Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance

Similar documents
EXPERIMENTAL INVESTIGATION OF HYBRID NANOFLUID ON THERMOSYPHON TYPE WICKLESS HEAT PIPE HEAT EXCHANGER THERMAL PERFORMANCE

Review of Thermosyphon heat exchanger charged with hybrid nanofluid for waste heat recovery applications

Recovery Using Heat Pipe Heat Exchanger with Hybrid Nanofluid

Review on Waste heat recovery application and scope of Heat pipe heat exchanger charged with Nanofluid

Experimental Study on Waste Heat Recovery from the Pyrolysis Stack using Heat Pipe

Enhancement of COP using Nanoadditives in Domestic Refrigerator

Numerical Studies On The Performance Of Methanol Based Air To Air Heat Pipe Heat Exchanger

IJSRD - International Journal for Scientific Research & Development Vol. 3, Issue 03, 2015 ISSN (online):

EXPERIMENTAL AND THEORTICAL STUDY OF THE THERMAL PERFORMANCE OF HEAT PIPE HEAT EXCHANGER

EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Pressure drop analysis of evaporator using refrigerants R-22, R-404A and R-407C

Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area

Investigation of Metal and Metal Oxide nanocoating on Fins in HPHE with Silver Water NanoFluid

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Mallikarjun 1, Anandkumar S Malipatil 2

Heat pump and energy recovery systems

Internal flow Patterns of the Horizontal Heat Mode Closed-Loop Oscillating Heat Pipe with Check Valves (HHMCLOHP/CV)

Experimental Analysis of Performance Characteristics of Mini Channel Heat Exchangers

Performance Study of Triple Concentric Pipe Heat Exchanger

Recent Advances in Energy, Environment and Economic Development

Performance analysis of ejector refrigeration system with environment friendly refrigerant driven by exhaust emission of automobile

Experimentation of Heat Pipe Used In Nano-Fluids

Performance investigation of Air-conditioning system using ejector as expansion device

EXPERIMENTAL INVESTIGATIONS ON AL 2 O 3 NANO REFRIGERANT WITH DIFFUSER AT CONDENSER INLET IN A VCR SYSTEM

Waste Heat Utilization of Vapor Compression Cycle for Operation of Vapor Absorption System

CHAPTER I INTRODUCTION. In the modern life, electronic equipments have made their way

Adsorption refrigeration system using waste heat

Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants

Numerical study of heat pipe application in heat recovery systems

MINIATURE HEAT TRANSPORT SYSTEMS WITH LOOP HEAT PIPES

Experimental study on heat transfer characteristics of horizontal concentric tube using twisted wire brush inserts

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

Analysis of Evaporative Cooler and Tube in Tube Heat Exchanger in Intercooling of Gas Turbine

Experimental Analysis of a Stirling Refrigerator Employing Jet-Impingement Heat Exchanger and Nanofluids

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM

EXPERIMENTAL INVESTIGATION OF WATER COOLER SYSTEM BY USING ECO-FRIENDLY REFRIGERANT (R-134a)

GSJ: VOLUME 6, ISSUE 6, JUNE GSJ: Volume 6, Issue 6, June 2018, Online: ISSN

Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System

Modelling the Performance of a Diffusion Absorption Refrigeration System

IJARI. 1. Introduction: Heat Pipes. Volume 3, Issue 3 (2015) ISSN International Journal of Advance Research and Innovation.

Compression of Fins pipe and simple Heat pipe Using CFD

Experimental Investigation of a Brazed Chevron Type Plate Heat Exchanger

Scientific Principals and Analytical Model. Charcoal Cooler. Lisa Crofoot MECH 425, Queens University

HEAT PIPES

Reducing energy consumption of airconditioning systems in moderate climates by applying indirect evaporative cooling

An Experimental Study of a Simple Vapour Compression Refrigeration System with Varying Parameters

Experimental study of hybrid loop heat pipe using pump assistance for high heat flux system

Heat Exchanger. The purpose may be either to remove heat from a fluid or to add heat to a fluid.

