Application Engineering

Similar documents
AE R13 August 2018 Economized Vapor Injection (EVI) for ZF*KVE and ZF*K5E Compressors TABLE OF CONTENTS

Technical Information

Technical Information

Technical Information

TEST REPORT #65. Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A) in a R-410A Scroll Compressor

Refrigeration Scroll Enhanced Vapour Injection

TEST REPORT #34. Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A Scroll Compressor

A Treatise on Liquid Subcooling

Application and Installation Bulletin for Master-Bilt Refrigeration Superheat Controller Kit Assembly(A ), 120/208/240/1/60, R404A, LT/MT APPS

Scroll compressors with vapour injection for Dedicated Heat Pumps. ZH24 KVE to ZH48 KVE Application Guidelines

Scroll compressors with vapour injection for Dedicated Heat Pumps. ZH13 KVE & ZH18 KVE Application Guidelines

Thomas J Kelly. Fundamentals of Refrigeration. Sr. Engineering Instructor Carrier Corporation. August 20, Page number: 1.

AE R8 March 2015

AE Application Guidelines for Refrigeration Copeland Discus Compressors with R-410A

Figure 1: Schematic of internal heat exchanger vapor-injection cycle

R32 Compressor for Air conditioning and Refrigeration applications in China

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

Copeland Scroll ( HP) ZB*KA and ZF*KA for Refrigeration

UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM

Scroll Compressor for Mobile HVAC/R Application

Copeland Scroll Condensing Units for the Food Service Market

Danfoss scroll for refrigeration LLZ013 to low temperature

Application Guidelines for Low Temperature ZF**KAE 1-2.5HP Copeland Scroll Refrigeration Compressors

TEST REPORT #4. Travis Crawford Dutch Uselton. Lennox Industries Inc Metrocrest Drive Carrollton, TX 75006

TEST REPORT #47. System Drop-in Test of R-32 and Refrigerant Blends ARM-71a, HPR2A, L-41-2 and DR-5A in a Five-Ton R-410A Rooftop Packaged Unit

TEST REPORT #32. System Soft-Optimized Test of Refrigerant D2Y60 in Air Source Heat Pump

Application Guidelines for ZS**KAE Refrigeration Copeland Scroll Compressors HP

September 2016 AE Application Guidelines for Copeland CS**KIE Compressors in Ice Machines AE4-1421

AE R17 November 2016

Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants

TEST REPORT #14. System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled Screw Chiller

2016 Annual Conference

Recommendations to retrofit positive existing installations running with HFCs (R404A & R507) RETROFIT POSITIVE & MEDIUM REFRIGERATING SYSTEMS

Technical Development Program. COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler

Application Guidelines for Glacier K3 Copeland Scroll Refrigeration Compressors

R4H4. Product Specifications

N4H4. Product Specifications 14 SEER HEAT PUMP. ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz

AE R1 October to 5 Ton ZPS*K6 Copeland Scroll Two-Stage Compressors

AE R9. AE R9 May Application Guidelines For K4 Refrigeration Copeland Scroll Compressors Horsepower

Application Engineering

Air Cooled Packaged Systems AIRAH Back to Basics

AIR CONDITIONING. Carrier Corporation 2002 Cat. No

Microchannel REMOTE AIR COOLED CONDENSER. Technical Bulletin: MXCC_004_ Products that provide lasting solutions.

XSTREAM Valve System With A.R.M.E.D. Technology Service & Installation Instructions Page 1

MYSTICOOL Max Valve System with Xstream and A.R.M.E.D. Technology Service & Installation Instructions Page 1

Energy Use in Refrigeration Systems

Chapter-8 Capacity Control of Refrigeration Systems

MACH N-407 Heat Pump Air-Cooled Chiller

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

BASIC HEAT PUMP THEORY By: Lloyd A. Mullen By: Lloyd G. Williams Service Department, York Division, Borg-Warner Corporation

R4H4. Product Specifications

AE October 1965 Reformatted October Hot Gas Bypass Control Systems

MAC-120HE-03 Air-Cooled Chiller

Copeland Scroll. Product Information. Outdoor condensing units for refrigeration applications

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

TEST REPORT #43. System Drop-in Tests of Refrigerants L-41-1, L-41-2, and R-32 in Water-to- Water Heat Pump

TEST REPORT #6. Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP)

TEST REPORT #53. System Drop-in Test of Refrigerant Blend DR-55 in a Five-Ton R-410A Rooftop Packaged Unit

Microchannel REMOTE AIR COOLED CONDENSER WITH ELECTRONICALLY COMMUTATED AXITOP MOTORS. Technical Bulletin. Products that provide lasting solutions.

