NFPA CODE TESTING & INSPECTION. Requirements & Recommendations for. Licensed Florida Hospitals, Ambulatory Surgery Centers,

Similar documents
Service Requirements SEMI- ANNUAL ANNUALLY OTHER REF. REQUIREMENT

Winnipeg Fire Department Fire Prevention Branch

Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment

Skilled Healthcare Documentation Requirements Life Safety and Fire Protection

Life Safety Code NFPA 10 NFPA 13 NFPA 25 NFPA 72 NFPA 90A NFPA 110 NFPA 99 THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #7

CMS Announcement 3/27/2017. Adoption of 2012 Life Safety Code Health Care Facilities Code. Kenneth Daily, LNHA

1. Are there any annual sprinkler head inspection forms available? No, there are none available at this time.

Other EC and LS documents may be requested by surveyors, as needed, throughout the survey.

FACILITY MANAGEMENT DEFICIENCIES IN CRITICAL ACCESS HOSPITALS (CAH)

FACILITY MANAGEMENT DEFICIENCIES IN ACUTE CARE SETTINGS

2-SUPPRESSION REQUIREMENTS - CODE REQUIRED INSPECTIONS TEST Page 1 of 7

WHEA FSE inspections.

Global Property. SEMIANNUAL FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location:

Fire Sprinkler Plan Submittal Form

Checklist For Life Safety

ADDENDUM #1 ITB# Fire Protection Maintenance Services Responses to Clarification Questions 10/06/2015

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY

Global Property. QUARTERLY FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location:

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST

Ohio Department of Health NFPA 2012 Life Safety Code Tips Sheet

False Sense of Security???

2012 Life Safety and Health Care Facility Codes - Door Inspections and Other Critical Inspection, Testing and Maintenance

EC 5.10 FIRE PREVENTION MANAGEMENT

Danilo B. Concepcion, CBNT, CCHT-A Operations Manager St. Joseph Hospital Renal Services

THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #5

First Aspen Federal Regulation Set: K LSC 2000 Health Existing

New Construction Fire Inspection Process

Purpose: To establish procedures for identifying fire hazards and preventing fires. Scope: All Central New Mexico Community College (CNM) Community.

PRINTED: 06/09/2017 FORM APPROVED CENTERS FOR MEDICARE & MEDICAID SERVICES OMB NO (X2) MULTIPLE CONSTRUCTION A. BUILDING 03 - A BUILDING

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Plan Review

Revised March 2015 Fire Alarm Systems Verification. Schedule I(A) Services. *Manditory Site visit required*

Iowa State Fire Marshal

MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS

The Impact the Reference Standards in the 2012 Edition of NFPA 101 have on the Operation of Health Care Facilities: NFPA 80 and 99

Osceola County Department of Fire Rescue and Emergency Medical Services

Compliance w/ the 2012 Life Safety Code

New DATE OF BLDG. PERMIT OR PLAN APPROVAL: SURVEYOR (SIGNATURE) TITLE OFFICE DATE REVIEW AUTHORITY OFFICIAL (SIGNATURE) TITLE OFFICE DATE

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY

10/28/2015. Enjoy Your TJC Survey. Bill H. McCully CHFM SASHE. Senior Consultant MSL Healthcare Partners. MSL Healthcare Partners, 2015 PREPARATION

GENERAL AREAS OF INSPECTION

Agency for Health Care Administration

Table of Contents CHAPTER 10 ADMINISTRATIVE RULES FOR CERTIFICATION OF CHILD CARE FACILITIES FIRE STANDARDS FOR FAMILY CHILD CARE HOME

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures

Agency for Health Care Administration

Agency for Health Care Administration

Agency for Health Care Administration

Checklist For Building Inspection & Fire Safety

System Test Report CLEAN AGENT

Fire Safety Requirements for Peer Review

LIFE SAFETY CODE MAINTENANCE MANUAL

Agency for Health Care Administration

School Fire Safety Checklist

EC EP 14 All other electrical K-920 equipment in patient care vicinity NFPA , Chapter 10

