Ventilation for Healthcare Facilities

Similar documents
Ventilation for Healthcare Facilities. Topics to be Covered

Technical Report 1. ASHRAE Standards 62.1, 170, and 90.1 Evaluation. Morton Hospital Expansion

Cleveland Clinic Design Standards MECHANICAL SYSTEMS DESIGN GUIDELINES HVAC AIR DISTRIBUTION PART I - GENERAL 1.1 SUMMARY

Prescriptions for Critical Healthcare Cx. John D. Villani, P.E. Associate Grumman/Butkus Associates

PHARMACY DESIGN GUIDANCE UPDATE ON COMPLIANCE WITH USP CHAPTER 797 PHARMACEUTICAL COMPOUNDING - STERILE PREPARATIONS

Pharmaceutical Facility Design

THE IMPACT OF FACILITY HVAC SYSTEMS ON BIOLOGICAL SAFETY CABINETS

Selected Laboratory Energy Efficiency Measures

Pharmacy Solution Set

Adv. 8.4 Guidelines for Biosafety Cabinets Rev

ประธานกรรมการว ชาการฯสมาคมปร บอากาศแห งประเทศไทย

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1

AIRSIDE COMPONENTS AND SYSTEMS

AIR-CONDITIONING SYSTEMS AND APPLICATIONS. Abdullah Nuhait Ph D. King Saud University

Senior Thesis Centre Community Hospital East Wing Addition - Proposal Keith Beidel Mechanical Option 12/05/02 1

THIS IS A DESIGN GUIDE NOT A SPECIFICATION. Montgomery County Public Schools Facilities Guide DIVISION 15 MECHANICAL

CONSIDERATIONS ON FACILITY AND ENGINEERING CONTROLS IN THE WAKE OF USP <800>

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems

4. OVERVIEW OF MECHANICAL SYSTEM

HVAC Controls Upgrades: Requirement Details ( )

PHYSICAL FACILITIES Consultant s Handbook Division 01 General Special Requirements for Laboratories. Page 1 of 6

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

Guidelines for Ideal Layout for an Operating Theater Complex. Dr.R.D.Ravindran Aravind Eye Hospital Madurai

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

PDH & Professional Training

DHS Design guidelines for hospitals and day procedure centres. Part E- Building Services and Environmental Design

INTRODUCTION TO: ASHRAE STANDARD 90.1, HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings

DACC Health Sciences Building Air Handler Assessment/Study

Energy-Efficient Makeup Air Units BY HUGH CROWTHER, P.ENG., MEMBER ASHRAE

Christopher Kelly Technical Report Three

State of the art building simulation software... Frenger Radiant chilled beam performance at 1 Shelly St - Sydney

Balancing Energy & Performance in Healthcare. Dan Koenigshofer, PE, MSPH, HFDP, SASHE Dewberry Engineers Inc. Raleigh, NC - November 12, 2014

BEST PRACTICE RECOMMENDATIONS

EarthWise System Seminar

Case Study: Furman University Charles H. Townes Center for Science. Michael K. Mantai, PE, CCP President System WorCx

Safe Operating Procedure (Revised 2/10)

7. MECHANICAL SYSTEM DESIGN

EADQUARTERS. Technical Report One. Stephanie Kunkel Mechanical Option

HVAC Controls Upgrades: Requirement Details ( )

System Components with ` Emphasis on Packaged Rooftop Application and Installation. Jerry Cohen President Jacco & Assoc.

The Role of Air Handling Units in Combating the Spread of Infectious Disease

Air-Conditioning for the Environment of Care

Theatre Classification and Air Particle Count Is that Surveillance?

How to comply with CDC Guidelines

CHAPTER 4. HVAC DELIVERY SYSTEMS

CALIFORNIA MECHANICAL CODE OVERVIEW OF 2016 UPDATES CHANGES AND RAMIFICATIONS

Element D Services Heating, Ventilating, and Air Conditioning

Civil Engineering Building

Space Air Diffusion II

FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney

DIGI-VAV APPLICATIONS

ASHRAE Standard 62 Ventilation Report Technical Assignment #1. Calvert Memorial Hospital Prince Frederick, MD

APPLICATION GUIDE BEAMS

ENERGY EFFICIENCY WITH SUPERIOR INDOOR AIR QUALITY

Continuous Commissioning: A Valuable Partner to Retrofit Projects

HAP e-help. Modeling Induction Beams in HAP v4.8 QB TIP 001

FORM EG2 (502) FlexSys Configured Packaged Rooftop Air Conditioning Units

Technical Assignment 3 11/15/04. Executive Summary

FAARM-Underground Facility. Conceptual Design Review. Mechanical Systems. Dunham Associates, Inc.

