TECHNICAL DATA & SERVICE MANUAL

Similar documents
TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW22AL AW28AL AW38AL AW42AL AW22AL AW28AL AW38AL

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: ASR609CL ASR612CL ASR609CL ASR612CL

TECHNICAL DATA & SERVICE MANUAL

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: CAF94R5 CAF124R5 CAF94R

TECHNICAL DATA & SERVICE MANUAL

TECHNICAL DATA & SERVICE MANUAL

TECHNICAL DATA & SERVICE MANUAL

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER OUTDOOR UNIT: AE22AC/ACL/AH AE28AC/ACL/AH AE38AC/ACL/AH AE42AC/ACL/AH

SPLIT SYSTEM AIR CONDITIONER

TECHNICAL DATA & SERVICE MANUAL

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

TECHNICAL DATA & SERVICE MANUAL

TECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER

INSTALLATION INSTRUCTIONS

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: MCAF72R5TA- MCAF92R5TA- MCAF122R5TA-

TECHNICAL DATA & SERVICE MANUAL MTF94C5TAA

SPLIT SYSTEM AIR CONDITIONER

TECHNICAL DATA & SERVICE MANUAL DISEGNO MACCHINA

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

TECHNICAL DATA & SERVICE MANUAL MULTI-SPLIT SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 123A FILE NO. SA 123A REFERENCE NO. SM700513

TECHNICAL & SERVICE MANUAL SAP K181A + SAP C181A

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 128S5 FILE NO. SA 128S5 REFERENCE NO. SM700338

TECHNICAL & SERVICE MANUAL

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 183A FILE NO. SA 183A REFERENCE NO. SM Destination Australia SA-183A

TECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER SAP K303A + SAP C303A FILE NO. REFERENCE NO. SM Destination: Australia

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

TECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER SAP K301AH + SAP C301AH FILE NO. SAP K301AH SAP C301AH REFERENCE NO.

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity 7,500BTU / h 9,000BTU / h 11,900BTU / h 17,500BTU / h 24,200BTU / h

INSTALLATION INSTRUCTIONS

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 93AH FILE NO. SA 93AH REFERENCE NO. SM700510

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

TECHNICAL DATA & SERVICE MANUAL

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

TECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER

TECHNICAL DATA & SERVICE MANUAL DISEGNO MACCHINA

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

AUTO COOL DRY FAN SPEED AIR SWING OFF ON TIMER TIMER OFF/ON FAN SPEED MODE TEMP AIR SWING TIMER ON SET OFF CANCEL AC RC SET CHECK CLOCK RESET

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

MULTI-SPLIT SYSTEM AIR CONDITIONER

AIR-CONDITIONER SERVICE MANUAL

INVERTER SPLIT SYSTEM AIR CONDITIONER

TEST RUN SERVICE MANUAL

Installation Instructions

INSTALLATION INSTRUCTIONS

Installation Instructions

AIR-CONDITIONER TOSHIBA SERVICE MANUAL SPLIT TYPE, HEAT PUMP COOLING ONLY FILE NO. A Tel: Fax:

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624. Models HFC. Revision A: MUZ-FH50VE- E1 has been added. Please void OBH624.

Installer manual AG-AA10. Air/air heat pump IHB GB AG-AA10-30 AG-AA10-40/50

INVERTER WALL MOUNTED TYPE ROOM AIR-CONDITIONER (Split system, air to air heat pump type)

SERVICE MANUAL AIR CONDITIONER SPLIT TYPE

Installation Instructions

Installation Instructions

TECHNICAL & SERVICE MANUAL WIRED REMOTE CONTROLLER STK-RCS-7TWSUA FILE NO. Product Code No Model No. STK-RCS-7TWSUA

INSTALLATION INSTRUCTIONS

SPLIT SYSTEM AIR CONDITIONER

WALL MOUNTED TYPE ROOM AIR-CONDITIONER

DLCLRA. INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 TABLE OF CONTENTS

