Dehumidification Strategies Application Note

Similar documents
Model 5190-F Temperature/Humidity Probe

Cooling Load Analysis and Computation Worksheet

Model 5190-E Temperature/Humidity Probe

Psychrometric Engineering Applications

REC-8R Environmental Control. Operation and Installation Manual

December 6, 2018 Optimizing Solutions through Superior Dehumidification Technology SM

THE PSYCHROMETRIC CALCULATOR By: Stanley F. Gallos, The Bastian-Blessing Company INTRODUCTION PROPERTIES OF THE RSES CALCULATOR

Solar Still - Improved Distillation

In Search of Indoor Comfort

Moisture Movement. By Ben Gromicko

Cooling Load Analysis and Computation Worksheet Answers Part 1 Psychrometrics

QUICK START GUIDE. QUESTemp o 32 Heat Stress Monitors

Modeling projects that require very tight space temperature control

MAXIMIZING FACILITY PERFORMANCE WITH INNOVATIVE HVAC & IRRIGATION SYSTEMS

TDSHS Air Change Requirements and the Basics of Psychrometrics. Presented by: Aric Murray December 06, 2013

Instructions manual DEHUMID HP50

Practical Fundamentals of Heating, Ventilation and Air Conditioning (HVAC) for Engineers and Technicians

Air Conditioning Clinic

100% Outdoor Air Dehumidification Methods

S.A. Klein and G.F. Nellis Cambridge University Press, 2011

Greenhouse Temperature Management

Removing The Potential For Condensation In An Electronic Cabinet

APC APPLICATION NOTE #119

By Thomas H. Durkin, P.E., Member ASHRAE, and James B. (Burt) Rishel, P.E., Fellow/Life Member ASHRAE

Maximizing Vine Crop production with Proper Environmental Control

Benefits Offered by Passive Dehumidification Wheel Speed Control

Humidity Control Systems for Civil Buildings in Hot Summer and Cold. Winter Zone in China

Owner s Manual Refrigerated Compressed Air Dryers Models F-200, 250, 300 & F350

CARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection.

ASHRAE Standard 90.1 Energy Requirements Wrap-Around Heat Pipes

To Keep Docs Cool, Dry and Happy

Air-Cooling Evaporators

Owner s Manual Refrigerated Compressed Air Dryers Model F-100

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

OTFAMU Fresh Air Make Up System For Chilled Water OPERATOR S MANUAL. Technicold Marine Systems

Chapter 14 GAS VAPOR MIXTURES AND AIR-CONDITIONING

Tune-Rite Software Operation Manual

Psychrometrics: The Science of Moisture in Air. Presented by Tom Peterson, CEO and Founder. Climate by Design International

For an ideal gas mixture, Dalton s law states that the sum of the partial pressures of the individual components is equal to the total pressure.

HYDROPONICS AND GREEN HOUSE CONTROLLER MODEL HGC-003 OWNER'S MANUAL FAN MAX TEMPERATURE LAMP DURATION FAN MAX HUMIDITY PUMP INTERVAL DECREASE

OT-FX2 OLED TOUCH for the FX II Touch control panel OPERATOR S MANUAL. Technicold Marine Systems

Week 4. Gas-vapor mixtures Air conditioning processes. ME 300 Thermodynamics II 1

Owner s Manual Refrigerated Compressed Air Dryers Models F-3528, F-3529, F-3530, F-3531 & F-3532

ME Mechanical Engineering Systems Laboratory. Experiment 3 - Mass and Energy Balances in Psychrometric Processes

Next Generation Passivhaus Archives

Article Energy Saving Benefits of Adiabatic Humidification in the Air Conditioning Systems of Semiconductor Cleanrooms

Section 4 of 6 DOAS Core Technologies

Humidity An excuse for the 80s

Standards and Guidelines. Presented by: Aric Murray December 12, 2014

Tech to Tech May 07 HRV s & ERV s

An Introduction of Below-Freezing and Humidity Environment Controlling Technology Equipped on Brake Test Equipment

Relative Humidity in Schools Jim Cummings and Chuck Withers

Energy Recovery Ventilation

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY

CRAWL SPACE MOISTURE CONTROL - A Fundamental Misunderstanding By Peter Carpenter, member ASHRAE, SBCCI

