Genesis Large (GL) Series Commercial Horizontal Packaged Heat Pumps. Installation, Operation & Maintenance Instructions.

Similar documents
LCU Series. Large Commercial Series Water Source Heat Pumps. Installation, Operation & Maintenance Instructions

Table of Contents. Commercial Horizontal & Vertical Packaged Water-Source Heat Pumps

GENESIS WATER-TO-WATER (GSW) SERIES. Table of Contents

G Series. G Series 7-25 Tons Installation Manual. Water Source/Geothermal Heat Pump Commercial 7-25 Tons. Installation Information

ICE AIR Vertical WSHP Technical Manual INSTALLATION

HEAT CONTROLLER, INC. HC Series 1/2 to 5 Tons Commercial Water Source Heat Pumps

Tranquility Compact. Belt Drive (TCH/V) Series. Installation, Operation & Maintenance. Models TCH TCV Hz - HFC-410A

RHGN-H: COMMERCIAL AIR HANDLER WITH VARIABLE FREQUENCY DRIVE (VFD) NOMINAL 10 TONS R-410A REFRIGERANT 2-STAGE AIR-FLOW

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L4EU NOMINAL TONS

CROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

C13-Series Engineering Guide

BasicTroubleshooting Information and Guidelines

Tranquility 22 (TZ) Series

Technical Guide SUNLINE 2000 DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWER K4EU NOMINAL TONS (WORLD 50 HZ)

CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L2EU NOMINAL TONS

OWNER S MANUAL. Vintage Signature Series models: AC750, AC1050, AC1100, AC1250, AC1500, AC1750. Proudly Made in the USA.

MHNCCX DX with Hot Water Heat Ceiling Concealed 4-Pipe Heat / Cool Fan Coil 12,000-36,000 BTUH

INSTALLATION MB SERIES MANUAL TABLE OF CONTENTS MB SERIES ( INSTALLATION ) UNIT DESCRIPTION. FHP MB series are available in two models: VH CABINET:

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

FILTERS MANIFOLD CABINET REFRIGERANT CONNECTION LOCATION

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT: INDOOR UNIT:

Technical Guide DESCRIPTION CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240A 20 NOMINAL TONS (WORLD 50 HZ) FEATURES XTG-A-0307

Your safety and the safety of others are very important.

K*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS*

Installation, Operation & Maintenance Manual

40LM Hz INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT

G Series. G Series Air Coils Installation ti Manual ENCASED/UNCASED AIR COILS. Geothermal/Water Source Heat Pumps R-410A Refrigerant 2-5 Ton

Residential Packaged Geothermal Heat Pump

User s Information and Installation Instructions

INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS WA121

Tranquility Coaxial Geothermal Open Loop Water-to-Water (TCW) Series

EMBASSY SERIES SINGLE PACKAGE AIR CONDITIONERS (WATER-COOLED) C2ED060, 090, 120 & 180 5, 7-1/2, 10 & 15 Nominal Tons

Genesis Compact (GC) Series Submittal Data

Installation, Operation, and Maintenance Information

SPLIT-SYSTEM EVAPORATOR BLOWERS K2EU060, K4EU090, K3EU120 & K1EU180 5 Thru 15 Nominal Tons DESCRIPTION ACCESSORIES FIELD INSTALLED

Tranquility 20 (TS) Series. Tranquility 16 (TC) Series. Commercial Horizontal & Vertical Packaged Water-Source Heat Pumps

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS

Tranquility 30 (TT) Series

Tranquility 16 COMPACT (TC) Series

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

SPLIT-SYSTEM EVAPORATOR BLOWER (AIR COOLED) INSTALLATION INSTRUCTION Supersedes: Nothing N4C-0500

*20D082-05NN* 20D082-05NN

ENGINEERING GUIDE. Water-Cooled Self-Contained Units C-Series, Vertical

Tranquility 16 COMPACT (TC) Series

Mortex INSTALLATION INSTRUCTIONS AIR CONDITIONING & HEAT PUMP INDOOR COILS

Tranquility 20 (TS) Series. Tranquility 16 (TC) Series. Commercial Horizontal & Vertical Packaged Water-Source Heat Pumps

Installation, Operating & Maintenance Instructions. Air Handler Models: AH & AV

Tranquility Modular Water-to-Water (TMW) Series

T-Series Air Conditioner T15 Model

Service Step by Step Trouble-Shooting Check-List

T-SERIES Air Conditioner. T43 Model INSTRUCTION MANUAL nvent Rev. I P/N

Installation Instructions. For the 18 Built-In Dishwasher and Front Color Panels

Rittling Fanvector. Installation, Operation and Maintenance. Cooling Fresh Air Clean Air

Advance Product Data. Features/Benefits. 42WKN Hydronic Fan Coil Units

SECTION AIR HANDLING UNIT

High Profile Evaporator

Condensing Unit Installation and Operating Instructions

FAN POWERED VAV TERMINALS

VertiCool Aurora Engineering Guide

MODELS B1PA024, 030 AND 036

McQuay. Ceiling Concealed Horizontal Water Source Heat Pump. CCH, CCG, CCW 048, 060 Vintage A. Last Manufactured: 1995

T-SERIES Air Conditioner. T29 Model INSTRUCTION MANUAL nvent Rev. I P/N

T-Series Air Conditioner T20 Model

INSTALLATION INSTRUCTIONS

SPLIT-SYSTEM HEAT PUMPS 50 AND 60 HZ DESCRIPTION

CAH SERIES INSTALLATION & MAINTENANCE MODELS CAH CAH

MHCCW Chilled Water Ceiling Concealed With 5kW Electric Heat 2-Pipe Heat / Cool Fan Coil 30,000 BTUH

VertiCool CLASSIC. Engineering Guide. Effective March Air-Cooled, Water-Cooled, Chilled Water and Water Source Heat Pump

40 RM/RMS Packaged Air-Handling Units

CWA2 Chilled Water Fan Coil With or Without Electric Heat 2-Pipe Heat / Cool Fan Coil 18,000-60,000 BTUH

T-SERIES Air Conditioner. T20 Model INSTRUCTION MANUAL nvent Rev. C P/N

ENGINEERING SPECIFICATIONS

CWA4 Chilled & Hot Water Fan Coil

maintenance should only be performed by a trained, qualified person. Consumer service is recommended only for filter replacement.

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer

MHCCW Chilled Water Ceiling Concealed Without Electric Heat 2-Pipe Heat / Cool Fan Coil 18,000 BTUH

T-SERIES Air Conditioner. T50 Model INSTRUCTION MANUAL nvent Rev. F P/N

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION ACCESSORIES - FIELD INSTALLED. K5EU090 and K4EU Hz 7.5 and 10 NOMINAL TONS SUNLINE 2000 (WORLD 50 HZ)

USER S MANUAL AND INSTALLATION INSTRUCTIONS IMPORTANT

ENGINEERING SPECIFICATIONS

MIN. CCT. QTY RLA LRA HP FLA AMPACITY /1/ /3/

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

EC SERIES MODEL NOMENCLATURE

SPECTRACOOL Air Conditioner. N21 Model INSTRUCTION MANUAL nvent Rev. G P/N

Technical Guide DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWERS. 7-1/2 and 10 NOMINAL TONS LA090 & LA120 SUPPLY AIR PLENUMS

