Blarenberglaan 21 B 2800 MECHELEN Tel.: +32 (0) Fax: +32 (0)

Similar documents
B SERIES ELECTRIC FURNACE

CROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

WHE 2.24 / WHE 2.24 FF

WMWLB / WMWFM / WTWLB / WTWFM Series Hydronic Heating Unit

INSTALLATION, COMMISSIONING AND OPERATING MANUAL

100 FLUEBOOST

HVG620 & HVG720 Gas Hob Manual for Installation, Use and Maintenance

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

ENGINEERING SPECIFICATIONS

MHG201 Gas Hob Manual for Installation, Use and Maintenance

ENGINEERING SPECIFICATIONS

BHW INSTALLATION, OPERATION AND MAINTENANCE MANUAL MEDIUM STATIC PRESSURE DUCTABLE TYPE. Models:

Technical Data Manual Model Nos. and pricing: see Price List

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw

VIESMANN. Operating instructions VITODENS 100-W. for the system user

Light oil burners. One stage operation

Instructions for installation and use English. More documents on: H B /09

AHU INSTALLATION & OPERATION MANUAL

12 VELOCITY OWNER S MANUAL OPERATING INSTRUCTIONS - MAINTENANCE - SAFETY - TROUBLESHOOTING

REFRIGERAT A OR USE DF1-15 F ridge

Vote for your Installer of the year at. 9/14, 14/19 & 19/24CBi. Worcester supports the Benchmark code of practice

I n s t r u c t i o n m a n u a l f o r b u i l t - i n h o o d. Model code: BORA600

LOW STATIC HYDRONIC DUCTED UNIT

VACUUM EXTRACTOR MODEL NO: CWVE1 OPERATING & MAINTENANCE INSTRUCTIONS PART NO: GC0916

SOUND-INSULATED FAN. Iso-K OPERATION MANUAL. Iso-K_v.1(2)-EN.indd :20:59

EHH SERIES DRAW THROUGH FAN COILS CFM

Lo-Carbon MULTIVENT MVDC-MS & MVDC-MS H VENTILATION SYSTEMS V~50Hz. Installation and Wiring Instructions IP22. Stock Ref.

SPECIFICATION GUIDE FLEXAIR. Possibility to add auxiliary heaters: Gas, Electrical Heater, Hot Water Coil Possibility to add Heat Recovery Module

40E ELECTRIC FAN HEATER

HIGH EFFICIENCY AIR HANDLER

INSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER

Light oil - kerosene burner

COMFORT PACK INSTALLATION AND MAINTENANCE INSTRUCTIONS

INSTALLATION INSTRUCTIONS

EarthLinked AVN Series Air Handlers Installation Manual

INSTRUCTIONS AND WARRANTY

5.0 Installation Instructions

Power 4. User Guide. HC85-P4-ZA hoover.za.com

INSTALLATION INSTRUCTION

INSTALLATION INSTRUCTIONS

Xcell 270 Longlife DC wholehouse heat recovery unit

40E ELECTRIC FAN HEATER

Excel Click & Go Lite

AVS Air Handlers Installation Manual for Classic SC, SD, and SDH

OWNERS MANUAL. PLEASE READ THIS MANUAL BEFORE OPERATION

DUST EXTRACTOR MODEL No: CDE1000

Installation, operating and servicing instructions

Fusion 200, 300 & 500

Space Saver. Installation and user manual SS3 SS5 SS7 SS9. Issue 001 September 2017 ENGLISH UK IRL SmithsEP.co.uk

TECAM S.A. harmony. 5PZA Direct Expansion. Air Conditioning Equipment Manufacturer. R-410A PRECISION UNIT 2 Ton 6 Ton / 60 Hz. Tecnología Ambiental

10 & 12 Ventilator. Please read and fully understand the instructions in this manual before operation. Keep this manual safe for future reference

VACUUM OVEN. Model: VPX9-2. Installation and Operation Manual

USER S MANUAL. Heat (Energy) Recovery Ventilator. Vents Frigate HRV 120 S Vents Frigate ERV 120 S

Installation Guide. Termix Distribution unit. 1.0 Table of Contents. 1.0 Table of Contents

CSH COMBINED STORAGE HEATERS INSTALLATION INSTRUCTIONS AND USER GUIDE

Models: Comfort SUPXX-C120D12 SUPXX-C240D12 SUPXX-C120D20 SUPXX-C240D20. Advantage SUPXX-A120D12 SUPXX-A240D12 SUPXX-A120D20 SUPXX-A240D20