D-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency

MSP WRAP-AROUND MULTIPLE SMALL PLATE DEHUMIDIFICATION TECHNOLOGY VS. CONVENTIONAL DEHUMIDIFICATION IN DEDICATED OUTDOOR AIR SYSTEMS (DOAS)

Session 3 Humidity definitions & units

Liquid Desiccant Air Conditioning Systems

Heat Pump Water Heaters

Optimize Evaporative Cooler

BD Viper Lysing Heater Manual (for BD Viper System)

Understanding Water Use by Plants in a Cloche System - Gardening

FS 231: Final Exam (5-6-05) Part A (Closed Book): 60 points

Principles of Active Desiccant Operation. Presented by Tom Peterson, CEO and Founder. Climate by Design International

ACHIEVING ENERGY-EFFICIENT DATA CENTER COOLING: DOES REDUCING FAN SPEED ALWAYS RESULT IN ENERGY SAVINGS?

QUICK START GUIDE. QUESTemp o 34/36 Heat Stress Monitors

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Redesign of Bennett Hall HVAC System

Dynamic performance of a novel dew point air conditioning for the UK buildings

Humidity Control in Tropical Climate with Heat Pipes - The GREEN Way

HVAC 101. The Basics of Heating, Ventilation and Air Conditioning

CONDENSATION/HUMIDITY PROBLEMS IN BREWERIES

A Treatise on Liquid Subcooling

Principles of Cold Insulation

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

ATMOX MAXX System THE Complete Moisture Control System for Crawlspaces. User s Guide

Air Conditioning Clinic. Absorption Water Chillers One of the Equipment Series TRG-TRC011-EN

Complete Ventilation, Heat Recovery and Dehumidification Packaged System by. Maintaining Your Climate for Indoor Pools and Waterparks

Technical Papers. 37th Annual Meeting. International Institute of Ammonia Refrigeration. March 22 25, 2015

T Caution. Page. Table of Contents Table of Contents Thermostat Operation Thermostat Quick Reference Thermostat Warranty Information

COMcheck Software Version Mechanical Compliance Certificate

DEHUMIDIFIERS /2015 OWNER S MANUAL FOR HEALTHY CLIMATE DEHUMIDIFIER CONTROL MODEL Y6456

Postharvest Storage. New Farmer Webinar. October 17, 2013

Desiccant Cooling with Solar Energy

Owner s Manual Refrigerated Compressed Air Dryer Model F-50

HVAC Mandatory Provisions Part II, Page 1

How to Read the South Plains Evapotranspiration Information

DES CHAMPS PRODUCTS. Specializing in: -- Air-to-Air Energy Recovery -- Conditioning Outdoor Air -- Controlling IAQ -- Indirect Evaporative Cooling

H EDRICK ASSOCIATES OF GRAND RAPIDS West Michigan s Factory Representative

Controlling Wrap-Around Heat Pipes for Systems with Strict Space Humidity Requirements. By Michael O. Davis, PE, August 2015

Heat Recovery Units. Heat Recovery 1

Life-Cycle Energy Costs and Greenhouse Gas Emissions for Gas Turbine Power

The Basics - B Practical Psychrometrics. Jerry Cohen President Jacco & Assoc.

A/C Cooling Load calculation and measurement

Experimental study of hybrid loop heat pipe using pump assistance for high heat flux system

Reducing energy consumption of airconditioning systems in moderate climates by applying indirect evaporative cooling

Standard SPECIFICATIONS FEATURES APPLICATIONS

White Paper Dehumidification in Humid Climates - A Theoretical Case Study

INSTALLER S & OWNER S MANUAL

Transcription:

Dehumidification Strategies Application Note Rev. May 2008

Dehumidification Strategies 2008 Argus Control Systems Limited. All Rights Reserved. This publication may not be duplicated in whole or in part by any means without the prior written permission of Argus Control Systems Limited. Limits of Liability and Disclaimer of Warranty: The information in this manual is furnished for informational use only and is subject to change without notice. Although our best efforts were used in preparing this book, Argus Control Systems Limited assumes no responsibility or liability for any errors or inaccuracies that may appear. Trademarks: Argus Controls, Argus Graph, Argus Control Systems, Argus Titan, and the Argus logo are trademarks of Argus Control Systems Limited. All other trademarks are the property of their respective owners. Telephone: (604) 538-3531 or (604) 536-9100 Toll Free Sales: (800) 667-2090 (North America) Toll Free Service: (888) 667-2091 (North America) Fax: (604) 538-4728 E-mail: argus@arguscontrols.com Web: www.arguscontrols.com Written and designed by Argus Control Systems Limited. Printed in Canada. Revised: May 2008