Heat Reclaim. Benefits,Methods, & Troubleshooting By Dave Demma, Manager Supermarket Sales, Sporlan Division - Parker Hannifin Corporation

500 EX Fusion Compressor Series

Danfoss Scroll for Refrigeration MLM / MLZ

Table of Contents. Service Procedures. Service Procedures. Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8)

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

MAC N-407 Air-Cooled Chiller

Executive Summary. Number of Low Number of High Number of Faults , Number of OK

Publication # RD-0003-E Rev 1, 10/17 SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS

B. A. T. Basic Appliance Training

Behavior of R410A Low GWP Alternative Refrigerants DR-55, DR-5A, and R32 in the Components of a 4-RT RTU

Packaged Heat Pump. 20 Ton Rooftop Units with ReliaTel TM Controls NOTICE

Use this Construction/HVAC Glossary to answer the questions below.

The Refrigeration Cycle

Calhoon MEBA Engineering School. Study Guide for Proficiency Testing Refrigeration

ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER OPERATIONS AND MAINTENANCE MANUAL

INTRODUCTION. Special Applications of Package Air Conditioners. Instant Cooling Requirement in Wedding Ceremonies

AHRI Standard 1250P (I-P) 2009 Standard for Performance Rating of Walk-In Coolers and Freezers

System Considerations for Refrigerant Blends with Temperature Glide

DAVE DEMMA ACHIEVING HEAD PRESSURE CONTROL

The Refrigeration Cycle

PAJ3. Product Specifications

Sustainable Techniques in Refrigerated Space

N4H4. Product Specifications

Installation, Operation, and Maintenance Information

MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

Subcooling is defined as the point at which liquid is cooled below it s condensing temperature. Example: Refrigerant R404A

Parallel Rack Systems

APPLICATION DATA SHEET

A 14 SEER Heat Pump with R---410A Refrigerant Series

Air Conditioning Clinic. Refrigerant Piping One of the Fundamental Series TRG-TRC006-EN

S-Therm Air to Water Heat Pumps

Catalog Air Cooled Split System Condensing Units for Rooftop Systems and Air Handlers

CO2 TRANSCRITICAL BOOSTER SYSTEMS

JCseries EVAPORATIVE CONDENSER. engineering data

Air-Cooled Split System Condensing Unit for Rooftop Systems and Air Handlers

BN-HGDTB June Replaces BN-HGDTB, March Mohave. Technical Guide

"COP Enhancement Of Domestic Refrigerator By Sub cooling And Superheating Using Shell &Tube Type Heat Exchanger"

Levitor II. AIR-COOLED CONDENSER WITH ELECTRONICALLY COMMUTATED AXITOP MOTORS (Available for Fluid Cooler Applications)

Transcritical CO2 Bottle Cooler Development

AE R21 September 2017

Warm Case Troubleshooting Guide 9/18/2014

Transcription:

Revised September, 2006 ECONOMIZED VAPOR INJECTION (EVI) COMPRESSORS INDEX SECTION PAGE 1. Introduction... 1 2. Theory of Operation... 1 3. Nomenclature... 3 4. ARI Low Temperature Ratings... 3 5. Approved Refrigerants... 3 6. Approved Oils... 3 7. Power Requirements... 3 8. Application Envelope... 3 9. Control Requirements... 3 10. Discharge Temperature Control... 3 10.1 Thermistor... 3 10.2 Discharge Line Thermostat... 4 11. TXV and Heat Exchanger... 4 12. System Configuration... 4 12.1 Downstream Extraction... 4 12.2 Upstream Extraction... 5 12.3 Heat Exchanger Piping Arrangements... 5 13. System Design Guidelines... 5 13.1 Heat Exchanger Sizing... 5 13.2 Line Sizing... 6 13.3 Heat Exchanger TXV Sizing... 6 13.4 Solenoid Valve... 6 13.5 Current Sensing Relay... 7 13.6 Multiple Compressor Applications... 7 14. Controlling Liquid Out Temperature 7 1. Introduction The Refrigeration Economized Vapor Injection (EVI) Compressor was developed to provide improved capacity and efficiency. EVI compressor systems benefit over standard refrigeration compressor systems of equivalent horsepower due to the following: Capacity Improvement - The capacity is improved by increasing the h (change in enthalpy) in the system rather than increasing mass flow. This is accomplished without increasing compressor displacement. Increased Energy Efficiency Ratio (EER) - The efficiency improves due to the fact that the gain in capacity is greater than the increase in power that the compressor consumes. Cost and Energy Advantage - Because a smaller horsepower compressor can be used to achieve the same capacity as a larger horsepower compressor, there is an inherent cost advantage. 2. Theory of Operation Copeland EVI Scroll compressors are equipped with an injection connection for Economizer Operation. Economizing is accomplished by utilizing a subcooling circuit similar to that shown in Figure 1. This mode of operation increases the refrigeration capacity and in turn the efficiency of the system. The benefits provided will increase as the compression ratio increases, thus, more gains will be made in summer when increased capacity may actually be required. The schematic shows a system configuration for the economizer cycle. A heat exchanger is used to provide subcooling to the refrigerant before it enters the evaporator. This subcooling process provides the increased capacity gain for the system, as described above. During the subcooling process a small amount of refrigerant is evaporated and superheated. This superheated refrigerant is then injected into the mid compression cycle of the scroll compressor and compressed to discharge pressure. This injected vapor also provides cooling at higher compression ratios, similar to liquid injection of standard ZF Scroll compressors.. 1

Figure 1 Circuit Diagram and Cycle for EVI (Upstream extraction shown here. See section 12 for details.) Definition(s) Tc Tli Tlo Pi Tsi Tvo Tvi Tsc M I T HX T SC Description Condensing temperature Liquid temperature entering H/X Subcooled liquid leaving H/X Intermediate Pressure Saturated temperature at intermediate pressure Vapor temperature leaving H/X Vapor temperature entering H/X Liquid subcooling in H/X Evaporator Mass Flow Vapor Injection Mass Flow Liquid temp out H/X-Liquid-Saturated temperature at intermediate pressure Liquid temp in to H/X-subcooled liquid temp out H/X The P-h diagram shows the theoretical gain in system performance achieved by using the economizer cycle. The extension outside of the vapor dome is what allows for the extra enthalpy increase in the evaporator, enhancing system performance. Although power increases due to the vapor injection into the compressor, there is still an efficiency gain given that the capacity gains exceed the power increase. 2

3. Nomenclature The EVI compressor has a model designation as follows, with the sixth digit shown as a "V": ZF18KVE-TFD. The model numbers include the nominal capacity without the economizer cycle for R-404A refrigerant at 60 Hz Low Temperature ARI rating conditions. 7. Power Requirements EVI compressors are only available for three phase power. 8. Application Envelope ZF**KVE Envelope (R-404A/R-507) Model Designation 1 Z = Compressor Family: Z = Scroll 2 F = Low Temperature 3 Nominal Capacity [BTU/h] @ 60 Hz and ARI low temperature conditions using multipliers K for 1000, without vapor injection 4 Vapor Injection for EVI Operation 5 POE Oil 6 Motor Version 7 Bill of Material Number The EVI rating curves have been developed to incorporate performance improvements while utilizing the economizer cycle. The capacity displayed is with maximum possible subcooling at the exit of the subcooling heat exchanger. Compressor performance information can be obtained by accessing the "Online Product Information" (OPI) database via emersonclimatecustomer.com. 4. ARI Low Temperature Ratings (-25 F/105 F) Model With EVI* Without EVI ZF13KVE 20100 Btu/hr 13000 Btu/hr ZF18KVE 29200 Btu/hr 18000 Btu/hr ZF24KVE 34200 Btu/hr 24000 Btu/hr ZF33KVE 47900 Btu/hr 33000 Btu/hr ZF40KVE 62500 Btu/hr 40000 Btu/hr ZF48KVE 72000 Btu/hr 48000 Btu/hr *Maximum possible subcooling. 5. Approved Refrigerants R404A and R507 are approved for use with the Scroll EVI compressors. 6. Approved Oils Polyol Ester (POE) lubricants are the only lubricants approved for the EVI compressor. For a complete list of approved POE lubricants, refer to Form 93-11 Copeland Accepted Refrigerants/Lubricants via emersonclimatecustomer.com. Figure 2 9. Control Requirements See Figure 3 for a detailed schematic for this system (shown for a single compressor application). The figure also shows the up-stream extraction method for tapping the liquid for the heat exchanger; see Section 12 for additional details. 10. Discharge Temperature Control A discharge temperature control is not required on all compressors. At this time, liquid injection is not approved for this application. Models ZF24KVE-TW*, ZF33KVE-TW*, ZF40KVE- TW*, ZF48KVE-TW* have an internal temperature sensor and no other discharge temperature control is required. For models ZF13KVE-TF*, ZF18KVE-TF* use one of the following two methods for discharge temperature control. 10.1 Thermistor A thermistor in the compressor control circuit is used to protect against high discharge temperatures and must be wired to the rack control systems. The cut out temperature is to be set at 280 F. The temperature resistance values for the sensor can be found in Appendix A. 3

