Sensor Interface Module Installation/Operation Instructions

Similar documents
THERMAL BUILDING SOLUTIONS EN-TraceTekTTSIM1A-IM-H /16

TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS

TTSIM-1A. TraceTek Sensor Interface Module with Relay. Installation/Operation Instructions. Installation Items (not supplied) Tools Required.

TTSIM-1 Sensor Interface Module

DESCRIPTION. 42 mm. 125 mm

TOUCH 1500 User Interface Terminal for Raychem NGC Systems Installation Instructions

NGC-UIT2-ORD-R Remote User Interface Terminal for Raychem NGC Systems Installation Instructions

TraceTek Sensing Module Installation, Operation and Maintenance Instructions DESCRIPTION SPECIFICATIONS APPROVALS TYPE NM

NGC-UIT-ORD User interface terminal for Raychem NGC systems Installation Instructions

Modular Sensing Cable Installation Instructions

910 Series Single-point heat-tracing control system

fuel leak detection find leaks before they find you

Industrial Strength Leak Detection

Dual-point heat-tracing control system

HTC-915-CONT. Heat-Trace Control system

JB-RTD-STAND RTD PIPE STAND FOR COMBINATION POWER CONNECTION BOX AND ELECTRONIC CONTROLLER INSTALLATION INSTRUCTIONS

JBS-100-EC Electronic controller replacement kit for JBS-100-ECP-A and JBS-100-ECW-A Installation Instructions

NGC-40-IO Control and monitoring modules for use with the Raychem NGC-40 system Installation Instructions

TT3000 and TT5000 Series

PRODUCT SELECTION GUIDE FOR WATER SENSING SYSTEMS

HWT-P HWAT POWER CONNECTION KIT WITH END SEAL INSTALLATION INSTRUCTIONS

AquiTron. AT-LDM Liquid Detection Module INSTALLATION INSTRUCTIONS

CSI Master Format 2004 Guide Specification for: Freezer Frost Heave Prevention (Mineral Insulated)

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3

CSI Master Format 2004 Guide Specification for: Flow Maintenance of Above Ground Greasy Waste Disposal Lines

CSI Master Format 2004 Guide Specification for: Snow Melting (Mineral Insulated)

FreezGard. Self-regulating crankcase heater. Product Overview

C SINGLE-POINT HEAT-TRACING CONTROL SYSTEM. product overview

JBS-100-ECP-A COMBINATION POWER CONNECTION BOX AND DIGITAL ELECTRONIC CONTROLLER INSTALLATION INSTRUCTIONS

NGC-40 Advanced Heat-Tracing Control System

THERMAL MANAGEMENT SOLUTIONS

CSI Master Format 2004 Guide Specification for: Flow Maintenance of Aboveground Fuel Oil Lines

HHS-WWH HOPPER HEATING SYSTEM WRAP-WOUND HEATER INSTALLATION INSTRUCTIONS DESCRIPTION. HHS-WWH PRODUCT SPECIfICATIONS

Sentry LIQUID LEVEL ALARM MODEL 100 OPERATING MANUAL.

Power Supply Display Module PSDM. Installation and Operation Manual

TraceTek Sensing Cable for Underground Leak Detection Installation Instructions. Description. Heat shrink tubing segments. Optional Materials

TT3000 and TT5000 Series

DL424/425 DirectLine Sensor Module for Dissolved Oxygen Probes Series DL5000 Specifications

C SINGLE-POINT HEAT-TRACING CONTROL SYSTEM PRODUCT OVERVIEW

SM3000 Videographic Recorder. User Guide. Modbus (RTU) Communications Option

THERMAL MANAGEMENT SOLUTIONS

ALARM OUTPUT MODULE. Product #7736

RAYCHEM NGC-30 COMPONENTS

aquilar - leak detection solutions

aquilar - leak detection solutions

Supervisor Standard Edition

NGC-UIT2 MODBUS PROTOCOL INTERFACE MAPPING FOR NGC-30 SYSTEMS. Firmware versions up to V2.0.X

water leak detection

CSI Master Format 2012 Guide Specification for: Hot Water Temperature Maintenance (HWAT) Systems

