Extreme Domestic Hot Water Loading System TECHNICAL DOCUMENTATION. Issue 11/09

Similar documents
TABLE OF CONTENTS TECHNICAL DOCUMENTATION 03. Technical Data Electrical Details Connection Details Dimensions Standing Losses

Unvented Calorifier Range. Operating and Maintenance Manual. For Models & 500

INSTALLATION MANUAL. RD SERIES Digital Electric Water Heater Wall-hung Unvented

Furrows Business Park, Haybridge Road Wellington, Telford, Shropshire TF1 2FE

Quantum. Installation, User and Service Manual. Hot Spring

1845 Tech Manual.qxd 23/11/05 1:20 pm Page 2 EXCELSIOR UNVENTED WATER HEATERS INSTALLATION MANUAL. Design for living

MW & EW 10 & 15 Litre Unvented Water Heaters HANDBOOK. IMPORTANT: This booklet should be given to the customer after installation and demonstration.

Unvented water heater

Installation and User Instructions Aquaheat Unvented Water Heaters Models: AH30H

Unvented Direct & Indirect Hot Water Cylinders (400L L)

extreme HIGH EFFICIENCY HOT WATER SYSTEMS

ZIP Varipoint III. Installation, Maintenance and User Instructions. Models VP303, VP503 VP803, VP953 direct unvented water heaters. Issued August 2008

Installation Manual EXCELSIOR Unvented Water Heater

ADVANCE STAINLESS STEEL UNVENTED HOT WATER SYSTEMS

Introduction. There is no obligation to follow the methods or comply with the standards set out in this Technical Booklet.

PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION INSTALLATION MANUAL

KYROS INSTALLATION MANUAL KYROS. Digital Electric Water Heater Wall-hung Unvented

PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION INSTALLATION MANUAL

INSTALLATION MANUAL. Ecoline Geo RI HP PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION

AquaFlo II. Issue 3 December Please read these instructions carefully before commencing installation of the AquaFlo unvented water heater

Schuco SS-TC/SC Cylinders

WATER HEATERS INSTALLATION MANUAL

Unvented Direct & Indirect Hot Water Cylinders (400L L)

Unvented Hot Water Storage Cylinders Installation and Maintenance Instruction Manual

Alpha CombiMax 350 and 600

Fusion 200, 300 & 500

Technical and Installation manual All Models

Advance Stainless Steel Unvented Hot Water Cylinders for Heat Pump Systems. Installation and Commissioning Manual

Megaflo Eco Unvented Direct & Indirect Hot Water Cylinders

Installation & User Instructions

Megaflo HE issue 6

Unvented Direct & Indirect Hot Water Cylinders

Megaflo Eco Slimline Unvented Direct & Indirect Hot Water Cylinders 100L - 200L

MEGAFLO Eco SystemReady Unvented Indirect Hot Water Cylinders

EPU - WM30 EPU - WM 50 EPU - WM100

CROWN WATER HEATERS CPU10 - CPU15 CPOS10 - CPOS15

POWERFLOW Series. Unvented Electric Storage Water Heaters. Installation & Operating Instructions Manual

UNVENTED MAINS PRESSURE SOLAR WATER HEATERS 210, 250 AND 300 LITRE CAPACITY INDIRECT MODELS INSTALLATION AND SERVICING INSTRUCTIONS

smart line E SLE

Unvented water heater

Instructions for Use Installation and Servicing

Instructions & Maintenance

Megaflo Eco Solar PV Ready Unvented Direct & Indirect Hot Water Cylinders 170L - 300L

Megaflo Eco Unvented Direct & Indirect Solar Hot Water Cylinders

MEGAFLO Eco Plus Solar Unvented Hot Water Cylinders 400L -570L

Installation & User Instructions

Powerflow Unvented water heater

Megaflo Eco SystemReady Unvented Indirect Hot Water Cylinders

PremierPlus Unvented Hot Water Cylinder Installation and User Manual

FASTflo. Working towards a cleaner future

Unvented Hot Water Storage Cylinders

Design, Installation, User & Servicing Instructions

MULTIPOINT 30 & 50 Litre

Design, Installation, User & Servicing Instructions

Megaflo Eco Plus Unvented Indirect Hot Water Cylinders 800L L

Plus. USER and INSTALLATION INSTRUCTIONS. 30,000-9kW for Heating and Hot Water

1 Dimensions Installation Mains/boosted cold water inlet Connection to the system Drain Dimension for fixing 6

PremierPlus SystemFit Unvented Indirect Hot Water Cylinder Installation and User Manual

SEALED THERMAL STORE

Instructions for Installation, Servicing and Use

R e n e w a b l e s. Tribune HE Unvented Hot Water Cylinders Installation and Maintenance Instructions. Issue 14 May 2011 Part No.

