Zeeco, Inc. Doc. No Tulsa, Ok Cover Page GLSF-14 Free-Jet and RWSF-4 Radiant Wall Burners. Range Fuels Soperton Plant, LLC

Similar documents
Burners Flares Incinerators Vapor Combustion

Rental Boiler Specifications (Nebraska Boiler)

LOW-NOX BURNER RETROFIT CHALLENGE

B - BEST O - ORIGINAL. R - Renown. N - Name. I n H e a t e r s

European Ethylene Producers Conference (EEPC) October 24-26, 2012 Flame Interaction and Rollover Solutions in Ethylene Cracking Furnaces

Fired Heaters Key to Efficient Operation of Refineries and Petrochemicals

A-8-01 Typical questions and answers on the boiler specifications on tender and boiler contract documents

DESIGNING A COMBUSTION AIR/GAS PRE MIX SYSTEM FOR RED RAY INFRARED PROCESS BURNERS

Zeeco recently had the opportunity

"HC" AIRFLO. In-duct firing line burner

PBG PACKAGED GAS BURNER

Specifications of V-Line burners

SECTION FLUID HEATER. 1.2 RELATED SECTIONS A. Division 16 - Equipment Wiring Systems: Electrical characteristics and wiring connections.

Technical Specification

BURNERS/ FLARES. VAREC BIOGAS 244W Series WASTE GAS BURNER & IGNITION SYSTEM

OPERATING AND MAINTENANCE MANUAL

NMC Nozzle Mix Gas/Oil Combination Burners

Technical Specification

FUEL-FIRED VERTICAL TUBELESS BOILERS

Internet Version for Reference Only INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #

Overview of Gas Range Types

NOx REDUCTION EXPERIENCE ON NATURAL GAS FIRED TURBO FURNACES

Technical Specification

INDITHERM. Low temperature gas burners

ECLIPSE AH-MA BURNERS. Air Make-Up Burners. Designed for trouble-free make-up or process air heating. Ready for the world

DESCRIPTION, CAPACITIES, SPECIFICATIONS, APPLICATIONS

Bryan Flexible Water Tube. Ultra-High Efficiency Condensing Hot Water Boilers. 3,000,000 BTUH Natural Gas Fired

Specifications of MULTIFIRE burners

ECLIPSE AIR HEAT BURNERS Series AH, DAH, TAH & CAH

DELTA-TE III. Nozzle-mix line burner

INDUSTRIAL MICRODIFFUSION OIL BURNERS

Product Information. Model: HG, HL, HLG Burner Sizes: 10, 13, 15, 17, 20, 21, 25 GENERAL DESCRIPTION U.L. STANDARD EQUIPMENT

Type CG Series Forced Draft Gas Burner

Power Flame Incorporated

Technical Specification

Power Flame Incorporated

Internal ridged board 1" x 1.5 foil face installation shall be installed on roof, walls and base of casing.

Fuel-Fired Vertical Tubeless Boilers

Technical Specification

A New Standard of Excellence

SECTION HEATING BOILERS

1500 SERIES SMALL CAPACITY ULTRA 2 LOW NO X TM BURNER

T-CLASS GAS-FIRED UNIT HEATERS Separated Combustion - Direct Vent - Horizontal - 60 HZ. Thermal Efficiency - up to 82% Input - 40,000 to 300,000 Btuh

FLAT FLAME AND EXCESS AIR BURNERS

Direct Fired Heater Model AD Specification

INFRA-RED BURNERS BR-70 SERIES FEATURES APPLICATIONS. Bulletin E3005 rev03 31/01/00

GP COMBUSTION EQUIPMENT INC 100 Sheldon Dr., Units 16/17 Cambridge, Ontario N1R 7S7. Model C Forced Draft Burners. Natural Gas or Propane MODEL C10

Multi-Position Gas Furnaces

product Industrial burners Industrial burners sizes 30 to 70 flexible and reliable Information on oil, gas and dual fuel burners

Burner Comparisons. Typical Competitor s Burner

SECTION DIRECT GAS-FIRED INDUSTRIAL HEATING AND VENTILATING UNITS

.2 Section Waste Management and Disposal..4 Section Vibration Isolation and Seismic Control Measures.