GS SERIES. Table of Contents CABINET CONFIGURATION: VT - VERTICAL HZ - HORIZONTAL CF - COUNTERFLOW

OPERATIONS AND MAINTENANCE MANUAL FOR THE 8-TON TURF CART ENVIRONMENTAL CONTROL UNIT (ECU) PART NUMBER

FCI500/600/FVI500/FCL/FVL600/FCQ-700 Installation and Maintenance Manual

PACKAGE AIR CONDITIONER

Commercial High-Efficiency Condensing Units

Installation, Operating & Maintenance Instructions. Horizontal Models: LH & HL

Installation, Start-Up, and Service Instructions

Installation & Maintenance Data IM Contents

Tranquility 16 COMPACT (TC) Series

INSTALLATION & OPERATING INSTRUCTIONS AEM SERIES VARIABLE SPEED MULTI-POSITION ELECTRIC HEAT AIR HANDLER

AP SERIES VOLTAGE DESIGNATION: 1-208/1/60 & 230/1/60 CABINET CONFIGURATION: VT - VERTICAL HZ - HORIZONTAL CF - COUNTERFLOW

Packaged Heat Pump. 20 Ton Rooftop Units with ReliaTel TM Controls NOTICE

STELLAR 2000 SINGLE PIECE AIR HANDLERS INSTALLATION INSTRUCTION Supersedes: N2Y (795) N2Y (1195)

INSTALLATION INSTRUCTIONS

T-Series Air Conditioner T53 Model

Transcription:

TM GC INSTALLED BY: Genesis Large (GL) Series Commercial Horizontal Packaged Heat Pumps Installation, Operation & Maintenance Instructions Release: 10/05/01

Table of Contents Model Nomenclature 3 Storage 3 Pre-Installation 3 Physical Data 4 Physical Dimensions 5 Unit Installation 6 Duct Installation 6 Piping Installation 8 Commercial Water Loop Applications 10 Electrical Data 11 Power Wiring 1 Blower Sheave Adjustment 1 Blower Performance Table 13-14 Low Voltage & Thermostat Field Wiring 15 Low Water Temperature Cutout Selection 15 Water Valve Wiring 15 Thermostat Wiring Diagrams 16 Electrical Wiring Schematics 17-18 Unit Start-Up and Operating Conditions 19 Piping System Cleaning & Flushing Procedures 19 CXM/DXM & Other Control References 0 Unit and System Checkout Procedure 0 Unit Start-Up Procedure 1 Coax Pressure Drop Table Operating Pressures CXM/DXM Safety Control Reset Preventive Maintenance 3 Page

General Information MODEL NOMENCLATURE Series 1 G L Configuration 3 4 5 H 0 9 Size 6 6 Revision Electrical Characteristics Controls Cabinet 7 8 9 10 11 A H C 1 A Blower Drive Option5 1 13 C L Return Coax Options 14 S Supply 15 S Standard GL = Large Commercial with Scroll compressors H = Horizontal 096 = 96,000 nominal cooling 10 = 10,000 nominal cooling capacity @ 85 F EWT A = Product Release H = 08-30/60/3 F = 460/60/3 U = 380-40/50/3 N = 575/60/3 C = CXM Controller D = DXM Controller L = CXM with LON M = DXM with LON L = Left Return C = Copper N = Cupro-Nickel A = Std Static & Std Motor B = Low Static & Std Motor C = High Static & Std Motor D = Std Static & Large Motor E = High Static & Large Motor S = Standard S = Straight Supply 1 = Commercial Extended Range = Commercial Extended Range & Mute 3 = Commercial Standard Range 4 = Commercial Standard Range & Mute NOTES: 1. Non painted galvanized cabinet is standard.. 1 inch shipping filter is standard. 3. 75VA transformer standard. 4. 08-30V wired for 08V operation and 380-40V wired for 380V operation. 5. Refer to the blower performance tables in the submittal. Revision: 09/4/01 B Inspection Upon receipt of the equipment, carefully check the shipment against the bill of lading. Make sure all units have been received. Inspect the carton or crating of each unit, and inspect each unit for damage. Assure the carrier makes proper notation of any shortages or damage on all copies of the freight bill and completes a common carrier inspection report. Concealed damage not discovered during unloading must be reported to the carrier within 15 days of receipt of shipment. If not filed within 15 days, the freight company can deny the claim without recourse. Note: It is the responsibility of the purchaser to file all necessary claims with the carrier. Notify the ClimateMaster Traffic Department of all damage within fifteen (15) days of shipment. Storage Equipment should be stored in its shipping carton in a clean, dry area. Store units in an upright position at all times. Stack units a maximum of 3 units high. Unit Protection Cover units on the job site with either shipping cartons, vinyl film, or an equivalent protective covering. Cap the open ends of pipes stored on the job site. In areas where painting, plastering, and/or spraying has not been completed, all due precautions must be taken to avoid physical damage to the units and contamination by foreign material. Physical damage and contamination may prevent proper start-up and may result in costly equipment clean-up. Examine all pipes, fittings, and valves before installing any of the system components. Remove any dirt or trash found in or on these components.! WARNING! DO NOT store or install horizontal units in corrosive environments or in locations subject to temperature or humidity extremes (e.g., attics, garages, rooftops, etc.) Corrosive conditions and high temperature or humidity can significantly reduce performance, reliability, and service life. Always move units in an upright position. Tilting units on their sides may cause equipment damage. Pre-Installation Installation, Operation, and Maintenance instructions are provided with each unit. GL Series horizontal equipment is designed for installation above false ceiling or in a ceiling plenum. The installation site chosen should include adequate service clearance around the unit. Before unit start-up, read all manuals and become familiar with the unit and its operation. Thoroughly check the system before operation. Prepare units for installation as follows: 1. Compare the electrical data on the unit nameplate with ordering and shipping information to verify that the correct unit has been shipped.. Keep the cabinet covered with the shipping carton Page 3

until installation is complete and all plastering, painting, etc. is finished. 3. Verify refrigerant tubing is free of kinks or dents and that it does not touch other unit components. 4. Inspect all electrical connections. Connections must be clean and tight at the terminals. 5. Remove any blower support cardboard from mouth of blower. 6. Loosen compressor bolts on units equipped with compressor spring vibration isolation until the compressor rides freely on the springs. Remove shipping restraints. 7. Locate and verify any hanger, or other accessory kit located in the compressor section and or the blower section.! WARNING! To avoid equipment damage, DO NOT use these units as a source of heating or cooling during the construction process. The mechanical components and filters used in these units will quickly become clogged with construction dirt and debris which may cause system damage. To avoid the release of refrigerant into the atmosphere, the refrigerant circuit of this unit must be serviced only by technicians who meet local, state, and federal proficiency requirements. All refrigerant discharged from this unit must be recovered WITHOUT EXCEPTION. Technicians must follow industry accepted guidelines and all local, state, and federal statutes for the recovery and disposal of refrigerants. If a compressor is removed from this unit, system refrigerant circuit oil will remain in the compressor. To avoid leakage of compressor oil, the refrigerant lines of the compressor must be sealed after it is removed. GL Physical Data Model 096 10 Refrigerant Circuit Compressor ( each) Scroll Scroll Factory Charge oz [kg] per Circuit 50 [1.417] 80 [.68] Fan Motor Standard (hp) [kw] [1.5] [1.5] Large (hp) [kw] 3 [.] 3 [.] Blower Wheel Size -Dia x W (in) [cm] - 10 x 10 [5.4 x 5.4] - 11 x 10 [7.9 x 5.4] Water Connection Size FPT - (in) 1-1/4" 1-1/4" Condensate Connection Size FPT - (in) 3/4" 3/4" Horizontal Units Air Coil Dimensions - H x W (in) [cm] - 0 x 30 [50.8 x 76.] - 0 x 30 [50.8 x 76.] Air Coil Total Face Area (ft) [m] 8.33 [0.359] 8.33 [0.359] Air Coil Tube Size (in.) [cm] 3/8 [0.953] 3/8 [0.953] Air Coil Fin Spacing (fpi) [fins per cm] 14 [5.5] 1 [4.7] Air Coil Number of Rows 3 4 Filter Standard - 1" Throwaway (in) [cm] 4-16 x 0 [40.6 x 50.8] 4-16 x 0 [40.6 x 50.8] Weight - Operating (lbs.) [kg] 560 [54] 610 [77] Weight - Packaged (lbs.) [kg] 580 [63] 630 [86] Rev.: 10/0/01 B Notes: All units have grommet & spring compressor mountings,and 1/" & 1-3/8" electrical knockouts. Check serial plate for refrigerant type (R or R407c). Page 4