The thermistor must conform to the curve characteristics outlined in Appendix A. The table expresses the ratio of the resistance at the indicated temperature and the resistance at 77 F (25 C). The resistance at 77 F (25 C) is 86Kohms nominal. The curve fit is Ratio = 0.8685e-0.257x, where x = resistance at the indicated temperature. NOTE: The system controller must open the contactor when the discharge line temperature exceeds 280 F Figure 3 10.2 Discharge Line Thermostat Another method of discharge temperature control is the use of a discharge line thermostat. It is required in the compressor control circuit. The thermostats have a cut out setting that will insure discharge line temperatures below the 260 F (127 C) maximum limit. (This value differs from the cut out value set on the thermistor because the temperature is measured closer to the discharge gas from the scroll when using the thermistor.) The discharge line thermostat should be installed approximately 7 (178mm) inches from the discharge tube outlet. If a service valve is installed at the discharge tube outlet, the thermostat should be located 5 (127mm) inches from the valve braze. For proper functioning, it is recommended the thermostat should be insulated to protect it from a direct air stream. Kits have been set up to include the TOD thermostat, retainer, and installation instructions. These thermostats must be used with ½" O.D. discharge lines to ensure proper thermal transfer and temperature control. They work with either 120 or 240 volt circuits, and are available with or without an alarm circuit capability. See Table 1 for a list of discharge line thermostat kit numbers. Kit Number Conduit Alarm Connector Contact Lead 998-7022-02 Yes No 998-0540-00 No No 998-0541-00 No Yes Table 1 Discharge Line Thermostat Kit Numbers 11. Thermostatic Expansion Valve (TXV) & Heat Exchanger In order to properly use an Enhanced Vapor Injection compressor a thermostatic expansion valve (TXV) and heat exchanger are needed in the system. Copeland provides a kit that has these components properly sized for the ZF13 and ZF18 single compressor applications, see Table 2. For multiple compressor applications, the subcooling components may be designed using the subcooling load and pressure and temperature data provided by the EVI calculator program. Model 24V 120V 240V Kits Include: ZF13 985-985- 985-1500-00 1500-01 1500-02 ZF18 985-985- 985-1500-00 1500-01 1500-02 TXV, ZF24 N/A N/A N/A Solenoid Valve, ZF33 N/A N/A N/A Current Sensing Relay, Heat Exchanger ZF40 N/A N/A N/A ZF48 N/A N/A N/A Table 2 12. System Configuration There are two methods of controlling refrigerant flow at the heat exchanger - downstream and upstream extraction. 12.1 Downstream Extraction The downstream extraction is the preferred method employed in the United States. In downstream extraction the TXV is placed between the liquid outlet and vapor inlet of the heat exchanger. The advantage of downstream extraction is that subcooling is ensured because the liquid is further subcooled as it flows through the heat exchanger. Therefore, more subcooled liquid enters the TXV which increases the 4

