Instructions for the heat exchanger control system SILVER C RX, RECOnomic, sizes 100/120, RECOsorptic, sizes

Similar documents
Instructions for the fan motor control system, SILVER C

Instructions for the fan motor control system with integrated wiring terminals SILVER C

Instructions OJ EC-Controller (Translation of the original) BA-ESR_OJ-EC /2013

Built-on speed controller for GMPM plug fan with permanent magnet motor

Instructions for the hand-held micro terminal of the fan motor control system, TBLZ-2-75 SILVER C

RE-PR3-E-27 3-Phase Panel Mount 27kW

TopMaster Air Handling unit. Installation instructions

SMART EVO 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS

USER GUIDE. DRENA 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS - WASTE WATER -

SERIES VAC Microprocessor-Based Intermittent Pilot Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION

SERIES VAC Microprocessor-Based Hot Surface Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION AGENCY CERTIFICATIONS

Installation and Wiring Instructions

CRU 200 and 500 Series Condensate Recovery Unit Installation and Maintenance Instructions

DOL 31 Speed Controller Technical User Guide

Instructions for the BASIC BCRW Fan, Sizes General

GM420. Digital Ground Continuity Relay For AC Systems. Technical Bulletin NAE /

SERIES VAC Microprocessor-Based Direct Spark Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION. Export Information (USA)

Operating instructions Safety-monitoring module SRB 302X3. 1. About this document. Content

AHW AHW(S) Hot water circulator pump INSTALLATION AND OPERATING INSTRUCTIONS HIGH-EFFICIENCY BLDC-MOTOR CIRCULATORS

Products documentation (REVISION DATE: 03/10/2011) OMFP6010 (60cm PIROLITIC OVEN)

QAF63.2-J QAF63.6-J. Frost detectors. for use on the air side

EBC20. Instructions for fitting, installation and operation. Read and save these instructions!

Cat. N. Cat. N (s) 1. DESCRIPTION - USE 3. OVERALL DIMENSIONS. Technology : 4. PREPARATION - CONNECTION 2. PRODUCT RANGE

REA 105 Arc Protection Module. Operator s Manual

FLÄkT WOOdS BuILT-ON FrEQuENCY CONVErTEr CENTRIFLOW 3D PLUG FAN WITH PERMANENT MAGNET AND ASYNCHRONOUS MOTOR

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL

BHW INSTALLATION, OPERATION AND MAINTENANCE MANUAL MEDIUM STATIC PRESSURE DUCTABLE TYPE. Models:

V80-H Multistage Pump Instruction Manual

VADA - V80-H PRODUCT OVERVIEW CONSTRUCTION USAGE LIMITATIONS MOTOR WARRANTY

1592P01. for liquids in piping DN

CarSense 303 O P E R A T I N G I N S T R U C T I O N S M A G N E T O R E S I T I V E V E H I C L E D E T E C T O R

MC 31 Speed Controller Technical User Guide Code no GB

Installation and Operating Manual

F17W44_MFB_F_EN INSTALLATION INSTRUCTIONS

INSTALLATION FB T: +44 (0) F: +44 (0) E: W:

Rectifier RC-series. Manual RC-series English MA doc. Manual Wall and 19 English

Lodam Compressor Protection Module. Technical manual. Version 3.0 SE-G1

RS Pro Infrared Temperature Sensor

Universal Dimmer N 528D01, 2 x 300VA, AC 230 V 5WG DB01

SERIES VAC Microprocessor-Based Direct Spark Ignition Control with Inducer Blower Relay FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION

5KW ELECTRIC FAN HEATER

PHOTOVOLTAIC HEAT CONTROLER PVHC 2.01 USER MANUAL

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas

rev3 INSTALLATION & OPERATION MANUAL OIL CIRCULATING HEATING SYSTEM MODEL OSM

TQ Series. Electronic Control Pump Instruction Manual. 50Hz. ISO 9001 Certified Walrus Pump Co., Ltd.

