CONTENTS Introduction and Characteristics. 1 Fire Alarm System Assembly Diagram.. 2 Fire Alarm Signal Flow Chart.. 2 Panel Descriptions 3 Standard

Similar documents
QA16 Addressable System

BT1 SINGLE ZONE FIRE ALARM SYSTEM OPERATORS MANUAL

RELEASE DEVICE CONTROLS

Installation, Operating and Maintenance Manual

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

HA-263K HA-263D. OWNER'S MANUAL Installation And Operation 8-ZONE ALARM CONTROL PANEL FOR HOME AND OFFICE PROTECTIONS OPEN THE CABINET FOR SERVICE

FEC400 Series. Installation Manual

MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL RELEASE DEVICES TEST WEEKLY TO ASSURE PROPER OPERATION OF RELEASE DEVICE/CONTROL PANEL

To operate the 5207 you can use either the built-in touchpad or the Model 5230 Remote Annunciator.

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

SECURIT 700L PLUS ENGINEERING MANUAL

HOME SECURITY MICROPROCESSOR CENTRAL UNIT HOME 5 USER S MANUAL

AL800ULADA. NAC Power Extender. Installation Guide

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

Operation and Maintenance Manual

EVO192 v3.0 Fire and Burglary What s New

System 800 Addressable Fire Detection & Alarm System

MODEL B2 INSTALLATION MANUAL

TECHNICAL DATA OBSOLETE

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels

reading carefully this guide, operating this system strictly on the standard procedure. System 816

reading carefully this guide, operating this system strictly on the standard procedure.

Model 17A00 Expansion Enclosure

Watchguard WGAP864 User Manual

Installation Guide & User Manual

Public Safety DAS Annunciator Panel

ACSI AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1089, REV. F

CPA6. Installation & User Guide. Intelligent Security & Fire Ltd. Compatible Equipment

AL600ULADA. NAC Power Extender. Installation Guide

Matrix2000. User Guide - CPD Advanced Analog Fire Alarm Control Panel 4 24 Zones. Version: 2.0 Revision: 1

Smoke Vent Control Panel RZN 4202 V1

MODEL ZAC ZONE ANNUNCIATOR/CONTROLLER DESIGNED FOR ZONE ANNUNCIATION AND MONITORING

V-MUL-033(A0) RADIOLINK BASE

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC.

NZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

Control Panel Engineering and Commissioning Instructions

PSN-1000 & PSN 1000(E) Installation Manual

AUR300C, AUR350C. Advanced Ultraviolet Burner Controller

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC.

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels

OPERATING GUIDE FOR YOUR RP1054D KEYPAD

SOFTWARE VERSION 2.20 CONTROL PANEL RESET: Installer lock must be unlocked. (Address 255: enter any value other than 147)

Master Code Arming Auto-Bypass Option - Home-Away Arming Entry Delay Off Arming

MODEL: SP12C7. (Portable 4 gas detector) Operating Manual

MANUAL. OEM (Unit) OZONE GENERATOR (100VA, 200VA and 300VA) INDEX

RANGER 7600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

CONTENTS. GST102A/104A/108A/116A Conventional Fire Alarm Control Panel Installation and Operation Manual

User Manual X8s Access Control System

Fire Control/Communicator

MODEL 5104B. Installation and Operation Manual. Fire Communicator. Part Number E, 09/04

Door Release Power Supply

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS

INTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3

3200 NON-ADDRESSABLE FIRE ALARM CONTROL PANEL

FlashGuard 3000B Dual Lighting System Troubleshooting Guide

Interscan Corporation. Instruction Manual Series Compact Portable Analyzer

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV

TABLE OF CONTENTS. FOR THE RECORD 15 PROGRAMMING WORK SHEETS 16 CONTROL PANEL WIRING DIAGRAM inside back cover

APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES

G34 AU1B (External Ultrasonic Sensor) Version 3

SOFTWARE VERSION 2.20 CONTROL PANEL RESET:

INDEX 1- Introduction The Control Pane...7l 4.1- The Control Panel 1 and 2 Loops The Control Panel 4 and 8 Loops...