CWX 3 - CWX 5 CASSETTE TYPE TERMINAL UNIT. Cooling

SERVICE MANUAL MUFZ-KJ50VE - E1, E2, ER1, ER2, ET1, ET2 MUFZ-KJ35VE OUTDOOR UNIT. No. OBH667. Models HFC

SERVICE MANUAL MUZ-FH25VE MUZ-FH35VE MUZ-FH50VE OUTDOOR UNIT. No. OBH624 REVISED EDITION-E. Models HFC

INSTALLATION INSTRUCTIONS

SPLIT TYPE ROOM AIR CONDITIONER FLOOR CONSOLE / UNDER CEILING DUAL TYPE

Installation Instructions

USER S MANUAL HSC-14/18/24/24A

Кондиционеры Mitsubishi Heavy

SERVICE Manual SYSTEM AIR CONDITIONER INDOOR UNIT GH052EAM GH070EAM OUTDOOR UNIT UH052EAMT UH070EAMT. 1. Product Specifications

SERVICE MANUAL ROOM AIR CONDITIONER TAN/TAG-A28FWIS TAN/TAG-A32FWIS CONTENTS

Operating Instructions Air Conditioner

CWX 6 - CWX 8 - CWX 10 CASSETTE TYPE TERMINAL UNIT

DESIGN & TECHNICAL MANUAL

AIR CONDITIONER SERVICE MANUAL SPLIT WALL TYPE

Installation Instructions

INSTALLATION INSTRUCTIONS CS-KS30NKU + CU-KS30NKUA CS-KS36NKU + CU-KS36NKUA

TECHNICAL & SERVICE MANUAL. Ceiling Cassettes

HEAT PUMP INSTALLATION MANUAL

SERVICE MANUAL MUZ-DM25VA - E1, ER1, ET1 MUZ-DM35VA - E1, ER1, ET1 OUTDOOR UNIT. No. OBH751. Models HFC R410A

DLCSRA. INSTALLATION INSTRUCTIONS Outdoor Unit Ductless Split System Sizes 09 to 36 TABLE OF CONTENTS

TECHNICAL & SERVICE MANUAL. Ceiling Concealed

6. INVERTER MULTI-SPLIT SYSTEM ROOM AIR-CONDITIONER (Air cooled cooling only type)

All side discharge units are having high pressure switch (LP switch- Optional) and time delay relay. Compressors are scroll type, Copeland make.

Installation Instructions

INSTALLATION INSTRUCTION for ceiling fan

SERVICE MANUAL MUZ-FE09NA MUZ-FE09NAH MUZ-FE12NA MUZ-FE12NA1 MUZ-FE12NAH MUZ-FE18NA OUTDOOR UNIT. No. OBH543 REVISED EDITION-F.

SERVICE MANUAL MUZ-HC25VA - E1 MUZ-HC35VA - E1 MUZ-HC35VA - E2 MUZ-HC35VAB - E1 MUZ-HC35VAB - E2 OUTDOOR UNIT. No. OBH467.

Wall Mounted Split Systems

7-5. Remove the Grille to Install the Indoor Unit

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DAIKIN AIR CONDITIONER

Part 3 Troubleshooting

Transcription:

TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: CAF97R5IAA CAF98MR5IAA CAF127R5IAA CAF128MR5IAA CAF187R5IAA SPLIT SYSTEM AIR CONDITIONER Model No. CAF97R5IAA CAF127R5IAA CAF187R5IAA CAF98MR5IAA CAF128MR5IAA Product Code No. 38.7106.005 38.7106.006 38.7106.007 38.7106.015 38.7106.016 0.8180.533.1 06/2008