Classic Heater Pool Controller

THERMOFILM CONVECTIVE PANEL HEATER INSTALLATION, OPERATION AND MAINTENANCE MANUAL. Models: CP 2400 CP 2000 CP 1500 CP 1000 TABLE OF CONTENTS

Product Data. 58CMA Multipoise Oil Furnace. Series 120 Input Capacities: 70,000 thru 154,000 Btuh. The Latest in Oil Furnace Technology

Light oil / kerosene burner

Operating instructions

Product Data. 58CMA Multipoise Oil Furnace. Series 110 Input Capacities: 70,000 thru 154,000 Btuh. The Latest in Oil Furnace Technology

Installation Instructions Remote Blowers

DC Heat Recovery Unit MVHR Wholehouse heat recovery unit

PHRIE / PHIE InvERTER monoblock air To water HEaT PumP medium TEmPERaTuRE

KADO LUX LED EXHAUST FAN 200

AIRGOCLEAN 10 E OPERATING MANUAL AIR CLEANER TRT-BA-AIRGOCLEAN10E-TC-001-EN

IDE 20 / IDE 30 / IDE 50 IDE 60 / IDE 80

BRISE. Heating and cooling from a single radiator

SPA DE USO PRIVADO SPA FOR PRIVATE USE SPA POUR UN USAGE PRIVÉ SPA FÜR PRIVATE NUTZUNG SPA PER USO PRIVATO SPA PARA USO PRIVADO SPA VOOR PRIVE-GEBRUIK

MX Series Indoor Modular Blowers Electric Heat, Hot Water Heat, or No Heat

Installation Guide. Dehumidification. Fresh Air Ventilation. Compact Size. Energy Efficient. RXID-AW90A Whole House Dehumidifier

Table of Contents. Forward Quality Policy Design Parameters Section A Unit Operation Section B Unit Maintenance...

of the openings blocked with any object that may restrict the airflow.

INSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER

WET & DRY VACUUM CLEANERS

VIESMANN. Operating instructions VITODENS 050-W. for the system user. With constant temperature or weather-compensated control unit

Flue Dilution Fans. Specialists in Air Movement Technology. IMPROVED GBDF MK5 Now includes a Pressure Safety Switch and easier Electrical Connections

Trimbox Mixed Flow Fans. Product Manual. ventilation systems TP220T TP221T TP222T TP223T

PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS. PLEASE SAVE THESE INSTRUCTIONS.

ECAH SERIES ECM AIR HANDLER

РУКОВОДСТВО USER ПО MANUAL ЭКСПЛУАТАЦИИ CENTRIFUGAL INLINE FANS VKM / VKMZ / VC SERIES

USER S INFORMATION MANUAL

JH Series Installation

1.03 RELATED SECTIONS: The following sections contain requirements that relate to this section.

Brivis Inverter Icebox

Product Data. 50HS Single-Package Heat Pumps to 5 Nominal Tons

... LCSA - LCSBD - LCSC Gas Fired Unit Heaters ...

Instruction Manual 1.1 CU. FT. Upright Freezer UF-114W (WHITE) UF-114SS (STAINLESS STEEL)

OWNER S MANUAL HIGH EFFICIENCY VARIABLE SPEED GAS-FIRED FURNACES

24 & 30 Drum Fan. Please read and fully understand the instructions in this manual before operation. Keep this manual safe for future reference

Brise speed speed control 2. BRIC ceiling model 3. BRIW wall model 4. BRBW wall build-in model 5. grille from ABS 6.

SPECIFICATION GUIDE NEOSYS. Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw

TTV 1500 / TTV 3000 OPERATING MANUAL CONVEYING FAN TRT-BA-TTV TC EN

Duct Heaters volts/1 phase volts/3 phase volts/3 phases volts/3 phases. Flange Type Duct Heater.

Installation & Maintenance Instructions

MODEL: DV72 R & L. Mechanical Ventilation with Heat Recovery Installation Instructions and User Manual

X X Packaged Air Conditioners - Vertical Units Air Cooled Models (AR) Water Cooled Models (AO) Refrigerant R407C to 18.