probability that the valve will not hunt. The disadvantage with this method is that it is not as efficient as the upstream method; however, the difference is too small for practical purposes. See Figure 4. VO = Vapor temperature leaving H/X VI = Vapor temperature entering H/X LI = Liquid temperature entering H/X LO = Subcooled liquid leaving H/X Figure 6 H/X Piping Arrangement Figure 4 Downstream Extraction 12.2 Upstream Extraction In upstream extraction the TXV is placed between the condenser and the heat exchanger. The TXV regulates the flow of subcooled refrigerant out of the condenser and into the heat exchanger. With this type of configuration there is a potential for flash gas which would cause the valve to hunt. See Figure 5. Figure 5 Upstream Extraction 12.3 Heat Exchanger Piping Arrangements Best subcooling effect is assured if counter flow of gas and liquid is provided as shown (see Figure 6). In order to guarantee optimum heat transfer, the plate heat exchanger should be mounted vertically and vapor should exit it at the top. 13. System Design Guidelines: NOTE: The following sections discuss system design guide lines for the EVI product. Please refer to the compressor Performance Calculator which can be found in the Online Product Information (OPI) database located in emersonclimatecustomer.com for further information needed to accommodate your sizing needs. 13.1 Heat Exchanger Sizing Heat exchangers should be sized so that they have adequate design margin for the entire range of system operation, but they should be optimized for normal operating conditions. The parameters used to determine the proper heat exchanger size are described below: SIT = Heat Exchanger saturated evaporating temperature at its outlet pressure. LIT = Liquid in Temp ~ Condensing Outlet LOT = Liquid Out Temp = SIT + TD VIT = Vapor In Temp ~ SIT + Loss VOT = Vapor Out Temp = SIT + Superheat H = Enthalpy Subcooling = LIT - LOT Superheat = VOT - SIT TD = LOT - SIT The key parameter in determining the proper heat exchanger is the Saturated Injection Temperature (SIT). It is imperative the following procedure be followed for optimized performance. The SIT has been derived experimentally and can be approximated by using Figure 7. After determining the SIT, a 10 F Condenser Subcooling, TD, and Superheat are targeted. This is done in order to optimize system performance while at the same time maintaining system reliability and functionality. Once these parameters have been established, the heat exchanger Btu/Hr capacity can be established, which gives the required heat exchanger size. 5

13.2 Line Sizing In single compressor applications, the vapor injection line from the heat exchanger to the compressor should be 3/8" - 1/2" and kept as short as possible in order to minimize pressure drop loss. The liquid line from the heat exchanger to the evaporator should be insulated and kept as short as possible in order to maximize the subcooling at the evaporator. If a vapor injection header is used, the header diameter should be such that the cross-sectional area is equal to the sum of the cross-sectional areas of the individual cross-sectional lines to the compressor. Figure 7 Example of Heat Exchanger Sizing Optimized ZF18KVE 404A Step 1 Know Conditions -25/105/0/65 T e /T c / Cond SC / Suct RG Step 2 Determine Flow M e From Product Data 355 lb/hr Step 3 Estimate SIT From Guideline 12 Step 4 Use the 10 Guidelines To Derive LIT LOT = T - 10 = SIT + 10 95 22 HX SC =LIT - LOT 73 =(T - SIT-20 ) HX Btu/hr =M x (H ft - H lot ) =355 x (47.0-20.1) 9550 Example of Heat Exchanger Sizing Fixed Liquid Temperature ZF18KVE 404A Step 1 Know Conditions -25/105/0/65 T e /T c / Cond SC / Suct RG Step 2 Determine Flow M From Product Data 355 lb/hr Step 3 Use the 10 Guideline LIT LOT = T - 10 user defined 95 50 HX SC =LIT - LOT 45 HX [Btu/hr] =M x (H ft - H lot ) =355 x (47.0-29.7) 6140 For multiple compressor applications the same process can be used to determine the heat exchanger size needed by adding together the individual heat exchanger capacities for each compressor. For example, for four compressors, each with a 3/8" vapor injection line, the header tube diameter should be a 7/8" tube. In addition, the individual injection lines to the compressors should tap into the header either on top or on the sides of the header tube; a bottom tap will increase the risk of returning liquid into the compressor through the vapor injection line. 13.3 Heat Exchanger TXV Sizing TXV's should be sized so that they have adequate design margin for the entire range of system operation, but they should be optimized for normal operating conditions. Select a TXV that is able to handle the Btu/hr capacity of the heat exchanger determined in the section above. 13.4 Solenoid Valve & Ball Valve A solenoid valve is required to stop the flow of vapor from the system to the compressor when the compressor is in the off cycle. This must be a vapor solenoid sized equivalent to or larger than the vapor injection tube size. For minimum orifice sizes see Table 3. For service purposes, a mechanical ball valve (not provided by Copeland) is also recommended in the vapor injection line. Model Minimum Orifice Size Table 3 Flow Control Valve Series ZF13 3/16" 200RB 3 ZF18 3/16" 200RB 3 ZF24 1/4" 200RB 4 ZF33 1/4" 200RB 4 ZF40 5/16" 200RB 5 ZF48 5/16" 200RB 5 6