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev

INSTALLATION GUIDE XR5FC AND XR5SL COMMERCIAL FIRE PANELS

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

TABLE OF CONTENTS TABLE OF CONTENTS 1

INSTALLATION AND INSTRUCTION MANUAL

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels

"SS90" SERIES CONTROLS MODEL C INSTALLATION MANUAL

D-TEK O P E R A T I N G I N S T R U C T I O N S V E HI C L E L O O P DETECTOR Johnston Parkway, Cleveland, Ohio 44128

Part 3 Troubleshooting

Operating Instructions

Security System. User s Guide for the Text Command Center

Quick Installation Manual LED Touch Keypad Autodial Wireless Alarm System

Fire Command Keypad. XR5 User s Guide

Electric Release Panel Wiring Tips

DH400. Accessories. NOTE: Set up for this sensor should be performed by an AAADM-certified installer.

GENERATOR SELF-TEST VERIFIER (GSV300) INSTALLATION INSTRUCTIONS

CORONA BURNER CONTROLLER INSTRUCTION MANUAL RCF15 EXCLUSIVE FOR FLAME ROD. Corona Corporation

DHR3. Accessories. NOTE: Set up for this sensor should be performed by an AAADM-certified installer. INSTALLATION INSTRUCTIONS

RANGER 8980E DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL

Installation Guide for AL400ULM. Multi-Output Access Control Power Supply Charger

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL

WM3000 WIRELESS MODULES

SPECIFICATIONS Control Panel Specifications Remote Keypad Specifications 21 zones including: (PC3000RK) Audible alarm output:

HEXA PROGRAMMING: STREAMLINED SECTION PROGRAMMING

(Cabinet Automatic Fire Extinguishing System)

INSPECTION AND TESTING FORM

Operator: Save these instructions for future use!

Securitron Magnalock Corporation S. 51 st St., Ste. 102 Phoenix, AZ Phone: (800) MAGLOCK

Installation Guide for models:

Installation Manual RINS1211-4

DL150 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

DIESEL ENGINE CONTROL UNIT DCU USER S MANUAL - N-2000 Lillestrøm, Norway Tel: (+47) Fax: (+47)

Functional Performance Test

Operation and Installation Guide. Fire Alarm Control Panel

Conventional Fire Alarm System 2014 V1.2

Transcription:

CONTENTS Introduction and Characteristics. 1 Fire Alarm System Assembly Diagram.. 2 Fire Alarm Signal Flow Chart.. 2 Panel Descriptions 3 Standard Detector Wiring Method. 4 Method of Wiring.. 5 Wiring Principle. 7 Operating Instructions 1.Fire Surveillance.. 8 2.Fire Alarm. 8 3.Reset. 8 4.Disconnection Alarm 8 5.Fire Alarm Test. 8 6.Disconnection Test.. 9 7.Standby Power. 9 8.Telephone Communication 9 9.Simultaneous Activation of Hydrants 10 10.Occurrence of Alarm Signal During Testing 10 11. Function of Attention SW Indicator 10 Installation Location 10 Important Notes On Maintenance 1.Normal State of Control Panel.. 10 2.Maintenance of Devices.. 10 3.Overall Maintenance 10 Trouble Shooting 1.Malfunction of Loop Indicator & Combination PBL Box.. 11 2.Functions of Fuses 12 3.Causes of Burnt Fuses & Inspection Guidelines.. 12 4.Combination PBL Fire Indicating Lamp & Alarm Bell malfunction 13 5.Loop Indicator Malfunction.. 13 6. Loop Indicator & Discon. Ind. Indicator light up. 13 7. Loop Indicator & Fire Indicator light up.. 14 Main Specifications.. 14