DUCT COOLERS KWK KFK OPERATION MANUAL. KWK_KFK_v2(4)_EN.indd :35:29

Transcription:

Multicalor MC Air handlers for heating and optional cooling Brand: Base model: Variants: Country of destination: Electrical supply: Maximum supply pressure: Multicalor MC20 MC30 MC40 UK 230V~ AC 50Hz 6 kg/cm² Maximum supply temperature: 90 C Manufacturer: Multicalor Industries NV Blarenberglaan 21 B 2800 MECHELEN Tel.: +32 (0)15 29 03 03 Fax: +32 (0)15 29 03 20 Please keep this manual close to the apparatus for further reference Date created: 08/06/2004 Last changed: 0/05/2004 Documentcode: MC2004H_uk_en.pdf

Table of contents Dimensions 3 1 General 4 1.1 Standard version 4 1.2 Outside air version 4 1.3 Upflow and Downflow 4 2 Technical data 4 2.1 General 4 2.2 Airflow 4 3 Installation 6 3.1 General 6 3.2 Electrical installation 6 3.3 Installing the hot water supply lines 7 3.4 Installing the ducting system 7 4 Commissioning 7 4.1 Standard control 7 4.2 Electronic control 8 4.3 Setting the air volume 8 4.4 Outside air version 8 4.5 Downflow version 8 4.6 Installing the ducting system 8 5 Maintenance 8 5.1 End user 8 5.2 Installer maintenance 9 6 Problem solving 9 6.1 Standard control 9 6.2 Electronic control 9 7 Electrical wiring diagram 10 7.1 Standard control 10 7.2 Electronic control 10 8 Warranty 10 8.1 General 10 8.2 Scope and duration of the warranty 10 8.3 Damage that is not covered by the warranty 10 8.4 Not covered under warranty 11 8.5 Repairs 11 8.6 Service-parts 11 9 Statement of compliance 11 2

Dimensions 90 SIZE 'A' SIZE 'B' 90 450 480 90 90 410 x 680 1 100 115 185 665 700 550 600 x 'C' Type MC20 A 340 B 400 C 280 MC30 440 500 380 MC40 540 600 480 660 720 725 3

1 General The Multicalor MC (Series 2004) air handling units are compact high performance units. The units are fitted with generously sized heat exchangers featuring 6 rows. This guarantees high air temperatures even with moderate supply water temperatures. As a result, the units are very well suited to be used in conjunction with modern condensing boilers. The fans of the MC units are installed downstream of the heat exchangers. This ensures that the fan motors are always optimally cooled and the life span of the fan bearings is increased. Special attention has been paid to the air tightness of the units, so leak losses are minimal. The heat exchanger compartments is insulated by means of a thick layer of air, so heat losses are minimal. The apparatus is supplied ready to use. It is sufficient to install on site the hot water supply lines, the air ducts and the electrical supply. 1.1 Standard version In standard use the apparatus is used to distribute recycled air to which not more than 25% outside air has been added, or to distribute up to 100% outside air after heat reclaim. The unit is factory supplied in this version. 1.2 Outside air version In outside air version the unit is used to distribute air to which more than 25% outside air is added. However, in the unit no special regulators are installed to keep the air temperature constant, nor is the heat exchanger protected from frost damage. If you want to use the unit as an outside air unit, we suggest that you: install an external regulator that keeps the minimum air temperature at a certain selectable level. protect the heat exchanger from frost related damage by means of addition of a suited anti-freeze solution to the heating circuit. 1.3 Upflow and Downflow The Multicalor MC units are available as upflow models. If you need a downflow unit, you can turn simply around the unit and add a second minimal thermostat. More details are found in point 4.5 Downflow versions. 2 Technical data 2.1 General The units comply to the machine directive 89/392/EEG, the low voltage directive 73/23/EEG and the EMC directive 89/336/ EEG. The MC units are available in 3 sizes. Each unit can be fitted with different fans as to adapt air flow or external static pressure as suited. 2.2 Airflow 2.2.1 MC20 The width of this unit is 400 mm. The air flow depends on the selected fan motor. In the table below you can find per fan the air flow and the respective external static pressure. Per airflow the heating output (with supply 75/65-20 C entering air temperature) and the hydraulic pressure loss are stated. Ventilator Heating output Hydraulic Dimensions 241-181 (9-7) 241-181 (9-7) 241-181 (9-7) pressure loss Motor type PSC PSC ECM Power 184 Watt 376 Watt 376 Watt Capacitor 6 µf 10 µf RPM 950 rpm 1450 rpm Electronic control Speed L M H L M H Supply 75/65-20 C (per EN442) Air flow [m³/h] External static pressure [Pa] [kw] [kpa] 600 133 145 152 311 340 352 800 110 126 134 276 306 320 11.3 1.36 1 000 60 101 111 227 270 286 13.7 1.97 1 200 63 81 158 223 248 15.9 2.52 1 400 35 166 209 18.0 3.21 1 600 89 160 20.0 3.81 1 800 103 22.0 4.56 2 000 36 23.8 5.33 2 200 4