SLATE. Sub-Base Module INSTALLATION INSTRUCTIONS R8001S9001

TraceTek Sensing Cable for Aboveground Leak Detection Installation Instructions

INSTALLATION INSTRUCTIONS

TT3000 and TT5000 Series

1SC-SSC Splice Connection Kit Installation Instructions

PANEL MOUNTED ELECTRONIC MULTI-CIRCUIT HEAT-TRACING CONTROL, MONITORING AND POWER DISTRIBUTION SYSTEM mm. 100 mm

ECW-GF, ECW-GF-DP DIGITAL ELECTRONIC CONTROLLERS AND REMOTE DISPLAY PANEL PRODUCT OVERVIEW

FTC-HST WARNING: CAUTION:

Solid Core and Split Core 0-5, 0-10 Vdc Output Current Sensors CTS-05,10; CTP-05,-10

WD-CS. Water leak detection cable. Technical Overview. Features. Page 1. Data Sheet Ref: Issue: 5.1.

INSTALLATION INSTRUCTIONS

Sensepoint XCL Fixed Gas Detector

For Raychem ACS-30 Controls Systems

Longline Heating. Contents. Introduction

TT7000-HUV TraceTek Sensing Cable for Strong Mineral Acids

sulfur transport pipelines Safe, Reliable and Cost-Effective Heat Management System

Greentrol Automation, Inc.

Product Bulletin. VeriSafe Absence of Voltage Tester. The Safe Way to Verify the Absence of Voltage.

Easy to use, initiate test with the push of a button No additional tools required Provides visual alert to abnormal power conditions

Mark 25 Ultrapure Water Conductivity Analyzer

HALOGUARD TM IR MONITOR (OPTIONAL) FOUR or EIGHT POINT SCANNER INSTRUCTION MANUAL

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3 PRODUCT OVERVIEW

Designed for testing three-phase circuits up to 600V Install on line or load side of electrical disconnect Detects absence of AC and DC voltage

Product Bulletin. VeriSafe Absence of Voltage Tester. The Safe Way to Verify the Absence of Voltage.

DL423 DirectLine Sensor Module for Conductivity Measurement Specifications

ACS-30 MULTIPOINT COMMERCIAL HEAT-TRACING SYSTEM PRODUCT OVERVIEW. ACS-30 System

Industrial Strength Leak Detection

Solid Core and Split Core 4-20 ma Output Current Sensors CTS-20; CTP-20

C910 Series. Single-point heat-tracing control system

Nitrogen Dioxide (NO2) Single-Point Gas Detection System

Factory and Field Installed Splices

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

SLATE. Base Module INSTALLATION INSTRUCTIONS R8001A1001

RC-2000 Thermostat Installation Instructions

MEGA. cal electronic gas alarm. Installation, Operation, and Maintenance Instructions. Part No Rev. D Pg.

4 Channel Contact Closure SFP DIN Fiber Link System

TT5000-HS (for fuel leaks) TT5001-HS (for solvent leaks) TraceTek Sensing Cable for Underground Leak Detection

Duct and Rough Service Carbon Monoxide Sensor

Operating Instructions. For. Alarm Control Module. Model SSR 500

User's Manual: Series 260A Model 260A Process Current Loop-Powered Alarm

Rosemount 3490 Series 4 20 ma + HART Compatible Controller

ISOMETER IR425. Insulation monitoring device for unearthed AC/DC control circuits (IT systems)

Fuel Leak Detection Find Leaks Before They Find You

Pioneer-R16 Gas Monitor Operator s Manual

SSV-DC user manual. Phason

Product Bulletin. VeriSafe Absence of Voltage Tester. The Safe Way to Verify the Absence of Voltage.