INTRODUCTION Due to the creativity and progress of fire fighting technology among highly developed countries, we never give up any chance to upgrade our new generation fire alarm control panel. We are not only pursuing higher technology level, but also compact design to meet high quality standard. CHARACTERISTICS This digital control panel primary use processor to handle relevant signal, which improve most weak points of traditional control panel. See below for more details. (1) The use of microprocessor has improved the unit s correctness that used to affected by bad characteristic of traditional devices. (2) Uses digital mode to transmit and control signal process, which highly increase the precision of signal. (3) Internal control voltage uses 5V that prevent burning circuit caused by traditional high voltage. (4) Module type design simplified entire system, function up-grade just has to change related module and no need big work to complete it. Thus, users are able to save big bucks on up-grade or repair cost. (5) Microprocessor can be revised according to user s request, its expand ability has much greater than traditional ones. (6) Shortage of terminal has not seen on this unit, one set of signal transfer and Aux. contacts are added for new design. (7) Loop test button and control board switches are electronic-type and used digital 0 and 1 signals for switch control signal. Also they will not damaged by abnormal high voltage because of undirected control high voltage and interfered by dust, these phenomenon usually happened on mechanical-type switch. (8) Electronic auto-inspect voltmeter is displayed by 3-color LED and it is easy for verification. 1

Annunciator AH-02124 508A TC TL 1 2 3 4 10 - - DC + BELL + COM E1 E2 E3 - LOAD + E4 502E E10 504B Fire Alarm Control Panel AH-00212 6

WIRING PRINCIPLE (1) Wiring Material Table (longer distance excluded; please refer to your local regulation) Item Specification Quantity Remarks Circuit line 1.0 ~ 1.2M/M N Depends on loop device, basically 1/loop. Common Line 1.2 ~ 1.6M/M N Area Bell 1.2 ~ 1.6M/M 2 Fire Indicating Lamp 1.2 ~ 1.6M/M 2 Manual Call Point 1.0 ~ 1.2M/M Parallel connect with detectors. Telephone 1.0 ~ 1.2M/M 1 T point on the back side of MCP MCP Push-down LED 1.0 ~ 1.2M/M 1 A point on the back side of MCP Earth 1.0 ~ 1.6M/M 1 AC Power 1.2 ~ 2.0M/M 2 Dependents on panel s load. (2) Wire Connection Box In order to facilitate inspection, maintenance and repair, every floor or appropriate area should install a Wire Connection Box in which connecting joints are provided. The Box case shall be waterproof and the wording Fire Fighting Only should labeled on an aluminum plate. (3) Wire-Point Labels and Joint Clips Inside the Control Panel and every Wire Connection Box, the wire points are to be attached to Label Covers or Label Stickers and then connected to the Y-clip. (4) Wiring Method Please refer to Page 4 ~ 6. (5) Terminal Resistor Connecting Method Every end of circuit line shall be fitted with a resistor (not more than one). If any loops in the control panel are not in use, should set Dip Switch on the Terminal to the ON position. (6) Area Labeling Once the wiring are laid, label the Loop Indicator with the Loop Indication Label provided by type or print for easy verification. (7) Wiring Record Once the external wiring is laid, a record of the detailed external wiring diagram shall be kept for future inspection and repair. 7