2.2.2 MC30 The width of this unit is 500 mm. The air flow depends on the selected fan motor. In the table below you can find per fan the air flow and the respective external static pressure. Per airflow the heating output (with supply 75/65-20 C entering air temperature) and the hydraulic pressure loss are stated. Ventilator Heating output Hydraulic Dimensions 270-270 (10-10) 270-270 (10-10) 270-270 (10-10) Type PSC PSC ECM Power 245 Watt 376 Watt 376 Watt Capacitor 8 µf 10 µf RPM: 950 rpm 1450 rpm Electronic control pressure loss Speed L M H L M H Supply 75/65-20 C (per EN442) Air flow [m³/h] External static pressure [Pa] [kw] [kpa] 800 177 191 197 306 390 426 1 000 155 172 180 259 353 406 14.6 1.38 1 200 128 151 162 190 314 384 17.0 1.77 1 400 93 129 140 114 273 360 19.4 2.28 1 600 40 100 118 35 226 329 21.6 2.73 1 800 67 91 158 293 23.8 3.30 2 000 23 59 47 253 25.9 3.87 2 200 22 200 28.0 4.38 2 400 138 30.0 4.99 2 600 60 31.9 5.51 2 800 2.2.3 MC40 The width of this unit is 600 mm. The air flow depends on the selected fan motor. In the table below you can find per fan the air flow and the respective external static pressure. Ventilator Heating output Hydraulic Dimensions 270-270 (10-10) 270-270 (10-10) 270-270 (10-10) pressure loss Type PSC PSC ECM Power 376 Watt 550 Watt 736 Watt Capacitor 16 µf 20 µf RPM: 1450 rpm 1450 rpm Electronic control Speed L M H L M H Supply 75/65-20 C (per EN442) Air flow [m³/h] External static pressure [Pa] [kw] [kpa] 1 000 295 379 436 419 458 479 1 200 246 352 421 387 431 460 17.8 1.40 1 400 192 324 400 356 405 441 20.3 1.82 1 600 112 290 380 319 374 422 22.7 2.18 1 800 24 253 357 276 344 402 25.1 2.65 2 000 201 329 221 309 380 27.4 3.13 2 200 130 297 132 267 355 29.6 3.55 2 400 18 262 211 325 31.8 4.06 2 600 214 144 291 33.9 4.50 2 800 163 58 252 36.0 5.04 3 000 81 205 38.0 5.50 3 200 154 40.0 6.05 3 400 91 41.9 6.53 3 600 2.2.4 Correction factors for other hot water supply or entering air temperatures. Entering air temperature Hot water supply 20 15 10 5 0 75/65 1.00 1.09 1.20 1.31 1.41 90/70 1.19 1.29 1.40 1.50 1.60 80/60 0.97 1.08 1.18 1.28 1.39 70/50 0.74 0.86 0.96 1.07 1.17 60/40 0.53 0.64 0.74 0.85 0.95 5