Table of Contents DEHUMIDIFICATION STRATEGIES... 2 Air - Water Relationships... 3 Using Heating for Dehumidification... 4 Using Dehumidify Ventilation... 5 Managing Dehumidification Costs... 6-1-

DEHUMIDIFICATION STRATEGIES Key Concept: With carefully coordinated simultaneous heating and venting, it is possible to control humidity levels while maintaining the climate temperature setpoint. In greenhouses, heating and ventilation are the most common methods used to reduce humidity levels relative to the dew point. There are other methods as well, such as mechanical air conditioning (removing water vapor from the air by temporarily chilling it to below the dew point, thus condensing some of the water vapor), and the use of chemical desiccants or brine solutions. These methods are used less often in commercial situations. Except for chemical desiccants, dehumidification strategies generally involve changing the psychrometric properties of the air, and the temperature of the air, at least temporarily. A given volume of air can hold progressively more water vapor as its temperature increases. Therefore, by manipulating the temperature of the air it is possible to influence the amount of humidity relative to the dew point. The Argus Energy Balance program provides 2 strategies for dehumidification control: 1 Apply Heat - to increase the air temperature, thereby reducing the relative humidity 2 Ventilate - to exchange moist air with drier external air In practice, these strategies must often be used together, particularly when you are trying to hold a steady temperature. It is also important to understand that whenever heating and ventilating are used to manage humidity, they cannot help but affect temperatures levels, since air temperature and humidity levels are so interdependent. Similarly, heating and venting for temperature control will affect humidity levels. In practical terms, whenever we need to use the same equipment to control both conditions, we can't adjust one without the other. -2-

Air - Water Relationships The diagram below illustrates the major relationships between air temperature and humidity. The top row of arrows shows the effects on air temperature, relative humidity, vapor pressure deficit, crop irrigation demand, and evapotranspiration (evaporation and plant transpiration) rates when supplemental heat or the heat from light energy is applied. The middle row shows what happens as humidity increases due to the evaporation of water in the climate. The third row shows the effects of ventilation: exchanging the climate air with cooler outside air. Since humidity levels and air temperature are so interrelated, it is seldom possible to adjust one without affecting the other. You might ask: If humidity and air temperature are so interdependent, why should we bother having separate control calculations? -3-

The Argus Climate Energy Balance program calculates separate heating and cooling requirements for temperature and humidity control. Separating the two allows us to independently calculate the degree and nature of the control response that is required for both humidity and temperature management, and to act accordingly. We can also control the relative resources that can be used for either objective. For example, suppose we have a climate where: Heating Target is 20 ºC. Cooling Target is 25 ºC. Dehumidify Target is 80%. Current Temperature is 21 ºC. Current Humidity is 85% RH. Outdoor Temperature is 10 ºC. Outdoor Humidity is 85% RH. From the above information, we can see that the current temperature does not require adjustment since it is between the Heating and the Cooling targets. Therefore, there is currently no demand for heating or ventilation for temperature management purposes. However, the humidity is above the current control target and something needs to be done about it. The Energy Balance program offers two strategies that can be used separately or together: We can apply Heat. We can apply Ventilation. We can apply both. Using Heating for Dehumidification Let's first assume that we are going to apply Heating for Dehumidification without applying any Ventilation for Dehumidification, here's what may happen: 1. First, the air temperature should begin to rise (because we are actively applying more heat) and the relative humidity will be reduced, at least temporarily. If it is reduced to below the target threshold, the control system will stop applying the additional heat. If we are lucky, the new temperature might stabilize at 24 ºC, still within the heating/cooling deadband. However, chances are that the heat applied will cause the temperature to rise above the cooling setpoint (particularly if the heating and cooling setpoints are close to one another). 2. Due to continued evaporation of free water in the climate, and the moisture released by animals, plants, or human activities, this drier, warmer air may well accumulate more water vapor, again causing the system to apply additional heating, until eventually the air temperature ventilation target is exceeded. 3. Ventilation control will now be applied, not for dehumidification purposes, but to mange this increased temperature. This will result in an exchange of warm moist air climate air for cool (and apparently just as moist) outdoor air. 4. In our example, notice that in the outdoor air and the indoor air are at the same relative humidity (85%) but different temperatures. It may appear at first that bringing in air that is the same relative humidity won't help solve our climate humidity problems. However, the outdoor air is much cooler, and when we bring it in, it is going to be warmed up to at least our heating setpoint (20 ºC). -4-