IH 025 VOLCANO. Portable Induction Heater. smart mounting

INSTRUCTIONS. OJ-DV-Relay-Module. OJ Drives A DRIVES PROGRAMME DEDICATED TO VENTILATION SOLUTIONS. Optional module for OJ-DV motor controller

QAF63.2 QAF63.6. Frost sensors for use on the air side. Building Technologies HVAC Products

CPS-1 USER S MANUAL AIR INLET / CURTAIN CONTROL

1 Declaration of conformity

LGA... Gas Burner Controls. Siemens Building Technologies HVAC Products

ISIS SAFETY SYSTEM Installation guide

CarSense 303 O P E R A T I N G I N S T R U C T I O N S M A G N E T O R E S I T I V E V E H I C L E D E T E C T O R

Freightliner Refrigerator Troubleshooting Guide For (TJ18F) (TJ22F) (TJ18FP3)

MR4PMUHV Electronic. Temperature/Defrost Control with Relay Pack

Servicing manual. 600 Series - 11S / 19S / 24S / 24C. Wall-mounted condensing gas boiler. For trade use

DRYTEK 1 - User Manual ELECTRICAL PANEL FOR 1 MOTOR WITH POWER FACTOR CONTROL

COMPASS HIGH-EFFICIENCY WET-ROTOR CIRCULATORS

Operating instructions Safety-monitoring module SRB 302X3. 1 About this document

Servicing manual. Wall-mounted condensing gas boiler 600 Series - 11S / 19S / 24S / 24C /2002 GB(EN) For trade use

DIESEL ENGINE CONTROL UNIT DCU USER S MANUAL - N-2000 Lillestrøm, Norway Tel: (+47) Fax: (+47)

MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT

PLENUM FAN EQLK PLENUM FAN, DIRECT-DRIVEN

Installer manual AG-AA10. Air/air heat pump IHB GB AG-AA10-30 AG-AA10-40/50

Snifter ATEX22 VERSION. User Manual. Distributor

Sentry LIQUID LEVEL CONTROLLER MODEL 120 OPERATING MANUAL.

GRUNDFOS INSTRUCTIONS LCD 108. Installation and operating instructions

15KW ELECTRIC FAN HEATER

QAF64.2-J QAF64.6-J. Frost detector. for use on the air side

Installation instructions for the optical detector with built-in control unit, TBLZ-1-72-a GOLD/COMPACT

SET Installation and Operating Instructions. Level switch for one sensor

MST-1. Varifan USER S MANUAL MST-1 ADJUST. 9 per day HI F2. DIFF on off TIMER. reduc.

PD154 & PD158 VIGILANTE II ANNUNCIATORS Instruction Manual

Technical manual NIBE AG-AA10 Single split air to air heat pump

Installation Instructions CS3 Three Phase Solid State Relay

ACS-30-EU-EMDR- 10-MOD

CRU-S Series Stainless Steel Condensate Recovery Unit

CAUTION - READ THESE INSTRUCTIONS BEFORE USING THE MACHINE

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual

CU 300 GRUNDFOS INSTRUCTIONS. Installation and operating instructions

ECS-2M USER S MANUAL ENVIRONMENT CONTROL SYSTEM

Operating Manual MS220KA and MSR220KA

GB-DAS. Installation and user manual DEVIreg 850 controller

LABORATORY OVENS MODELS INCLUDE: TO-152G & TOH-152G TO-152F & TO-235F DEHYDRATING OVENS MODELS INCLUDE: TD-150F TD-330F TD-500F

INSTALLATION & OPERATION MANUAL

INSTRUCTION MANUAL (English version) Water still

FIL-SPL Flow-through heater for central heating USER MANUAL

Part 3 Troubleshooting

Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual

HEATFAST HF9101-V1 AMBIENT SENSING TRACE HEATING THERMOSTAT

Revision: None DCN No. First Issue Date: November 30, 1998 Product: Standard DCT, 120-volts

Forced draught gas burner

LINEAR HEAT DETECTION CABLE DURÁN-SAFE

D-TEK -MS Vehicle Loop Detector. Operating Instructions

LC3000 Level Controller Installation and Maintenance Instructions

Max HT Air Heater FOR SAFETY & LONG HEATER LIFE, CAREFULLY READ THIS MANUAL BEFORE USE.