MEGAFLO HE Iss 1

StainlessLite HP. Design, Installation & Servicing Instructions. Unvented cylinders specifically designed to work with a heat pump

INSTALLATION MANUAL. Ecoline Geo RI HP PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION

IMAGINATION SOLAR LTD. Installation Guide B1. Planning the Plumbing and Wiring

Installations, User and Service Manual. Section A Domestic Hot Water Cylinder 3C382B 3C510B 3C382HP 3C510HP. Section B Solar 3C Heating System

PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION INSTALLATION MANUAL

ADVANCE ECB ELECTRIC COMBINATION BOILER

Ethos Range High Efficiency Domestic Boilers. Combination Boilers Condensing Combination Boilers Condensing System Boilers

Zircon Installation Manual

PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION INSTALLATION MANUAL

Broag Pressurisation equipment

PremierPlus SystemFit Unvented Indirect Hot Water Cylinder Installation and User Manual

unistor Instructions for Installation and Use Unvented hot water storage cylinder

APP STAINLESS UNVENTED HORIZONTAL HOT WATER CYLINDERS

MULTIPOINT SS H 50/80 & 100

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS,

Instructions for Installation, Servicing and Use

Installation, Operation and Maintenance Instructions for Thermax Semi-Storage Calorifier

Unvented Copper Hot Water Cylinders

ZIP AquaFlo II. Models: Direct, Indirect and Solar Compatible. Unvented cylinder water heaters

ADVANCED WATER COMPANY LTD COPPERFORM. Advanced Water Company Ltd. Unvented Hot Water Cylinders. Supplied By Advanced Water Company Ltd

MEGAFLO Eco SystemFit Unvented Indirect Hot Water Cylinders

PANDORA HEAT BANKS OXFORD BROOKES, HARCOURT HILL. Operation and Maintenance. THERMAL INTEGRATION LTD. Tel: Internet:

STAINLESSLITE PLUS INSTRUCTION MANUAL DESIGN, INSTALLATION & SERVICING ONE NAME. EVERY SOLUTION. UNVENTED MAINS PRESSURE HOT WATER STORAGE

Design, Installation & Servicing Instructions

Electromax Combined Electric Flow Boiler and Direct Unvented Hot Water Cylinder Installation and Servicing Instructions

Installation and Servicing Instructions. Alpha CD50

INSTALLATION & SERVICING

Flomaster. Unvented Hot Water Cylinders INSTALLATION INSTRUCTIONS FOR COPPERFORM FLOMASTER UNVENTED CYLINDERS: DIRECT, INDIRECT AND SOLAR MODELS.

StainlessLite Horizontal

UNIQ HEAT BATTERIES REFERENCE MANUAL_V2.2. Version: 2018_07_19_v2.2

PLEASE LEAVE THIS MANUAL WITH THE OSO UNIT AFTER INSTALLATION. For Super SXD, SX, SCI & SC

MAXIMISER Semi-Storage Calorifiers

Instructions for use Installation and Servicing. Solar Hot Water Cylinders/ Flurocyl

S T O R E R A N G E C Y L I N D E R & G R A N T FEATURES: GRANT MONOWAVE UNVENTED DIRECT AND INDIRECT SINGLE-COIL CYLINDERS

THERMflow Thermal Store Cylinders

UK-specific appendix to Installation instructions DHP-A DHP-A Opti DHP-AQ Maxi DHP-H DHP-H Opti DHP-H Opti Pro DHP-L DHP-L Opti DHP-L Opti Pro

STAINLESSLITE PRO, PRE-PLUMBED SYSTEM PLUS AND SYSTEM READY

Installation and Commissioning Manual

Transcription:

I N S P I R E D E F F I C I E N C Y Extreme Domestic Hot Water Loading System TECHNICAL DOCUMENTATION Issue 11/09

Technical data Description Extreme 200 Extreme 300 Extreme 500 Weight (empty) kg 63 77 98 Max Working pressure bar 10 10 10 Max Temperature C 90 90 90 DHW Flow Connection 1 1¼ 1½ DHW Return Connection 1 1 1 Primary Flow & Return Connections mm 28 28 28 MCWS Connection 1 1¼ 1½ Dimensional data G DHW Flow DHW Return H t g F l o w H t g R e t u r n D E F H A MCWS B C Dimensions Extreme 200 Extreme 300 Extreme 500 A 380 mm 910 mm 910 mm B 280 mm 810 mm 810 mm C 465 mm 465 mm 570 mm D 735 mm 1260 mm 1265 mm E 995 mm 1530 mm 1510 mm F 1305 mm 1830 mm 1810 mm G 710 mm 710 mm 735 mm H 300 mm 300 mm 300 mm Vented diagram shown above, for unvented installation please see G3 unvented installation section.