GL Horizontal Dimensions LEFT RETURN STRAIGHT DISCHARGE Z BSP LEFT INLET A 4 [61] Service Access 1.0 [.5] 4. [10.7] Y 3 FRONT OF UNIT O CSP Q P B Filter Bracket Shown 5 N CAP L M LS 1 G H 5.5 [64.8] E D F C STRAIGHT (RIGHT) DISCHARGE Legend CAP=Control Access Panel CSP=Compressor Service Panel BSP=Blower Service Panel 1 - Water Outlet 1-1/4 FPT - Water Inlet 1-1/4 FPT 3 - Condensate 3/4 FPT 4 - High Voltage 1-3/8 KO 5 - Low Voltage 1/ KO 4 [61] Service Access 4 K Hanger Bracket Dimensions R U A S V FRONT PLAN VIEW (TOP) 34.1" [86.7] T C 1.75" [4.4] Left Return Left View - Air Coil Opening 74.1" [188.3] NOTE: All Dimensions in inches [cm]. Flanged filter bracket shipped with unit. Leave one end of duct collar open for filter removal. All side panels are removable. Available in left return, straight discharge only. Rev.: 08/0/01 B Horizontal Model Overall Cabinet A B C D E F G H K L M N O P Q R S T U V Width Depth Height Supply Height Discharge Connections duct flange (± 0.10 in) Supply Depth Water Connections Electrical Knockouts Return Air Connections 096 in. 36.3 7.3 1.0 15. 3.3 3.3 1.0 15. 0. 18.0 3.3 1.9 0.5.5 10.0.0 6.8 18.8 1.1 7.4 cm. 9. 183.6 53.3 38.6 8.3 8.3.5 38.6 51.3 45.7 8.3 55.7 1.3 6.4 5.3 5.1 159.4 47.6.9 18.7 10 in. 36.3 7.3 1.0 15..6 4.3 1.0 15. 18.4 18.6 3.3 1.9 0.5.5 10.0.0 6.8 18.8 1.1 7.4 cm. 9. 183.6 53.3 38.6 6.7 10.8.5 38.6 46.8 47.3 8.3 55.7 1.3 6.4 5.3 5.1 159.4 47.6.9 18.7 Return Depth using return air opening Return Height Condensate is 3/4" FPT copper. Horizontal unit shipped with filter bracket only. This bracket should be removed for return duct connection. Rev.: 10/01/01 B Page 5

GL Horizontal Unit Location These units are not designed for outdoor installation. Locate the unit in an INDOOR area that allows enough space for service personnel to perform typical maintenance or repairs without removing from the ceiling. Horizontal units are typically installed above a false ceiling or in a ceiling plenum. Refer to Figure 3 for an illustration of a typical installation. Conform to the following guidelines when selecting unit location: 1. Provide a hinged access door in concealed-spline or plaster ceilings. Provide removable ceiling tiles in t- bar or lay-in ceilings. Refer to physical dimensions page or submittal drawing for horizontal unit dimensions. Size the access opening to accommodate the service technician during the removal or replacement of the compressor and the removal or installation of the unit itself.. Provide access to hangar brackets, water valves and fittings. Provide screwdriver clearance to access panels, discharge collars and all electrical connections. 3. DO NOT obstruct the space beneath the unit with piping, electrical cables and other items that prohibit future removal of components or the unit itself. 4. Use a manual portable jack/lift to lift and support the weight of the unit during installation and servicing. The installation of water source heat pump units and all associated components, parts and accessories which make up the installation shall be in accordance with the regulations of ALL authorities having jurisdiction and MUST conform to all applicable codes. It is the responsibility of the Installing Contractor to determine and comply with ALL applicable codes and regulations. Locate the unit in an indoor area that allows easy removal of the filter and access panels, and has enough space for service personnel to perform maintenance or repair. Provide sufficient room to make water, electrical, and duct connection(s). If the unit is located in a confined space provisions must be made for return air to freely enter the space by means of a louvered door, etc. Any access panel screws that would be difficult to remove after the unit is installed should be removed prior to setting the unit. These units are not approved for outdoor installation and, therefore, must be installed inside the structure being conditioned. Do not locate in areas where ambient conditions are not maintained within 40-100 F and up to 75% relative humidity. Mounting Horizontal Units Figure 3 shows a typical commercial horizontal unit installation. Horizontal heat pumps are typically suspended above a Installation Figure 1. Hanger Bracket 3/8" Threaded Rod (by others) Vibration Isolator (consult hanger installation instructions for color rating & installation notes) Washer (by others) Double Hex Nuts (by others) Install screws as shown This screw must only be 1/ long to prevent damage ceiling or within a soffit using field supplied, threaded rods sized to support the weight of the unit. A mounting kit including four (4) mounting brackets and four (4) vibration isolators is bagged within the unit. Refer to Figure 1 to complete mounting bracket installation. Attach brackets and isolators to the bottom corners of the unit. Use four (4) field supplied threaded rods to suspend the unit. Hang the unit clear of the floor slab above and support the unit by the mounting bracket assemblies only. DO NOT attach the unit flush with the floor slab above. Figure. Horizontal Unit Pitch 1/4 pitch for drainage Drain Connection Duct System Installation The duct system should be sized to handle the design airflow quietly. Refer to Figure 3 for horizontal duct system details. A flexible connector is recommended for both discharge and return air duct connections on metal duct systems to eliminate the transfer of vibration to the duct system. To maximize sound attenuation of the unit blower, the supply and return plenums should include internal duct liner of glass fiber or be of ductboard construction for the first few feet. Application of the unit to uninsulated ductwork in an unconditioned space is not recommended as the unit s performance will be adversely affected. At least one 90 elbow should be included in the supply duct to reduce air noise. If air noise or excessive air flow is a problem, the blower speed can be changed. See the Blower Performance and Fan Speed sections for further instruction. If the unit is connected to existing ductwork, a previous Page 6

Figure 3. Typical Horizontal Unit Installation 3/8 threaded rods Return Air Optional Balancing Valve Thermostat Wiring Power Wiring Y-Strainer with blowoff valve Building Loop Unit Power Unit Power Disconnect Optional Low Pressure Drop Water Control Valve Dual Blower Discharge Ball Valve with integral P/T plug Stainless steel braid hose with integral J swivel Water Out Water In Insulated supply duct with at least one 90 deg elbow to reduce air noise Supply Air check should have been made to assure the ducts have the capacity to handle the air required for the unit. If ducting is too small, as in the replacement of heating only systems, larger ductwork should be installed. All existing ductwork should be checked for leaks and repaired as necessary. Air Coil To obtain maximum performance, the air coil should be cleaned before start-up. A 10% solution of dishwasher detergent and water is recommended for both sides of coil. A thorough water rinse should follow. Sound Attenuation for Horizontal Units Sound minimization is achieved by correct placement of the unit. Place the units so that principal sound emission is ducted outside the occupied, sound sensitive space. Note: If a fire wall is penetrated, a fire damper may be required by local codes. Page 7