OPERATING INSTRUCTIONS 1. Fire Surveillance After installed system devices into the panel, connect with a AC220V 50Hz/60Hz supply source. The AC power indicator light up and Voltmeter indicate N (normal) position. Fire Indicating Lamp of the combination PBL box light up and surveillance begins. 2. Fire Alarm When a Detector has detected or a MCP press-down, it is an indication of fire. At this moment, the Fire Indicator (red) and the related loop indicator will light up simultaneously. The Main Bell and Area Bell will also sound. The Fire Indicating Lamp of the combination PBL box will become blinking. These activities indicate that the fire alarm is valid. (1) Main Bell Disable To stop the Main Bell from sounding, press Main Bell button the sounding stop immediately. (2) Area Bell Disable To stop the Area Bell from sounding, press Area Bell button the sounding stop immediately. 3. Reset Once the fire alarm is activated, the Fire Indicator and the related Loop Indicator will remain lighten. If the control panel requires starting the surveillance again after the previous fire situation has been resolve, just depress the Reset button. However, if detectors have been burnt or the MCP press-down not recovered, reset cannot be activated. For this matter, repair should be completed first, then depress the Reset button to reset the system. 4. Disconnection Alarm The panel is equipped with a Loop Disconnection Auto Indication function. Should there be a Circuit Break in certain areas, or detachment of the terminal resistor, the Discon. Ind indicator and related Loop indicator will light up simultaneously. The disconnection beeper will sound. Upon repair of the circuit, above mentioned situation will cease. (1) Disable Disconnection Sound To stop the disconnection sound, press Caution Snd button the sounding stop immediately. 5. Fire Alarm Test To perform fire alarm simulation test to test the functions of the fire alarm. (1) Auto Reset, Accum. SW, S. Trans. SW button Press down above three button, then perform loop alarm test, and reset automatically afterwards. 8

(2) Field Fire Alarm Test (A) Detector Test Method: uses a Tester, place it near detector for a few seconds. As soon as detector has back to normal condition, the fire alarm signal on the control panel will automatically reset itself. (B) MCP Push-down Test Method: Press the Manual Test Button to activate the alarm. Pull up the button and the fire alarm signal on the control panel will automatically reset itself. (3) Control panel self-test Repeat (1), press Alarm Test button, the indicator will light up, and then press Loop Test button (on the loop Indicator down side right corner). Once completed, press Auto Reset and Reset button, the control panel will back to surveillance status. 6. Disconnection Test (1) Press Discon. Test button, the indicator will light up, and then press Loop Test button (on the loop Indicator down side right corner). Once completed, press Auto Reset and Reset button, the control panel will back to surveillance status. (2) Field Disconnection Test: Just remove the detector. 7. Standby Power The control panel is equipped with automatic rechargeable batteries the stand-by power source (DC24V) shall be installed during operation. When the Main power source has been terminated, the AC Power indicator will light off and the stand-by PW indicator will light up. Voltmeter indicates to N (normal) position. (1) Standby Power Test The control panel should be powered by the main source under normal condition. To test the function of stand-by power source, press Batt. Test button and the control panel should response same as power - off situation. 8. Telephone Communication The control panel is equipped with a telephone communication device and two sets of compact phones. Whenever the communication is needed, just plug one of compact phones into the phone jack of field manual call point. Thus, the beeper inside the control panel will sound and Telephone indicator will light up. Then plug another compact phone into the phone jack of control panel, the beeper sound will stop and now communication is conducted. After the communication is complete, pullback the phone and signal will reset automatically. 9

9. Simultaneous Activation of Hydrants The panel has a voltage-free contact for signal transfer (A contact point x 2 set voltage pack = 24V/10A). It can be utilized to simultaneous activate Hydrant Activating Devices when the Fire Alarm is valid. 10. Occurrence of Alarm Signal During Testing If there is a alarm signal in any Circuit other than those under testing, the test must be end immediately and handle the alarm signal Circuit first. 11. Function of Attention SW Indicator When any of indicators on the display board is not set to ready status, the Attention SW indicator will blink. The signal will only cease when all indicators have been set to ready status. INSTALLATION LOCATION Please refer to your local regulation for installation details. IMPORTANT NOTES ON MAINTENANCE 1. Normal State of Control Panel (1) Normal Condition (Fire Surveillance Alert) Under normal conditions, the AC Power indicator should light up, Voltmeter to indicate N (normal) position. All indicators should be set to ready status and Fire Indicating Lamp on the Combination PBL Box should light up. (2) Power Failure When there is a power failure, the AC Power indicator will light off Standby PW indicator will light up the Voltmeter should indicate N (normal) position. 2. Maintenance of Devices (1) If maintenance may cause disturbances to public, appropriate coordination must be made before hand. (2) Priority should be given to those faulty devices in the area. (3) Maintenance should be scheduled at least twice a year and must include both physical and functional inspections. 3. Overall Maintenance Annual overall inspection should carry out by the professional institution or the original equipment manufacturer. Inspection records must be tabulated and kept by a responsible person or the department concerned, to ensure the public safety. 10