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

Challenges and Methods of Estimating a Conceptual HVAC Design

BARRIER TECHNOLOGY RABS & ISOLATORS FOR ASEPTIC PROCESSING

ENGINEERING BULLETIN. Overview of Chilled Beam Technology. Purpose. Summary. Theory

2009 IECC Commercial Mechanical Requirements

Ventilation System Description. September 8, 2000 HETA

Dehumidifying with Dedicated Outdoor Air

Hospital ventilation & infection prevention

1080 Marina Village Parkway, Suite 501 Alameda, CA (510) Fax (510) HVAC DESIGN INTENT

Architectural Engineering Senior Thesis Mechanical System Redesign

BES-TECH TECHNOLOGY & SYSTEM INTEGRATION

Energy Recovery with Cooling and Heating Model ERCH

Biological Safety Cabinets or Fume Hoods Which one to use?

Technical Report Three

Energy Efficiency Baselines for CLEANROOMS. Non-Residential New Construction and Retrofit Incentive Programs. Version 2 October 1, 2008.

Biological Safety Cabinets. Biological Safety Cabinets

COMcheck Software Version Mechanical Compliance Certificate

UFAD and Displacement Ventilation. Dan Int-Hout, FASHRAE Chief Engineer Krueger Richardson, Texas

b.) Technical Information:

Trane Performance Climate Changer Air Handlers. An air handler for every need.

LABORATORY DESIGN HANDBOOK

Biosafety Cabinets and Fume Hoods Supplemental Material (OHS_BIO304)

Custom Air Handler Solutions Custom Units to Meet Your Unique Design Needs

Heat Pumps SA SERIES. Vertical Self-Contained Unit Water-Source Heat Pumps (23-70 tons) Features:

Florida International University. Biosafety Cabinet Program

SECTION HVAC TABLE OF CONTENTS PART 1 - SYSTEM DESCRIPTION / OUTLINE SPECIFICATIONS FILED SUB BID PROJECT OVERVIEW...

Heat Pumps M2 SERIES. Modular Self-Contained Unit Water-Source Heat Pumps (3-70 tons) Features:

Engineering Guide VAV Diffusers. Please refer to the Price Engineer s HVAC Handbook for more information on VAV Diffusers.

HVAC Mandatory Provisions Part II, Page 1

Mechanical Redesign, Proposal Elizabeth C. Krauss Mechanical Option September 18, 2013

Chilled Beam and Radiant Cooling Basics. Salt Lake City, UT ASHRAE Chapter December 2013 Nick Searle

WORKSHOP VENTILATION- PSYCHROMETRICS-AHU

Biological Safety Cabinets. Presented by Mr. Rene Soetens President

MID MICHIGAN COMMUNITY COLLEGE HARRISON CAMPUS Harrison, Michigan 2015 MASTER PLAN

Design Considerations For Dedicated OA Systems BY HUGH CROWTHER, P.ENG, MEMBER ASHRAE; YI TENG MA, ASSOCIATE MEMBER ASHRAE

PRESSURE RELATIONSHIPS IN HOSPITAL CRITICAL-CARE FACILITIES

Standards and Guidelines. Presented by: Aric Murray December 12, 2014

Research Document Type: PROCEDURE. Effective Date: January 01,2015 Author Steven Hayes

Animal Tissue Culture SQG 3242 Equipment and Lab design. Dr. SITI PAULIENA MOHD BOHARI

B. Use UT Austin specifications and equipment schedule format for HVAC equipment where available.

Strategies for Building Energy Efficiency

Transcription:

Ventilation for Healthcare Facilities Presented to Wisconsin Healthcare Engineering Association November 13, 2014 Need ideas to make this first page interesting; picture? Henneman logo? 1

Topics to be Covered Relevant codes and standards Air handling units Space ventilation requirements HVAC distribution systems Real world examples of spaces focusing on challenges, particularly pressure relationships and pressure control Patient rooms Operating rooms Airborne infectious isolation (AII) rooms Pharmacies 2

Relevant Codes and Standards Wisconsin Department of Health Service: AIA 2006 Healthcare Guidelines which references: ASHRAE 170B Ventilation of Healthcare Facilities Joint Commission on Accreditation of Healthcare Organizations (JCAHO) FGI Guidelines for Design and Construction of Hospitals and Outpatient Facilities 2010 which references: American Society of Heating, Refrigerating and Air- Conditioning Engineers (ASHRAE) Standard 170 Ventilation of Healthcare Facilities 2008 ASHRAE Standard 170 2013 is most recent version 3