USER S MANUAL BUCKET FAN SERIES BUCKET FAN WHISPER SERIES

S F IT 6" / 8"HES. Quick Installation Guide. franklinwater.eu

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS

Operator: Save these instructions for future use!

Transcription:

Instructions for the heat exchanger control system SILVER C RX, RECOnomic, sizes 100/120, RECOsorptic, sizes 50-120 1 General The heat exchanger control system is a control system for 380 W step motors It is designed for precise and quiet control of rotary heat exchangers in the SILVER C RX ventilation units with standard rotor (RECOnomic) in size 100/120, and with sorption rotor (RECOsorptic) in sizes 05-120 Integrated functions: 0-10 V DC analogue input for controlling the speed Alarm for overloading, over-voltage and under-voltage Protective motor switch with integrated current limiting function Short-circuit protected inputs and outputs Digital input for start/stop Digital input for alarm resetting Integrated EMC filter The electrician is accountable for ensuring correct earthing as well as protection according to local standards and regulations An earth fault circuit breaker, multiple protective earthing or ordinary earthing can be used as extra protection, provided that the local regulations are complied with The earth leakage currents exceed 35 ma Therefore a fixed, permanent installation and heavy-duty protective earthing are required NOTE! If an earth fault occurs, there can be a direct current component in the leakage current Earth fault circuit breakers should therefore be designed to be able to detect this and be installed according to applicable national and international regulations, where they are used In the size 50-80 SILVER C units the heat exchanger control system is located inside the filter section in the lower level In the size 100/120 SILVER C units the heat exchanger control system is located inside the fan or filter section to the left of the centre section in the lower level (viewed from the inspection side) For access, open the inspection door Forbidden to start operation It is absolutely forbidden to start operation until the entire air handling unit, where the above-mentioned heat exchanger control system is integrated, has been declared to conform to relevant regulations in Machinery Directive 98/37/EEC and to existing national legislation, if applicable The heat exchanger control system must not be energized until the entire installation conforms to the provisions in ALL relevant EU Directives If the heat exchanger control system has been damaged, for instance during transport, it must be inspected and repaired by qualified personnel before the voltage is connected Safety functions The heat exchanger control system is protected against phase-to-phase shortcircuiting, and has integrated current limiting function for protection of the motor We reserve the right to alter specifications wwwswegoncom 1

2 Technical data Power supply Rated motor shaft power: Motor current cons (max load) Maximum fuse protection 50-60 Hz, 1x230 V AC -10%/+15 % 038 kw 45 A 10 A Ambient air temp, operation -40/+40 C Ambient air temperature, storage -40/+70 C Enclosure class Control voltage Weight IP54 0-10 V DC 49 kg 3 Function General The motor control system advantageously replaces the traditional solution with gear motor The step motor has uniform torque across the entire rpm range, in contrast to gear motors that lose torque at low and high speeds of rotation respectively The step motor's constant torque curve provides an essentially greater operating range where the speed of rotation can be controlled with precision It is therefore possible to control the heat recovery in an energy-optimum manner and achieve a more accurate temperature The heat exchanger control system is controlled with 0 10 V signals The step motor is controlled in micro steps with sinusoidal constant current for ensuring motor shaft rotation with uniform torque throughout the revolution This prevents torque pulses and at the same time provides quieter operation Rotation monitor The rotation monitor consists of an inductive sensor When the rotation monitor is mounted correctly, the sensor's LED flashes yellow each time the detection surface passes the rotation monitor Fig 1 Dimensions Operation LED indications The junction box has 2 integrated LEDs located under the cover They are therefore not visible when the cover is mounted The green LED is constantly lit when voltage is supplied The red LED is lit if at least one active alarm has been initiated Warning The chassis on the heat exchanger control system can become very warm! Warning! Do not repair the heat exchanger control system at the site Never attempt to repair a defective control system unit Contact the supplier to obtain a replacement unit 2 wwwswegoncom We reserve the right to alter specifications