3 Installation 3.1 General We wish to emphasize that only qualified fitters or contractors shall install the air heater. The installation shall be done in accordance with the latest issue of all local standards as well as the installation manual of the device concerned. Ensure that the conditions of local utility provision (electrical supply) match the device settings before installing the device or making it operational. 3.1.1 Transport damage Please check the air heater for transport damage upon delivery. If damage is observed, this shall be mentioned on the waybill and you shall advise your supplier thereof in writing. 3.1.2 Packaging The air heaters are always packaged in a box made from recycled paper. We ask you not to earmark the paper for waste disposal, but for further recycling. 3.1.3 Location Adhere to the following guidelines when selecting a location for the device: place the unit in a central position in relation to the ducting system; place the unit on a flat and solid surface; if installation surface is wet, then raise the unit; Always place the device in such a way that it is insulated from the construction building structure to avoid the transmission of noise and vibrations. Attention: The unit must be installed level! The device must be installed in a frost free location. If impossible, please add a suitable anti-freeze to the hydraulic system as to protect the heat exchanger from frost damage. If a return air is inspired in the combustion compartment, then under no condition devices with an open combustion circuit may be present in the installation area! 3.1.4 Minimal clearance When installing please provide minimal clearance around the unit: keep 50 mm clearance around the sides of the unit; keep a minimum of 50 mm between hot water supply and any flammables.. At the front of the device there shall be at least 720 mm of free service space (ensure a comfortable standing height). 3.1.5 Transport on site Never move the air heaters by tilting them on their angles, as this may irrevocably damage the device encasing. Such damage is not covered by the device s warranty. 3.2 Electrical installation The electrical installation shall always be performed according to the latest issue of the relevant standards and the prescriptions of the local energy provider (utility). Mind your safety: always ground the unit. 3.2.1 Standard control 3.2.1.1 Electrical connection In the casing different cut-outs are provided to run cables through. The PCB features a three-pole terminal for connecting the mains power 230V~AC. Connect the cable to a 230V~AC power supply with earthing. We recommend that the machine should be directly connected to a switchboard with 16A fuses. 3.2.1.2 Thermostat The device works perfectly together with the Honeywell electronic programmable thermostat Chronotherm IV. This thermostat is suited for heating, ventilation and cooling, and has been specifically designed for use with warm air systems. Connect the thermostat as per the instructions on the wiring diagram. Mount the room thermostat at an approximate height of 1.6 m, in a central position in the living room and readily accessible to the normal air circulation in the room. Always mount the thermostat on an inner wall shielded from the effects of other heat sources including exhaust grilles, powered devices, direct sunlight, etc. Accordingly, we also do not recommend placement near windows, outer walls (<1.20 m) or in the vicinity of stairs. For additional information on assembly and programming we 6

refer to the thermostat manual. 3.2.1.3 Cooling condensing unit The PCB features a two-pole terminal for connecting an auxiliary relay that can start an external condensing unit. Warning: never connect the cooling system relay directly to this output, but always use an auxiliary relay. For further information, please contact Multicalor. 3.2.2 Electronic control The electronic control is not yet implemented. 3.3 Installing the hot water supply lines The diameter of the supply lines is 28mm. Usually hot water supply is from the front, but for ease of installation the supply lines can also be brought in from the sides or the top of the unit (UP F only). The heat exchanger is installed with rubber grommets as to minimise leakage. Install an automatic air bleed valve in the supply circuit. Install ball valves and flexible tubing so the heat exchanger can be easily removed for inspection or cleaning. 3.3.1 Hydraulic installation (standard regulation) There are a number of ways to install the unit hydraulically. Standard the PCB gives out a 230V~AC signal (on terminal 1 2). This contact can be used to drive a circulator of MAXIMUM 3.00A. 3.3.2 Hydraulic installation (electronic control) The electronic control is not yet implemented. 3.4 Installing the ducting system 3.4.1 Installing the supply ducts For the MC units a complete range of acoustically insulated supply air plenums is available. These are installed of top of the unit (Downflow versions: under the unit) and facilitate connection of the ductwork. 3.4.2 Installing the return air ducts For the MC units a complete range of acoustically insulated supply air plenums is available. These are installed under the units (Downflow versions: on top of the units) and facilitate connection of the ductwork. It is also possible to connect the return air ductwork to the side of the units. For this purpose matching white return air filter frames are available. Multicalor does not recommend to connect the ductwork directly to the sides of the unit, as this means that a large portion of the acoustic insulation is lost. Never remove the air filter. The unit must always be fitted with an air filter class EU3/G3 or better. Using the unit without a filter can damage the unit. Change filters regularly. If you connect an outside air duct, always install a butterfly register as to regulate the amount of outside air. 4 Commissioning 4.1 Standard control 4.1.1 Switching the apparatus on and off Normally the machine shall permanently be supplied with mains power. At the installation or maintenance stage you may proceed as follows to switch on or off the device. 4.1.1.1 Switching on Proceed as follows to switch the machine ON: Connect the mains power. Set the room thermostat at the desired setting. 4.1.1.2 Switching off Proceed as follows to switch the machine OFF: Set the room thermostat 5 C lower than the actual temperature. Disconnect mains power. 4.1.2 Setting the air temperature 4.1.2.1 Minimum air temperature In order to function properly the minimal air temperature should be selected on site. This can be done by setting the minimal air thermostat. The fan will not turn during heat request UNLESS the measured temperature is higher than the selected value. 7

