esense CO2 Transmitter and Alarm

Similar documents
Installation Manual. esense Duct (Disp) Figure 1 The esense Duct with and without display

CO2 Sensor User and Installation Guide

Pocket CO2 Monitor & Data Logger SAN-0001

Falcon-II Next Generation, Air Quality Monitor CO2 & Temperature

Remote Storage Safety 3 Alarm Installation Guide

Installation Manual KS8-LCP 0-10 C0 2 TRANSMITTER. Instructions for :- KS8-LCP0-10 C02 Sensor

RK CO 2 Transmitter Operator s Manual

CO2 & Oxygen Monitor Operating Instructions Model: RAD

Warranty Registration

RK Carbon Monoxide Transmitter Operator s Manual

C7232A,B Sensor and Controller

RK / RK CO 2 Detector Operator s Manual

C7232A,B Sensor and Controller CARBON DIOXIDE SENSOR

RK Carbon Monoxide Transmitter Operator s Manual

CMF, CMX & CMA series

Miniature Thermoelectric Cooler Controller MTCC-01 user's guide

Miniature Thermoelectric Cooler Controller MTCC-01 user's guide

GASGUARD NH 3. Ammonia Sensor OPERATING & INSTALLATION MANUAL

Oxygen Monitor Operating Manual

GG-2 2-CHANNEL GAS DETECTION CONTROL PANEL. Installation and Operation Manual

GASGUARD Cl 2. Chlorine Sensor OPERATING & INSTALLATION MANUAL

GASGUARD NH 3 2% Ammonia Sensor OPERATING & INSTALLATION MANUAL

RK/ RK Carbon Monoxide Detector Operator s Manual

RK Combustible Gas Transmitter Operator s Manual

User s Manual For Model Aero-551 (Rev. Orig.)

Environmental Monitoring SmartSlot Card

GASGUARD O 2. Oxygen Sensor OPERATING & INSTALLATION MANUAL

GASGUARD SO2 Sulfur Dioxide Sensor OPERATING & INSTALLATION MANUAL

RK Carbon Monoxide Transmitter Operator s Manual

User's Guide. Pinless Moisture Meter. Model MO257

Gas Safety Products. Installation, operating and maintenance. Merlin CO2 Monitor 4500PPM. Merlin CO2 Monitor. Rev: 11 Date:

RK-05 Carbon Monoxide Detector Operator s Manual

CO2 Monitor Operating Instructions

Appearance and sensing characteristic Specification (temperature range) Model 10 to 70 C ES1B. 2 mm 20 mm 40 mm 60 mm. 40 dia. 60 dia.

User Manual R1.0 CO2Meter, Inc. Personal CO2 Monitor SAN-10

GG-CO-EXP CARBON MONOXIDE SENSOR. Installation and Operation Manual

RK-02 Multi Point Detector Operator s Manual

RK-05 Combustible Gas Transmitter Operator s Manual

CT-7 Series Toxic Gas Transmitter Operator s Manual

GASGUARDIAN Channel Controller OPERATING & INSTALLATION MANUAL

RK-05 Carbon Monoxide Transmitter Operator s Manual

GG-NO2 NITROGEN DIOXIDE GAS SENSOR. Installation and Operation Manual

User Manual. PolyGard CO LC-1112 V3. Electrochemical analog carbon monoxide transmitters serial no. EC-S 002. August 29, 2006

Warranty Registration

Sentry LIQUID LEVEL ALARM MODEL 100 OPERATING MANUAL.

MST MODEL S1 AIRLINE "CO" MONITORING AND LOW PRESSURE WARNING SYSTEM MANUAL

GG-EM ENTRANCE MONITOR. Installation and Operation Manual

GG-NH3-2% AMMONIA GAS SENSOR. Installation and Operation Manual

Carbon Dioxide Sample-Draw Detector Operator s Manual

CLIMAGUARD Air-to-Air Outdoor Heat Exchangers INSTRUCTION MANUAL. Rev. H 2015 Pentair Equipment Protection P/N

RK/ RK Oxygen Detector Operator s Manual

RK Hydrogen Sulfide Transmitter Operator s Manual

Ion Endeavor Pump Controller Digital Level Control with Pump Alternation and High Water Alarm

ES2-HB. Ordering Information. Dimensions. Specifications. Humidity Sensor Temperature/Humidity Sensor