Numerical Study on Improvement of COP of Vapour Compression Refrigeration System

Experimental Investigation of a Hybrid Evacuated Tube Solar Collector

Modified Air Cooler with Split Cooling Unit

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

American International Journal of Research in Science, Technology, Engineering & Mathematics

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

Heat Recovery Units. Heat Recovery 1

DESIGN, DEVELOPMENT AND TESTING OF CROSS FLOW CIRCULAR HEAT PIPE TO COOLING OF OIL

Effect of Parameters on Internal Flow Patterns of a Top Heat Mode Closed-loop Oscillating Heat Pipe with Check Valves (THMCLOHP/CV)

Performance Analysis of Li-Br Water Refrigeration System with Double Coil Anti-Swirl Shell and Coil Heat Exchangers

Regenerator Design for Open Cycle Liquid Desiccant Systems Theoretical and Experimental Investigations

Experimental Study of Fins Effect on Thermal Performance of HPHX for Air Conditioning System

Performance analysis of a vapour compression refrigeration system with a diffuser for theeco-friendly refrigerants R-134a, R-600a and R-152a

Experimental Investigation of Elliptical Tube Bank Cross Flow Heat Exchanger with Inline Arrangement & 45 Angle of Attack

Design and Experimental Studies on Modified Solar Dryer

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

Heat Transfer Analysis of Vapor Compression System Using Nano Cuo-R134a

Open Cycle Liquid Desiccant Air Conditioning Systems Theoretical and Experimental Investigations

Enhancement of COP in Vapour Compression Refrigeration System

THE ANALYSIS AND EXPERIMENTAL INVESTIGATION OF HEAT PUMP SYSTEM USING THERMOBANK AND COS EJECTOR CYCLE

II. OBJECTIVE OF RESEARCH

Theoretical Performance Analysis of a Liquid Desiccant Air- Conditioning System for Air Heating and Cooling

PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS

Design and Development of Combined Direct and Indirect Evaporative Cooling System

Thermal Performance of a Loop Thermosyphon

CFD Analysis of temperature dissipation from a hollow metallic pipe through circular fins using Ansys 14.5

ICMIEE Experimental Investigation of an Air to Air Heat Pipe Heat Exchanger for Moderate Temperature Waste Heat Recovery

STUDY ON HYBRID SYSTEM OF SOLAR POWERED WATER HEATER AND ADSORPTION ICE MAKER

ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY

REVIEW OF DESIGN OF SINGLE EFFECT SOLAR POWERED VAPOUR ABSORPTION AIR CONDITIONING SYSTEM

CASE STUDIES OF THERMALLY DRIVEN HEAT PUMP ASSISTED DRYING. Minh Cuong Tran, Jamy Logie, Bruno Vanslambrouck, Martijn van den Broek

Heat Transfer Enhancement using Herringbone wavy & Smooth Wavy fin Heat Exchanger for Hydraulic Oil Cooling

Open and Closed Door Moisture Transport and Corresponding Energy Consumption in Household Refrigerator

International Engineering Research Journal Experimental Investigation of Effect of length on Performance of Axially Grooved Heat Pipe.

Keywords : Evaporative cooling, Saturation efficiency, Cooling capacity, Cooling pad, Cellulose, Aspen, Coconut coir. IJSER

Experimental Analysis on Effect of Design Parameters on the Performance of Single Loop Pulsating Heat Pipe

Performance of Water-in-Glass Evacuated Tube Solar Water Heaters

Performance of window air conditioner using alternative refrigerants with different configurations of capillary tube

THERMAL PERFORMANCE ASSESSMENT OF GREENHOUSE SOLAR DRYER UNDER PASSIVE MODE

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Solar Heating and Cooling Systems

PERFORMANCE OF VCRS SYSTEM WITH HEAT EXCHANGER AND PHASE CHANGE MATERIAL

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Experimental Investigation of a Multi Effect Membrane Based Regenerator for High Concentration Aqueous LiCL Solution as Desiccant