CHILLGARD M-100. Refrigerant Sensor. Operating Manual. Order No.: /02

GasScanner 4C. Four Channel Monitor. Operator s Manual. MINT-0280-XX Rev. A 02/25/08

Oxygen (O2) Single-Point Gas Detection System

SMART EVO 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS

Autocalibration Systems for In Situ Oxygen Analyzers

Transcription:

TraceTek TTSIM-1 Sensor Interface Module Installation/Operation Instructions Approvals and Certifications TYPE NM General Signaling Equipment 76LJ Only AC versions are UL listed and VDE Certified. For DC models use a Listed Class 2 Power Supply. Product Information TTSIM-1 TTSIM-1-12VDC TTSIM-1-24VDC Power consumption Installation categories Storage temperature Operating temperature Enclosure 24 Vac ±10% (22 to 26 Vac) 50/60 Hz 12 Vdc ± 10%24 Vdc ± 10% 24 Vdc ± 10% 3 VA (3 watts); 2W for DC versions Overvoltage Category II Pollution Degree 2 18 C to 60 C (0 F to 140 F) 0 C to 50 C (32 F to 122 F) NEMA 1; IP20 (NEMA 4X / IP 56 with optional enclosure) General Information Please read these instructions and keep them in a safe place. These instructions must be followed carefully to ensure proper operation. The TTSIM-1 has been designed for use with TraceTek sensing cables, point sensors and normally open, dry contact devices (float switch, pressure or vacuum switch, optical probe with adapter, limit switch, etc.). Up to 1500 M (5000 feet) of sensor cable can be monitored by the TTSIM-1 (contact factory for information regarding longer monitoring distance). The TTSIM-1 is designed for installation in ordinary (nonhazardous) areas. The TTSIM-1 requires 24 Vac 50/60 Hz, 12 Vdc or 24 Vdc to operate and this voltage can be supplied either locally or through the same four wire jumper cable used for communication. The TTSIM-1 has five small LED s to indicate power, status and communications activity but no other user readout or interface. All alarm and monitoring functions are analyzed and displayed either at a TTDM-128 alarm and control panel, computer, or at the operator console of a Building or Factory Automation System. Tools Required Small flat blade screwdriver Small needle nose pliers Tools to mount DIN rail or enclosure Installation Items (not supplied) 35 mm DIN rail mounting strip (for wall mounts or interior of large control cabinets) and attachment hardware. TT-RS485 power and telemetry jumper cable. Optional TTSIM-ENC-4X-Outdoors environmental enclosure for outdoor or corrosive environments, or TTSIM-ENC-4X-Indoors for indoor, non-corrosive environments. Storage Keep the TTSIM-1 modules in a dry place prior to installation. Avoid damage to components. Additional Items An agency-approved zener barrier must be used where sensing cable connected to the TTSIM-1 will be located in Class1 Div 1 (Zone 0 or Zone 1 in Europe) Hazardous Locations. 1 / 6

Installing the TTSIM-1 Note: To avoid damage to the TTSIM-1, store the unit in its packaging until ready to install. Selecting the mounting position Choose a location where the module will be protected from the elements, temperature extremes or vibration. The TTSIM-1 is designed to be snapped onto standard 35 mm DIN rail. Existing electrical or instrumentation cabinets with spare rail space make good mounting locations. It is also possible to install a small section of DIN rail directly on a wall or cabinet surface and mount the TTSIM-1 in any location as long as it does not create a tripping hazard or expose the TTSIM-1 to impact damage. The TTSIM-1 should be mounted within 1200 m (4000 feet) wire run from the controlling TTDM-128 or control system host. (Contact the factory for methods to increase the wire run distance beyond 1200 m). Mounting Important: The the TTSIM-1 is an module electronic (without unit. Take the NEMA following 4x precautions to avoid damage to electronic components: Handle with care, avoid mechanical shock and impact. Keep dry. Avoid exposure to static electricity by touching a nearby piece of grounded equipment or water pipe prior to handling the TTSIM-1. Avoid contact with metal filings, grease, pipe dope and other contaminants. Mounting the TTSIM-1 module (without NEMA 4x Enclosure Figure 1) Secure a sufficient length of DIN rail to the desired mounting surface, or locate an existing DIN rail with sufficient space to install the TTSIM-1. Remove the TTSIM-1 from it s packaging and snap onto the DIN rail with the release tab towards the bottom. Note: When properly oriented, there will be two terminal strips on the top of the module and one on the bottom. See Figure 1. 35 mm DIN rail Figure 1. DIN Rail Mount Release tab Mounting the TTSIM-1 module in the optional NEMA-4X Enclosure Figure 2 Plan conduit alignment and drill holes as necessary. A typical outdoor or harsh environment installation will require up to three holes in the TTSIM-ENC: one for inbound power and telemetry, one for outbound power and telemetry and one for the sensor cable leader. See Figure 2. Secure the TTSIM-ENC to any convenient vertical surface using the four corner mounting holes and hardware suitable for the selected surface. Rough-in conduit as required and pull the cables for power and telemetry. Leave approximately 20 cm (8 in) for connections to the TTSIM-1 terminals. Pull in the sensor circuit leader cable. In order to provide maximum electrostatic discharge protection, and to be CE compliant, the DIN rail must be grounded. Note: Rough-in and final connections do not have to be completed at the same time, however make sure to replace the cover and tighten the cover screws if the enclosure will be left in a partially installed condition overnight or longer. Figure 2. NEMA 4x Enclosure 2 / 6 EN-TraceTekTTSIM1-IM-H56830 04/16 THERMAL BUILDING SOLUTIONS

