental Investigation of a Hybrid Evacuated Tube Solar Collector

A STUDY ON COMPACT HEAT EXCHANGERS AND PERFORMANCE ANALYSIS

FABRICATION OF REFRIGERANT FLOW RATE WITH SPIRALLY COILED CAPILLARY TUBE

V.R.Badgujar * * Department of Mechanical Engineering,Pimpri Chinchwad College Of Engineering,

Numerical Stability Analysis of a Natural Circulation Steam Generator with a Non-uniform Heating Profile over the tube length

Available online Journal of Scientific and Engineering Research, 2018, 5(10): Research Article

Chapter 3 DESIGN OF THE STUDY

ANALYSIS OF THERMAL PERFORMANCE OF SOLAR AIR DRYER FOR THREE DIFFERENT ABSORBER PLATES

Numerical investigation of a solar greenhouse tunnel drier for drying of copra

Analysis of the performance profile of the NCERD thermosyphon solar water heater

EFFECT OF WATER RADIATOR ON AIR HEATING SOLAR COLLECTOR EFFICIENCY

Numerical Studies On The Performance Of Methanol Based Air To Air Heat Pipe Heat Exchanger

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

HEAT TRANSFER ENHANCEMENT IN SHELL AND TUBE HEAT EXCHANGERS USING INSERTS

Feasibility Study of Condensation Heat Exchanger with Helical Tubes for a Passive Auxiliary Feedwater System

Effect of Louvered Strips on Heat Transfer in a Concentric Pipe Heat Exchanger

Experimental Study and Analysis of Flat Plate Solar Water Heater with Different Flow Rates using of Circulating Pump

THERMAL PERFORMANCE ASSESSMENT OF GREENHOUSE SOLAR DRYER UNDER PASSIVE MODE

Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System

Keywords : Evaporative cooling, Saturation efficiency, Cooling capacity, Cooling pad, Cellulose, Aspen, Coconut coir. IJSER

MULTI-CHANNEL R134A TWO-PHASE FLOW MEASUREMENT TECHNIQUE FOR AUTOMOBILE AIR-CONDITIONING SYSTEM

Experimental Investigation of a Brazed Chevron Type Plate Heat Exchanger

ANALYSING THE EFFECTIVENESS OF THE HEAT EXCHANGER BY INCREASING OVERALL HEAT TRANSFER COEFFICIENT

Experimental Study And CFD Based Simulation of Closed Loop Pulsating Heat Pipe Using of Refrigerants (R-134a)

Performance of Shell and Tube Heat Exchanger under Varied Operating Conditions

Seyedeh Sepideh Ghaffari 1 & Seyed Ali Jazayeri 2

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Specific Energy Consumption comparative study of Hot Air dryer and Heat Pump dryer for highland drying process Sayompon Srina

Performance Study of Solar Heat Pipe with Different Working Fluids and Fill Ratios

1, 2

PERFORMANCE OF EARTH TUBE HEAT EXCHANGER COOLING OF AIR A REVIEW

[Eswaran, 3(3): March, 2014] ISSN: Impact Factor: 1.852

Transcription:

Current World Environment Vol. 6(1), 151-157 (2011) Experimental Investigations on Packed Bed Solar Air Heater M.K. LALJI*, R.M. SARVIYA¹ and J.L. BHAGORIA¹ *Department of Technical Education and Skill Development, M.P. Govt, S.V. Polytechnic College, Shyamla Hills, Bhopal - 462 002 (India). ¹Department of Mechanical Engineering, MANIT, Bhopal - 462 052 (India). (Received: April 25, 2011; Accepted: May 29, 2011) ABSTRACT Solar collector is important component of active solar heating systems. It has been observed that the performance of flat plate collector improves appreciably by packing its duct with blackened wire screen matrices and this improvement is a strong function of bed and operating parameters. In this paper an experimental test setup is designed and fabricated. Performance evaluation of packed bed Solar air heater using wire mesh screen matrices and its comparison with conventional design has been done. Data collection at different mass flow rates for a number of configurations has been done. Further suitable recommendations have been made accordingly. Key words: Solar Energy, Air-heater, Test-duct, Wire-mesh, INTRODUCTION Solar air heaters have been observed to have generally poor convective heat transfer coefficient from absorber plate to the air. This low heat transfer coefficient results in relatively higher absorber plate temperature leading to higher thermal losses to the environment and hence lower thermal efficiency. It is therefore, necessary to improve convective heat transfer coefficient to increase the thermal efficiency of flat plate solar air heaters. To enhance the thermal efficiency research attempts have been made by modifying the conventional design of solar air heater. Applications of flat plate solar air heater in heating building drying agriculture products and heating green houses etc Packed bed Solar air heater The performance of plate collector improves appreciably by packing its duct with blackened wire screen matrices and this improvement is a strong function of bed and operating parameters. Packed bed can be successfully used for the enhancement of heat transfer coefficient in solar air heaters. The air flows through the porous medium on which the solar radiation is directly incident. The radiation penetrates absorbing medium in depth and in turn gets absorbed. The high heat transfer area to volume ratio promotes heat transfer capability and the turbulence producing air flow path through the bed provide for a rapid increase of heat exchange. Use of packed bed for the improvement of performance of solar air heater has been proposed by several investigators. The materials used for packed bed includes wire mesh screen, matrices, pebble bed, chips of different materials etc. Literature review and objective Thermo hydraulic investigations on a packed bed solar air heater having its duct packed with blackened wire screen matrices of different geometrical parameters (wire diameter and pitch) has been done by Mittal M.K. et al., 14. Based on energy transfer mechanism in the bed, a mathematical model is developed to compute effective efficiency. A design criterion is also suggested to select a matrix for packing the air flow

152 LALJI et al., Curr. World Environ., Vol. 6(1), 151-157 (2011) the porous packed bed. A decrease in porosity increases the volumetric heat transfer coefficient. Fig. 1: Solar air heater principle duct of a solar air heater which results in the best thermal efficiency with minimum pumping power penalty. Resulting values of effective efficiency clearly indicate that the packed bed solar air heater investigated is thermo hydraulically efficient as compared to flat plate collectors. An experimental investigation carried out by Varshney L. et al., 20 on heat transfer and fluid flow characteristics of a solar air heater having its duct packed with wire mesh screen matrices. The investigations covered a wide range of geometrical parameters of wire mesh screen matrix (wire diameter, pitch and number of layers). Correlations developed for Colburn j-factor and friction factor indicate that heat transfer coefficient and friction factor are strong functions of geometrical parameters of matrices. In another experimental investigation carried out by Thakur N.S. et al., 19 on a low porosity packed bed solar air heater covering a wide range of geometrical parameters of wire screen matrix, i.e. wire diameter 0.795 to 1.40 mm, pitch 2.50 to 3.19 mm and number of layers from 5 to 12. The correlations have been developed for the Colburn j factor and friction factor for a low range of porosities from 0.667 to 0.880 and packing Reynolds number range from 182 to 1168. It is observed that both the heat transfer coefficient and the friction factor are strong functions of geometrical parameters of Further experimental study conducted by Nasri Rabadi et al., 15 on enhancing solar energy collection by using curved flow technology coupled with flow in porous media. Porous media (with 0.1453 porosity) composed of coarse aluminum chips fill the flow channels to provide for further increase in heat transfer performance and for extra energy storage capability. Al housing porous medium will decrease the temperature rise across the collector during sunlight. The maximal outlet temperature reached was 73 C for the collector without porous media at 70 l/h flow rate and 60 C for the collector backed with porous medium at 50 l/h flow rate. Study on thermal performance conducted by Paswan M.K. et al., 16 on Wire-Mesh Roughened Solar Air Heaters providing wire-screen mesh (metal) as artificial roughened on the underside of its absorber plate. Instead of comparing the efficiency of the same rate of discharge, the same amount of pumping power was employed so that the unequal frictional losses were also taken into account in the comparison of overall heater efficiency. The rating parameters such as plate efficiency factor, heat-removal efficiency factor, over heat loss coefficient, and the effective absorption coefficient are reported for these heaters. Based on literature review packed bed solar air heating systems with wire screen mesh is used in the present investigation. In this methodology, the desired numbers of layers of wire mesh screen are stacked on top of each other, parallel to back plate of the collector, at equal distances along the depth to form a matrix., it is desirable that the flow at the heat-transferring surface is made turbulent. This can be done by placing a material in the path of air flow. It may be recalled that the parameters that strongly influence the heat transfer coefficient and friction factor include porosity, P which is determined by the geometry i.e. diameter and pitch of individual wires in the mesh and number of layers that have been filled into a given space; and the flow rate of air through the bed. Earlier studies have shown that