Installation of Supply and Return Piping Follow these piping guidelines. 1. Install a drain valve at the base of each supply and return riser to facilitate system flushing.. Install shut-off / balancing valves and unions at each unit to permit unit removal for servicing. 3. Place strainers at the inlet of each system circulating pump. 4. Select the proper hose length to allow slack between connection points. Hoses may vary in length by +% to -4% under pressure. 5. Refer to Table 1. Do not exceed the minimum bend radius for the hose selected. Exceeding the minimum bend radius may cause the hose to collapse which reduces water flow rate. Install an angle adapter to avoid sharp bends in the hose when the radius falls below the required minimum.! CAUTION Piping must comply with all applicable codes. Table 1. Metal Hose Minimum Bend Radii Hose in Inches 1/ 3/4 1 1-1/4 Minimum Bend Radius -1/ 4 5-1/ 6-3/4 Insulation is not required on loop water piping except where the piping runs through unheated areas or outside the building or when the loop water temperature is below the minimum expected dew point of the pipe ambient. Insulation is required if loop water temperature drops below the dew point. Pipe joint compound is not necessary when Teflon threaded tape is pre-applied to hose assemblies or when Piping Installation! WARNING! Do not bend or kink supply lines or hoses. Figure 4. Supply/Return Hose Kit Rib Crimped Length ( Foot Length Standard) Swivel Brass Fitting Brass Fitting MPT flared-end connections are used. If pipe joint compound is preferred, use compound only in small amounts on the male pipe threads of the fitting adapters. Prevent sealant from reaching the flared surfaces of the joint. Note: When anti-freeze is used in the loop, assure that it is compatible with Teflon tape or pipe joint compound employed. Maximum allowable torque for brass fittings is 30 foot-pounds. If a torque wrench is not available, tighten finger-tight plus one quarter turn. Tighten steel fittings as necessary. Optional pressure-rated hose assemblies designed specifically for use with ClimateMaster units are available. Similar hoses can be obtained from alternate suppliers. Supply and return hoses are fitted with swiveljoint fittings at one end to prevent kinking during installation. Refer to Figure 4 for an illustration of a Supply/Return Hose Kit. Male adapters secure hose assemblies to the unit and risers. Install hose assemblies properly and check them regularly to avoid system failure and reduced service life. Page 8

! CAUTION Corrosive system water requires corrosion resistant fittings and hoses and possibly water treatment. Condensate Piping Figure 5 illustrates a typical trap and vent used with GL series equipment. Design the depth of the trap (waterseal) based upon the amount of ESP capability of the blower (where inch of ESP capability requires inches of trap depth). As a rule 1-1/ inch trap depth is a minimum trap depth. Each unit must be installed with its own individual trap and connection to the condensate line (main) or riser. Provide a means to flush or blow out the condensate line. DO NOT install units with a common trap and or vent. Always vent the condensate line when dirt or air can collect in the line or a long horizontal drain line is required. Also vent when large units are working against higher external static pressure than other units connected to the same condensate main since this may cause poor drainage for all units on the line. WHEN A VENT IS INSTALLED IN THE DRAIN LINE, IT MUST BE LOCATED AFTER THE TRAP IN THE DIRECTION OF THE CONDENSATE FLOW. Figure 5. Horizontal Condensate Connection! WARNING! Ensure condensate line is pitched toward drain 1/4" per foot of run. Units are typically installed directly above each other on successive floors with condensate drains located near the units. Connect the unit condensate drain connection to the building condensate drain with a flexible, non-pressurerated 3/4 inch ID plastic hose. Ensure the hose is without kinks to maintain unobstructed flow of condensate from the unit to the drain. Ensure condensate line is pitched toward drain 1/4" per foot of run. Pitch the unit toward the drain as shown in Figure 5 to improve the condensate drainage. On small units (less than 30,000 Btuh) ensure that unit pitch does not cause condensate leaks inside the cabinet. The horizontal run of a condensate hose is usually too short to cause drainage problems, however, the horizontal run of the condensate line should pinched at least 1 inch for every 10 feet of run in the direction of flow to ensure connection will not slip off due to excessive weight or piping expansion/contraction. Avoid low points and unpitched piping since dirt collects in low or level areas and may cause stoppage and overflow. Install condensate trap at each unit with the top of the trap positioned below the unit condensate drain connection. 3/4 FPT Trap Depth 1.5 3/4 PVC or Copper by others Min 1.5 Vent (below top of drain line) 1/4 per foot drain slope Rev.: 09/4/01 B Page 9

Commercial Water Loop Applications Commercial systems typically include a number of units plumbed to a common piping system. Any unit plumbing maintenance work can introduce air into the piping system, therefore air elimination equipment is a major portion of the mechanical room plumbing. In piping systems expected to utilize water temperatures below 50 F, 1/" closed cell insulation is required on all piping surfaces to eliminate condensation. Metal to plastic threaded joints should never be employed due to their tendency to leak over time. All non-distributor class units include a low temperature-soldered bracket-supported FPT water connection. Teflon tape thread sealant is recommended to minimize internal fouling of the heat exchanger. Do not overtighten connections and route piping so as not to interfere with service or maintenance access. Hose kits are available from ClimateMaster in different configurations as shown in Figure 8 for connection between the GL Series and the piping system. The hose kits include shut off valves, P/T plugs for performance measurement, high pressure stainless steel braid hose, "Y" type strainer with blowdown valve, and "J" type swivel connection. Balancing valves to facilitate the balancing of the system, and an external low pressure drop solenoid valve for use in variable speed pumping systems, may also be included in the hose kit. The piping system should be flushed to remove dirt, piping chips, and other foreign material prior to operation. See page 19 for Piping System Cleaning and Flushing Procedures. The flow rate is usually set between.5 and 3 gpm per ton of cooling capacity. ClimateMaster recommends.5 gpm per ton for most applications of water loop heat pumps. To insure proper maintenance and servicing, P/T ports are imperative for temperature and flow verification, as well as performance checks. Cooling Tower/Boiler Systems typically utilize a common loop maintained 60-90 F. The use of a closed circuit evaporative cooling tower with a secondary heat exchanger between the tower and the water loop is recommended. If an open type cooling tower is used continuously, chemical treatment and filtering will be necessary. Low Water Temperature Cutout Setting CXM or DXM Control: When an antifreeze is selected, the FP1 jumper (JW) should be clipped to select the low temperature (Antifreeze 13 F) setpoint to avoid nuisance faults. See Low Water Temperature Cutout Selection. NOTE THAT THE EXTENDED RANGE OPTION SHOULD BE SELECTED WHEN LOOP CONDITIONS ARE EXPECTED TO DROP BELOW 60 F. Figure 6. Typical Water Loop Application Power Wiring g Y-Strainer with blowoff valve Building Loop Unit Power Unit Power Disconnect Water Control Valve Ball Valve with integral P/T plug Stainless steel braid hose with integral J swivel Water Out Water In Page 10

! WARNING! To avoid possible injury or death due to electrical shock, open the power supply disconnect switch and secure it in an open position during installation.! CAUTION Use only copper conductors for field installed electrical wiring. Unit terminals are not designed to accept other types of conductors. Table a. GL Electrical Data Electrical - Line Voltage All field installed wiring, including electrical ground, must comply with the National Electrical Code as well as all applicable local codes. Refer to the unit wiring diagrams for fuse sizes and a schematic of the field connections which must be made by the installing (or electrical) contractor. Consult the unit wiring diagram located on the inside of the compressor access panel to ensure proper electrical hookup. All final electrical connections must be made with a length of flexible conduit to minimize vibration and sound transmission to the building. Rated Voltage Blower Compressor Fan Fan Total Min Max Model Volt Code Voltage Min/Max Motor Motor Motor Unit Circ Fuse/ Option Qty RLA LRA HP FLA FLA Amp HACR 096 10 H F N H F N 08-30/60/3 460/60/3 575/60/3 08-30/60/3 460/60/3 575/60/3 187/53 414/506 518/633 187/53 414/506 518/633 Standard Standard Standard Standard Standard Standard 14.3 7. 5.7 19.3 7.5 6.4 91.0 46.0 37.0 13.0 49.5 40.0.0.0.0.0.0.0 6.5 3.1.8 6.5 3.1.8 35.1 17.5 14. 45.1 18.1 15.6 38.7 19.3 15.6 49.9 0.0 17. 50 5 0 60 5 0 Large Large Large Large Large Large 14.3 7. 5.7 19.3 7.5 6.4 91.0 46.0 37.0 13.0 49.5 40.0 3.0 3.0 3.0 3.0 3.0 3.0 8.8 4. 3.4 8.8 4. 3.4 37.4 18.6 14.8 47.4 19. 16. 41.0 0.4 16. 5. 1.1 17.8 50 5 0 70 5 0 HACR circuit breaker in USA only All fuses Class RK-5 Rev.: 08/0/01 B Page 11