PROFIRE -E SERIES BURNERS

THE WORLD S FIRST FLAMELESS CRUDE HEATER

Title: Standard Operating Procedure for Measurement of Total Hydrocarbon Using a Flame Ionization Detection

LFL Monitoring. MEGTEC Systems

INDITHERM. Low temperature gas burners

M3RL Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. High Efficiency / Direct Vent Condensing Downflow Gas Furnace

STR-Series Indirect-Fired Air Turnover Units

TABLE OF CONTENTS BRADFORD WHITE BOILERS

Design Guide 111 9/25/2008. Eclipse Winnox Burners WX Series Version 1

40 SERIES GAS BURNER MODEL 400 NATURAL GAS/PROPANE INSTALLATION INSTRUCTIONS AND OWNER S HANDBOOK

Shell Martinez Refinery Callidus CUBL Burners

Section (CSI ) I-Series Drum & Tube (04/23/10) Indirect-Fired Heating & Ventilating

INDUSTRIAL WATERTUBE BOILERS

ABB. Measure IT Uvisor System Flame scanner for fuel oil and coal flame. UR600 IR Mod flame scanner Product Data Sheet (rev.

Solutions to Pollution

Direct Gas-Fired Make-Up Air

Coker Heaters Performance Improvement. Don Tran LyondellBasell, Houston Refinery & Ashutosh Garg Furnace Improvements Sugar Land, TX

COMPACT UNIT HEATERS Low Profile - Horizontal - 60 HZ. Steady-State Efficiency - up to 81% Input - 30,000 to 75,000 Btuh

Installation & Service Instructions for Jackson & Church Flexaire Packaged Furnaces SDF-125 thru SDF-400 Gas Firing

Typical Specifications For: ADVANTUS TM DOMESTIC HOT WATER SUPPLY Models AV(W)0500 AV(W)4000

WATER HEATERS / BOILERS GSB8-E. Gas-Fired Steam Boiler PRODUCT SPECIFICATIONS. AFUE up to 82.7% Heating Input 75,000 to 299,000 Btuh GSB E

Typical Specifications For: ADVANTUS TM DOMESTIC HOT WATER SUPPLY Models AV(W)0500 AV(W)4000

SUBMITTAL SCHEDULE & DATA

Bosch Greentherm T9800 SE 199 Gas Tankless Water Heater

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2000 EDITION

Multi-Position Gas Furnaces

2x58 MW Coal Fired Power Plant at Mauritius

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER

GSB8. CONSERVATOR Gas-Fired Steam Boiler. AFUE up to 82.7% Heating Input 75,000 to 299,000 Btuh GSB S MODEL NUMBER IDENTIFICATION FEATURES

Bert Uneken, Field Engineering Manager Ruben Kranenburg, Technical Support

Hybrid Series. Innovative Heating Solutions continentalheatingandcooling.com

Residential/Commercial Gas Condensing Tankless Models

Lanemark Midco HMA2A Series Air Heating Burner and DB Duct Burner System Application Manual

Engineering Bulletin. Gas Heat. for M-Series and T-Series Climate Changer Air Handlers CLCH-PRB010-EN. March 2004

DESCRIPTION AND INSTALLATION

Direct Fired Units w/ Packaged Cooling

Hybrid Series. Innovative Heating Solutions continentalheatingandcooling.com

Originators of the Flexible Water Tube design

Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA MATERIALS MANAGEMENT

There are two devices used together for heating crude oil in petroleum refinery as in figure (1), and these devices are:

Originators of the Flexible Water Tube design

Installation Instructions

HORIZONTAL FIRE TUBE BOILERS Piping (HVAC) Pumping Equipment (HVAC).