LALJI et al., Curr. World Environ., Vol. 6(1), 151-157 (2011) 153 the systems and flow parameters that are considered important to influence the heat transfer and friction characteristics are given below: (i) Packed bed Reynolds number, Re p (ii) Porosity MATERIAL AND METHODS The schematic diagram of experimental set-up used in the present investigation, is shown in Fig. 2 has been designed, fabricated, and used for data collection on heat transfer and fluid flow characteristics of solar air heaters with packed bed and without packed bed. It consisted of a test section having two identical ducts, one smooth duct (like that in a solar air heater in common use) and the other one identical in size but provided with a packed bed using wire screen matrices. Both the ducts had an identical length of 1.60 m, width of 0.62 m, and depth of 0.025 m and were made of softwood, both inclined at an angle of 25 to the horizontal. The smooth (or conventional) duct had an absorber plate of 2 mm GI sheet. It was blackened with black board paint on the side facing solar radiation. It had a 3 mm thick glass sheet cover fixed 20 mm above the absorber plate. The sides and bottom of the duct were insulated with thermocol sheet. (Thermocol is a commercial insulation of foamed polystyrene having a thermal conductivity 0.037 W/m/K). The reason for using two ducts in the present set-up was to compare the performance at the same operating conditions such as mass flow rate, insolation and inlet fluid temperature. The packed bed duct had a 2 mm GI sheet having several layers of wire mesh screens arranged one above the other on the upper side of the GI sheet while below it there was 50 mm of thermocol and 12 mm plywood. The sides were made of softwood, 25 mm thick. A glass cover was provided on the upper side which rested on batons fixed adjacent to the sidewall at a height of 25 mm. Another glass cover was fixed at a height of 20 mm above the first one and supported on the frame, leaving a stagnant air gap of 20 mm between the two glass covers. A wooden exit section was provided at the outlet of the test duct, which was followed by a mixing device, namely baffles for mixing the air. The exit section reduced the effect of sudden change on the test section. The mixing device enabled measurement of the bulk mean temperature at the outlet of the test section. The length of the exit section was 0.5 m and the cross section area matched with that of the test duct. Three equally spaced baffle plates which spread over 100 mm length beyond the exit section were provided for the purpose of mixing the hot air coming out of the solar collectors to obtain a uniform temperature of the air at the outlet. The mixing section was connected to the Mild Steel pipefitting through a transition piece and flexible pipes. A 2.2 kw (3.0 h.p.) centrifugal blower was used for drawing air through the duct. A standard set of inlet and outlet pressure taps were provided at a distance of 25.4 mm on each side of the orifice plate. The temperature distribution in the bed and temperature of the air at the inlet and outlet of the test section were measured by means of precalibrated copper constantan thermocouples. A digital micro-voltmeter was used to indicate the output of the thermocouples in mili-volts. The temperature measurement system was calibrated to yield the correct temperature values. The pressure drop across the test section was measured by using a calibrated micromanometer. Fig. 2: Schematic line diagram of experimental duct Following are the main components of experimental set-up Test duct The duct consists of 1.6 m length, 0.62m width and 0.025 m depth made up of galvanized iron sheet and kept inclined at angle of 25 to the horizontal. The bottom surface of the duct