! WARNING! Disconnect electrical power source to prevent injury or death from electrical shock. General Line Voltage Wiring Be sure the available power is the same voltage and phase as that shown on the unit serial plate. Line and low voltage wiring must be done in accordance with local codes or the National Electric Code, whichever is applicable. GL Power Connection Line voltage connection is made by connecting the incoming line voltage wires to the power block as shown in Figure 7. Consult Table for correct fuse size. 08 Volt Operation All 08-40 Volt units are factory wired for 08 Volt. The transformers may be switched to 40V operation as illustrated on the wiring diagram. By switching the Red (40V) and the Orange (08V) at the contactor terminal L. Figure 7. GL Series Line Voltage Field Wiring Unit Power Supply See electrical table for breaker size CXM CXM Control 1 Control Low Low Voltage Voltage Connector Connector Power Block CB Transformer Grnd L3 L L1 L3 L L1 L L1 Contactor -CC1 Contactor -CC Blower Contactor! CAUTION Use only copper conductors for field installed electrical wiring. Unit terminals are not designed to accept other types of conductors. Rev.: 8/4/01 B Airflow and External Static Pressure Selection Adjustment The GL Series is available with standard, low, and high static options. These options will substitute a different blower drive sheave for each static range. In addition certain static ranges (bold print in Tables 3a and b) may require the optional 3 hp fan motor. Please specify static range and motor horsepower when ordering. See model nomenclature. Sheave Adjustment The GL Series is supplied with variable sheave drive on the fan motor to adjust for differing airflows at various ESP conditions. Select an airflow requirement on the left side of Table 3a and b, then move horizontally to right under the required ESP. Note the sheave turns open, rpm and horsepower (non-bold = hp and bold = 3 hp) for that condition. Fully closed the sheave will produce the highest static capability (higher rpm). To adjust sheave position: loosen belt tension and remove belt, loosen set screw on variable sheave (on fan motor) and open sheave to desired position. Retighten set screw and replace belt and set belt tension as below. Belt Tensioning An overly loose belt will, upon motor start, produce a slippage 'squeel' and cause premature belt failure and or intermittent airflow. An overly tight belt can cause premature motor or blower bearing failure. Belt Tensioning Procedure 1) Remove belt from motor sheave ) Lift motor assembly 3) Loosen the 5/16" hex nuts on the grommet motor adjustment bolts ( per bolt). To increase the belt tension loosen the top hex nut. To decrease the belt tension loosen the bottom hex nut. 4) Turn the bolts by hand to the desired position then tighten the 5/16" hex nuts ( per bolt). 5) Lower the motor assembly 6) Install the belt 7) The belt should be tensioned using one of the following tension measurement methods: -Tighten until belt deflects approximately 1/" with very firm finger pressure. -Grasp belt midway between two pulleys and twist for a 90 rotation. Less than 90 is overtightened and more than 90 is too loose. -Use tensioning gauge method such as the Browning Belt Tensioner to set proper belt tension of 70-80 lbs. Page 1

Notes: -Motor position should not need adjustment. -The belt can also be accomplished by turning the 5/16" hex nuts to the desired position. -Motor sheave position is at mid position of each sheave. Thus the motor sheave is typically.5 turns open on a 5 turn sheave. Special Note for ARI Testing The Units should be setup as follows for rated airflow: GL 096-300cfm/3.5 turns and 0.4 in wg ESP GL 10-4000cfm/.5 turns and 0.5 in wg ESP Table b. GLH blower sheave and belt information. Model 096 10 Fan Motor Standard (hp) [kw] [1.5] [1.5] Large (hp) [kw] 3 [.] 3 [.] Standard Sheave (in) [cm] 1VP56 x 7/8 [.] 1VP56 x 7/8 [.] Low Static Sheave (in) [cm] 1VP56 x 7/8 [.] 1VP56 x 7/8 [.] High Static Sheave (in) [cm] 1VP56 x 7/8 [.] 1VP56 x 7/8 [.] Blower Wheel Size -Dia x W (in) [cm] - 10 x 10 [5.4 x 5.4] - 11 x 10 [7.9 x 5.4] Standard Sheave (in) [cm] AK61 X 1 [.5] AK66 X 1 [.5] Low Static Sheave (in) [cm] AK74 X 1 [.5] AK79 X 1 [.5] High Static Sheave (in) [cm] AK51 X 1 [.5] AK56 X 1 [.5] Belts Standard Belt A41 A43 Low Static Belt A44 A45 High Static Belt A40 A41 Rev.: 10/03/01 B Electrical - Blower Performance Table 3a. GLH 096 Blower Performance Airflow in CFM with dry coil and clean air filter. Rated CFM External Static Pressure (in. w.g.) 0.0 0.1 0. 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1. 1.3 1.4 1.5 BHP 0.84 0.91 0.97 1.04 1.10 1.17 1.4 1.31 1.37 1.44 1.51 1.58 1.65 1.7 600 RPM 1048 1095 1140 1184 16 167 1308 1346 1384 141 1457 1493 157 1560 TURNS OPEN 4.0 3.0.0 1.0 0.0 4.0 3.5.5.0 1.5 1.0 4.5 4.0 3.5 BHP 0.87 0.94 1.01 1.08 1.15 1. 1.9 1.36 1.43 1.51 1.58 1.65 1.73 1.80 1.87 1.95 800 RPM 101 1058 1104 1148 1191 13 173 1313 1351 1389 146 1461 1497 1531 1564 1597 TURNS OPEN 4.5 3.5.5.0 1.0 4.5 4.0 3.5.5.0 1.5 1.0 4.5 4.0 3.5 3.0 BHP 1.05 1.1 1.0 1.7 1.35 1.4 1.50 1.57 1.65 1.73 1.80 1.88 1.96.04.1.0 3000 RPM 1070 1114 1157 1199 139 180 1319 1356 1394 1430 1465 1501 1534 1568 1601 163 TURNS OPEN 3.5.5 1.5 0.5 4.5 4.0 3.0.5.0 1.5 0.5 0.0 4.0 3.5 3.0.5 BHP 1.5 1.3 1.40 1.48 1.56 1.64 1.7 1.80 1.88.00.04.13.1.9.38.46 300 RPM 116 1167 108 148 187 135 136 1400 1435 1470 1505 1538 1571 1604 1636 1667 TURNS OPEN.5 1.5 0.5 4.5 3.5 3.0.5.0 1.0 0.5 0.0 4.0 3.5 3.0.5.0 BHP 1.46 1.54 1.6 1.71 1.79 1.88 1.96.05.13..31.39.48.57.65.74 3400 RPM 1179 119 157 196 1333 1369 1406 1441 1475 1510 1543 1576 1608 1639 1671 170 TURNS OPEN 1.0 0.5 4.5 3.5 3.0.5 1.5 1.0 0.5 0.0 4.0 3.5 3.0.5.0 1.5 BHP 1.69 1.78 1.87 1.95.04.13..31.40.49.58.67.76.85.94 3600 RPM 130 168 1305 1341 1377 1413 1447 1481 1515 1548 1580 161 1643 1674 1705 TURNS OPEN 4.5 4.0 3.5 3.0.0 1.5 1.0 0.5 0.0 4.0 3.5 3.0.5.0 1.5 BHP 1.94.03.13..31.41.50.59.69.78.88.97 3800 RPM 180 1316 1351 1387 141 1455 1488 151 1553 1586 1617 1648 TURNS OPEN 4.0 3.0.5.0 1.5 1.0 0.5 4.0 3.5 3.0 3.0.5 Bold Face Requires 3 HP Motor A=Std Static/Std Mtr; B=Low Static/Std Mtr; C=High Static/Std Mtr; D=Std Static/Large Mtr; E=High Static/Large Mtr Units factory shipped with standard static sheave and drive at.5 turns open (300 cfm @ 0.6 in. ESP). Other speeds require field selection. ISO/ARI rating point with standard static sheave and drive at 3.5 turns open (300 cfm @ 0.4 in. ESP). Other speeds require field selection. For applications requiring higher static pressures, contact your local representative. Based on -10x10(R) blowers. Performance data does not include drive losses and is based on sea level conditions. Do not operate in gray region. All airflow is rated at lowest Voltage if unit is dual Voltage rated, i.e. 08V for 08-30V units. For wet coil performance first calculate the face velocity of the air coil (Face Velocity [fpm] = Airflow [cfm] / Face Area [sq ft]). Then for velocities of 00 fpm reduce the static capability by 0.03 in. wg, 300 fpm by 0.08 in. wg, 400 fpm by 0.1in. wg. and 500 fpm by 0.16 in. wg. Rev.: 09/4/01 B Page 13