RK Transmitter Technical Notice

GASGUARD LEL 3 OPERATING & INSTALLATION MANUAL

INSTALLATION. and INSTRUCTION MANUAL. for QUALITY AIR BREATHING SYSTEMS. Model ABM - 715

GASGUARD H 2-1% Hydrogen Sensor OPERATING & INSTALLATION MANUAL

RK/ RK Combustible Gas Detector Operator s Manual

GG-NH3 AMMONIA GAS SENSOR. Installation and Operation Manual

RK/ RK Oxygen Detector Operator s Manual

Sentry LIQUID LEVEL GAUGE MODEL 200 or 200C OWNER MANUAL REV 1.7 SEPT08 PAGE 1 OF 12

NT DUAL CHANNEL DISPLAY. User Guide

M3050 Detector Operator s Manual

WATCHMAN Model LBW-WATCHMAN Ammonia Leak Detector

RK-CH4-4 Combustible Gas Transmitter Operator s Manual

User's Guide. CO 2 Monitor. Model CO200

Preamplifier Power Supply PPS-02 user's guide

GG-VL-R REFRIGERANT VENT LINE SENSOR. Installation and Operation Manual

CD6102 / CD6102 OC / CD6102-2

Operating Instructions. Temperature and Humidity EC Control. Model 35YV93

GROUP OF COMPANIES. MERLIN STEALTH Electric Fence Energizer. Users Manual

Model NT20e Installation Guide

GASGUARD VENT LINE3. Ammonia Sensor OPERATING & INSTALLATION MANUAL

CO2 RESPONDER Portable Carbon Dioxide Detector QUICK REFERENCE GUIDE

EXC-450 User s Manual

ProTalk. Expander. Operating Manual Model B1292. July 28, 2009 Rev. 1.01

Automatic Humidity Controller. Model 512 (Revision C) Operating Manual

EOS. Instruction Manual. 120V High Amperage Digital Humidity Controller. Part #

Wireless Base Remote Test and Hush

User Manual. PolyGard Gas Controller MGC3. Two-Channel Analog Gas Controller Serial Number _E _0907. September 2007

ANALOX 101 D2 PORTABLE OXYGEN MONITOR USER MANUAL

1500W STOVE HEATER INSTRUCTION MANUAL. Item No: 050-HA-50090

SEC 2000 Millenium Infrared Gas Detector

Datasheet: K-22 LO Sensor

GG-R REFRIGERANT SENSOR. Installation and Operation Manual

VX SERIES Wireless Thermostat with Occupancy Sensor

Environmental Monitoring Card

IMPORTANT INFORMATION - PLEASE READ CAREFULLY

2-Port alarmcharge Hub - Manual

GG-LEL2 COMBUSTIBLE GAS SENSOR. Installation and Operation Manual

Ion Genesis II Pump Controller Digital Level Control with Pump Alternation and High Water Alarm

MGC Dock User s Manual

GG-H2S HYDROGEN SULFIDE GAS SENSOR. Installation and Operation Manual

Setra Model SRH Relative Humidity Sensor Series with Active or Passive Temperature Sensing Installation Instructions

INSTALLATION. and INSTRUCTION MANUAL. for QUALITY AIR BREATHING SYSTEMS. Model ABM - 700

M113S Users Manual. MERLIN STEALTH M113S Electric Fence Energizer GROUP OF COMPANIES. PDF created with pdffactory trial version

Carbon Monoxide (CO) Gas Detectors with (0)2-10 Vdc or (0)4-20 ma Output

User Manual. Humidity-Temperature Chart Recorder. Model RH520

RSMFM-2R MULTIFUNCTIONAL

Transcription:

esense CO2 Transmitter and Alarm Installation & Manual SE-0010, SE-0012, SE-0013, SE-0014 Rev. 22 November 2015 2015, CO2Meter.com. All Rights Reserved.

Table of Contents General... 3 Opening the Housing... 3 Recommended Mounting Height from Floor... 4 Dimensions... 4 Electrical Connections... 4 Buzzer & Jumper Settings... 6 LED Display Configuration... 7 Self Diagnostics... 7 Maintenance... 7 Theory of Operation... 7 Calibration Options... 7 Manual Calibration... 8 EMC Directives... 9 Support... 9 Warranty... 9 Returns... 9 Liability... 10 Contact Us... 10 esense Manual 2 of 10