Experimental Investigate on the Performance of High Temperature Heat Pump Using Scroll Compressor

EXPLORING POSSIBILITIES WITH THE DEVELOPMENT OF THE LOOP HEAT PIPE TECHNOLOGY. Roger R. Riehl

Energy Consumption Reduction of AHU using Heat Pipe as Dehumidifier

PERFORMANCE OF SOLID DESICCANT COOLING WITH SOLAR ENERGY IN HOT AND HUMID CLIMATE

Feasibility study on an energy-saving desiccant wheel system with CO 2 heat pump

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

Transcription:

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance #1 Jaydev S. Bade, #2 Dr. Nitin U. Korde 1 Department of Mechanical Engineering, Savitribai Phule Pune University, GHRCOEM, Ahmednagar, India. 2 Department of Mechanical Engineering, Savitribai Phule Pune University, GHRIET, Pune, India. Abstract: Waste heat is heat which is produced in a process by way of fuel combustion or chemical reaction, and then dumped into the environment even though it can be still be reused for some useful and economic purpose. The essential quality of heat is not the amount instead of its value. The strategy of how to recover this heat depends in part on the temperature of the waste heat gases and the economics involved. Direct and indirect benefits are involved in heat recovery. Recovery of waste heat has a direct effect on the efficiency of the process and indirect benefits involve reduction in pollution, equipment size and auxiliary air consumption. This paper focuses on investigation of thermal performance of wickless heat pipe heat exchanger by using hybrid nanofluid (CuO+CNT/H 2 0) as a working fluid. Hybrid nano fluid of 2% volume concentration with 75% of copper oxide (CuO) and 25% of carbon nano tube (CNT) was prepared. Several studies have performed on heat pipe heat exchanger using conventional fluids and nanofluids. Effectiveness of heat pipe heat exchanger charged with hybrid nanofluid will be compared with heat pipe heat exchanger effectiveness charged with conventional fluid. Keywords: Weak less Heat Pipe, Heat Pipe heat exchanger, Thermal performance, Hybrid nanofluid, CuO+CNT/H 2 0, Effectiveness. I. INTRODUCTION With increasing trend of energy demand, there are a lot of concerns over energy supply and it is a major issue for the policy makers. Universally, buildings consume about 40% of the total world annual energy consumption and most of this energy can be used for the purpose of heating, ventilation & air conditioning (HVAC) system. Therefore, Engineers and scientists try to find alternate energy recovery technologies to enhance the performance in terms of air quality and energy utilization level. Furthermore, increasing awareness of the environmental impact of CFC refrigerants, make the engineers to adopt environmentally friendly energy recovery technologies. Most of heat is wasted in many of the outputs like industrial, automobiles etc. There are many types of energy recovery system, but most commonly used are rotating wheels, plates, heat pipes & run around loops. This experiment considers the thermal design & the experimental testing of a heat pipe (Thermosyphon) heat exchanger for a relatively small commercially available waste heat. The purpose of the heat exchanger is to recover maximum heat from moist waste air stream to preheat the fresh incoming air. A significant amount of waste heat exhausted through the exhaust ducts of commercials & industrials exhausts. Fig. 1 working principle of heat pipe 2015, IERJ All Rights Reserved Page 1