Electrical - Blower Performance (cont.) Table 3b. GLH 10 Blower Performance Airflow in CFM with dry coil and clean air filter. Rated CFM External Static Pressure (in. w.g.) 0.0 0.1 0. 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1. 1.3 1.4 1.5 BHP 1.10 1.15 1.0 1.5 1.30 1.35 1.40 1.45 1.50 1.54 1.59 1.63 1.68 1.73 1.77 1.8 3400 RPM 1014 1043 107 110 119 1156 1183 109 134 160 185 1309 1333 1356 1380 1403 TURNS OPEN 3.0.5.0 1.0 0.5 4.5 4.0 3.5 3.0.5.0 1.5 1.0 4.5 4.0 4.0 BHP 1.6 1.31 1.37 1.4 1.48 1.53 1.58 1.63 1.68 1.74 1.79 1.84 1.89 1.94 1.99.04 3600 RPM 105 1081 1109 1136 1163 1190 116 141 166 191 1315 1338 136 1385 1408 1430 TURNS OPEN.5 1.5 1.0 0.5 4.0 3.5 3.0.5.5.0 1.5 1.0 4.5 4.0 3.5 3.5 BHP 1.44 1.50 1.56 1.61 1.67 1.73 1.78 1.84 1.89 1.95.00.06.11.16.1.6 3800 RPM 1090 1118 1145 117 1199 13 148 173 198 131 1345 1368 1391 1413 1435 1457 TURNS OPEN 1.5 1.0 0.0 4.0 3.5 3.0.5.0 1.5 1.0 1.0 0.5 0.0 3.5 3.5 3.0 BHP 1.63 1.70 1.76 1.8 1.88 1.94.00.06.11.17..8.34.39.45.50 4000 RPM 117 1154 1181 107 13 157 181 1306 139 135 1375 1398 140 1441 1463 1485 TURNS OPEN 0.5 4.5 4.0 3.5 3.0.5.0 1.5 1.0 0.5 0.0 0.0 3.5 3.0 3.0.5 BHP 1.84 1.91 1.98.04.10.16..8.34.40.47.53.59.65.71.77 400 RPM 1164 1191 117 141 166 191 1314 1337 1360 1383 1406 147 1449 1470 149 1513 TURNS OPEN 4.0 3.5 3.0.5.5.0 1.5 1.0 0.5 0.0 3.5 3.5 3.0.5.5.0 BHP.07.13.0.7.33.40.46.53.60.66.73.79.86.93.99 4400 RPM 10 17 151 176 1300 133 1346 1369 139 1414 1435 1457 1478 1500 150 TURNS OPEN 3.5 3.0.5.0 1.5 1.0 1.0 0.5 0.0 3.5 3.5 3.0.5.5.0 BHP.30.37.44.51.59.66.73.80.87.95 4600 RPM 137 16 187 1310 1333 1356 1379 140 143 1444 TURNS OPEN 3.0.5.0 1.5 1.0 0.5 0.0 4.0 3.5 3.0 Bold Face Requires 3 HP Motor Rev.: 09/4/01 B A=Std Static/Std Mtr; B=Low Static/Std Mtr; C=High Static/Std Mtr; D=Std Static/Large Mtr; E=High Static/Large Mtr Units factory shipped at ISO/ARI setting with standard static sheave and drive at.5 turns open (4000 cfm @ 0.5 in. ESP). Other speeds require field selection. ISO/ARI rating point with standard static sheave and drive at 3.5 turns open (300 cfm @ 0.4 in. ESP). Other speeds require field selection. For applications requiring higher static pressures, contact your local representative. Based on -11x10(R) blowers. Performance data does not include drive losses and is based on sea level conditions. Do not operate in gray region. All airflow is rated at lowest Voltage if unit is dual Voltage rated, i.e. 08V for 08-30V units. For wet coil performance first calculate the face velocity of the air coil (Face Velocity [fpm] = Airflow [cfm] / Face Area [sq ft]). Then for velocities of 00 fpm reduce the static capability by 0.03 in. wg, 300 fpm by 0.08 in. wg, 400 fpm by 0.1in. wg. and 500 fpm by 0.16 in. wg. Page 14

Low Voltage Thermostat wiring Thermostat Connections The thermostat should be wired directly to the CXM/ DXM board as shown in Figure 11. Consult the Thermostat section for specific wiring. Figure 8. Low Voltage Field Wiring (CXM shown- NOTE:For DXM, Y wiring at DXM1) Low Water Temperature Cutout - FP1 The CXM/DXM control allows the field selection of source fluid low temperature cutout points. The factory setting of FP1 is set for water (30 F). In cold temperature applications jumper JW3 (FP1- antifreeze 10 F) should be clipped as shown in Figure 1 to change the setting to 10 F, a more suitable temperature when using antifreezes. It should be noted that the extended range option should be specified to operate the GL Series at entering water temperatures below 60 F. Electrical - Low Voltage CXM CXM Control 1 Control Low Low Voltage Voltage Connector Connector Power Block CB Transformer Grnd L3 L L1 L3 L L1 L L1 Contactor -CC1 Contactor -CC Blower Contactor Rev.: 8/4/01 B Accessory Connections A terminal paralleling the compressor contactor coil has been provided on the CXM/DXM control of the GL line. "A" has been provided to control accessory devices, such as water valves, electronic air cleaners, humidifiers, etc. Note: This terminal should be used only with 4 Volt signals and not line voltage signals. This signal operates with the compressor contactor. See Figure 13 or the wiring schematic for details. Figure 10. Accessory Wiring Terminal Strip C A 4VAC Typical Water Valve Water Solenoid Valves When using external solenoid valves on ground water installations. Figure 14 illustrates a typical slow closing water control valve wiring which will limit wasted water during a lockout condition. A slow closing valve may be required to prevent water hammer. When using an AVM -Taco Slow Closing valves on GL Series equipment Figure 14 wiring should be utilized. The valve takes approximately 60 seconds to open (very little water will flow before 45 seconds) and it activates the compressor only after the valve is completely opened (by closing its end switch). Only relay or triac based electronic thermostats should be used with the AVM valve. When wired as shown, the valve will operate properly with the following notations: 1-The valve will remain open during a unit lockout. -The valve will draw approximately 5-35 VA through the Y signal of the thermostat. Note: This can overheat the anticipators of electromechanical thermostats. Therefore only relay or triac based thermostats should be used. Figure 9. Changing FP1-Low Water Temperature Cutout Setpoint Figure 11. Well Water AVM Valve Wiring Genesis CXM/DXM Series #1 C Y GL Unit BR BRG CCG CC C R JW3 JW Test FP1 FP Off On CXM PCB Comp Relay JW3-FP1 jumper should never be clipped on GL Series equipment 1 3 Heater Switch C Y Thermostat AVM Taco Valve Page 15