154 LALJI et al., Curr. World Environ., Vol. 6(1), 151-157 (2011) is covered with 2mm aluminum sheet below which 3 mm plywood, below which 50 mm thermocol insulation, supported on another plywood of 3 mm. The sun facing side of aluminium sheet is painted black by the black board paint. A 3 mm thick glass cover is fixed above the absorber plate, which rests on frame having a height of 25 mm. Another glass cover is fixed at a height of 20 mm above the first one support on a frame leaving a stagnant air gap of 20 mm between the two glass covers. The solar air heater has a dimension of 1.6 m x 0.62 m x 0.025 m. Blower Unit A centrifugal air blower with 3-phases 3 HP motor is provided with one end connected to the mild steel pipe to suck the air through the test duct. Orifice meter For the measurement of rate of air flow through the test ducts orifice plates have been orifice plate is fixed between two flanges fixed with straights M.S. pipe e.g. 80 mm inner diameter. The length of the M.S.pipe upstream of the orifice meter was 800mm and towards the downstream of orifice plate was 400mm. Manometer A manometer is connected to the pressure taps for the measurement of pressure drop, ( ÄP 0 ) across each orifice plate. Mass flow rate can be calculated using the following expression: m = C d x A 0 x [2ρ ΔP 0 /(1 ß 4 )] 0.5 where, C d is the coefficient of discharge β is the ratio of orifice diameter to pipe diameter A 0 is the orifice area ρ is the density of air Both the orifice plates were calibrated using a standard pitot tube.the pitot tube measured the local velocity across the diameter of the pipe having orifice plates.the experimental values of local velocities were used to calculate the average velocity of the air in the pipe. With the knowledge of this average velocity, density of air and cross sectional area of the pipe, mass flow rate of the air were obtained. These values of mass flow rate and reading of manometer yielded the value of the coefficient of discharge. Pyranometer A Pyranometer, model No 0052 supplied by M/s National Instruments Ltd Calcutta,India was used to measure the intensity of solar radiation.the Pyranometer was kept at an inclination of 25 with the horizontal, which is also the slope of solar collectors. This way the solar insolation falling on the inclined collector was measured directly from the pyranometer. Thermometer Digital thermometer of range 0 to 100 C was used to measure temperatures at the inlet and outlet of air. EXPERIMENTAL The experimental data has been collected by following the procedure described in ASHRAE Standard Handbook (1977) for testing the solar air collector operating in open loop mode. Data pertaining to a given mass flow rate was collected between 11 a.m. and 2 p.m. at an interval of 1 hr were taken on a clear sky day. Before starting the experiment, all the joints of duct, inlet section, mixing device and pipe fittings were examined for leakage and leakage was sealed by using glass putty. While recording the temperature, the ice-bath and lead wire for micro-voltmeter were protected from direct solar radiation. The blower was run for an hour and thereafter, the thermocouple readings for wire mesh temperatures at various locations and inlet and outlet air temperatures, pyranometer readings for intensity of solar radiation and manometer readings for pressure drop across the duct were recorded for a particular day. Experimental data were collected for flow rates ranging from 0.0261 to 0.031 kg/s for four set of matrices. First of all a low porosity wire mesh of square shape with 6-layers is used. Afterwards same wire mesh with 5 layers, 4 & 3 is used and again the above mentioned data was collected. RESULTS AND DISCUSSION The results have been shown graphically as follows, the data is presented in the form of

LALJI et al., Curr. World Environ., Vol. 6(1), 151-157 (2011) 155 Fig. 3: Volumetric heat transfer co-efficient vs Reynold No Fig. 4: Nusselt No. vs Reynold No.