FIRE SAFETY SYSTEMS MAINTENANCE INFORMATION

Fire Suppression Introduction Contact Information

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry

Agency for Health Care Administration

Changes to Environment of Care, Equipment Management, and Life Safety Chapters Related to Life Safety Code Updates

Functional Performance Test

Agency for Health Care Administration

Prepublication New Text Jan 2018 Changes to Environment of Care and Life Safety Chapters

5.07 Air Replenishment Systems

a) Establishment of emergency procedures to be followed at the time of an emergency;

Agency for Health Care Administration

Fire Safety Plan (Single-Stage Fire Alarm System) (Small Establishment):

FIRE SAFETY SURVEY REPORT AMBULATORY SURGICAL CENTERS (ASC) & END STAGE RENAL DISEASE (ESRD) MEDICARE

Agency for Health Care Administration

HEALTHCARE SAFETY INSPECTION

Crosswalk of 2014 HFAP Standards against HFAP Standards Acute Care Hospital Manual

DEALING WITH FIRE SAFETY

Module 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements

FIRE INSPECTION CHECKLIST

S a n F r a n c i s c o F i r e D e p a r t m e n t B u r e a u o f F i r e P r e v e n t i o n & I n v e s t i g a t i o n 1 of 8 P a g e

MAINTENANCE OF FIRE PROTECTION DEVICES WITHIN RESIDENTIAL SUITES OF MULTI-FAMILY BUILDINGS

Owner/Operator Guide for Successful Sprinkler and Fire Pump Systems

Florida Building Code 2010

Are there any policies regarding outlets that contain USB ports?

Agency for Health Care Administration. Eddie Alday Life Safety Code Lead 30 th AHCA Seminar 23 September 2014

INSPECTOR I SKILLS ADMINISTRATION

Candy Easterling K-063. Adequate and Reliable Water Supply for the Sprinkler System. CITY WATER or WATER TANK for Sprinkler System

NFPA 101 Code Update from 2012 Edition to the 2015 Edition

FIRE INSPECTION GUIDELINES FOR FOSTER GROUP HOME PARENTS Effective June 1, 2002, Update September 2011

MAINTENANCE AND INPSECTION OF FIRE PROTECTION SYSTEMS AND APPLIANCES

Camden County Fire Rescue Office of the Fire Marshal 125 N. Gross Road, Kingsland, GA

Safety Tips for the Office

GUILFORD COUNTY SCHOOLS

FIRE SAFETY UPGRADING CONSIDERATIONS for EXISTING SENIOR CITIZEN LODGES

Residential-based Care Facility R-4 Guideline

ALABAMA. Downloaded

Established /10/2015. Doran Pruisner Dan Wood

FIRE DEPARTMENT DESCRIPTION OF SERVICE UNIT FEE I. INSPECTION FEE

Life Safety Code Common Discepancies Course# LSC102. EZpdh.com All Rights Reserved

Revision May All designs must be submitted to FM Global for review and approval prior to issuing such for bids.

I. Scope: II. Environmental Health and Safety Fire Alarm System Impairment Program - Guideline Revision Date: April, 2018

B. The Facility Emergency Planners and Alternate Planners will successfully complete the in-house DJJ Fire Prevention course.

Quick Guide for Fire Sprinkler Inspection Requirements Key Deficiencies with NFPA References NFPA & NFPA 13/

Fire & Life Safety Code Compliance. Common Safety Deficiencies and Tips for Compliance for Long Term Care and Skilled Nursing Facilities

TIPS FOR BETTER JOINT COMMISSION SURVEYS

Tennessee Department of Health Bureau of Health Licensure and Regulations Division of Health Care Facilities

Bold items are particular to the City of Euless

Transcription:

NFPA CODE TESTING & INSPECTION Requirements & Recommendations for Licensed Florida Hospitals, Ambulatory Surgery Centers, ICF/IID Healthcare, & In-patient Hospice Facilities per NFPA Life Safety Code 101 (2012) Edition Required Tests & Inspections Frequency NFPA Reference I. Fire Alarm System: A. System operational test & 72 (2010) 14.4.5 central station notification B. All manual pull stations 72 (2010) 14.4.5 C. All indicating smoke detectors 72 (2010) 14.4.5 operational test D. All smoke detectors Within 1 year of install & then 72 (2010) 14.4.5.3 sensitivity test every other year thereafter E. Restorable Heat Detectors 20% or 100% in 5 years 72 (2010) 14.4.5.5 72 (2010) 14.4.5.5.4 F. Non-restorable Heat Detectors After 15 years test 2 for every 100 or replace all 72 (2010) 14.4.2.2, Table 14.4.2.2(14)(2-3) G. Remote Annunciators 72 (2010) 14.4.5, Table 14.4.5(14) H. Fire Panel inspection, 72 (2010) 14.4.5, Table 14.4.5(1) certification & tag I. Alarm Supervisory & Trouble 72 (2010) 14.4.5, Table 14.4.5(9) Signals II. Ventilating System Dampers & Detectors A. Fire Damper maintenance remove thermal links, operate damper to verify closure & lubricate 1 year after install Every 4 years Hospitals-every 6 years 80 (2010) 19.4.1 B. Fire/Smoke & Ceiling Dampers 1 year after install Every 4 years Hospitals-every 6 years 105 (2010) 6.5.2 III. Automatic Fire Sprinkler Systems A. Mechanical water-flow switches (fire alarm in 90 seconds per NFPA 72 (2010) 17.12.2) B. Vane-type/Pressure switchtype water-flow switches (fire alarm in 90 seconds per NFPA 72 (2010) 17.12.2) Quarterly 25 (2011) 13.2.6.1 Semi-annually 25 (2011) 13.2.6.2 Updated 9/12/2014 Page 1

C. Sprinkler system inspection 25 (2011) 5.2.1 (not test) D. Fire Pump flow capacity test Weekly 25 (2011) 8.3.1 run (no flow) E. Fire Pump flow capacity test 25 (2011) 8.3.3 (flow) F. Calibrate pressure gauges Every 5 years or replace 25 (2011) 5.3.2 G. Solder-type extra high Every 5 years 25 (2011) 5.3.1.1.1.4 (325*F) or greater-sample testing H. System Obstruction & Every 5 years 25 (2011) 14.2.2 Investigation (not required for non-metal pipe) I. Post Indicator & Control Monthly 25 (2011) 13.3.2.1.1 Valves-inspection J. Post Indicator & Control Valves-testing -position & operation Semi-annually-supervisory 25 (2011) 13.3.3.1 25 (2011) 13.3.3.5 K. Water storage tanks, temp & water level switch alarmsupervised Monthly-temp Quarterly-level alarm 25 (2011) 9.2.4.2 25 (2011) 9.2.1.1 L. Water storage tanks, temp & water level switch alarm- not supervised Weekly-temp Monthly-level alarm 25 (2011) 9.2.4.3 25 (2011) 9.2.1.2 M. Dry Pipe - valve trip test 25 (2011) 13.4.4.2.2 N. Dry Pipe - Full valve trip test Every 3 years 25 (2011) 13.4.4.2.2.2 O. Dry Pipe - Quick Opening Quarterly 25 (2011) 13.4.4.2.4 devices P. Fire Hose (occupant use) inspect & re-rack 25 (2011) 6.2.1, Table 6.2.1 1962 (2008) 4.3.4 Q. Fire Hose (occupant use) pressure testing 5 years from date of manufacture/ every 3 years 25 (2011) 6.2.1, Table 6.2.1 1962 (2008) 4.3.2 R. Fire Hydrant (private) functional test S. Fire Hydrant (private) piping flow test T. Sprinklers fast response At 20 years from manufacture/every 10 years thereafter till 75 year U. Sprinklers testing 50 year At 50 years from manufacture/every 10 years thereafter till 75 year V. Sprinklers testing 75 year At 75 years from manufacture/every 5 years thereafter W. Sprinklers-Dry (including Walk-ins) thereafter 25 (2011) 7.3.2 Every 5 years 25 (2011) 7.3.1 At 10 years from manufacture/every ten years 25 (2011) 5.3.1.1.1.3 25 (2011) 5.3.1.1.1, 5.3.1.1.1.1 25 (2011) 5.3.1.1.1.5 25 (2011) 5.3.1.1.1.6 X. Sprinklers Prior to 1920 Shall be replaced 25 (2011) 5.3.1.1.1.2 Y. Sprinklers in corrosive or Every 5 years 25 (2011) 5.3.1.1.2 harsh environments Updated 9/12/2014 Page 2