IMPORTANT! Please read before installation This air conditioning system meets strict safety and operating standards. For the installer or service person, it is important to install or service the system so that it operates safely and efficiently. For safe installation and trouble-free operation, you must: Carefully read this instruction booklet before beginning. Follow each installation or repair step exactly as shown. Observe all local, state and national electrical codes. Pay close attention to all warning and caution notices given in this manual. The unit must be supplied with a dedicated electrical line. WARNING This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death. CAUTION This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage. If necessary, get help These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sale/service outlet or your certified dealer for additional instructions. In case of improper installation The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document. SPECIAL PRECAUTIONS During installation, connect before the refrigerant system and then the wiring one; proceed in the reverse orden when removing the units. WARNING When wiring ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY QUALIFIED, EXPERIENCED ELECTRICIANS SHOULD ATTEMPT TO WIRE THIS SYSTEM. Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked, to ensure the grounding. Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury and death. Ground the unit following local electrical codes. The Yellow/Green wire cannot be used for any connection different from the ground connection. Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard. Do not allow wiring to touch the refrigerant tubing, compressor, or any moving parts of the fan. Do not use multi-core cable when wiring the power supply and control lines. Use separate cables for each type of line. When transporting Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminium fins on the air conditioner can cut your fingers. When installing... In a ceiling Make sure the ceiling is strong enough to hold the unit-weight. It may be necessary to build a strong wooden or metal frame to provide added support. In a room Properly insulate any tubing run inside a room to prevent "sweating", which can cause dripping and water damage to walls and floors.... In moist or uneven locations Use a raised concrete base to provide a solid level foundation for the outdoor unit. This prevents damage and abnormal vibrations.... In area with strong winds Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.... In a snowy area (for heat pump-type systems) Install the outdoor unit on a raised platform that is higher then drifting snow. Provide snow vents. When connecting refrigerant tubing Keep all tubing runs as short as possible. Use the flare method for connecting tubing. Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them; screw by hand and then tighten the nut with a torque wrench for a leak-free connection. Check carefully for leaks before starting the test run. NOTE: Depending on the system type, liquid and gas lines may be either narrow or wide. Therefore, to avoid confusion, the refrigerant tubing for your particular model is specified as narrow tube for liquid, wide tube for gas. When servicing Turn the power OFF at the main power board before opening the unit to check or repair electrical parts and wiring. Keep your fingers and clothing away from any moving parts. Clean up the site after the work, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced. Ventilate the room during the installation or testing the refrigeration system; make sure that, after the installation, no gas leaks are present, because this could produce toxic gas and dangerous if in contact with flames or heat-sources. 2

Table of Contents Page 1. SPECIFICATIONS 4 1-1 Unit specifications 4-5 1-2 Major Component specifications 6-7 1-3 Other Component specifications 8 2. DIMENSIONAL DATA 9 3. ELECTRICAL DATA 10 3-1 Electric Wiring Diagrams 10 4. FUNCTION 11 4-1 Operation Functions 11-12 4-2 Protective Functions 13-14 4-3 Drain Pump and Float Switch 15 5. TEST RUN 16 5-1 How to Test Run the Air Conditioner 16 6. TROUBLESHOOTING 17 6-1 Precaution before Performing Inspection or Repair 17 6-2 Method of Self-Diagnostics 18 6-3 Checking the Indoor and Outdoor Units 19 6-4 Noise Malfunction and Electromagnetic Interference 20 7. CHECKING ELECTRICAL COMPONENTS 21 7-1 Measurement of Insulation Resistance 21 7-2 Checking Continuity of Fuse on PCB Ass'y 22 7-3 Checking Motor Capacitor 22 3

1. SPECIFICATIONS 1-1 Unit Specifications CAF 97/127 R5IAA - CAF 98/128 MR5IAA Power source Voltage rating Performance Capacity Air circulation High/Med./Low m³/h 220-240 V ~ 50 Hz 230 V See catalogue with the requested matching 700/600/500 Features Controls/Temperature controls Control unit Timer Fan speed Airflow direction Vertical Microprocessor/ I.C. thermostat Wireless remote control unit ON/OFF 24 hours & Daily program, 1-hour OFF 3 and Auto /1(Hi) Auto Air Filter Power noise level High/Med./Low db-a Refrigerant tubing connections Refrigerant Narrow tube (in.) tube diameter Wide tube (in.) Refrigerant Refrigerant tube kit / Air clean filter Dimensions & Weight Dimensions Unit Height Width Depth Ceiling panel Height Width Depth Package dimensions Unit Height Width Depth Volume m3 Ceiling panel Height Width Depth Volume m3 Weight Unit Net kg Shipping kg Ceiling panel Net kg Shipping kg Washable, Anti-Mold 53/49/46 Flare type 6,35 (1/4) 9,52 (3/8) R410A Optional / -------------- 273 575 575 64 730 730 380 744 650 0,18 110 800 800 0,07 16,5 21 2,50 4,70 4

