quick response extra-large orifice upright sprinkler vk531 (storage-density/area)

Similar documents
standard response elo upright sprinkler

micromatic standard response Upright sprinkler VK100 (K5.6)

QUICK RESPONSE ELO PENDENT SPRINKLER VK377 (STORAGE-DENSITY/AREA) TECHNICAL DATA 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3.

TECHNICAL DATA. 2. LISTINGS AND APPROVALS culus Listed: Category VNIV FM Approved: Class 2009 NYC Approved: MEA E, Volume 3

TECHNICAL DATA. The Web site may include a more recent Frame Casting: Brass UNS-C84400

The Viking Corporation s Web site at Rated to 175 psi (12 bar) water working pressure

standard response Fusible Link Upright sprinkler VK204 (K8.0)

microfast and microfasthp quick response horizontal sidewall sprinklers (vk305 & vk319)

microfast quick response Pendent sprinkler VK302 (K5.6)

MICROMATIC STANDARD RESPONSE CONVENTIONAL SPRINKLER VK118 (K5.6) TECHNICAL DATA

micromatic standard sprinkler VK003 (K2.8) 3. technical data Page 1 of 7

MICROFAST QUICK RESPONSE PENDENT SPRINKLER VK302 (K5.6) TECHNICAL DATA

TECHNICAL DATA. Refer to Approval Chart 1 and FM Design Criteria for FM Approval requirements that must be followed.

MICROMATIC STANDARD RESPONSE CONVENTIONAL SPRINKLER VK120 (K8.0) TECHNICAL DATA

micromatic standard sprinkler VK004 (K4.2) 3. technical data Page 1 of 6

TECHNICAL DATA. Page 1 of 6

TECHNICAL DATA. Refer to Approval Chart 1 and UL Design Criteria for culus Listing requirements that must be followed.

MicrofastHP QUICK RESPONSE HORIZONTAL SIDEWALL HIGH PRESSURE SPRINKLER VK319 (K5.6) TECHNICAL DATA

micromatic Standard response Horizontal Sidewall sprinkler

STANDARD RESPONSE FUSIBLE LINK PENDENT SPRINKLER VK008 (K4.2) TECHNICAL DATA 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3. TECHNICAL DATA.

standard response elo upright and pendent sprinklers (storage-density/area)

MICROMATIC STANDARD RESPONSE PENDENT SPRINKLER VK102 (K5.6) TECHNICAL DATA 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3. TECHNICAL DATA.

QUICK RESPONSE EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLER VK630 (K8.0) TECHNICAL DATA

quick response extended coverage horizontal sidewall sprinkler vk630 (k8.0)

TECHNICAL DATA. Viking Technical Data may be found on UNS-C84400 for Sprinkler VK202.

microfast and microfasthp quick response horizontal sidewall sprinklers (vk305 & vk319)

standard response dry horizontal sidewall sprinklers

STANDARD/QUICK RESPONSE CONCEALED PENDENT SPRINKLER VK352-D (K8.0) TECHNICAL DATA

TECHNICAL DATA. The Viking Corporation s Web site at Frame Casting: Brass UNS-C84400

standard response large orifice dry

MICROFAST QUICK RESPONSE PENDENT SPRINKLER VK3311 (K4.2) TECHNICAL DATA

STANDARD RESPONSE DRY HORIZONTAL SIDEWALL SPRINKLERS TECHNICAL DATA

standard response/ quick response extended coverage

TECHNICAL DATA OBSOLETE

quick response horizontal sidewall sprinkler vk360 (K8.0)

standard response dry horizontal sidewall sprinklers

TECHNICAL DATA. MicrofastHP QUICK RESPONSE FUSIBLE ELEMENT PENDENT HIGH PRESSURE SPRINKLER VK318 (K5.6)

qr fusible element sprinklers (part nos , 13959, 17535, and 17536) 3. technical data Sprinkler 42h March 14, 2013

microfast and microfasthp quick conventional sprinklers

EC/QREC ORDINARY HAZARD UPRIGHT SPRINKLER VK570 (K14.0) TECHNICAL DATA

STANDARD/QUICK RESPONSE EXTENDED COVERAGE DRY HORIZONTAL SIDEWALL SPRINKLER TECHNICAL DATA

VK3021 QUICK RESPONSE PENDENT SPRINKLER (K5.6) TECHNICAL DATA

Microfast quick response Fusible element hsw sprinkler

quick response Sprinkler 105a October 25, 2010

standard response fusible link sidewall sprinkler VK112 (K5.6)