CXM/DXM or LonWorks Control Operation Note: See CXM/DXM AOM (part #97B0003N08) included separately with this heat pump or Lon Controller AOM (part #97B0013N01) included with any unit utilizing the Lon Controller Option. Typical Thermostat Selection and Wiring Electrical - Thermostat Practically any multi-stage thermostat will work with the GL Series. Figure 1 show s typical thermostat wiring. Figure 1a. Typical Manual Changeover heat/ cool thermostat wiring with GL unit & CXM Figure 1b. Typical Manual Changeover heat/ cool thermostat wiring with GL unit & DXM CXM 1 Typical T-Stat Heat/ Cool DXM Typical T-Stat Heat/ Cool Y Y Y1 Y1 W Y Y W1 O G R C AL1 O G R C L/X1 O/W G R C AL1 O G R C L/X1 CXM Y Y W O G R C AL1 Page 16

GL Three Phase with CXM Schematic GLH096-10 with CXM 08-30, 460-480, 575/60/3 PN 69663607 Rev. E 8/6/99 Page 17

GL Three Phase with DXM Schematic GLH096-10 with DXM 08-30, 460-480, 575/60/3 PN 69663608 Rev. B 8/4/99 Page 18

Operating Limits Unit Starting and Operating Conditions Environment This unit is designed for indoor installation only. Power Supply A voltage variation of +/ 10% of nameplate utilization voltage is acceptable. Starting Conditions GL Units Units start and operate in an ambient of 45 F with entering air at 50 F, entering water at 30 F and both air and water at the stated flow rates of 3 gpm per ton for initial winter start-up. Notes: 1. These are not normal or continuous operating conditions. It is assumed that winter start-up is to bring the building space up to occupancy temperatures.. Voltage utilization range complies with ARI Standard 110. Determination of operating limits is dependent primarily upon three factors: 1) return air temperature. ) water Cleaning and flushing of the WLHP piping system is the single most important step to ensure proper start-up and continued efficient operation of the system. Follow the instructions below to properly clean and flush the system: 1. Verify electrical power to the unit is disconnected.. Install the system with the supply hose connected directly to the return riser valve. Use a single length of flexible hose. 3. Open all air vents. Fill the system with the water. DO NOT allow system to overflow. Bleed all air from the system. Pressurize and check the system for leaks and repair appropriately. 4. Verify all strainers are in place. Start the pumps, and systematically check each vent to ensure all air is bled from the system. 5. Verify make-up water is available. Adjust make-up water appropriately to replace the air which was bled from the system. Check and adjust the water/air level in the expansion tank. 6. Set the boiler to raise the loop temperature to approximately 85 F. Open the a drain at the lowest point in the system. Adjust the make-up water replacement rate to equal the rate of bleed. 7. Refill the system and add trisodium phosphate in a proportion of approximately one pound per 150 gallons of water (or other equivalent approved cleaning agent). temperature and 3) ambient temperature. When any one of these factors is at minimum or maximum levels, the other two factors should be at normal levels to ensure proper unit operation. Extreme variations in temperature and humidity and corrosive water or air will adversely affect unit performance, reliability, and service life. Table 4. Operating Limits Air Limits Cooling Heating Min Ambient Air 45 F 45 F Rated Ambient Air 80 F 70 F Max. Ambient Air 100 F 85 F Min. Ent. Air 50 F 40 F Normal Entering Air db/wb 75/63-80/67 F 70 F Max Entering Air db/wb 110/83 F 80 F Water Limits Min. Entering Water *30 F 45 F (*0 F) Normal Entering Water 40-90 F 40-90 F Max. Entering Water 110 F 90 F Note: * with antifreeze, optional extended range insulation and low temperature cutout jumper clipped for antinfreeze. Piping System Cleaning and Flushing! CAUTION To avoid possible damage to a plastic (PVC) piping system, do not allow temperatures to exceed 110 F. Reset the boiler to raise the loop temperature to about 100 F. Circulate the solution for a minimum of 8 to 4 hours. At the end of this period, shut off the circulating pump and drain the solution. Repeat system cleaning if desired. 8. When the cleaning process is complete, remove the short-circuited hoses. Reconnect the hoses to the proper supply, and return the connections to each of the units. Refill the system and bleed off all air. 9. Test the system ph with litmus paper. The system water should be slightly alkaline (ph 7.5-8.5). Add chemicals, as appropriate, to maintain acidity levels. 10. When the system is successfully cleaned, flushed, refilled and bled, check the main system panels, safety cutouts and alarms. Set the controls to properly maintain loop temperatures.! CAUTION DO NOT use 'stop leak' or any similar chemical agent in this system. Addition of these chemicals to the loop water will foul the system and inhibit unit operation. Page 19

Unit and System Checkout BEFORE POWERING SYSTEM, please check the following: UNIT CHECKOUT Balancing/Shutoff Valves: Ensure all isolation valves are open, water control valves wired and open or coax may freeze and burst.! WARNING! Verify ALL water controls are open and allow water flow prior to engaging the compressor. Freezing of the coax or water lines can permanently damage the heat pump. Line Voltage and Wiring: Ensure Voltage is within an acceptable range for the unit and wiring and fuses/breakers are properly sized. Low voltage wiring is complete. Unit Control Transformer: Ensure transformer has properly selected control voltage tap. 08-30V units are factory wired for 08V operation unless specified otherwise. Entering Water and Air: Ensure entering water and air temperatures are within operating limits of Table 4. Low Water Temperature Cutout: Verify low water temperature cut-out on CXM/ DXM is properly set. Unit Fan: Manually rotate fans to assure free rotation and ensure blower wheel is secured to motor shaft. Be sure to remove any shipping supports if needed. DO NOT oil motors upon start-up. Fan motors are pre-oiled at factory. Verify unit fan speed selected is correct. Condensate Line: Condensate line is open and properly pitched toward drain. Water Flow Balancing: Verify inlet and outlet water temperatures are recorded for each heat pump upon startup. This check can eliminate nuisance trip outs and high velocity water flows that can erode heat exchangers. Unit Air Coil & Filters: Ensure filter is clean and accessible. Clean or 'season' air coil of all manufacturing oils if needed. Unit Controls: Verify CXM or DXM field selection options are proper and complete. SYSTEM CHECKOUT System Water Temperature: Check water temperature for proper range and also verify heating and cooling setpoints for proper operation. System ph: System water ph is 7.5-8.5. Proper ph promotes longevity of hoses and fittings. System Flushing: Verify all hoses are connected end to end when flushing to ensure debris bypasses unit heat exchanger and water valves etc. Water used in the system must be potable quality initially and clean of dirt, piping slag, and strong chemical cleaning agents. Verify all air is purged from the system. Air in the system can cause poor operation or system corrosion. Cooling Tower/Boiler: Check equipment for proper setpoints and operation. Standby Pumps: Verify the standby pump is properly installed and in operating condition. System Controls: Verify system controls function and operate in the proper sequence. Low Water Temperature Cutout: Verify low water temperature cut-out controls are provided for the outdoor portion of the loop or operating problems will occur. System Control Center: Verify control center and alarm panel for proper setpoints and operation. Miscellaneous: Note any questionable aspects of the installation.! WARNING! To avoid equipment damage, DO NOT leave system filled in a building without heat during the winter unless antifreeze is added to system water. Condenser coils never fully drain by themselves and will freeze unless winterized with antifreeze. Page 0