Control with 0 10 V DC The heat exchanger control system can be controlled via external input signals The heat exchanger control system needs a start/stop signal in order to start The start/stop signal is transmitted by short-circuiting Terminals 7 (Start/ stop) and 8 ( ) (See Fig 2) The heat exchanger control system regulates the speed linearly between 0 % and 100 %, however it is limited to the regulation range between the preset lowest and highest speeds (See Fig 3) 100 % speed is defined as an input voltage of "0-10 V in" (Terminal 13) at 95 V (100 % at 95 V, +/-2 %) Compensation for non-linear heat transfer The 0 10 V signal is compensated internally in the heat exchanger control system with a contrary rotor characteristic to provide far more linear heat transfer than comparable systems and better regulation (See Fig 4) Fig 2 Junction box, overview of the wiring terminals, The function selector switch positions (Factory preset): 4 = Sizes 100/120, standard rotor 5 = Sizes 50/60, sorption rotor 6 = Sizes 70/80, sorption rotor 7 = Sizes 100/120, sorption rotor To reverse the direction of rotation The direction of motor rotation is reversible so that the rotor always has the correct direction of rotation in relation to the purging sector Fig 3 The ratio between the speed and the min/max speed setting To reverse the motor's direction of rotation, transpose two optional conductors to Motor Terminal V - U - W (See Fig 6) Automatic restart after alarm The heat exchanger control system automatically attempts to start again following an alarm, such as over or undervoltage alarm This automatic restart is carried out maximally 3 times (rotation monitor alarm: 1 restart) After that, the heat exchanger control system will remain in the error mode, and must be restarted by resetting the alarm Alarm resetting: See Section on "Alarm resetting" Alarm relay/output The heat exchanger control system is equipped with an alarm output in the form of an alarm relay The alarm relay is activated if an alarm arises in the heat exchanger control system or if alarms are discovered in motors or fans Connect the alarm signal cable leads to Terminals 16 (C) and 17 (normally closed) The relay contact is closed in deenergized condition and if there are active alarms Fig 4 Compensation for non-linear heat transfer Alarm reset The heat exchanger control system is equipped with a digital input for resetting alarms The alarm input is reset by short-circuiting Terminals 11 (Alarm reset) and 12 ( ) (See Fig 2) The alarm output can also be reset by switching off the supply voltage to the heat exchanger control system for more than 60 seconds We reserve the right to alter specifications wwwswegoncom 3

4 Electrical connections The heat exchanger control system has a junction box installed in the lower part of the heat exchanger section For access, open the inspection cover in front of the heat exchanger To connect control signal wiring Insert the control cables into the junction box through the cable grommets fitted with rubber gaskets Clip an appropriately large hole in the gaskets to enable the gasket to seal tightly around the cable Only by doing so can the stated Enclosure class IP54 be complied with Connect the 0 10 V DC control signal from an external regulator in the junction box to Terminals 13 (0-10 V in) and 14 (See Fig 5) The heat exchanger control system regulates the speed in a capacity linear manner between 0 % and 100 % (100 % at 95 V +/- 2 %), however according to the preset times for up ramp and down ramp, and limited to the regulation range between the preset lowest and highest speeds (See Fig 3 and 4) The Control with 0-10 V DC function is described in Section 3 Function Connect the start/stop signal cable leads in the junction box to Terminals 7 (Start/stop) and 8 ( ) (See Fig 5) This should be a potential-free digital contact The Start-/stop function is described in Section 3 Function Connect the Alarm Reset signal cable leads to the heat exchanger control system's junction box to Terminals 11 (Alarm reset) and 12 ( ) (See Fig 5) This should be a potential-free digital contact The "Alarm Reset" function is described in Section 3 Function The heat exchanger control system is equipped with an alarm relay output with normally-open contact function in the event of a malfunction or alarm The alarm signal cable is marked "Alarm relay", and should be connected in the junction box to Terminals 16 (C) and 17 ( ) (See Fig 5) This should be a potential-free digital contact The "Alarm Relay" function is described in Section 3 Function Connect the sensor cable of the rotation monitor to Terminals 9 (digital in), 10 ( ) and 15 (+10 V out, power supply to sensor), Black Blue Brown Fig 5 Junction box, overview of the wiring terminals 4 wwwswegoncom We reserve the right to alter specifications