Flow Characteristics 120 110 10 min peak output @60 C 100 Heat Input (kw) 90 80 70 60 Rapide Extreme 200 Rapide Extreme 300 Rapide Extreme 500 50 40 30 200 300 400 500 600 700 800 900 1000 DHWS Flow (litres) 120 110 1st Hour continuous operation @60 C 100 Heat Input (kw) 90 80 70 60 50 Rapide Extreme 200 Rapide Extreme 300 Rapide Extreme 500 40 30 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500 2600 DHWS Flow Rate (l/hr)

Flow Characteristics cont d. 120 110 Continuous operation @60 C Rapide Extreme 200,300 &500 100 (kw) Input Heat 90 80 70 60 50 40 30 0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 DHWS Flow Rate (l/hr) Flow Rate l/s Resistance kpa 1.0 0.9 50 45 Primary Flow Characteristics 0.8 40 0.7 35 0.6 0.5 30 25 0.4 0.3 20 15 Flow Rate Resistance 0.2 10 0.1 0 5 0 30 40 50 60 70 80 90 100 110 120 Heat Input (kw)

Description. The Mikrofill Rapide Extreme is a Domestic Hot water generator that combines the advantages of both an instantaneous water heater and a storage system, whilst ensuring that the associated boiler plant operates at its optimum efficiency during Domestic Hot water generation,the Rapide Extreme is suitable for open vented or unvented applications. Based on a stainless steel storage vessel the unit utilises a stainless steel plate heat exchanger to load the vessel with water at 60 C, during hot water demand the plate heat exchanger effectively delivers hot water directly to the outlets, so heat up is reduced to minutes, and recovery time is a thing of the past. The Rapide extreme does not rely on convection within the vessel to transfer heat, the loading system introduces water at 60 C into the top of the vessel. This drastically reduces the proliferation of Legionella bacilli,and in instances where the associated boiler is of the condensing type the boiler will remain in its condensing mode throughout Domestic Hot Water generation, a situation that is unattainable using conventional coil type hot water cylinders, The Rapide Extreme is supplied fully assembled, prewired and inclusive of charging pump and electronic controller, advanced insulation ensures that the standing losses are reduced to a minimum The anode free stainless steel vessel carries a 30 year guarantee, whilst maintenance is minimal. The Rapide Extreme is suitable for open vented or unvented applications. See our animation on Mikrofill.com Advantages Domestic Hot Water available at all times Very high flow rates available, Generates full cylinder of water at 60 c Reduces Legionella risks Optimises boiler operation. Simple installation. Low maintenance Low standing losses 30 year guarantee Short payback period

Operation. The Rapide Extreme utilises a conventional simple storage cylinder, with a cold water feed connection at its lowest point and a hot water draw off connection at its highest point, in addition there is a plate heat exchanger draw off connection situated diametrically opposite to the cold water feed connection, both connections extend within the cylinder, thus reducing the gap between them within cylinder, see diagram. Similarly at the top of the unit there is a plate heat exchanger flow connection diametrically opposite the hot water draw off connection, again the connections are extended within the cylinder, a secondary hot water return connection is situated around midway up the cylinder. The plate heat exchanger draw off is connected to the secondary side of the plate via a bronze charging pump, with the secondary flow side of the plate being connected to the connection at the top of the cylinder. The primary connections of the plate are extended outside of the casing and made available for connection to a Mikrofill Ethos condensing boiler or other suitably sized boilers.