13.5 Current Sensing Relay To prevent the solenoid from remaining open during a "motor protector trip" a current sensing relay must be provided that senses whenever the compressor is "off" and closes the solenoid to stop injection. See Table 2 for a kit with the correct current sensing relay. 13.6 Multiple Compressor Applications EVI can also be used in multiple compressor applications. Unlike a standard compressor system, the EVI compressor system changes its delivered capacity by changing the amount of sub-cooling provided at the sub-cooling heat exchanger. The result is that in high ambient temperature conditions (summer operation) and in low ambient temperature conditions (winter operation), the same number of compressors tend to run. It is important to note this since most personnel are used to seeing fewer compressors in operation in the cooler winter months compared to the hotter summer months; with EVI, almost the same number of compressors will be running in the summer and winter. Figure 8 EVI Paralleling with HX Thermostatic valves of different capacity Multiple EVI compressors can be used with either a single heat exchanger for each compressor or a common heat exchanger for all compressors. In case of a common heat exchanger, a solenoid valve should be installed on each individual vapor injection line. Special care has to be given to the design of the heat exchanger and of the thermostatic expansion valve (TXV) to allow for part load operation. Good refrigerant distribution is required in the common heat exchanger as well as sufficient velocities for oil return, even at part load. In the case of a large range of capacity modulation (more than 2 compressors in parallel), the use of an Electronic Expansion Valve (EXV) or of two different TXV(s) controlled by individual solenoid valves, may improve performance. For example, one at 100% full load and the second solenoid valve for 30% of full load. (See Figure 8 and Figure 9). It is necessary to ensure that the solenoid valves, vapor injection lines and header(s) are adequately sized in order to keep pressure drop to a minimum. At the same time, the layout should be such that excessive amounts of oil do not accumulate in the header. Figure 9 EVI Paralleling with HX Electronic Expansion valve (EXV) 14. Controlling Liquid Out Temperature (LOT) The LOT will typically be determined by the operating condition of the compressor. If the LOT needs to be fixed at any specific value (for example, 50 F) for purposes of good system control, an Evaporator Pressure Regulator (EPR) valve may be introduced at the vapor outlet of the subcooling heat exchanger. Table 4 shows approximate EPR settings for different liquid temperature. Subcooler Liquid Out Temperature, F R404A Approximate EPR Setting, psig (psia) 60 124.4 (139.0) 50 103.8 (118.4) 40 85.6 (100.2) Table 4 7

The performance calculator program can be used to determine the effect of fixing LOT on the capacity and efficiency of the compressor. See Figures 10 & 11 below. Figure 10. Screen shot of the Calculator program, showing the maximum sub-cooling obtained when the default "Auto" is selected for Economizer sub-cool. Figure 11. Screen shot of the Calculator program, showing the constant liquid temperature at outlet of the subcooling heat exchanger. 8