Z. Backflow Preventers Inspection & Testing IV. Other Fire Suppression Systems & Equipment: (does not include all types-just most common) A. Portable Fire Extinguishers in-house inspection B. Portable Fire Extinguishers (tagging) maintenance C. Portable Fire Extinguishers refill D. Portable Fire Extinguishers hydrostatic testing E. Portable Fire Extinguishers (Halon) inspect, test, disposal F. Kitchen Hood Extinguishing Systems tag & service G. Kitchen Hood Extinguishing Systems replace fusible links H. Kitchen Hood Extinguishing Systems In-house Quick Check Wet Chemical System I. Water Spray Systems flow test & flush J. Clean Agent Systems tag & service K. Clean Agent Systems quantity & pressure L. Clean Agent Systems Hose inspect & test M. Clean Agent Systems Room Enclosure Protection V. Essential Electrical Systems: A. Emergency Power Supply System inspection B. Emergency Power Supply System run under load C. Emergency Power Supply System Automatic Transfer Switches - manually test Monthly Inspection - Testing 25 (2011) 13.6.1.1.1, 13.6.1.2.1 25 (2011) 13.6.2.1 Monthly 10 (2010) 7.2.1.2 10 (2010) 7.3.1.1.1 Every 6 years 10 (2010) 7.3.1.2 Every 5 years-stored pressure water, wetting agent, AFFF, FFFP, Dry Chem w/stainless steel, CO, & Wet Chem. Every 12 years-dry Chem, Halogenated Agents, & Dry Powder Monthly-inspect 6 year-disposal by manufacturer or approved vendor -AFSS protected Wet Chemical-Semi-annually 10 (2010) 8.3.1, T 8.3.1 10 (2010) 7.2.1.2 10 (2010) 2.2.3.3, 7.3.1.2.1.2, 7.3.1.2.1.3, 7.3.1.2.1.4 96 (2011) 10.2.6(1-4) AFSS 13 (2010) 7.10.12.1 17A (2009) 7.3.3 Semi-annually 96 (2011) 10.2.6(4) 17A (2009) 7.3.4 Monthly 96 (2011) 10.2.6(4) 17A (2009) 7.2.2(1-8), 7.2.5 96 (2011) 10.2.6(2) 15 (2012) 11.1.1 25 (2011) 10.3 2001 (2012) 7.1.1 Semi-annually 2001 (2012) 7.1.3 -inspect 2001 (2012) 7.3.1 5 years-test 2001 (2012) 7.3.2.1 2001 (2012) 7.4 Weekly 110 (2010) 8.4.1 Diesel-Monthly 110 (2010)8.4.1, 8.4.2(1-2) Spark-ignited-Monthly 110 (2010) 8.4.1, 8.4.2.4 Monthly 110 (2010) 8.4.6, 8.4.6.1 Updated 9/12/2014 Page 3