ASHRAE Standard 170 AHUs - Outside Air Intakes 25 ft from cooling towers, exhausts, vents 6 ft above grade 3 ft above roof ASHRAE 170 for Areaways: Bottom of the air intake 6 above grade, intake at bottom of areaway 3 above bottom of areaway. 3-0 4

Filter Bank 1 shall be upstream of coils Filter Bank 2 shall be downstream of coils and supply fan. Bank 2 must be sealed and airtight ASHRAE Standard 170 AHUs - Filters 5

ASHRAE Standard 170 Minimum Filter Efficiencies Space Function Filter Bank 1 ASHRAE/AIA (MERV) Filter Bank 2 ASHRAE/AIA (MERV) Operating Rooms 7/7 14/14 Comments Inpatient Care 8/7 14/14 Includes patient rooms Protective Environment Rooms 7/8 HEPA/17 Laboratories 13/13 NR/NR Administrative 8/7 NR/NR Nursing Facilities 13/7 NR/13 Nursing homes Psychiatric Hospitals 7/8 NR/14 6

Types of MERV 14 Final Filters Bag filters Supported media filters Low pressure drop green filters Electronic filters 7

MERV 14 Final Filters Examples of Pressure Drops Filter Type Initial Pressure Drop* (inches w.g.) Final Pressure Drop* (inches w.g.) Comments Bag 0.60 1.0 24 x24 x30 Rigid Media 0.60 1.0 24 x24 x12 Low Pressure Drop Green 0.41 1.0 24 x24 x30 Electronic 0.25 0.75 SecureAire ACS *Based on 500 fpm face velocity 8

MERV 14 Standard versus Electronic Filter Loading (1) (1) Slide Courtesy of Temperature Equipment Corporation and SecureAire 9

Filter Type Summary There is no one right filter type New developments in filters low pressure drop filters and electronic filters warrant an economic analysis Replacing filters with lower pressure drop filters on an existing system can help you find some extra air. Healthcare facilities require more and higher levels of filtration than other type of buildings. 10

ASHRAE Standard 170 Humidifiers Steam humidifiers must be used; no reservoir type or evaporative pan, etc. Chemical additives for humidifier steam shall comply with FDA requirements. Direct boiler steam is acceptable with good chemical treatment. RO system on boiler make-up will reduce chemical usage If unable to use boiler steam need steam-to-steam clean steam humidifier. Location of humidifier? Before cooling coil reduces risk of wetting final filters Can do after cooling coil if careful with absorption distance. 11

Typical Hospital Air Handling Unit 12

Typical Hospital Air Handling Unit 13

Space Design Criteria Ventilation Requirements Function of Space Pressure (1) ACH AIA 2006 ASHRAE 170 ACH Comments Patient room NR (2) 6 4 or 6 6 for single-bed patient room service by aspirating diffusers Protective isolation Positive 12 12 Airborne infectious isolation (AII) Negative 12 12 All air exhausted to outside Operating room (OR) Positive 15 20 Caesarian delivery room Positive 20 Procedure (minor surgery) Positive 15 15 Emergency room waiting Negative 12 12 All air exhausted to outside Radiology room waiting Negative - 12 All air exhausted to outside 1. Pressure Relationship to Adjacent Areas 2. NR = No Requirement 14

Space Design Criteria Ventilation Requirements Function of Space Pressure (1) ACH AIA 2006 ASHRAE 170 ACH X-Ray (treatment/ diagnosis) NR 6 6 X-Ray (surgery/catheterization) Lab (general, cytology, histology, and other types) Labs (sterilization and glass washing) Bronchoscopy, sputum collection Positive - 15 Negative 6 6 Negative 10 10 Comments Negative 12 12 All air exhausted to the outside Pharmacy Positive 4 4 USP <797> governs, if applicable 1. Pressure Relationship to Adjacent Areas 15

Space Design Criteria Nursing Facility Ventilation Requirements Function of Space Pressure (1) 2006 AIA ACH ASHRAE 170 ACH Resident room NR 2 2 Resident gathering/dining NR 4 4 Physical therapy Negative 6 6 Occupational therapy Negative/NR (2) 6 6 Comments 1. Pressure Relationship to Adjacent Areas 2. NR = No Requirement 16