If you install the unit as a DOWNFLOW version, you should (field) install a second thermostat in parallel to the existing one in the location as indicated in the unit. 4.2 Electronic control The electronic control is not yet implemented. 4.3 Setting the air volume 4.3.1 Standard control The unit is fitted with a 3 speed PSC motor. The desired speed can be selected during installation by changing the selected speed on the printed circuit board. 4.3.2 Electronic control The electronic control is not yet implemented. 4.4 Outside air version In outside air version the unit is used to distribute air to which more than 25% outside air is added. However, in the unit no special regulators are installed to keep the air temperature constant, nor is the heat exchanger protected from frost damage. If you want to use the unit as an outside air unit, we suggest that you: install an external regulator that keeps the minimum air temperature at a certain selectable level. protect the heat exchanger from frost related damage by means of addition of a suited anti-freeze solution to the heating circuit. 4.5 Downflow version The Multicalor MC units are factory supplied in an UPFLOW version. If you need a DOWNFLOW version, you can simply turn around the unit and install a second TR2 minimal air temperature thermostat. The extra minimum air temperature is to be ordered separately. 4.6 Installing the ducting system 4.6.1 Fitting the return air ducts Noise problems are often created if air heaters are used with very short and/or undersized return air ducts. These problems can be avoided by: insulating the return air ducts by means of an acoustic liner; installing a sound damper in the return air ducts; making sure the that there are at least 2 generously sized 90 turns in the ducting system; Increasing both diameter and length of the return air ducts. You can connect the return air duct to the left, right or the bottom of the unit. We strongly suggest using only the bottom return air opening (please remove the cut-out when commissioning). If possible, install the unit on an insulated plenum, on which side return ducts can be connected. If you do not have sufficient free space to use an insulated return air plenum, it is possible to install an optional side filter frame. However, in doing so, a large part of the acoustic insulation is lost. Always use a return air duct and return air from OUTSIDE of the combustion compartment. If you do wish to apply an open return, make sure that there are (will be) no other devices with open combustion circuit in the installation area. 4.6.2 Fitting the supply ducts Fit a matching supply air on the unit. The height of the plenum should be at least as high as the width of the unit. The supply air plenum should, like the supply ducting system, be thermally insulated. The supply air duct should be of a sufficient size to permit air displacement with normal speeds and pressure losses. 5 Maintenance 5.1 End user 5.1.1 Cleaning the air filter The standard air filter is a synthetic air filter with a life span of 1 year. However the filter requires monthly cleaning, to be performed as set out below: Set the thermostat 5 C lower than the environment temperature. You may wait until the apparatus has cooled down. Disconnect the mains. Remove the air filter and use a vacuum cleaner to clean it Put the filter back into the machine. Restore the mains. Set the room thermostat again to the required value. 8

Never remove the air filter from an MC unit. The machine must always be fitted with a EU3 (or better) air filter. Heating or ventilating without a filter may pollute the heat exchanger to such an extent that the machine may incur irretrievable damage, which the warranty does not cover. 5.1.2 Cleaning the casing The casing may be cleaned with a soft humid cloth. Do not use aggressive media such as bleaching water, solvents or petrol, as these products are likely to damage the paint. 5.2 Installer maintenance The unit is nearly free of maintenance. It is sufficient to replace the air filter and to check the unit for leakage and proper functioning. 1. Set the thermostat 5 C lower than the environment temperature; 2. You may wait until the apparatus has cooled down; 3. Disconnect the mains; 4. Remove and replace the air filter; 5. Check unit for functioning and check for leaks; 6. Verify pressure in the supply lines; 7. Switch mains power on; 8. Set the room thermostat again to the required value; 6 Problem solving 6.1 Standard control 6.1.1 Fan does not start during heat request. If the fan does not start, even though hot water is circulating in the heat exchanger, then the problem is presumably located in the TR2 minimal thermostat. Please check the setting of the minimal thermostat. Also check that the temperature sensing bulb is touching the heat exchanger in order to measure the temperature as good as possible. If working with low water temperatures, you can increase the performance of the temperature sensing bulb by wrapping a denuded stiff copper electrical wire around the temperature sensing bulb and then inserting both leads between the fins of the heat exchanger.. 6.1.2 Fan turns without heat or ventilation/cool request Check the setting of the TR2 thermostat. If the setting is too low, ambient temperature can cause the contact to close and, as a result, start the fan. If the thermostat is set high enough, but the fan keeps on starting, there probably is a problem in the hydraulic circuit (usually naturally occurring convection). 6.2 Electronic control The electronic control is not yet implemented. 9