General The esense alarm is designed to measure carbon dioxide (CO2) in rooms. It displays the measured CO2 value in ppm (parts-per-million) on the LCD. LEDs give an overview of the CO2 value. On alarm models, an acoustic alarm sounds when the CO2 goes above the set value. The acoustic alarm can be silenced with a push button on the front of the meter. In addition, the esense may be connected to a Direct Digital Control (DDC) with 0-10V analog signal outputs corresponding to 0-2,000ppm CO2 by default, 0-2,000ppm for the LEED variation, and 0-9,999ppm for the OSHA variation. 4-20mA output is also available for the model SE=0012 only. Opening the Housing Front Insert screw driver Push upwards to open Front Wall Wall Figure 1. Closed housing seen from the top and the side. The housing is opened by inserting a screw driver and pushing to the front side of the housing. The locking hooks will then be released. Figure 2. Closed housing seen from the side. The housing is opened by inserting a screwdriver and pushing left (to the front side). Figure 3. Closed housing seen from the side. Never push to the right. The locking hooks may break and damage the housing. esense Manual 3 of 10

The locking hooks will then be released. Recommended Mounting Height from Floor - 18-36 inches for OSHA, CO2 storage applications, fermentation IAQ level applications - 48-60 inches for LEED, Indoor Air Quality applications - As required for custom indoor horticultural cultivation applications Dimensions 30(1,18) 85(3,34) 30(1,18) 30(1,18) 32,7(1,29) 128,4(5,06) 30(1,18) 52,5(2,07) 30(1,18) Figure 3. The dimensions of the sensor in mm and (inches) Electrical Connections The power supply has to be connected to +~ and. is considered as system ground. The same ground reference has to be used for the esense and for the DDC/signal receiver. PLEASE NOTE! The same ground reference has to be used for the esense unit and for the control system! esense Manual 4 of 10

Terminal Function Electrical data Remarks +~ Power (+) 24 VAC/DC+ (+-20%), 2W Power ground (-) 24 VAC/DC- System voltage reference OUT1 Analog Output 1 (+) 0-10 VDC 0-2,000 ppm CO2 default 0-9,999 ppm CO2 OSHA 0-2,000 ppm CO2 LEED OUT2 Acoustic Alarm SE-0010, 0013,0014 Buzzer Push button silences the acoustic alarm for 30 minutes. SE-0012 0-10VDC/4-20mA Select via Jumper Table I. Connections of the main terminal White striped wire is + Positive esense Manual 5 of 10

Buzzer & Jumper Settings Models SE-0010, SE-0013, SE-0014 Analog Output 2 Voltage & Buzzer Only Model SE-0012 only. Analog Output 2 options: 0-10V Jumper Settings 4-20mA Jumper Settings Figure 4. The upper part of the esense PCB seen from the back with the jumper in voltage (default) or current position. esense Manual 6 of 10

LED Display Configuration LED Colour esense esense Programmable esense LEED esense OSHA Green n/a User-Defined. Limit must be less than Yellow Yellow n/a User-Defined. Limit must be between Green & Red Red n/a User-Defined. Limit must be higher than Yellow Green < 800 ppm CO2 Yellow 801-1400 ppm CO2 Red > 1401 ppm CO2. Buzzer sounds. Green < 4500 ppm CO2 Yellow 4501-5000 ppm CO2 Red > 5001 ppm CO2. Buzzer sounds. Self Diagnostics The system contains complete self-diagnostic procedures that are executed automatically when the sensor is in operation. Sensors with display show a wrench if an error is found. The wrench is shown during the first seconds after power up and if the measuring range is exceeded. Maintenance The esense is basically maintenance free in normal environments thanks to the built-in selfcorrecting ABC algorithm. Discuss your application with your distributor in order to get advice for a proper calibration strategy. Theory of Operation The CO2 sensor inside this meter uses NDIR (non-dispersive infrared) technology to sense, as a function of transmitted light, the concentration of CO2 in the air. It has been factory calibrated to operate within the specified range and precision. Calibration Options The CO2 sensor has 2 calibration modes: manual, and Automatic Background Calibration (ABC). Manual calibration is required if the sensor does not regularly sense 400ppm CO2 (fresh outdoor air) at least once every 7 days. ABC calibration may be used to ensure maximum accuracy by continuously adjusting the zero-point. However, it requires the sensor be exposed to fresh air at least once every 7 days. ABC calibration mode is default for Model SE-0010 LEED units. For all others, manual calibration mode is pre-set at the factory. You may request ABC calibration be enabled at time of purchase, or the calibration mode can be changed using our GasLab Software and esense programming cable (sold separately). The ABC algorithm allows the CO2 sensor to dynamically shift its CO2 reading by a constant. It works via storing the lowest CO2 sample taken over the ABC Period and assuming that this low value is equal to a known value (the target value). It then adjusts the output of the CO2 reading by the delta between these values. This algorithm does not affect the linearization of the output signal. esense Manual 7 of 10