Capturing the energy in that waste heat represents rich potentials for energy savings. The heat pipe heat exchanger heat recovery system is cost effective to install and operate could potentially recover wasted heat economically and be an effective addition to utility CIPs. This project was undertaken to design, develop, install and measure the effectiveness of a heat recovery system at a small temperature range. The design concept was to capture waste heat from exhaust duct and use that heat for the fresh air supply. The limiting factor against increasing the heat transfer performance of heat pipe depends on the working properties of the working fluid. The enhancement of liquid thermal conductivity is achieved by adding highly conductive solid nanoparticles inside the base fluid. The special characteristics of the nanofluid shows increment in the heat transfer coefficient, thermal conductivity and liquid viscosity. Two types of nanoparticles used in heat pipes are aluminum oxide and copper oxide. Noie et al. [1] investigated the thermal performance of a heat exchanger consisting of thermosyphons arranged in six rows and the variable parameters which were being altered were the air velocity and the inlet temperature to the evaporator. A computer program was developed to analyze the thermosyphons heat exchanger using the ε NTU method. Leads to verify its accuracy and conformity, the test results were compared to those assumed by the simulation program. The overall effectiveness of the thermosyphons heat exchanger achieved from experiments varied between 37% and 65%. G. J. Parker [2] from University of Canterbury designed and dynamically simulated a domestic hot water system which included a waste water heat exchanger and/or a solar panel collector. The heat exchanger was a concentric cylinder unit. A 70-litre cylinder containing cold water to be pre-heated was surrounded by an annular space of 160 litres of waste warm water. The research shows that the energy saved by only employing the heat exchanger reached a maximum of 32%. Singh et al., 2010 [3] are proposed for datacenters: 1) Heat pipe heat exchanger (HPHE) pre-cooler for datacenter chiller and 2) Heat pipe based ice storage system for datacenter emergency cooling. Both the systems utilize thermal diode characteristics of passively operating heat pipes, to capture cold ambient energy for cooling purposes. The thermosyphons can absorb heat from the high temperature media to low temperature ambient by means of continuous evaporation-condensation process Wasimsaman [4] examined the possible use of a heat pipe heat exchanger for evaporative cooling as well as heat recovery for fresh air preheating. Thermal performance of a heat exchanger consisting of 48 wickless heat pipe arranged in six rows was evaluated. The tests were carried out in a test rig where the humidity and temperature of both air streams could be controlled and monitored before and after the heat exchanger. Their results showed that indirect evaporative cooling using this arrangement decreases the fresh air temperature by several degrees below the temperature drop using dry air alone. Yau and Tucker [5] mentioned that for many years, heat pipe heat exchangers (HPHEs) with two-phase closed thermosyphons, and have been widely applied as dehumidification enhancement and energy savings device in HVAC systems. Heat pipes can increase latent cooling by 25-50% depends on the application. Hospitals, supermarkets and laboratories are more good heat pipe applications. G.R. Majideian [6] carried out theory, design and construction of heat pipe. Experimentation on heat pipe heat exchanger charged with conventional fluids like water, methanol & acetone shows Effectiveness of 0.16. The purpose of this work was to investigate the effect of heat transfer rate on heat pipe heat exchanger using CuO+CNT/water hybrid nanofluid and to investigate the performance of heat pipe heat exchanger at various heat loads and mass flow rates. The average effectiveness of heat pipe heat exchanger charged with hybrid nano fluid is compared with heat pipe heat exchanger charged with conventional nanofluid. II. EXPERIMENTAL SET UP Heat pipe heat exchangers are devices that made the exchange of waste heat from a waste heat source to a colder source. Figure 2 shows the experimental layout of the test apparatus. The system is composed of three major parts: air heater (for waste air preparation), heat pipe heat exchanger and devices for measurement and control of parameters. In the installation there are two circulating fluids: the waste air in the lower chamber of the heat exchanger and the cold air in the upper chamber of the heat exchanger. Fig. 2: Schematic diagram of the experimental apparatus. 2015, IERJ All Rights Reserved Page 2