STANDARD RESPONSE DRY PENDENT STANDARD ORIFICE SPRINKLERS TECHNICAL DATA

TECHNICAL DATA. Cover Plate Assembly must be ordered separately:

quick response ordinary hazard dry hsw sprinklers (8.0K) (VK275, VK277, & VK279)

TECHNICAL DATA 2. LISTINGS AND APPROVALS 3. TECHNICAL DATA

Special Features: For Light Hazard Occupancies Only Designed for Corridor Applications 28 Maximum Width Spacing. 3. technical data

TECHNICAL DATA. Page 1 of 5

microfast sr/qr extended coverage pendent sprinkler

TECHNICAL DATA STANDARD/QUICK RESPONSE EXTENDED COVERAGE LIGHT HAZARD ELO PENDENT SPRINKLER VK608

QUICK RESPONSE FUSIBLE ELEMENT HSW SPRINKLERS VK308 AND HP VK320 (PART NOS AND 13955) TECHNICAL DATA

TECHNICAL DATA STANDARD/QUICK RESPONSE EXTENDED COVERAGE PENDENT SPRINKLER VK534 (K11.2)

QUICK RESPONSE EXTENDED COVERAGE CONCEALED HSW SPRINKLER VK630 (K8.0) TECHNICAL DATA

micromatic Standard response Horizontal Sidewall sprinkler

TECHNICAL DATA. Refer to Approval Chart 1 and Design Criteria for culus Listing requirements that must be followed.

standard/quick response extended coverage light and ordinary hazard elo sprinklers

QUICK RESPONSE EXTENDED COVERAGE FUSIBLE ELEMENT PENDENT SPRINKLER VK601 (K5.6) TECHNICAL DATA

microfast quick response extended coverage hsw sprinkler vk606

STANDARD/QUICK RESPONSE EXTENDED COVERAGE PENDENT SPRINKLER VK602 TECHNICAL DATA

MICROFAST AND MicrofastHP QUICK RESPONSE PENDENT SPRINKLERS TECHNICAL DATA

standard response sprinklers (vk102 & vk202) 3. technical data Specifications: Minimum Operating Pressure: 7 psi (0.5 bar) Sprinkler 11j

STANDARD/QR EXTENDED COVERAGE LIGHT HAZARD ELO FUSIBLE ELEMENT PENDENT SPRINKLER VK617 TECHNICAL DATA

MICROMATIC STANDARD RESPONSE HORIZONTAL SIDEWALL SPRINKLER VK104 (K5.6) TECHNICAL DATA

STANDARD/QUICK RESPONSE ECOH ELO FUSIBLE ELEMENT UPRIGHT SPRINKLER VK535 (K11.2) TECHNICAL DATA

standard response dry horizontal sidewall sprinklers

MICROFAST SR/QR EXTENDED COVERAGE HSW SPRINKLER VK605 (K5.6) TECHNICAL DATA

FREEDOM RESIDENTIAL PENDENT SPRINKLER VK470 (K3.0) TECHNICAL DATA

micromatic standard response stainless steel sprinklers

STANDARD/QR EXTENDED COVERAGE LIGHT HAZARD TECHNICAL DATA ELO FUSIBLE ELEMENT PENDENT SPRINKLER VK617

FREEDOM RESIDENTIAL HORIZONTAL SIDEWALL SPRINKLER VK479 (K3.0) TECHNICAL DATA

EC/QREC ORDINARY HAZARD PENDENT SPRINKLER VK572 (K14.0) TECHNICAL DATA

TECHNICAL DATA. Refer to the Approval Chart and Design Criteria for C-UL-US-EU Listing requirements that must be followed.

ec/qrec ordinary hazard upright and pendent sprinklers vk570 and vk572 (k14.0)

TECHNICAL DATA vk470 (K3.0)

freedom residential pendent sprinkler vk466 (K5.2)