Space Design Criteria Humidity Levels Recently ASHRAE has lowered the winter humidity level requirements in some spaces, including ORs from 30% RH to 20% RH: Function of Space AIA 2006 % RH ASHRAE 170 % RH Patient room NR Max 60% Newborn nursery 30-60 30-60 Operating room (OR) 30-60 20-60 Procedure room 30-60 20-60 Critical and intensive care 30-60 30-60 17

Space Design Criteria Implementing 20% RH in ORs: CMS is allowing a waiver organization must declare waiver at the beginning of a CMS-conducted survey. Must check humidity requirements of equipment used in ORs. AAMI, the Association for the Advancement of Medical Instrumentation, has issued caution: Supplies and medical devices used in the ORs may be sensitive to lower humidity levels. Electrodes, for example, are sensitive to humidity, as are other devices with sensors. Legacy medical devices still are in use and have not been tested in the lower humidity range. Devices with temperature controls or electronics are particularly sensitive to humidity. 18

Patient Room HVAC Plan A common patient room HVAC layout VAV with reheat supply and radiant panel perimeter heat 19

Patient Rooms and Chilled Beams Active chilled beams are induction units in the ceiling. 20

Patient Rooms and Chilled Beams Active chilled beams can and have been used in patient rooms Question has been the need for filters at the chilled beams some jurisdictions required/others did not ASHRAE Standard 170 2012 has clarified: Provide a minimum MERV 6 filter for airflow passing over any surface that is designed to condense water. This filter shall be located upstream of any such cold surface, so that all of the air passing over the cold surfaces is filtered. 21

Patient Rooms and Chilled Beams One manufacturer with filters: 22

Patient Room HVAC Plan with Chilled Beam 23

Patient Rooms and Chilled Beams Advantages: Thermal comfort Can have low sound levels Need less ceiling height than all air VAV system Possible energy savings: moving only minimum ventilation air with AHU lower fan energy Dedicated OA unit with heat recovery Disadvantages: Must change filters in patient rooms/over bed Risk of condensation A 2 nd piping system to room, CHW Possible energy adds Limited airside economizer Possible increase in pumping energy Photo Courtesy of Trox, USA 24

Operating Rooms Design Criteria 20 ach with 4 ach OA Recently low end reduced for 30% RH 68F to 75F by code (lower as required by procedure/doctor) Humidity levels: 20% to 60% RH Positive pressure to adjacent areas 25

Operating Rooms Typical Ventilation System 26

Operating Rooms Air Distribution AIA 2006 and ASHRAE 170-2012 Agree Supply unidirectional downwards over patient and surgical team Primary supply diffusers shall extend a minimum of 12 beyond the surgical table Room must have at least 2 low sidewall return grills Supply diffuser velocity of 25 to 35 cfm/sf No more than 30% of supply diffuser area shall be used by non-diffusers Additional return grilles may be placed high on walls 27

Operating Rooms Air Distribution 28

OR System Challenge #1 Low Temp OR & Humidity Level If all ORs at 72F and 35% One OR temp lowered to 65F 57%RH One OR temp lowered to 63F 64% RH One OR temp lowered to 60F 75% RH If all ORs at 72F and 20% One OR temp lowered to 65F 37%RH One OR temp lowered to 63F 43% RH One OR temp lowered to 60F 54% RH 29

OR System Challenge #2 Low Temp OR & Humidity Level Lesson Learned If implementing a new low temperature OR, analyze the psychometrics of the specific situation. If controlling to 30% rh, consider 20% rh or lower to 20% rh when high humidity levels occur in low temp OR May need booster humidifiers at all ORs Control AHU humidifier to the room that needs the least amount of humidity (low temp OR). Boosters will trim other rooms required rh 30

Operating Room Challenge #2 Unoccupied Airflow Setback and Pressurization Why unoccupied shut-back of airflow? Energy savings Reduction of facility s carbon footprint For more information, ASHE has a booklet available online entitled Operating Room HVAC Setback Strategies 31

Operating Room Challenge #2 Unoccupied Airflow Setback and Pressurization Estimated annual energy dollars saved for one OR $2,023 $2,846 $2,027 $3,260 $2,597 $2,378 Savings based on Chicago weather; $0.11/kWh for electricity and $0.65/therm for gas,13 unoccupied hours per day 10 ORs annual savings is $20,000 to $32,000 32

Operating Room Challenge #2 Unoccupied Airflow Setback and Pressurization Per AHSRAE Standard 170: OR s must be positive, at least +0.01 at all times ACH can be reduced when unoccupied provided the pressurization is maintained 33