The working fluid used in heat pipe is hybrid nanofluid. The source temperature waste heat is regulated by heating load on heater. Determination of efficiency of heat recovery will be achieved under the various temperature conditions. The heat pipe heat exchanger was equipped with 08 heat pipes arranged vertically at an angle of 90 (Figure 3). Fig. 3: Schematics of the Wickless Heat Pipe Heat Exchanger. 2.1 Test Methodology Experiments are conducted to investigate Performance of heat recovery heat pipe heat exchanger by using hybrid nanofluid with variable source temperature. The heat is generated within the variable temperature source. An arrangement was made to measure and vary the heat input with the help of transformer, voltmeter and ammeter. Fig. 4: Working setup The hot and cold air temperatures are measured with the help of RTD s mounted at different locations of ducts. Four RTD s are to be fixed inside of ducts at inlet and outlet of hot and cold air in order to measure temperature. Heat input to heater varied from 250W to 1500 W in the step of 250W to vary the source temperature. By varying the source temperature the hot air at different temperature will pass on heat pipe heat exchanger. III. HEAT LOAD CALCULATION While designing the heat pipe heat exchanger, we have to calculate the total heat load for proposed heat pipe heat exchanger. Assuming maximum inlet hot air temperature 60 C and corresponding ambient temperature 25 C with maximum mass flow rate of air as 0.2361 kg/sec. The heat load on heat exchanger can be calculated as follows, Heat Load (Q) = m..δt = 0.2361 X 1.005 X 35 = 4.32 kw. Heat Load on Single Heat Pipe (Q Heat Pipe ) 2015, IERJ All Rights Reserved Page 3

= = = 0.54 kw 3.1 Design Procedure for Proposed Heat Pipe Heat pipes undergo various heat transfer limitations depending on the working fluid, the dimensions of the heat pipe, and the heat pipe operational temperature. 3.1.1 Viscous limitation- Viscous limit depends on the viscous pressure losses in vapor phase and the vapor pressure of the working fluid. The viscous limit is sometimes called the vapor pressure limit, 3.1.2 Sonic limitation- The sonic limit is due to the fact that at low vapor densities, the corresponding mass flow rate in the heat pipe may result in very high vapor velocities, and the occurrence of choked flow in the vapor passage may be possible. 3.1.3 Entrainment limitation- The entrainment limit refers to the case of high shear forces developed as the vapor passes in the counter flow direction over the liquid saturated wick, where the liquid may be entrained by the vapor and returned to the condenser. This results in insufficient liquid flow of the wick structure. 3.1.4 Boiling limitation- The boiling limit occurs when the applied evaporator heat flux is sufficient to cause nucleate boiling in the evaporator wick. This creates vapor bubbles that partially block the liquid return and can lead to evaporator wick dry out. The boiling limit is sometimes referred to as the heat flux limit. 3.1.5 Various heat pipe limits- The various heat pipe limits calculated considering the operating temperature and parameters related to heat pipe are shown in table 01. For heat pipe parameters mentioned above the axial heat flux under variable operating temperatures are calculated for different mentioned above i.e. viscous limit, boiling limit, entrainment limit and sonic limit. Temp ( C) Sonic Limit Table 01 Heat Pipe Limits Viscous limit Entrainment Limit Boiling Limit 20 103.41 92.09 111.01 132.45 30 182.90 119.89 106.87 125.65 40 308.69 186.49 102.19 121.10 50 500.98 453.16 97.25 106.84 60 783.92 1111.27 91.92 94.32 70 1190.5 2049.01 86.66 89.32 2015, IERJ All Rights Reserved Page 4

IV. RESULTS AND DISCUSSION To evaluate thermal performance of heat pipe heat exchanger, Nusselt number and heat transfer coefficient are compared with air velocity. The above graph of Nusselt number verses Air velocity at condenser section shows that Nusselt number of heat pipe heat exchanger increases as heat input increases. Fig. 5 Nusselt number verses Air velocity The above graph of Nusselt number verses Air velocity shows that Nusselt number of heat pipe heat exchanger increases as air velocity increases. Nusselt number ranges between 28.3 to 75.9 and 36.2 to 96.4 for condenser and evaporator section respectively. The graph of Heat transfer coefficient verses Air velocity shows that heat transfer coefficient of heat pipe heat exchanger increases as air velocity increases. Heat transfer coefficient ranges between 45.9 to 123.5 and 58.1 to 158.1 for condenser and evaporator section respectively. Fig. 8 Heat transfer coefficient verses Air velocity at condenser section The graph of Heat transfer coefficient verses Air velocity at condenser section shows that Heat transfer coefficient of heat pipe heat exchanger increases as heat input increases. Fig. 9 Nusselt number verses Air velocity at evaporator section Fig. 6 Heat transfer coefficient verses Air velocity The above graph of Nusselt number verses Air velocity at evaporator section shows that Nusselt number of heat pipe heat exchanger increases as heat input increases. Fig.7 Nusselt number verses Air velocity at condenser section Fig. 10 Heat transfer coefficient verses Air velocity at evaporator section 2015, IERJ All Rights Reserved Page 5