MicrofastHP EC/QREC FUSIBLE ELEMENT HSW HIGH PRESSURE SPRINKLER VK613 (K5.6) TECHNICAL DATA

STANDARD/QUICK RESPONSE ECOH ELO FUSIBLE ELEMENT PENDENT SPRINKLER VK537 (K11.2) TECHNICAL DATA

STANDARD/quick. Sprinkler 42o. August 8, 2011

MicrofastHP EC/QREC FUSIBLE ELEMENT PENDENT HIGH PRESSURE SPRINKLER VK611 (K5.6) TECHNICAL DATA

MIRAGE STANDARD AND QR CONCEALED PENDENT SPRINKLER VK462 AND HP SPRINKLER VK463 (K5.6) TECHNICAL DATA

MIRAGE STANDARD AND QR CONCEALED PENDENT SPRINKLER VK462 AND HP SPRINKLER VK463 (K5.6) TECHNICAL DATA

TECHNICAL DATA. Viking Technical Data may be found on Maximum Working Pressure: 175 psi (12 Bar).

standard response/qr extended coverage concealed pendent sprinklers vk614 & vk616

freedom residential Upright sprinkler vk467 (k4.9)

TECHNICAL DATA. Viking Technical Data may be found on Pip Cap: Brass UNS-C31400 or UNS-C31600

TECHNICAL DATA. Refer to the Approval Chart and Design Criteria for C-UL-US-EU Listing requirements that must be followed.

HORIZON STANDARD RESPONSE FLUSH PENDENT SPRINKLER VK400 TECHNICAL DATA

mirage Quick response extended coverage concealed pendent sprinklers (vk632 and vk634)

QUICK RESPONSE DRY CONCEALED PENDENT SPRINKLER VK194 TECHNICAL DATA

DRY VERTICAL SIDEWALL SPRINKLERS TECHNICAL DATA

December 14, 2015 Page 1 of 7 TECHNICAL DATA

quick response sprinkler vk194 Sprinkler 104j January 1, 2011

standard/quick response sprinklers (vk302 & vk352) 3. technical data Specifications: Available since Sprinkler 41g May 1, 2009

TECHNICAL DATA. 2. LISTINGS AND APPROVALS NOTE: Viking Dry Vertical Sidewall Sprinklers are NOT listed or approved. Sprinkler 103a.

Form No. F_ Rev 14.1 Page 1 of 6 TECHNICAL DATA

mirage Quick response concealed pendent sprinkler vk465 (K4.2)

FREEDOM RESIDENTIAL HORIZONTAL SIDEWALL SPRINKLER VK486 (K4.0) TECHNICAL DATA

Transcription:

Page of 4. DESCRIPTION The Viking Quick Response Extra-Large Orifice Upright Sprinkler VK5 is a thermosensitive glass bulb spray sprinkler available in several different finishes and temperature ratings to meet design requirements. The special Polyester, Electroless Nickel PTFE (ENT), and PTFE coatings can be used in decorative applications where colors are desired. In addition, these coatings have been investigated for installation in corrosive atmospheres and are listed/approved as corrosion resistant as indicated in the Approval Charts. (Note: FM Global approves the ENT coating as corrosion resistant. FM Global has no approval classification for PTFE and Polyester coatings as corrosion resistant.) The provides greater flows at lower pressures than standard orifice or large orifice sprinklers. This feature allows reduced pipe sizing for hydraulically calculated sprinkler systems, which require high densities of water. Viking Standard Response Extra-Large Orifice Sprinklers may eliminate the need for a fire pump or reduce the size of the pump if it is required. On existing systems, replacing large orifice sprinklers with sprinklers may provide the higher densities required to allow an increase in the hazard classification of an occupancy. Viking Quick Response Extra-Large Orifice Upright Sprinkler VK5 may be ordered and/or used as an open sprinkler (glass bulb and pip cap assembly removed) on deluge systems. Refer to Ordering Instructions below.. LISTINGS AND APPROVALS culus Listed: Category VNIV FM Approved: Class 00 VdS Approved: Certificate G4059, G4060 LPCB Approved Refer to Approval Chart and Design Criteria on page for culus Listing requirements, and refer to Approval Chart and Design Criteria on page 4 for FM Approval requirements that must be followed.. technical data Specifications: Available since 000. Maximum Working Pressure: 75 psi ( bar). Factory tested hydrostatically to 500 psi (4.5 bar). Thread size: See Approval Charts Nominal K-Factor:. U.S. (6. metric*) * Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kpa, divide the metric K-factor shown by 0.0. Glass-bulb fluid temperature rated to -65 F (-55 C) Overall Length: -5/6 (58.7 mm) Material Standards: Sprinkler Frame: Brass UNS-C84400 Deflector: Brass UNS-C6000 Bulb: Glass, nominal mm diameter Pip Cap and Insert Assembly: Copper UNS-C000 and Stainless Steel UNS-S0400 Compression Screw: Brass UNS-C6000 Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with Teflon Tape For Polyester Coated Sprinklers: Belleville Spring-Exposed For ENT Coated Sprinkler: Belleville Spring-Exposed, Screw and Pipcap-ENT plated. Replaces page 70h-k dated Dec. 6, 0. (Outdated reference removed; removed Black PTFE; upgraded images.)