7 Electrical wiring diagram 7.1 Standard control Thermostat Thermostaat W R T87F W W G G R Rc Y R Rc Y T8602 T87F & Q539A MAX. 3.00 A PM TR2 (DFonly field installed) TR2 16AT Fan speed selector Maximum 65 C C Common WHITE H High BLACK M Medium BLUE L Low RED LIM COM FAN W G R Y Y X 1 2 N L 3 4 5 6 C H M L WHITE BLACK BLUE RED 24V~ MULTICALOR Industries NV-SA Blarenberglaan 21 BE 2800 MECHELEN 24V 16VA 230V~ 230V X-Y AC control relay 24V 0.50 A 3-4 Air cleaner 230V 0.25 A 5-6 Humidifier 230V 0.25 A N-L TR2 AC mains Minimal thermostat 230V 230V 8.00 A 16.00 A PM Water pump 230V 3.00 A 7.2 Electronic control The electronic control is not yet implemented. 8 Warranty 8.1 General Multicalor Industries NV guarantees the MC units against all manufacturing defects or material faults, subject to the terms and conditions described under Scope and duration of the warranty. Moreover Multicalor Industries NV guarantees the machine will achieve the output indicated in normal conditions. 8.2 Scope and duration of the warranty The warranty starts at the moment of purchase by the first user and entitles the beneficiary of the warranty, through the dealer or the service department of Multicalor Industries NV, to: One (1) year free exchange of faulty parts; One (1) year free labour costs, required for the replacement of the faulty parts; One (1) year free travel and freight expenses on the condition that the machine to be repaired is in Belgium; Five (5) year free exchange of the heat exchanger, but exclusive of labour costs and travel expenses. Replacement of parts does not change the initial warranty period, i.e. the warranty is not extended by the replacement of faulty parts. 8.3 Damage that is not covered by the warranty All damage resulting from: Machine use which does not match normal household or light commercial use; 10

Failure to meet the user instructions as summed up in the user manual; Insufficient or wrong maintenance; Irretrievable fouling up of the heat exchanger caused by heating, ventilating or cooling with a highly fouled up or absent dust filter; Modifications or adaptations to the machine not covered by prior written approval by Multicalor Industries NV; Repairs carried out with non-original parts or wrong equipment or materials; The heat exchanger when used in an atmosphere polluted with chlorine or other chemicals; Causes foreign to the machine, including (but not restricted to): 1. Damage incurred during transport, including dents, scratches, etc.; 2. Damage caused by disasters, including fire, lightning, flooding; 3. Damage linked to frost; 4. Damage caused by a departure from the normal power voltage, water or gas pressure deviating widely from the nominal values suitable for the normal supply of the machine; 5. Damage caused by a non-conformity of the installation to the local standards applicable. 8.4 Not covered under warranty Parts subject to normal wear, including air filters, fuel filters and other parts that have to be replaced periodically; Machines the serial number of which has been removed or altered; Travel expenses and labour costs if the matching warranty period has expired; Result damage caused by the faulty machine; Any loss of productivity attributable to the faulty machine; Any loss of use caused by a fault to the machine; When the machine proves unsuitable for the purposes for which the purchaser bought the machine. 8.5 Repairs During the warranty period the customer may call upon the services of the dealer who sold the machine or, in Belgium, to the after-sales department of Multicalor Industries NV. 8.6 Service-parts If it is necessary to replace a part, we recommend that the matching article code of the part concerned be mentioned on the order, in addition to the type of air heater, the machine s serial number as well as the name of the part concerned. The machine type and serial number are mentioned on the registration plate placed in the machine. 9 Statement of compliance Multicalor Industries declares that the air handlers Multicalor MC 20 Multicalor MC 30 Multicalor MC 40 meet the provisions of the machine directive 89/392/EEC, the low-voltage directive 73/23/EEC as well as the EMC directive 89/396/EEC. 11

For more information please contact your dealer: MULTICALOR Industries NV-SA Blarenberglaan 21 BE 2800 Mechelen (Belgium) Tel.: +32 (0)15 29 03 03 Fax: +32 (0)15 29 03 20 e-mail: info@multicalor.be web: www.multicalor.be