5. If we were to consult a psychometric chart (a chart used for calculating air properties at various temperature and humidity levels), we would see that when you take air at 10 ºC, 85% RH and warm it up to 20 ºC the relative humidity will actually fall to 45% RH. Therefore, when this cool air is reheated, the net effect will be that we have mixed in a volume of drier air at 45% RH with our 85% RH climate air. The resulting humidity will be somewhere in between the two and hopefully lower than our maximum humidity setpoint. To accomplish the dehumidification above, we caused the control system to do something that we don't normally want to see happen; we operated our heating equipment and our cooling equipment at the same time. However, this is often the only practical way that dehumidification can be accomplished. Using Dehumidify Ventilation To avoid raising the temperature all the way to the Cooling Target, we can simultaneously employ the Ventilation for Dehumidification options in the Energy balance program. If carefully configured, this will cause the ventilation machinery to act before the greenhouse temperatures rise above the controlled levels. In this way, it is possible to control excess humidity without significantly affecting the climate temperature, since it is possible to simultaneously exhaust warm moist air and reheat the incoming cool air at a rate that maintains a stable climate temperature. The objective is to achieve a steady ventilation/reheating state that maintains the climate temperature within the temperature setpoints, while at the same time keeping the humidity levels just under the target threshold. The ventilation and heating systems often do not produce their results at the same rate. For example, ventilation systems can often lower the temperature faster than heating systems can raise it due to differing process lags in the two systems. Therefore, there are offset settings in the Energy Balance program that can help you to adjust for this. If the heating system takes longer to produce a result, you may want to have the Heating for Dehumidification control kick in before the Ventilation for Dehumidification controls. With the Proportional/Integral tuning settings for each method, you can control how aggressively each method should tackle the problem, and provide tuning for the respective process lags in each system. You can also control the maximum amount of each resource (Heating or Venting) that you wish to use for dehumidification purposes. -5-

Managing Dehumidification Costs Simultaneous heating and venting for humidity control can be likened to driving with one foot on the gas and the other on the brake. You can achieve a balance (a constant speed) by applying just a small amount of gas and brake, or by applying lots of gas and countering this with lots of brake. Obviously, for humidity control, we want to apply the smallest amount of resources possible to get the job done. Dehumidification can be expensive, and you might not want to turn all of your heating and cooling resources over to the control system to manage tight humidity targets. To manage this, you can set maximum limits on your Argus system for both dehumidification heating and dehumidification ventilation controls. This will limit the amount of resources applied by each. You can also create management alarms to monitor current dehumidification requirements. You should also record and regularly review all of your heating, ventilation and humidity control parameters to check system performance. Whenever you limit the Heating or Ventilation resources that can be applied, there may be times when you may not be able to achieve the Dehumidification Targets you have established. You should make sure that your dehumidification goals are realistic for the intended application. Don't do any more dehumidifying than is necessary to accomplish your objectives. Also, make sure that the sensors used to monitor humidity levels are working properly and placed in locations that are representative of the average humidity conditions. -6-

ARGUS CONTROL SYSTEMS LTD. Telephone: (604) 538-3531 or (604) 536-9100 Toll Free Sales: (800) 667-2090 (North America) Toll Free Service: (888) 667-2091 (North America) Fax: (604) 538-4728 E-mail: argus@arguscontrols.com Web Site: www.arguscontrols.com Information in this manual is subject to change without notice. Copyright 2008 Argus Control Systems Ltd. Printed in Canada Argus is a registered trademark of Argus Control Systems Ltd.