Page of 4 Ordering Information: (Also refer to the current Viking price list.) Order Quick Response Extra-Large Orifice Upright Sprinkler VK5 by first adding the appropriate suffix for the sprinkler finish and then the appropriate suffix for the temperature rating to the sprinkler base part number. Finish Suffix: Brass = A, Chrome = F, White Polyester = M-/W, Black Polyester = M-/B, ENT = JN Temperature Suffix: 55 F (68 C) = B, 75 F (79 F) = D, 00 F (9 C) = E, 86 F (4 C) = G, OPEN = Z (PTFE only). For example, sprinkler VK5 with a Brass finish and a 55 F (68 C) temperature rating = Part No. 06AB Available Finishes And Temperature Ratings: Refer to Table. Accessories: (Also refer to the Viking website.) Sprinkler Wrenches: A. Standard Wrench: Part No. 058CW/B (available since 98). B. Wrench for coated sprinklers: Part No. 66W/B** (available since 00) **A ½ ratchet is required (not available from Viking). Sprinkler Cabinets: A. Six-head capacity: Part No. 074A (available since 97) B. Twelve-head capacity: Part No. 075A (available since 97) 4. Installation Refer to appropriate NFPA Installation Standards. 5. Operation During fire conditions, when the temperature around the sprinkler reaches its operating temperature, the heat-sensitive liquid in the glass bulb expands, causing the bulb to shatter, releasing the pip cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extin- guish or control the fire. 6. inspections, tests and maintenance Refer to NFPA 5 for Inspection, Testing and Maintenance requirements. 7. availability The Viking Quick Response Extra-Large Orifice Upright Sprinkler is available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. Guarantee For details of warranty, refer to Viking s current list price schedule or contact Viking directly. TABLE : AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES Sprinkler Temperature Sprinkler Nominal Maximum Ambient Classification Temperature Rating Ceiling Temperature Bulb Color Ordinary 55 F (68 C) 00 F (8 C) Red Intermediate 75 F (79 C) 50 F (65 C) Yellow Intermediate 00 F (9 C) 50 F (65 C) Green High 86 F (4 C) 5 F (07 C) Blue Sprinkler Finishes: Brass, Chrome, White Polyester, Black Polyester, and ENT Corrosion-Resistant Coatings : White Polyester, and Black Polyester in all temperature ratings. ENT in all temperature ratings except 5 F (57 C). The sprinkler temperature rating is stamped on the deflector. Based on NFPA-. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts. These tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compatible with or suitable for the proposed environment. For automatic sprinklers, the coatings indicated are applied to the exposed exterior surfaces only. Note that the spring is exposed on sprinklers with Polyester, and ENT. For all ENT coated sprinklers, the waterway is coated.