Electric Power Connections In the size 50-80 SILVER C units the heat exchanger control system is located inside the filter section in the lower level In the size 100/120 SILVER C units the heat exchanger control system is located inside the fan or filter section to the left of the centre section in the lower level (viewed from the inspection side) For access, open the inspection door For appropriate connection, see Fig 6 For electrical data, see Section 2 To change the rotor's direction of rotation, transpose two optional conductors to Motor Terminal V - U - W Fig 6 To connect power supply wiring to the heat exchanger control system We reserve the right to alter specifications wwwswegoncom 5

5 Trouble shooting To open the heat exchanger control system Before you open the heat exchanger control system, isolate the line voltage and wait at least 2 minutes Failure to do so will expose you to the risk of coming into contact with harmful residual voltage inside the unit Troubleshooting when the heat exchanger control system is controlled with external (A/D) signals: Symptoms Cause Action Check whether there is voltage on the heat exchanger control system's L and N terminals on the models for 230 V There is no power supply (Operating voltage is specified on the rating plate, affixed to the side of the heat exchanger control system) Poor electrical connections Check the connectors and other electrical connections There is no in-operation signal Short-circuit Terminals 7 and 8 in the heat exchanger control system junction box marked (GND) and Start/Stop (Fig 5) The motor is not rotating There is no 0 10 V DC control signal The motor has been stopped by the internal protective motor switch 3 times due to overloading or some other alarm Defective heat exchanger control system Defective motor Check that the 0-10 V DC control signal is correctly connected to Terminals 13 and 14 in the heat exchanger control system junction box marked (GND) and 0-10 V in (Fig 5) Reset the alarm by short-circuiting Terminals 11 and 12 in the heat exchanger control system junction box marked (GND) and Alarm reset (Fig 5) You can also reset the alarm by switching off the supply voltage to the heat exchanger control system and switching it back on after 60 seconds Replace the heat exchanger control system Replace the motor The heat exchanger control system switches off ) Remember to reset the alarm by short-circuiting Terminals (GND) and "Alarm Reset" At least two phases are short-circuited on the motor wiring terminals Eliminate the short-circuit on the motor wiring terminals ) Defective motor Replace the motor ) Overloaded motor Remedy the overload condition of the motor ) Defective motor Replace the motor ) Overloaded motor Remedy the overload condition of the motor ) 6 wwwswegoncom We reserve the right to alter specifications

6 Service and maintenance No particular maintenance is required Contact Swegon if any problem arises To troubleshoot the unit: See Section 5 Troubleshooting 7 Alarm The integrated alarm relay in the junction box has normally-closed contacts and is marked "Alarm Relay" The alarm relay contacts are closed in deenergized condition and open in faultless condition The alarm relay contacts close in the event of an alarm The heat exchanger control system stops and an alarm indicating LED is lit If the fault ceases to exist, the alarm is reset automatically and the heat exchanger control system starts up 8 Environment and waste disposal Help to protect the environment by ensuring correct disposal of the packaging and use the products in accordance with applicable environmental regulations Disposal of the product Products with this mark must not be disposed as ordinary household refuse They must be collected in separate containers according to applicable local rules 9 Applicable standards GB-61800-2 Electric motor operation with variable speed, General Requirements EN-61800-3 General electromagnetic compatibility 10 CE marking Swegon AB certifies under its own sole responsibility that this product conforms to the Commission's Directive 92/31 with subsequent modifications concerning electric compatibility as well as the Commission's Directive 73/23 dealing with electric material for use within certain voltage limitations APPROVALS EMC EN 61800-3 LVD EN 61800-2 PRODUCT STANDARD THE ROHS DIRECTIVE PRODUCT APPROVALS EN 61800 PART 2 & 3 YES CE We reserve the right to alter specifications wwwswegoncom 7

8 wwwswegoncom We reserve the right to alter specifications