Operating Room Challenge #2 Unoccupied Airflow Setback and Pressurization Occupancy sensor or time schedule indicates unoccupied conditions Supply VAV box closes and return damper or VAV box closes If supply VAV box closes faster than return damper or VAV box, the OR may go negative 34

Operating Room Challenge #2 Unoccupied Airflow Setback and Pressurization Example: Occupied Mode: OR at +0.023 to +0.014 Unoccupied Mode Initiated After 1 minute: -0.028 After 10 minutes: -0.009 After 17 minutes: -0.001 After 18 minutes: +0.001 After 25 minutes: +0.01 ) OR was negatively pressurized for 17 minutes and less than +0.01 for 25 minutes 35

Operating Room Challenge #2 Unoccupied Airflow Setback and Pressurization Lesson Learned If implementing an unoccupied airflow setback in an operating room Recommend the same control device on supply and return either VAV boxes or air valves Speed of response of air control devices must be commissioned and adjusted so room remains positive when switching from occupied to unoccupied mode and back 36

Airborne Infection Isolation Rooms Used to reduce the spread of airborne infectious diseases (TB) from the patient in the AII Room to the rest of the hospital. In addition to ASHRAE Standard 170 and AIA Guidelines: Guidelines for Environmental Infection Control in Healthcare Facilities, Recommendations of CDC and the Healthcare Infection Control Practices Advisory Committee (HICPAC), 2003 37

Airborne Infection Isolation Rooms Codes and Standards CDC Temp/humidity not addressed Min 12 ach exhaust for rooms constructed since 2001 Min 0.01 H 2 O pressure differential to achieve airflow into room All air exhausted to outside away from air intakes and traffic or exhausted after HEPA filtration AIA 2006 75F 30%-60% rh 12 ach minimum total airflow/2 ach outside air All air exhausted to outside Min 0.01 H 2 O pressure differential to achieve airflow into room ASHRAE Standard 170-2013 (incorporates CDC) 70F-75F ability to maintain at all times 60%rh (no minimum) 12 ach minimum total airflow/2 ach outside air All air exhausted to outside Negative pressure relative to adjacent spaces 38

Airborne Infectious Isolation Room Architectural Design Considerations Ante room not required but per AIA Each room shall have an area for handwashing, gowning, and storage of clean and soiled materials located directly outside or immediately inside the entry door to the room. Ante room with hand wash sink satisfied these requirements 39

Airborne Infectious Isolation Room Architectural Design Considerations AII room constructed to minimize leakage areas Walls slab-to-slab Ceilings plaster or drywall Self-closing doors with door sweeps Sliding doors preferred Finishes should be smooth and cleanable Seal all penetrations Room will not remain pressurized or will need a lot of air to stay pressurized if room is leaky. Lesson Learned 40

Airborne Infectious Isolation Room Pressurization Design Considerations AII room negative to ante room/ante room negative to corridor (ASHRAE) Min ΔP between AII room and adjacent rooms/corridor -0.01 wg (ASHRAE) Min of 10% more EA than SA but no less than 50 cfm New tight construction 200 cfm to 300 cfm differential Poorly constructed - 300 cfm to 500 cfm Permanently installed ΔP monitoring device (ASHRAE) 41

Airborne Infectious Isolation Room Room Supply & Exhaust Design Considerations Location of supply diffusers and exhaust grilles - CDC 2003 and ASHRAE Standard 170 disagree CDC 2003: Supply above patient, exhaust low on wall ASHRAE Standard 170 2008/2013: Exhaust grilles or registers shall be located directly above the patient bed on the ceiling or on the wall near the head of the bed Designer may consider discussing discrepancy with hospital infection control If chose to supply above patient, use non-aspirating laminar flow type diffusers 42

Airborne Infectious Isolation Room Airflow Diagram Diagram from CDC Guidelines 43

Airborne Infectious Isolation Room Exhaust system: Room HVAC Design Example EA from AHII to maintain 12 ach: 1,400 cfm Toilet exhaust: 100 cfm EA from ante room to maintain 10 ach: 250 cfm Constant volume exhaust box to maintain EA / Total EA = 1,400 cfm + 100 cfm + 250 cfm = 1,750 cfm Transfer air from corridor to ante room and ante room to AII room Assume mid range in tightness use 300 cfm transfer air (TA) Supply system: AII SA = EA TA from ante room + TA to toilet /AII SA = 1,400 cfm 300 cfm + 100 cfm = 1,200 cfm Constant volume box to maintain total SA / Total SA = 1,200 cfm + 250 cfm = 1,450 cfm SA to ante room: 250 cfm (Ante room neutral) Reheat coil to provide space temperature control 44