Appendix A Temp Ratio Temp Ratio Temp Ratio Temp Ratio Temp Ratio -40 C 33.60000 7 C 2.30130 8 C 2.19180 99 C 0.07000 145 C 0.02090-39 C 31.44900 8 C 2.19180 9 C 2.08830 100 C 0.06800 146 C 0.02039-38 C 29.45200 9 C 2.08830 10 C 1.99030 101 C 0.06612 147 C 0.01990-37 C 27.59700 10 C 1.99030 11 C 1.89720 102 C 0.06430 148 C 0.01942-36 C 25.87300 11 C 1.89720 12 C 1.80900 103 C 0.06255 149 C 0.01895-35 C 24.27000 12 C 1.80900 13 C 1.72550 104 C 0.06085 150 C 0.01850-34 C 22.76100 13 C 1.72550 14 C 1.64640 105 C 0.05920 151 C 0.01801-33 C 21.35700 14 C 1.64640 15 C 1.57140 106 C 0.05760 152 C 0.01754-32 C 20.05100 15 C 1.57140 16 C 1.50000 107 C 0.05605 153 C 0.01708-31 C 18.83400 16 C 1.50000 17 C 1.43230 108 C 0.05456 154 C 0.01663-30 C 17.70000 17 C 1.43230 18 C 1.36810 109 C 0.05310 155 C 0.01620-29 C 16.63420 18 C 1.36810 19 C 1.30710 110 C 0.05170 156 C 0.01584-28 C 15.64040 19 C 1.30710 20 C 1.24930 111 C 0.05027 157 C 0.01549-27 C 14.71340 20 C 1.24930 21 C 1.19420 112 C 0.04889 158 C 0.01515-26 C 13.84820 21 C 1.19420 22 C 1.14180 113 C O.04755 159 C 0.01482-25 C 13.04020 22 C 1.14180 23 C 1.09210 114 C 0.04625 160 C 0.01450-24 C 12.28070 23 C 1.09210 24 C 1.04490 115 C O.04500 161 C 0.01418-23 C 11.57100 24 C 1.04490 25 C 1.00000 116 C 0.04372 162 C 0.01388-22 C 10.90750 25 C 1.00000 26 C 0.95710 117 C 0.04248 163 C 0.01358-21 C 10.28680 26 C 0.95710 27 C 0.91640 118 C 0.04128 164 C 0.01328-20 C 9.70600 27 C 0.91640 28 C 0.87760 119 C 0.04012 165 C 0.01300-19 C 9.15880 28 C 0.87760 29 C 0.84070 120 C O.03900 166 C 0.01275-18 C 8.64630 29 C 0.84070 30 C 0.80560 121 C O.03793 167 C 0.01250-17 C 8.16620 30 C 0.80560 31 C 0.77200 122 C 0.03690 168 C 0.01226-16 C 7.71620 31 C 0.77200 32 C 0.74010 123 C 0.03590 169 C 0.01203-15 C 8.29400 32 C 0.74010 33 C 0.70960 124 C 0.03494 170 C 0.01180-14 C 6.89570 33 C 0.70960 34 C 0.68060 125 C 0.03400 171 C 0.01157-13 C 6.52190 34 C 0.68060 35 C 0.65300 126 C 0.03315 172 C 0.01134-12 C 6.17110 35 C 0.65300 36 C 0.62660 127 C 0.03233 173 C 0.01112-11 C 5.84150 36 C 0.62660 37 C 0.60140 128 C 0.03153 174 C 0.01091-10 C 5.53190 37 C 0.60140 38 C 0.57740 129 C 0.03075 175 C 0.01700-9 C 5.23920 38 C 0.57740 39 C 0.55460 130 C 0.03000 176 C 0.01049-8 C 4.96400 39 C 0.55460 40 C 0.53270 131 C 0.02926 177 C 0.01029-7 C 4.70520 40 C 0.53270 41 C 0.51170 132 C 0.02854 178 C 0.10090-6 C 4.46170 41 C 0.51170 42 C 0.49180 133 C 0.02784 179 C 0.00989-5 C 4.23240 42 C 0.49180 43 C 0.47270 134 C 0.02716 180 C 0.00970-4 C 4.01530 43 C 0.47270 44 C 0.45440 135 C 0.02650 181 C 0.00949-3 C 3.81090 44 C 0.45440 45 C 0.43700 136 C 0.02586 182 C 0.00928-2 C 3.61820 45 C 0.43700 46 C 0.42030 137 C 0.02525 183 C 0.00908-1 C 3.43670 46 C 0.42030 47 C 0.40420 138 C 0.02465 184 C 0.00889 0 C 3.26540 47 C 0.40420 48 C 0.38890 139 C 0.02407 185 C 0.00870 1 C 3.10300 48 C 0.38890 49 C 0.37430 140 C 0.02350 186 C 0.00853 2 C 2.94980 49 C 0.37430 95 C 0.07870 141 C 0.02295 187 C 0.00837 3 C 2.80520 5 C 2.53960 96 C 0.07641 142 C 0.02242 188 C 0.00821 4 C 2.66860 6 C 2.41710 97 C 0.07420 143 C 0.02190 189 C 0.00805 5 C 2.53960 7 C 2.30130 98 C 0.07206 144 C 0.02139 190 C 0.00790 6 C 2.41710