(1) Power Supply Check whether the external wiring of the panel its power consumption are within the safety regulation, whether the standby power conforms to specifications and whether the duration of power supply is within the safety regulation. (2) Control Panel (A) Fire Test: by Loop Test button (on the loop Indicator down side right corner) to check whether it is functioning properly. (B) Disconnection Test: by Loop Test button (on the loop Indicator down side right corner) to check whether it is functioning properly. (3) Detectors To perform a site test for the detectors in order to check whether they are functioning properly and also to check the condition of detector s Indicating LED (on the detector s base). (4) Manual Call Point Check for integrity of plastic plate, press-down button and condition of wiring inside the MCP. (5) Insulation Test The insulation between power terminal of control panel and earth shall have a value of 250V 20M and above. TROUBLE SHOOTING The Control Panel is produced with an advanced technology and delicate design that is easy to assemble. It requires no special skills to trouble-shoot a malfunction, thus avoiding any teething problems that might be encountered during maintenance. 1. Malfunction of Loop Indicator & Combination PBL Box The system devices are assembled with many single units (refer page 2), either the Detectors, Circuits or Combination PBL Box become defective, it will affect the functionality of the Control Panel. (1) Measure terminal AC with a Multi-meter for any voltage. (2) Check whether the AC SW inside the control panel is set to ON and the AC Power indicator on the Display Board is light up. (3) Check whether the AC Power indicator and the Voltmeter on the Display Board are functioning properly. The system should specify DC24V. (4) Check whether fuses are in good condition. Whether LED next to AC SW inside the control panel is light up. (5) Check whether the external devices and wiring conform to specifications, as stated in this handbook. 11

2. Function of Fuses The Control Panel inside has several fuses, each fuse with individual protection function. It must not be replaced with fuses that do not conform to specifications or are of low quality, otherwise we will not be liable for any damage. Burnt fuses are probably caused by external wiring error, short circuit or faulty external devices. (1) F1: Fuse for power source AC 220V. (2) F2: Fuse for standby power source. (3) F3: Fuse for Combination PBL Fire Indicating Lamp. (4) F4, F4-1: Fuse for area bell. (5) F5: Fuse for direct current source DC24V. 3. Causes of Burnt Fuses & Inspection Guidelines (1) F1 Fuse Burnt (A) It could be due to excessive voltage supply that causes the F1 Fuse to be burnt. (B) Conformance of Specification (lower-rated fuse may be burnt by a surge of current). (2) F2 Fuse Burnt (A) Check whether the standby power polarity + and have been in reversed position. (B) Similar to inspection guidelines for F1 Fuse, the standby power supply will pass through F2 Fuse when power supply from the Main Source has been cut-off. (3) F3 Fuse Burnt (A) Check for any short circuit wiring of the Fire Indicating Lamps or any short circuit of the Fire Indicating Lamp s bulb or bulb holder. (B) Check for any excessive current consumption of the Fire Indicating Lamp and check for any short circuit of solder wires on the Indicating Lamp s head. (C) Disconnect the outlet wire ( + and ) of the Fire Indicating Lamps and replace F3 Fuse. Measure the outlet for any voltage. (D) If the output of Control Panel is correct, then to connect the wire only after the external wiring have been repaired. (4) F4, F4-1 Fuse Burnt (A) Check for short circuit of the Area Bells and their respective wiring. (B) Check for excessive current consumption of the Area Bells. (C) Disconnect the outlet wire ( + and ) of the Area Bells and replace F4, F4-1 Fuse, measure the outlet current for correct output. (D) If the output of Control Panel is correct, then to connect the wire only after the external wiring have been repaired. 12