Power Supply Options: The TTSIM-1 units require 24 Vac ±10% (22 to 26 Vac) 50/60 Hz or 12 Vdc ±10% or 24 Vdc ±10% depending on model selected. In most networks the operating voltage will be supplied from a step down transformer mounted near the TTDM-128 alarm panel or from a DC power supply or from a back-up DC power source provided by the building site. Figure 3 shows typical wiring adequate for any network that will be monitored by a TTDM-128. For very large networks or very long telemetry cable runs, there may be too much voltage drop in the power/telemetry cable to power the entire network from one location. In those situations, a second transformer or DC power source at the distant end of the system may be required. Be sure that each TTSIM-1 receives operating voltage from one and only one source. Important: Observe polarity for 12 Vdc or 24 Vdc power options. 12 Vdc, 24 Vdc or 24 Vac epending on TTSIM-1 Model Number Figure 3. Power Supply to TTSIM units Connections for Power and Telemetry TTSIM-1 communicates all alarm and status messages via RS-485 twisted pair shielded telemetry. Two of the four conductors in the power/telemetry cable are used for telemetry and the other two wires are used to supply the operating voltage. For all TTSIM-1 modules except the last one, there will be an incoming cable (from the TTDM-128 or other host system) and an outgoing cable (to the next TTSIM-1). Use only TraceTek TT-RS485 telemetry cable (Belden 8722) or equal. Strip a sufficient amount of the jacket insulation and shielding to expose about 2.5 cm (1 in) of the four wires. Strip the primary wires to expose approximately 6 mm (1/4 in) of conductor and make the following connections: (see Figure 4) Terminal Color Item 13 Shield Drain Wire 14 Black RS-485 ( ) Shielded pair 15 Red RS-485 (+) 16 Green 24 Vac (no polarity), 12 Vdc + or 24 Vdc + (observe polarity of DC supply 17 White 24 Vac (no polarity), 12 Vdc or 24 Vdc (observe polarity of DC supply) Figure 4. Power and Telemetry Connections 20 Shield Drain Wire 21 Black RS-485 ( ) Shielded pair 22 Red RS-485 (+) 23 Green 24 Vac (no polarity), 12 Vdc + or 24 Vdc + (observe polarity of DC supply) 24 White 24 Vac (no polarity), 12 Vdc or 24 Vdc (observe polarity of DC supply 3 / 6

Place the End Of Line Jumper in the correct position: If the TTSIM-1 will be connected to a host for communication, it is necessary to set the End of Line Jumper in the correct position as follows: On the last TTSIM-1 in the circuit, place the jumper as shown in Figure 5a. On all other TTSIM s in the circuit, place the jumper as shown in Figure 5b. Jumper Jumper Figure 5a. End of Line Jumper for last TTSIM-1 Figure 5b. End of Line Jumper for all other TTSIM s Leader Cable Connections for Sensor The TTSIM-1 can be used with most of the TraceTek family of sensors including: TT1000, TT3000, TT5000 and TT5001 cables. Connect the TraceTek leader cable to the TTSIM-1 as shown in Figure 6. Terminal Color Item 8 Red Red / Green Sensor Cable Loop 9 Grn 10 Yel Yellow /Black Sensor Cable Loop 11 Blk 12 For diagnostic use only Figure 6. Sensing Cable Connections 4 / 6 EN-TraceTekTTSIM1-IM-H56830 04/16 THERMAL BUILDING SOLUTIONS