The above graph of Heat transfer coefficient verses Air velocity at evaporator section shows that Heat transfer coefficient of heat pipe heat exchanger increases as heat input increases. Fig. 11 Effectiveness verses Air velocity at various Watt The graph of air velocity verses effectiveness shows effectiveness of heat pipe heat exchanger decrease as mass flow rate increase V. CONCLUSION In this study heat recovery by using heat pipe heat exchanger characteristics waste heat has been investigated experimentally. The effect of variation in heat inputhas been investigated. The following conclusions were drawn from this study. Nusselt number of heat pipe heat exchanger increases as air velocity increases. Nusselt number ranges between 28.3 to 75.9 and 36.2 to 96.4 for condenser and evaporator section respectively Heat transfer coefficient of heat pipe heat exchanger increases as air velocity increases. Heat transfer coefficient ranges between 45.9 to 123.5 and 58.1 to 158.1 for condenser and evaporator section respectively. Nusselt number of heat pipe heat exchanger increases as heat input increases. Heat transfer coefficient of heat pipe heat exchanger increases as heat input increases. Effectiveness of heat pipe heat exchanger decreases as air velocity increases. Effectiveness ranges in between 0.19 to 0.29. Maximum effectiveness of heat pipe heat exchanger charged with conventionalfluids like water methanol and acetone fluid is 0.16, which is less than effectiveness of heat pipe heat exchanger charged with hybrid (CuO+CNT/H 2 0)nano fluid. Effectiveness of heat pipe heat exchanger decreases as heat input increases. Nomenclature m Q ΔT Viscous limitation for heat transfer (kw) Radius of vapour space (m) Enthalpy of vaporization/latent heat (kj/kg) mass flow rate of air (kg/s) Specific heat at constant pressure (kj/kg K) Heat load on 8 heat pipe (kw) Heat load on single heat pipe Vapour density (kg/ ) Maximum temperature difference ( C) Vapour pressure (N/ ) Viscosity of vapour (kg/m s) Effective length of heat pipe (m) Sonic limitation for heat transfer (kw) Area of vapour space ( ) Entrainment limitation for heat transfer (kw) Boiling Limitation for heat transfer (kw) 2015, IERJ All Rights Reserved Page 6

REFERENCES 1. Noie S., Investigation of thermal performance of an air to air thermosyphons heat exchanger using - NTU method, Applied Thermal Engineering 26, 2006, pp. 559 567. 2. G. J. Parker & A. S. Tucker, Dynamic Simulation of a Domestic Hot-Water System, Applied Energy (40) (1991) pl-19. 3. Singh, R., Mochizuki, M., Mashiko, K., Nguyen, T., 2011, Heat Pipe Based Pre Cooler and Emergency Cooling Systems for Data Centre Energy Conservation, Paper no. S051024, JSME 2011, Proceedings of the Japan Society of Mechanical Engineers Annual Conference, 11 14 September, 2011. 4. W. Y. Saman 'Performance of a thermosyphons heat exchanger in an evaporative air conditioning system', Proc. 5th Australasian heat & Mass Transfer Conference, Brisbane, 1993. 5. Y. H. Yau, A.S. Tucker, The performance study of a wet six-row heat pipe heat exchanger operating in tropical buildings, International Journal of Energy Research 27, 2003, 187-202. 6. S.H. Noie-Baghban, G.R. Majideian, Waste heat recovery using heat pipe heat exchanger (HPHE) for surgery rooms in hospitals. 2015, IERJ All Rights Reserved Page 7