Page of 4 Protective clip -/4 (45 mm) Wrench flat /4 NPT (0 mm) -5/6 (59 mm) 058CW/B Figure : Sprinkler VK5 and Wrench Figure : Sprinkler VK5 Dimensions Sprinkler wrench 66W/B** must be used for installing coated sprinklers. Step : Carefully slide the wrench sideways around the deflector, ensuring engagement with the sprinkler wrench flats. Step : Carefully press the wrench downward and ensure engagement with the sprinkler wrench flats. Coated Upright Sprinkler ** A / ratchet is required (not available from Viking) Figure : Wrench 66W/B for Coated Sprinkler VK5

Page 4 of 4 Base Part Number SIN Sprinkler Style Approval Chart (UL) Quick Response Extra-Large Orifice Upright Sprinkler VK5 Thread Size Maximum 75 PSI ( Bar) WWP Nominal K-Factor Overall Length Listings and Approvals (Refer also to Design Criteria below.) NPT BSP U.S. metric Inches mm culus 4,5 NYC VdS LPCB 06 VK5 Upright /4 0 mm. 6. -5/6 58.7 A See Footnote 6. -- -- 904 VK5 Upright /4 0 mm. 6. -5/6 58.7 -- -- A A 905 VK5 Upright / 5 mm. 6. -5/6 58.7 -- -- A A Approved Temperature Ratings A - 55 F (68 C), 75 F (79 C), 00 F (9 C), and 86 F (4 C) Approved Finishes - Brass, Chrome, White Polyester 7, Black Polyester 7, and ENT 7 - Brass, Chrome, White Polyester 7, and Black Polyester 7 Base part number shown. For complete part number, refer to Viking s current price schedule. Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kpa, divide the metric K-factor shown by 0.0. This table shows the listings and approvals available at the time of printing. Other approvals may be in process. 4 Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada. 5 culus-listed only for use in wet pipe sprinkler systems (or preaction systems qualifying as wet systems). 6 Meets New York City requirements, effective July, 008. 7 culus Listed as corrosion-resistant. culus Listing Requirements: DESIGN CRITERIA - UL (Also refer to Approval Chart above.) Quick Response Extra-Large Orifice Upright Sprinkler VK5 is culus Listed for installation in accordance with the latest edition of NFPA for standard upright spray sprinklers: Designed for use in hazard occupancies up to and including Ordinary Hazard Group II with a minimum operating pressure of 7 PSI (0.5 bar). Also Listed for use in High-Piled Storage Occupancies as defined in NFPA with a minimum operating pressure of 7 PSI (0.5 bar). Listed only for use in wet pipe sprinkler systems (or preaction systems qualifying as wet systems). The sprinkler installation and obstruction rules contained in NFPA for standard spray s must be followed. IMPORTANT: Always refer to Bulletin Form No. F_09699 - Care and Handling of Sprinklers. Also refer to Form No. F_08064 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable.

Page 5 of 4 Base Part Number SIN Sprinkler Style Approval Chart (FM) Quick Response Extra-Large Orifice Upright Sprinkler VK5 Maximum 75 PSI ( Bar) WWP Thread Size Nominal K-Factor Overall Length FM Approvals NPT BSP U.S. metric Inches mm (Refer also to Design Criteria below.) 06 VK5 Upright /4 0 mm. 6. -5/6 58.7 A Approved Temperature Ratings A - 55 F (68 C), 75 F (79 C), 00 F (9 C), and 86 F (4 C) Base part number shown. For complete part number, refer to Viking s current price schedule. Approved Finishes - Brass, Chrome, and ENT 4 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kpa, divide the metric K-factor shown by 0.0. This table shows the FM Approvals available at the time of printing. Other approvals may be in process. 4 FM Approved as corrosion-resistant. FM Approval Requirements: DESIGN CRITERIA - FM (Also refer to Approval Chart above.) Quick Response Extra-Large Orifice Upright Sprinkler VK5 is FM Approved as a upright Non-Storage sprinkler and as a quick response upright Storage sprinkler as indicated in the FM Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (including -0 and 8-9). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling. NOTE: The FM installation guidelines may differ from culus and/or NFPA criteria. IMPORTANT: Always refer to Bulletin Form No. F_09699 - Care and Handling of Sprinklers. Also refer to Form No. F_08064 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. Replaces page 70h-k dated Dec. 6, 0. (Outdated reference removed; removed Black PTFE; upgraded images.)