Installation IMPORTANT : PLEASE READ AND UNDERSTAND THESE INSTRUCTIONS BEFORE INSTALLING THE RAPIDE EXTREME HOT WATER LOADING SYSTEM. INCORRECT INSTALLATION MAY INVALIDATE THE GUARANTEE THE RAPIDE EXTREME MUST BE INSTALLED BY A COMPETENT INSTALLER IN ACCORDANCE WITH BUILDING REGULATION G3 (ENGLAND AND WALES), TECHNICAL STANDARD P3 (SCOTLAND) OR BUILDING REGULATION P5 (NORTHERN IRELAND). SITING THE RAPIDE EXTREME The Rapide Extreme must be vertically floor mounted. It can be placed anywhere convenient provided the discharge pipe(s) from its safety valves can be correctly installed. Areas that are subject to freezing must be avoided. Ensure that the floor is of sufficient strength to support the full weight of the unit. Pipe runs should be kept as short as possible for maximum economy. Access to associated controls, immersion heaters should be possible for servicing and maintenance of the system. APPLICATION The Mikrofill Rapide Extreme is suitable for both open vented ( storage tank fed ) or unvented applications Open vented applications This is the conventional application utilising feed from a storage tank and where the system is open to atmosphere via a vent pipe ( usually discharging back into the storage tank ). Available pressure is subject to the static head i.e. the height of the storage tank above the Rapide Extreme. In open vented applications it is recommended that the cold water feed pipework and DHW flow pipe are sized accirding to the Rapide Extreme tapping size to ensure maximum possible flow rates. WHEN INSTALLING THE RAPIDE EXTREME ONTO A OPEN VENTED SYSTEM WE STRONGLY RECOMMEND THAT A STRAINER/FILTER ARE INSTALLED ON THE DHW RETURN PIPEWORK AND COLD WATER FEED PIPEWORK, FAILURE TO DO SO MAY INVALIDATE THE GUARANTEE.

UNVENTED APPLICATIONS The Rapide Extreme can be fed directly from the mains supply to the property without the need for seperate feed cisterns or vent pipes. It is supplied complete with all its necessary inlet and safety controls, thermal cut out and two port motorised valve. Schematic installation details for unvented applications Thermal cut out T&P RELIEF VALVE T O HOT OUTLETS PRESSURE REGULATING VALVE c/w NON RETURN VALVE MAINS WATER SUPPLY PRIMARY FLOW & RETURN EXPANSION VALVE SECONDARY RETURN TAPPING TUNDISH EXPANSION VESSEL 2 port motorised valve to be installed onto primary connections - Included with Mikrofill Rapide Unvented kit DRAIN COCK (NOT SUPPLIED) DISCHARGE PIPE Examples of acceptable discharge arrangements are; i. Ideally below a fixed grating and above the water seal in a trapped gully. ii. Downward discharges at low level; i.e. up to 100mm above external surfaces such as car parks, hard standings, grassed areas etc. are acceptable providing that where children may play or otherwise come into contact with discharges a wire cage or similar guard is positioned to prevent contact, whilst maintaining visibility. iii. Discharges at high level; e.g. into a metal hopper and metal downpipe with the end of the discharge pipe is clearly visible (tundish visible or not) or onto a roof capable of withstanding high temperature discharges of water and 3m from any plastic guttering systems that would collect such discharges (tundish visible). iv. Where a single pipe serves a number of discharges, such as in blocks of flats, the number served should be limited to not more than 6 systems so that any installation discharging can be traced reasonably easily. The single common discharge pipe should be at least one pipe size larger than the largest individual discharge pipe (D2) to be connected. If unvented hot water storage systems are installed where discharges from safety devices may not be apparent i.e. indwellings occupied by blind, infirm or disabled people, consideration should be given to the installation of an electronically operated device to warn when discharge takes place. Note: The discharge will consist of scalding water and steam. Asphalt, roofing felt and non metallic rainwater goods may be damaged by such discharges.

Worked example of discharge pipe sizing The example below is for a G1/2 temperature relief valve with a disc harge pipe(d2) having 4 No. elbows andlength of 7m from the tundish to the point of discharge. From T able1: Maximum resistance allowedfor a straight length of 22mm copper discharge pipe(d2) from a G1/2 temperature relief valve is 9.0m. Subtract the resistance for 4 No. 22mm elbows at 0.8m each= 3.2 m Therefore thepermitted lengthequatesto: 5.8 m 5.8m is less thanthe actuallength of 7m therefore calculate the next largest size. Maximum resistance allowed for a straight length of 28mm pipe(d2) from a G1/2 temperature relief valve equates to 18m. Subtract the resistance of 4 No. 28mm elbows at 1.0m each= 4.0 m Therefore the maximum permitted length equatesto: 14m As the actuallength is 7m, a 28mm (D2) copper pipewill be satisfactory. Sizing of copper discharge pipe (D2) for common T& P relief valve sizes Valve outlet size Minimumsizeof discharge pipe D1 G1/2 15mm G3/4 22mm G1 28mm Minimumsizeof discharge pipe D2 fromtundish 22mm 28mm 35mm 28mm 35mm 42mm 35mm 42mm 54mm Maximum resistance allowed, expressedas a length of straight pipe(i.e. no elbows or bends) up to 9m up to 18m up to 27m up to 9m up to 18m up to 27m up to 9m up to 18m up to 27m Resistance createdby each elbow or bend 0.8m 1.0m 1.4m 1.0m 1.4m 1.7m 1.4m 1.7m 2.3m Schematic discharge pipe arrangement Safety device (e.g. Temperature relief valve) Metal discharge pipe (D1) from Temperature relief valve to tundis h 500mm maximum Tundish 300mm minimum Discharge below fixed grating (Building Regulation G3 s ection 3.9d gives alternative points of discharge) Dischargepipe (D2) fromtundish, with continuous fall. SeeBuilding Regulation G3 section 3.9di-iv, Table4 andworkedexample F ixed grating T rapped gully