Manual Calibration There are 2 methods of manual calibration: 1. Fresh Air (400ppm CO2) Calibration: if Din3 is shorted for a minimum time of 8 seconds, the internal calibration code bcal (background calibration) is executed. The sensor must be operating in a fresh air environment (400 ppm CO2). Do not blow or breathe near the sensor. 2. Nitrogen (0ppm CO 2) Calibration: If Din2 is shorted for a minimum time of 8 seconds, the operation code CAL (zero calibration) is executed. The sensor must already be purged by some gas mixture free from CO2 (i.e. Nitrogen or Soda Lime CO2 scrubbed air) in a sealed calibration chamber. For the vast majority of applications, fresh air calibration is recommended. If your company has ISO, LEED or OSHA environmental systems requirements documentation, you should verify that zero calibration is not required. Input Switch Terminal (normally open) Din3 Default function (when closed for minimum 8 seconds) bcal (background calibration) assuming 400 ppm CO2 sensor exposure Din2 CAL (zero calibration) assuming 0 ppm CO2 sensor exposure Table I. Switch input default configurations Manual Calibration Procedure: 1. Separate the Top and Bottom halves of the device 2. Remove the PCB from the top half by depressing the plastic tabs 3. Reset the PCB and its pins into the bottom half of the device 4. Short either Din3 or Din2 (not both) for a minimum of 8 seconds 5. Reassemble the device If calibration is unsuccessful, wait at least 10 seconds before repeating either procedure again. Make sure that the sensor is not exposed to human breath, or it will be mis-calibrated. Jumper Din2 for 0 ppm CO2 calibration or Din3 for 400 ppm CO2 for a minimum of 8 seconds esense Manual 8 of 10

Addtional Notes The sensor accuracy is defined at continuous operation (at least 3 weeks after installation). Electronic products should be disposed of via a suitable recycling center. EMC Directives This product is in accordance with the EMC 2004/108/EC, 92/31/EEG including amendments by the CE-marking Directive 93/68/EEC. The product fulfils the following demands: EN 61000-4-2 level 2, EN 61000-4-3 level 2, EN 61000-4-4 level 4, EN 61000-4-6, EN 61000-4-8 level 4, EN 55022 class B Support The quickest way to obtain technical support is via email. Please send all support inquires to support@co2meter.com. Please include a clear, concise definition of the problem and any relevant troubleshooting information or steps taken so far, so we can duplicate the problem and quickly respond to your inquiry. Warranty This meter comes with a 1YEAR (warranty period) limited manufacturer s warranty, starting from the date the meter was shipped to the buyer. During this period of time, CO2Meter, Inc. warrants our products to be free from defects in materials and workmanship when used for their intended purpose and agrees to fix or replace (at our discretion) any part or product that fails under normal use. To take advantage of this warranty, the product must be returned to CO2Meter, Inc. at your expense. If, after examination, we determine the product is defective, we will repair or replace it at no additional cost to you. This warranty does not cover any products that have been subjected to misuse, neglect, accident, modifications or repairs by you or by a third party. No employee or reseller of CO2Meter, Inc. products may alter this warranty verbally or in writing. Returns If the product fails under normal use it may be returned. An RMA (Return Material Authorization) number is required to process any return no matter the reason. To obtain an RMA number, please send an email to: support@co2meter.com When requesting an RMA number, please provide the reason for return and original order number. Once you have an authorization code you may complete your return processing by visiting www.co2metersupport.com/rma. When asked, enter the authorization code you were provided. esense Manual 9 of 10

Please use the original packaging (if available) when returning the meter to CO2Meter. Include the provided RMA number on the outside of the box, preferably on the shipping label. Secure the meter inside the package properly to prevent any damage during transit. Ship your meter to the address listed on your RMA paperwork. CO2Meter, Inc. will not, under any circumstances, be responsible or issue refunds for any shipment expenses. NOTE: For items returned during the warranty period, return shipping will not be charged. Meters that are have failed due to improper use, damaged, abuse, or are out of warranty period will be examined and an estimate of repair/replacement will be provided to you. Liability All liabilities under this agreement shall be limited to the actual cost of the product paid to CO2Meter, Inc. In no event shall CO2Meter, Inc. be liable for any incidental or consequential damages, lost profits, loss of time, lost sales or loss or damage to data, injury to person or personal property or any other indirect damages as the result of use of our products. Contact Us We are here to help! For information or technical support, please contact us. support@co2meter.com (386) 256-4910 (Technical Support) (386) 872-7665 (Sales) www.co2meter.com Address: CO2Meter.com 131 Business Center Drive Ormond Beach, FL 32174 USA esense Manual 10 of 10