Airborne Infectious Isolation Room Room HVAC Design Example 45

Airborne Infectious Isolation Room Room Pressure Monitors Locate outside of ante room door in corridor Alarms visually and audibly if negative pressure is not maintained Tie-in alarm to building automation system Lesson Learned: To avoid nuisance alarms, control to a higher ΔP than to the ΔP at which the alarm is set Control to 0.03 and alarm at 0.01. 46

Airborne Infectious Isolation Room HVAC Design Example Example simplified AII room sequence of operation Modulate supply CAV air terminal unit damper to maintain supply airflow setpoint. Modulate exhaust air terminal unit damper to maintain exhaust airflow setpoint. Modulate reheat valve and radiation valve to maintain temperature setpoint. Coordinate with users to setup time delay to allow entrance/exit to the pressurized space without audible alarm. If an exhaust fan failure alarm is received at the front end, close the supply air terminal damper operator. 47

Pharmacies US Pharmacopeial Convention (USP) <797> Pharmaceutical Compounding Sterile Preparations applies to: Facilities in which sterile products are prepared and where manipulations are performed during the compounding of sterile products which increase the potential for microbial contamination of the end product. Facilities where products are compounded using devices or ingredients which are not sterile to prepare products which must be sterilized prior to use. Many hospitals have upgraded - upgrades and renovations typically exceed of $1M. 48

Pharmacies and <USP 797> Requirements A positive or negative pressure cleanroom with ISO Class 7 air quality An ISO Class 7 Anteroom for entry from the outside areas An ISO Class 7 Buffer Zone (and Compounding Rooms) Airlocks or pass-throughs for material movement Hand-washing facilities Laminar Air Flow Workbench(es), Biological Safety Cabinet(s), or Barrier Isolator(s) in which sterile compounding takes place 49 49

Pharmacy Compounding Equipment Laminar Airflow Work Benches (LAFWs) ISO Class 5 (Class 100) cleanliness. Provides laminar airflow across the work surface HEPA supply filter with 99.99% minimum efficiency in capturing 0.3 micrometer particulates Applications: IV admixture preparation Drug compounding Media preparation Pharmaceutical procedures Electronic assembly Used in clean workroom and does not require ducted exhaust air 50 50

Pharmacy Compounding Equipment Biological Safety Cabinet(s), (BSC s) Down flow of air and HEPA treatment of re-circulated air Depending on type, some or all air is exhausted Inflows and downflows certified at sash velocities (90-105 fpm), per ASHRAE Types: A1, A2, B1, B2 A1 & A2 exhaust 30% of air B1 exhaust 40% of air B2 exhaust 100% of air Use type B2 for chemo compounding unless glove box used Caution requires about 1,000 cfm at -2.0 at inlet 51 51

Pharmacy Compounding Equipment Barrier Isolators (Glove Boxes) Leak tight negative pressure work area HEPA filtered air better than ISO 5 Exhaust volumes typically 300-500 cfm at -2.0 w.g. (50% of type B2 BSC ) 52

Pharmacies and USP <797> ISO Classes Maintaining ISO Class 7 and 8 requires HEPA filters and the following air changes per hour: ISO Class 7: 30 to 60 53 53

Pharmacy Plan Fan Filter Units for Clean Rooms HEPA filter and small fan in ceiling tile ECM Speed Control Filters changeable from room-side 54

Pharmacy Plan Separate Clean Room for Chemo How are high airflows and static pressures for terminal HEPA diffusers cleanrooms achieved? Can use central AHU but frequently existing AHU does not have adequate capacity Additional recirculation only fan coil units Ceiling mounted fan filter units 55

Pharmacy Plan Separate Clean Room for Chemo Ante Room Chemo Prep Cleanroom where hazardous drugs are prepared Clean Compounding Cleanroom where non-hazardous drugs are prepared 56

Pharmacy HVAC Plan Chemo Hood Exhaust Duct EA Constant Volume VAV Box Fan Filter Unit Low Exhaust or Return 57

Pharmacy HVAC System Challenge Fan filter units are in line with the CV boxes CV boxes dampers will modulate in response to a change in pressure in the duct Fan filter units ECM motors modulate as the filters load up Two modulating devices in series fight each other and leads to hunting One device must be fixed ECM motors can be set fixed 58

Thank you for you time Questions? 59