6 Bar pressure Relief Valve 3.5Bar Pressure Reducing Valve Brass Manifold c/w Non return valve Outlet to Rapide Extreme Mains Cold Water Supply Expansion Vessel Connection Balanced cold water connection Unvented Kit

Multiple Extreme Installation DHW Flow DHW Return Expansion Vessel Unvented Mains Water Kit Rapide Extremes installed in parallel to ensure equal flow through both units

Extreme Wiring Diagram L M 1 3 sensors G H I J K 1 2 3 4 5 6 2 3 4 5 6 7 N L 8 9 1 0 1 1 A B C D E F Connection Description A External Anti Legionella Circuit B N/A C N/A D Electrical Supply 230V E Primary Pump Supply 230V 1 Amp F N/A G TT4 Primary heating supply temperature sensor H TT3 Secondary loading temperature sensor I TT2 J TT1Start Temperature sensor K Loading pump L Boiler Enable Circuit ( between 1 & 2) M Fault Relay ( made on fault between 4&5) Electrical supply 230 vac single phase 50Hz max 100W (excluding HWS primary pump) TT 4 TT 3 TT 2 Pl TT 1 DHW Flow DHW Return Cold Water Supply

Fault Diagnosis It is possible to interogate the Rapide Extreme controller to find sensor readings and fault fault history to do this you must press and hold the button on the contoller for 5 seconds this will then put the controls into diagnosis mode, by pressing the button again you can scroll through the menu of sensor readings, after the sensor readings on the menu previous faults will be displayed. see below for explanation of readings. Diagnosis Nr. Possible Displays Software (product) Version Operation Status T1: Flow sensor temperature T2: Stop sensor temperature T3: Load sensor temperature T4: Primary Htg sensor temperature Loading pump operation Boiler output Fault codes S0 D0 D1 D2 D3 D4 D5 D6 E(1-7) 0-99 OF,nr,nL,hr or hl 0-99( C) or -- if there is a sensor fault 0-99( C) or -- if there is a sensor fault 0-99( C) or -- if there is a sensor fault 0-99( C) or -- if there is a sensor fault Only shown if opentherm boiler connected Fault Fault Code Effect Priority TT1 Flow Sensor Fault 01 Loading pump runs with normal speed control. The sensor function is overridden by sensor TT3 3 TT2 Stop Sensor Fault 02 The sensor function is overridden by sensor TT3 4 TT3 Loading Sensor Fault 03 The loading process continues with the loading pump running at 100%. Output to all pumps active with 3min overrun when loading complete 5 TT4 Primary HTG Sensor Fault 04 The loading process is operational. The loading pump will not operate at the minmum primary temperature but will start after a preset time period. 6 Frost Protection Active 05 The loading pump is controlled at a set speed. Primary pump and boiler outputs are activated. 2 Anti legionella programme active for more than 2 hours 06 The programme returns to the normal operation and the fault code is displayed. If terminals 2&3 are closed the fault will not reset. 7 Normal operation programme active for more than 2 hours 07 The fault relay will be activated and the loading process will continue to operate. 1

Maintenance Due to the high quality material used in the manufacture of this product and the simple construction the Rapide Extreme needs no maintenance and enables an exceptionally long guarantee period. Included in the unit is a service valve on the loading pipe from the base of the cylinder to the plate heat exchanger, this may only be usd when the unit is no longer active. DO NOT CLOSE THE SERVICE VALVE WHILST THE UNIT IS RUNNING. Inspection and cleaning inside the cylinder, It is possible to clean out the cylinder using fresh mains cold water if so desired. To carry out this operation isolate and disconnect all water supplies and ensure all electrical supplies are isolated. Run a drain hose from the drain valve to an operating drain, then connect a controlled mains water supply to the unit, drain the unit fully and then slowly supply water to the unit at the rate of drainage. carry on at this rate until the water running out of the bottom of the cylinder runs clear, then carry out two full fills and drains. Reconnect and re-commission.