Operating Instructions Network Address Assignment Each TTSIM-1 in a TraceTek network must have a unique address in the range 001 to 127. The SIM board built into the TTDM-128 is factory assigned address 001. All external TTSIM-1 units are shipped from the factory with their network address preset to a value above the range of valid addresses, in order to prevent communications conflicts during system startup and configuration. Each TTSIM-1 must therefore be configured to its unique address before it can communicate with the TTDM-128 or other host. To set the TTSIM-1 network addresses, repeat the following procedure for each TTSIM-1. Perform the complete procedure one module at a time: Place the TTSIM-1 configuration jumper in the CFG position, as shown in Figure 7a. Using the TTDM-128 or host system, assign the new TTSIM-1 address (refer to the TTDM-128 User Manual, H56853). Place the configuration jumper in the normal operating position, as shown in Figure 7b, or remove it completely (the jumper is not required in normal operation). Write the address in the space provided on the TTSIM-1 cover. Figure 7a. Configuration Jumper in Configuration Position Figure 7b. Configuration Jumper Set for Normal Operation TTSIM-1 Reset In the event that the TTSIM-1 appears to be hung-up and unresponsive to the network it is possible to force a RESET. To force a RESET of the TTSIM-1 processor, use a small flat blade screwdriver to momentarily short the pads shown in Figure 8. Reset pads Figure 8. Reset Pads 5 / 6

Maintenance and Troubleshooting No user maintenance is required! There are no user adjustments or calibrations that can be performed in the field. Each TTSIM-1 is tested and calibrated in the factory during production. An operating TTSIM-1 runs a continuous self check routine and reports any discrepancies to the TTDM-128 host computer. If the TTSIM-1 or the network wiring fails is such a way that the TTSIM-1 cannot communicate with the host, then the host reports the failure as a communications failure. Status Indicators There are 5 LED s on the TTSIM-1 circuit board to indicate: operating power, communications (RX = inbound and TX = outbound), sensor status (leak detected and trouble). See Figure 9 for locations and colors. RX (Yellow) Power (Green) TX (Yellow) Table 1 indicates various status conditions and possible corrective actions: Service (Yellow) Alarm (Red) Figure 9. TTSIM-1 LED Locations Table 1. TTSIM-1 LED Status Indications POWER TX RX ALARM SERVICE INDICATION OFF OFF OFF OFF OFF No power to unit. Check wiring, connections and power supply. Measure voltage at terminals 16 and 17. Should be 24 Vac, 12 Vdc, or 24 Vdc, ±10%. ON FLASHING FLASHING SLOW FLASH OFF Normal Operation. No alarms or service requests. Alarm LED flashes once every 5 seconds to indicate normal operation. ON FLASHING FLASHING ON OFF Leak detected by sensor. Check sensor being monitored for leak or spill. ON FLASHING FLASHING OFF FLASHING Unit has detected a condition requiring outside attention. The flash sequence indicates the type of condition: 1 Flash Sensor cable break 2 Flashes Sensor cable loop imbalance 3 Flashes EPROM hardware error 10 Flashes Sensor cable contamination ON OFF FLASHING SLOW FLASH OFF Unit is not responding to TTDM-128 or host. Re-initialize the SIM network on the TTDM-128 (or host), and check the TTSIM-1 address. ON OFF OFF OFF OFF Unit not receiving any communication from TTDM-128 or host. Check network master unit and telemetry wiring and connections. WWW.PENTAIRTHERMAL.COM NORTH AMERICA Tel: +1.800.545.6258 Fax: +1.800.527.5703 Tel: +1.650.216.1526 Fax: +1.650.474.7215 thermal.info@pentair.com Europe, Middle East, Africa Tel: +32.16.213.511 Fax: +32.16.213.603 thermal.info@pentair.com Asia Pacific Tel: +86.21.2412.1688 Fax: +86.21.5426.2937 cn.thermal.info@pentair.com Latin America Tel.: +1.713.868.4800 Fax: +1.713.868.2333 thermal.info@pentair.com Pentair is owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right to change specifications without prior notice. 2003-2016 Pentair. 6 / 6