CAF 187 R5IAA Power source Voltage rating Performance Capacity Air circulation High/Med./Low m³/h 220-240 V ~ 50 Hz 230 V See catalogue with the requested matching 790/660/580 Features Controls/Temperature controls Control unit Timer Fan speed Airflow direction Vertical Microprocessor/ I.C. thermostat Wireless remote control unit ON/OFF 24 hours & Daily program, 1-hour OFF 3 and Auto /1(Hi) Auto Air Filter Power noise level High/Med./Low db-a Refrigerant tubing connections Refrigerant Narrow tube (in.) tube diameter Wide tube (in.) Refrigerant Refrigerant tube kit / Air clean filter Dimensions & Weight Dimensions Unit Height Width Depth Ceiling panel Height Width Depth Package dimensions Unit Height Width Depth Volume m3 Ceiling panel Height Width Depth Volume m3 Weight Unit Net kg Shipping kg Ceiling panel Net kg Shipping kg Washable, Anti-Mold 54/49/46 Flare type 6,35 (1/4) 12,7 (1/2) R410A Optional / -------------- 273 575 575 64 730 730 380 744 650 0,18 110 800 800 0,07 18,2 22,7 2,50 4,70 5

1-2 Major Component Specifications CAF 97/127 R5IAA - CAF 98/128 MR5IAA Controller PCB Part No. Controls Control circuit fuse CAF97R5I CAF127R5I CAF98MR5I CAF128MR5I CB-XRV93EH CB-XRV123EH CB-XMRV94EH CB-XMRV124EH Microprocessor 250 V - 3,15 A Remote Control Unit CAF97/127R5I CAF98/128MR5I RCS-4HVPN4EX RCS-4MHVPN4EX RCS-4MHVPNW4EX Fan & Fan Motor Type Q'ty. Dia. and lenght Fan motor model Q'ty No. of poles rpm (230 V, High / 2nd / 3rd / Low) Running Amps Power input Coil resistance (Ambient temp. 20 C ) A W Ω Safety devices Type Operating temp. Open C Close Run capacitor µf VAC Centrifugal fan 1. Ø 280 / L 166 K35407 M01972 1 4 870 / 720 / 600 / 270 0,27 61 BLU-BRN: 33,9 39,1 BLU-BLK: 325 374 BLK-GRY: 78,7 90,5 GRY-RED: 49,7 57,2 RED-WHT/YEL: 155 178 Internal thermal protector 150 ± 10 Automatic 2 400 Flap Motor Type Model Rating Coil resistance (Ambient temp. 25 C ) Heat Exch. Coil Coil Rows Fin pitch face area Ω m2 Stepping motor MP24GA2 DC 12 V 400±7% Aluminium plate fin / Copper tube 1 1,3 0,258 DATA SUBJECT TO CHANGE WITHOUT NOTICE 6