(5) F5 Fuse Burnt F5 Fuse is allocated to a secondary power and also serves as a second line protection for the panel s direct power source. If F5 Fuse burnt, should check whether other wiring (except F1, F2, F3, F4, F4-1) has power leakage happened. 4. Combination PBL Fire Indicating Lamp & Alarm Bell Malfunction (1) Remove the external wiring of the Fire Indicating Lamp and Area Bell. (2) Measure the ( + and ) outlet of Fire Indicating Lamp with a multi-meter and heck whether it is read DC24V. Then perform a fire test. Reset after it is completed. (3) Measure the ( + and ) outlet of the Area Bell with multi-meter. It should not have any voltage supplied. Then perform a fire test and a DC24V voltage should be recorded. Reset after the test. (4) When the test results conform to (2) and (3), it indicates that the control panel is functioning properly. The wires should only be connected after the external wiring have been repaired. 5. Loop Indicator Malfunction Based on our experience, most of the Loop Indicator malfunction due to incorrect external wiring. Other factors are mainly due to incorrect handling or incorrect wiring terminal inside the control panel. 6. Loop Indicator & Discon. Ind. Indicator light up When one or several Loop Indicator light up and Discon. Ind. Indicator blink simultaneously, it should be regarded as a signal of circuit break. In this instance, inspection and repairs should be carried out in the following manner: (1) Check for any loops in the control panel are not in use, if yes check whether the Dip Switch on the Terminal is in the ON position. (2) Remove the circuit that in trouble; the disconnection signal should immediately go off. (3) If test results conform to (2), it indicates that the control panel is functioning properly. The wire shall only be connected after the external wiring has been repaired. (4) Inspect the external circuit to check whether last detector has been installed one End of Line Resistor, or improperly installed. (5) Check for any break in the external wiring as well as any dislocation of detectors. (6) Set the multi-meter to mode and measure the malfunction circuit resistance value. The resistance value between the circuit line and common line should be around 10k. (7) After removal of the circuit line, there should not be any voltage between the circuit line and common line. The wire shall only be connected after the external wiring has been repaired. 13

7. Loop Indicator & Fire Indicator light up When one or more Loop indicators and FIRE Indicator light up simultaneously, it should be regarded as a fire alarm signal. The inspection and repair guidelines are as follows: (1) Remote the circuit that in trouble. Measure between the circuit line and common line to check for short circuit or resistance value is normal (normal value is around 10k ). (2) After remote the circuit that in trouble, the control panel must be reset. At this moment, the loop indicator should carry a circuit break signal. To cut off the signal, set the Dip Switch on the Terminal to ON position. After repairing the circuit line, re-activate the Dip Switch on the Terminal and then re-connect the external circuit line. (3) Check for presence of any short circuit of the external wiring, or any defective detectors. MAIN SPECIFICATION Descriptions Remarks Power AC 220V 50/60Hz Others also available Voltage range Nominal voltage + 20% Standby power DC 24V 800mA ~ 2100mA With auto adjustment function Charging voltage, current DC 26V 100mA ~ 400mA Loop voltage, current DC 24V; short circuit under 5V 30mA Exterior resistance Round-trip under 50 # of heat detector Except No limit connected electronic- type # of smoke detector Manufactured by 30/loop connected Horing Lih # of fire indicating lamp connected # of loop x 1.2 # of alarm bell connected # of loop x 1.2 Digital Switch 500000 cycles Min. reliability End of line resistor 10K One per loop Material 1.2m/m steel plate Color Ivory white Others also available Accessory functions Aux. Contacts for signal transfer and computer monitor, MCP contact and phone Jack. Optional selections 14

HORING LIH INDUSTRIAL CO., LTD.