! WARNING! When the disconnect switch is closed, high voltage is present in some areas of the electrical panel. Exercise caution when working with energized equipment. 1. Turn thermostat fan position to ON. Blower should start.. Balance air flow at registers. 3. Adjust all valves to their full open position. Turn on the line power to all heat pump units. Verify ALL water controls are open and allow water flow prior to engaging the compressor. Freezing of the coax or water lines can permanently damage the heat pump. 4. Operate unit in cooling cycle. Room temperature should be approximately 45-100 F DB. For Start-up check, loop water temperature entering the heat pumps should be between 45 F and 110 F. 5. Two factors determine the operating limits of a ClimateMaster GL System (a) return air temperature, and (b) water temperature. When any one of these factors is at a minimum or maximum level, the other factor must be at normal levels to ensure proper unit operation. a. Adjust the unit thermostat to the warmest position. Slowly reduce thermostat setting until the compressor activates. b. Check for cool air delivery at the unit grille within a few minutes after the unit has begun to operate. Note: Units have a five minute time delay in the control circuit that can be eliminated on the CXM PCB as shown below in Figure 16. See controls description for detailed features of the control. c. Verify that the compressor is on and that the water flow rate is correct by measuring pressure drop through the heat exchanger using the Pete s plugs and comparing to Table 5. d. Check the elevation and cleanliness of the condensate lines. Dripping may be a sign of a blocked line. Check that the condensate trap includes a water seal. e. Refer to Table 6. Check the temperature of Figure 13. Test Mode Pins C R BR BRG Test CCG CC Off On CXM Board JW3 JW FP1 FP! WARNING! Co Re Unit Start Up Procedure Short test pins together to enter Test Mode and speed-up timing and delays for 0 minutes. both supply and discharge water. If temperature is within range, proceed with test. If temperature is outside operating range, check cooling refrigerant pressures in Table 7. Verify correct water flow by comparing unit pressure drop across the heat exchanger versus the data in Table 6. Heat of rejection can be calculated and compared to specification catalog. f. Check air temperature drop across the coil when compressor is operating. Air temperature should drop between 15 F and 5 F. g. Turn thermostat to OFF position. A hissing noise indicates proper functioning of the reversing valve. 6. Operate the heat pump in the heating cycle immediately after checking cooling cycle operation. Allow five (5) minutes between tests for pressure to equalize or cycle the reversing valve to equalize. a. Turn thermostat to lowest setting and set thermostat switch to HEAT position. b. Slowly turn thermostat to a higher temperature until the compressor activates. c. Check for warm air delivery at the unit grille within a few minutes after the unit has begun to operate. d. Check the temperature of both supply and discharge water. Refer to Table 6. If temperature is within range, proceed with test. If temperature is outside operating range, check heating refrigerant pressures in Table 7. e. Check air temperature rise across the coil when compressor is operating. Air temperature should rise between 0 F and 30 F. Heat of extraction can be calculated and compared to specification catalog. f. Check for vibration, noise, and water leaks. 7. If unit fails to operate, perform troubleshooting analysis (CXM/DXM AOM). If the check described fails to reveal the problem and the unit still does not operate, contact a trained service technician to ensure proper diagnosis and repair of the equipment. 8. When testing is complete, set system to maintain desired comfort level. 9. BE CERTAIN TO FILL OUT AND FORWARD ALL WARRANTY REGISTRATION PAPERS TO CLIMATEMASTER. Note: If performance during any mode appears abnormal, refer to the troubleshooting section of CXM/DXM AOM. To obtain maximum performance the air coil should be cleaned before start-up. A 10% solution of dishwasher detergent and water is recommended. Page 1

Table 5. Coax Water Pressure Drop Model GPM Pressure Drop (psi) 30 F 50 F 70 F 90 F 1 5.9 5.7 5.6 5.4 096 18 7.9 7.7 7.5 7. 4 10.6 10.3 10.0 9.7 3 14.3 13.8 13.4 13.0 15 5.1 4.9 4.8 4.6 10 3 8.5 8. 7.9 7.7 30 14.1 13.6 13. 1.8 40.5 1.7 1.0 0.4 Rev: 07/08/01 B Unit Start Up (cont.) Table 6. Water Temperature Change Through Heat Exchanger Water Flow Rate (GPM) Rise (Clg) Drop (Htg) For Closed Loop: Ground Source or 9-1 4-8 Cooler/Boiler systems at 3 gpm/ton For Open Loop: Ground Water systems 0-6 10-17 at 1.5 gpm/ton CXM/DXM Safety Control Reset Lockout - In Lockout mode, the Status LED will begin fast flashing. The compressor relay is turned off immediately. Lockout mode can be soft reset via the thermostat Y input or can be hard reset via the disconnect. The last fault causing the lockout will be stored in memory and can be viewed by going into test mode. Fault Retry - In Fault Retry mode, the Status LED begins slow flashing to signal that the control is trying to recover from a fault input. The CXM control will stage off the outputs and then try again to satisfy the thermostat "Y" input call. Once the thermostat input calls are satisfied, the control will continue on as if no fault occurred. If 3 consecutive faults occur without satisfying the thermostat "Y" input call, then the control will go to Lockout mode. The last fault causing the lockout will be stored in memory and can be viewed by going into test mode. Consult the CXM/DXM AOM for complete descriptions. Table 7. Typical Unit Operating Pressures and Temperatures Cooling** Heating Entering Water Suction Discharge Water Air Suction Discharge Water Air Water Temp F Flow GPM/ton 1.5 Pressure PSIG 75-85 Pressure PSIG 90-105 Superheat 5-40 Subcooling 1-0 Temp Rise F 1-4 Temp* Drop F DB 1-6 Pressure PSIG 34-39 Pressure PSIG 167-186 Superheat 1-16 Subcooling 1-4 Temp Drop F DB 7.6-8.4 Temp* Rise F 14-0 30.3 3.0 1.5 74-84 73-83 75-85 80-95 70-85 15-155 5-40 5-40 1-0 11-18 10-16 10-18 13-16 6-11 0-3 1-6 1-6 0-5 37-43 40-46 50-60 17-191 177-196 180-10 1-16 1-16 10-17 1-4 1-4 1-5 4.8-5.6 3.4-4. 10.8-11.9 16-16- 3-9 50.3 3.0 1.5 74-84 73-83 75-85 10-14 115-138 179-198 1-0 1-0 9-16 9-16 8-14 8-15 1-15 8-1 19-0-5 0-5 19-4 53-6 55-65 71-8 185-15 190-0 05-30 10-17 10-17 14-19 1-5 1-5 1-5 6.7-8.1 5.1-5.9 14.0-15. 4-30 5-31 8-34 70.3 3.0 1.5 74-84 73-83 75-85 168-186 158-175 9-51 9-16 9-16 9-17 8-14 8-1 8-15 1-17 7-1 18-1 19-4 19-4 17-3 73-85 76-88 85-95 10-38 15-4 0-60 14-19 14-19 18-8 1-5 1-5 -5 9.0-10. 6.7-7.9 14.4-16.6 30-37 31-38 3-39 90.3 3.0 74-84 73-83 18-41 08-30 9-17 9-17 8-14 8-1 10-14 6-11 17-3 17-3 90-100 95-105 5-65 30-70 18-8 18-8 -5-5 10.8-1.4 7.-8.3 33-41 35-4 1.5 77-87 80-30 8-15 10-5 17-0 15-0 110.3 76-86 70-310 8-15 10-4 9-13 15-0 3.0 75-85 60-300 8-15 10-5-10 15-0 *Based on Nominal 400 cfm per ton airflow and 70 F EAT htg and 80/67 F EAT cooling **Cooling air and water numbers can vary greatly with changes in humidity Subcooling is based upon the head pressure at compressor service port Page