CAF 187 R5IAA Controller PCB Part No. Controls Control circuit fuse Remote Control Unit Fan & Fan Motor Type Q'ty. Dia. and lenght Fan motor model Q'ty No. of poles rpm (230 V, High / 2nd / 3rd / Low) Running Amps Power input Coil resistance (Ambient temp. 20 C ) A W Ω Safety devices Type Operating temp. Open C Close Run capacitor µf VAC CB-XRV184EH Microprocessor 250 V - 3,15 A RCS-4MHVPNW4EX Centrifugal fan 1. Ø 280 / L 166 K35407 M01972 1 4 950 / 790 / 700 / 300 0,27 61 BLU-BRN: 33,9 39,1 BLU-BLK: 325 374 BLK-GRY: 78,7 90,5 GRY-RED: 49,7 57,2 RED-WHT/YEL: 155 178 Internal thermal protector 150 ± 10 Automatic 2 400 Flap Motor Type Model Rating Coil resistance (Ambient temp. 25 C ) Heat Exch. Coil Coil Rows Fin pitch face area Ω m2 Stepping motor MP24GA2 DC 12 V 400±7% Aluminium plate fin / Copper tube 1 1,3 0,258 DATA SUBJECT TO CHANGE WITHOUT NOTICE 7

1-3 Other Component Specifications CAF 97/127 R5IAA CAF 98/128 MR5IAA CAF 187 R5IAA Trasformer (TR) Rating Coil resistance Thermal cut-off temp. Primary Secondary Capacity Ω (at 25 C) ATR-I55 AC 230 V, 50/60 Hz 13.7 V - 0.4 A 5.48 VA Primary (WHT-WHT): 307 ± 10% Secondary (BRN-BRN): 1.8 ± 10% 150 C Thermistor ( Coil sensor TH1) Resistance Thermistor ( Room sensor TH2) Resistance Thermistor ( Humidity sensor TH3) Resistance κω κω κω DTN-C583G3U-TKS121B 0 C: 188,0 ± 4% DTN-C502H3T-TKS128B 25 C: 5,0 ± 3% C7-M3-SY 25 C - 60% RH (± 5% RH): 31,0 Drain pump Model Rating Total head capacity Safety float switch Model Contact rating Voltage Input PC 309564003 220-240 V - 50 Hz 14 W 0,4 l/min BI 1300 2725 230 V AC/DC - 0,5 A Resistance (kω) Indoor air temp sensor 10 9 8 7 6 5 4 3 2 1 10 15 20 25 30 35 40 Temperature ( C) Resistance (kω) Indoor heat exchanger sensor 200 180 160 140 120 100 80 60 40 20 0 0 10 20 30 40 50 60 70 80 90 Temperature ( C) Humidity sensor 1000 Resistance (kω) 100 10 25 C 1 30 35 40 45 50 55 60 65 70 75 80 85 90 Relative humidity (%) 8

2. DIMENSIONAL DATA Unit: REFRIGERANT TUBING JOINT WIDE TUBE: CAF97/127R5I - CAF98/128MR5I o.d. 9,52 (3/8) CAF187R5I o.d. 12,7 (1/2) 9

3. ELECTRICAL DATA 3-1 Electric Wiring Diagrams CAF 97/127 R5IAA CAF 187 R5IAA CAF 98/128 MR5IAA 10

4. FUNCTIONS 4-1 Operation Functions 11

12

4-2 Protective Functions 13

14

4-3. Drain Pump and Float Switch 15

5. TEST RUN 5-1 How to Test Run the Air Conditioner display area HIGH POWER button 1HR. TIMER button ON/OFF operation button 16

6. TROUBLESHOOTING 6-1 Precaution before Performing Inspection or Repair 6-2 Method of Self-Diagnostics ON/OFF button 1HR. TIMER button ACL (reset) button 17

(1) Self-diagnostics lamps OPERATION lamp TIMER lamp SERVICE lamp + Since the indications cover various units, the corresponding parts listed below may not be present in some models. (2) If the self-diagnostics function fails to operate 18

6-3 Checking the Indoor and Outdoor Units 19

6-4 Noise Malfunction and Electromagnetic Interference 20

7. CHECKING ELECTRICAL COMPONENTS 7-1 Measurement of insulation Resistance 21

7-2 Checking Continuity of fuse on PCB Assy 7-3 Checking Motor Capacitor 22

R.D. 28 Reyrieux BP 131-01601 Trévoux CEDEX France Tél. 04.74.00.92.92 - Fax 04.74.00.42.00 R.C.S. Bourg-en-Bresse B 759 200 728