156 LALJI et al., Curr. World Environ., Vol. 6(1), 151-157 (2011) Nusselt number plot to bring out clearly the effect of parameters and enhancement in heat transfer. From fig 3 & 4 it is seen that heat transfer increases as Renolds no. increase, also from the figure it is clear that as porosities reduces in the duct, heat transfer increase as decrease in porosity increases turbulence and there by increase volumetric heat transfer coefficient and nusselt no. CONCLUSIONS The packed bed type solar air heater can be successfully used to enhance the heat transfer rate. The heat transfer enhancement is a function of Porosity and operating parameters. The Reynolds number has been found to be a strong parameters affecting heat transfer and friction factor for packed bed solar heater. Heat transfer is high for six layer matrix having porosity (P=0.961) and maximum area to volume ratio (a v =335m 2 ) within the range of present investigation. Porosity also strongly influences the heat transfer coefficient and hence thermal performance of packed bed solar air heater. It can also be concluded that a considerable enhancement of heat transfer can be obtained from the packed bed solar air heater by lowering the porosity of the bed. The porosity of the bed governs the performance of packed bed solar air heater at a given Reynolds number, the porosity and area to volume ratio are the key parameters for heat transfer. The Reynolds number also has been found to be a strong parameters affecting heat transfer and friction factor for packed bed solar heater. A solar heater with square void matrix having 6 layer of matrix, is found to yield the best performance in almost the entire range of mass flow rate investigated.(mass flow rate=0.0261-0.033kg/s). Thus the heat transfer enhancement is a function of Porosity as an operating parameters. Also the Reynolds number has been found to be a strong parameters affecting heat transfer and friction factor for packed bed solar heater. REFERENCES 1. Ahmad A., Saini J. S. and Varma H. K., Thermohydraulic performance of packed bed solar air heaters. Energy Conv. Manag 37: 205-214 (1996). 2. ASHRAE Standard 93-77, Method of testing to determine the thermal performance of solar air heater, New York, 1-34 (1977). 3. Bhagoria J.L., Saini J.S., Solanki S.C., Heat transfer coef.cient and friction factor correlations for rectangular solar air heater duct having transverse wedge shaped rib roughness on the absorber plate. Renewable Energy, 25: 341 69 (2002). 4. Chiou J. P. and El-Wakil M. M., Heat transfer and flow characteristics of porous matrices with radiation as heat source. J. Heat Transfer 88: 69-76 (1966).. 5. Chiou J. P., El-Wakil M. M. and Duffie J. A., A slit and expanded aluminium-foil matrix solar collector. Solar Energy 9: 73-80 (1965). 6. Collier R. K., The characterization of crushed glass as a transpired air heating solar collector material. In Proceedings of ISES Silver-Jubilee Congress, Boer K. W. and Glenn B. H. (Eds), Atlanta, GA, pp. 264-268 (1979). 7. Coppage J. E. and London A. L. Heat transfer and flow friction characteristics of porous media. Chem. Eng. Progr 52: 57F - 63F (1956). 8. Choudhury C, Garg HP and Prakash J, Design studies of packed-bed solar air heaters, Energy Conversion Management. 34(2): 125 138 (1993). 9. Dhiman P., Thakur N.S., Kumar A. and Singh S., An analytical model to predict the thermal performance of a novel parallel flow packed bed solar air heater, Applied Energy., 88: 2157 2167 (2011) 10. El-Sebaii A.A, Aboul-Enein S, Ramadan MRI, Shalaby SM and Moharram BM, Thermal performance investigation of double pass-

LALJI et al., Curr. World Environ., Vol. 6(1), 151-157 (2011) 157 finned plate solar air heater. Applied Energy. 88: 1727 1739 (2011). 11. Gupta M.K. and Kaushik S.C., Performance evaluation of solar air heater having expanded metal mesh as artificial roughness on absorber plate, Thermal Sciences. 48: 1007-1016 (2009) 12. Jain A., Bhagoria J.L., Sharma M.C., Thermal Performance of Solar Air Heater by using Shot Peened absorber plate. Proceedings of 9th International Conference on Shot Peening, Paris., 67-74 (2005). 13. Jaurker A.R, Saini J.S.,Gandhi B.K., Heat transfer and friction factor characteristics of rectangular solar air heater duct using ribgrooved artificial roughness. Solar Energy, 80: 895-907 (2006). 14. Mittal MK and Varshney L, Optimal thermohydraulic performance of a wire mesh packed solar air heater. Solar Energy. 80: 1112 1120 (2006). 15. Nasri R., On the performance and entropy generation of the double-pass solar air heater with longitudinal fins, Renewable Energy., 30 (2006). 16. Paswan MK and Sharma SP, Thermal performance of wire-mesh roughened solar air heaters. ARISER. 5(1): 31-40 (2009). 17. Paul B and Saini JS, Optimization of bed parameters for packed bed solar energy collection system. Renewable Energy. 29: 1863-1876 (2004). 18. Singh R, Saini RP and Saini JS, Nusselt number and friction factor correlations for packed bed solar energy storage system having large sized elements of different shapes. Solar Energy. 80: 760-771 (2006). 19. Thakur NS, Saini JS and Solanki SC, Heat transfer and friction factor correlations for packed bed solar air heater for a low porosity system. Solar Energy. 74: 319-329 (2003). 20. Varshney L and Saini JS, Heat transfer and friction factor correlations for rectangular solar air heater duct packed with wire screen matrices. Solar Energy. 62(4): 255-262 (1998). 21. Velmurugan P. and Ramesh P., Evaluation of thermal performance of wire mesh solar air heater, Indian Institute of Science & Technology., 4(1), 12-14, (2011).