D. Emergency Power Supply System Load Bank Testing (if unable to meet 30% or greater monthly) E. Emergency Power Supply System Batteries inspect & test electrolyte levels & voltage F. Main & Feeder circuit breakers inspect & exercise G. Emergency Power Supply System Breakers in excess Of 600 volts exercise & overload test H. Emergency Power Supply System Level 1 (4 hour load test) 110 (2010) 8.4.2.3 Weekly-inspect Monthly-testing -inspect Per Manufacturer Exercise Every 6 months exercise Every 2 years overload test 110 (2012) 8.3.7 110 (2010) 8.3.7.1 110 (2010) 8.4.7 110 (2010) 8.4.7.1 Every 36 months 110 (2010) 8.4.9 I. Diesel Fuel Testing 110 (2010) 8.3.8 VI. Electrical Testing: A. Receptacles at patient bed, deep sedation, or general anesthesia locations - testing Hospital Grade-Install, replacement, service, & performance based data 99 (2012) 6.3.4.1.1, 6.3.4.1.2 B. Receptacles in patient care rooms - testing Non-hospital Grade- 99 (2012) 6.3.4.1.3 99 (2012) 6.3.3.2 C. Receptacles in wet locations or based on 99 (2012) 6.3.4.1 performance data D. Ground fault circuit 99 (2012) 6.3.4.1.3 interrupters -test E. Patient care- related electrical As established by policies & 99 (2012) 10.5.2.1.1 equipment testing policy protocols F. Patient care-related electrical equipment testing First time in-service After repair 99 (2012) 10.5.2.1.2 G. Wet Procedure Locations fixed receptacles, equipment connected by cord and plug, & fixed electrical equipment electrical continuity testing H. Line Isolation Monitors test circuit I. Test Instrument continuity testing J. Emergency Lighting 30 seconds K. Emergency Lighting 90 minutes Any modification Install Evidence of damage After repairs Intervals not exceeding 6 months 99 (2012) 6.3.2.2.8.5(A-B) Monthly 99 (2012) 6.3.4.1.4 -automated self-test & self-calibration 99 (2012) 6.3.3.1.5 Monthly 101 (2012) 7.9.3.1.1(1) 101 (2012) 7.9.3.1.1(3) Updated 9/12/2014 Page 4

L. Battery Back-up Exit Signage Monthly-30 seconds -90 minutes 101 (2012) 7.10.4 101 (2012) 7.9.3.1.1(1) 101 (2012) 7.9.3.1.1(3) VII. Medical Gas Systems A. Category 1 Medical Gas B. Category 2 Medical Gas C. Category 3 Medical Gas 99 (2012) 5.1.14.2.2 99 (2012) 5.1.15 99 (2012) 5.2.14 99 (2012) 5.2.15 99 (2012) 5.3.13.4 VIII. Other A. Fire Drills 1 per quarter per shift 101 (2012) 4.7, 18.7.2, 19.7.2, 20.7.2, 21.7.2 B. Disaster Drills-Internal & External C. Fire Plan Approval by local Fire Department and/or Emergency Management 1 each per year/6 months apart Hospital-59A-3.078(4) ASC-59A-5.018(4) Nursing Home-59A-4.126 Reviewed and updated as required by the authority s having jurisdiction. 101 (2012) 4.8.2.3 D. Disaster Plan Approval by County Emergency Management E. Laboratory Drills Fire & Spills F. Fire & Smoke Doors inspection & testing G. Boilers-Power Boilers, High Pressure, High Temperature Hospital-59A-3.078(3) ASC-59A-5.018(3) Nursing Home-59A-4.126 Quarterly 45 (2011) 6.6.3.1, 6.6.3.2 Fire-80 (2010) 5.2.1 Smoke-105 (2010) 5.2.1.1 -internally & externally F.A.C. 69A-51.050(2)(a) not under pressure 6 months after Annual under pressure inspect externally H. Boilers-Heat Boilers Every 2 years F.A.C. 69A-51.050(2)(b) I. Boilers-Hot Water Boiler & Every 2 years F.A.C. 69A-51.050(2)(c) Hot Water Supply Boiler Internal-every 4 years Updated 9/12/2014 Page 5