MBCE-110/230UV Flame Sensor Module

Glossary. Carbon Dioxide (CO 2

ECLIPSE INFORMATION GUIDE

Eclipse AirHeat Burners

12711 TOWNEPARK WAY / LOUISVILLE, KY / / FAX

Transcription:

Zeeco, Inc. Doc. No. 17928-601 Tulsa, Ok Cover Page + 10 Client : P.O.: SOP 10606 Item : Burner Data Sheets Zeeco S.O.: 17928 GLSF-14 Free-Jet and RWSF-4 Radiant Wall Burners FOR AT Soperton, Georgia Burner Data Sheets Rev By Date Description 0 RDR 24-Mar-09 First Issue 1 RDR 7-Apr-09 Revised per Customer Comments Revised Plant Site Elevation

Burner Design Criteria Customer: End User: Jobsite: Soperton, Georgia Heater Tag Number: Reformer (Floor Burners Option A) Type of Heater: Heating of Product Burner Designation: GLSF Burner Description: Round Flame, "Free-Jet" Patent Info: US Patent # 6,499,990 Revision Table Rev # Issue Description of Revision Rev Date Name 1 4 Revised per Customer Comments - Changed Plate Site Elevation 7-Apr-09 RDR 0 3 Revised to Project S.O. 17928 24-Mar-09 Ryan Roberts B 2 Revised to correct heater identification 11-Feb-09 Jesse S. Chambers A 1 Original Issue. 4-Feb-09 Jesse S. Chambers Burners Reformer (Floor Burners Option A) Combustion Systems Round Flame, "Free-Jet" SHEET 1 OF 5

GENERAL INFORMATION Customer Name End User Name Jobsite Soperton, Georgia FURNACE DATA / SITE CONDITIONS Furnace Tag Number Reformer (Floor Burners Option A) Plant Site Elevation Above Sea Level, ft 500 1 Type of Furnace Heating of Product Ambient Air Temperature ( F) 70 Refractory Thickness, in 12 Minimum Relative Humidity 0% Heater Steel Thickness, in 0.25 Normal Relative Humidity 50% Type of Draft Induced Maximum Relative Humidity 100% Direction of Firing Vertical, Up Heater Height (to convective sec.), ft 20.0 Mounting Direction Vertical, Up, Near Wall Heater Width (ft) 22.0 Heater Length, ft 20.0 PROCESS DATA Gas Maximum Heat Release (MM BTU/hr) 11.000 Available Combustion Air dp (in H2O) 0.500 Normal Heat Release (MM BTU/hr) 9.000 Combustion Air Temperature ( F) 70 Minimum Heat Release (MM BTU/hr) 2.200 Furnace Temperature ( F) 2200 Turndown 5.00 Combustion Test Available Fuel Pressure (psig) 25 Design Excess Air 15% GENERAL BURNER DESCRIPTION Burner Model / Size GLSF 14 Flame Shape Round Flame Burner Description Round Flame, "Free-Jet" Maximum Predicted Flame Length (ft) 16.4 Number Required 4 Maximum Predicted Flame Width (ft) 2.5 Oil Gun Model / Size N/A Pilot Model JM-1S-E Atomizing Media N/A Pilot Ignition Method Electric Ignition Atomizing Type N/A Pilot Heat release (Btu/hr) 90,000.00 Available Atomizing Pressure (psig) N/A Pilot Operating Pressure (psig) 10 Atomizing Media Rate (# / # fuel) N/A Pilot Fuel Natural Gas Flame / Ionization Rod Provided None NOISE DATA (SINGLE BURNER BASIS) Predicted @ 63 Hz (db) 85 Predicted @ 2000 Hz (db) 72 Predicted @ 125 Hz (db) 89 Predicted @ 4000 Hz (db) 74 Predicted @ 250 Hz (db) 82 Predicted @ 8000 Hz (db) 72 Predicted @ 500 Hz (db) 86 Guar. Noise Level @ 3 ft from burner, dba 85 Predicted @ 1000 Hz (db) 76 GENERAL BURNER COMMENTS 2-1. The above noise emissions are "Sound Pressure Level". 2-2. The above heat releases are based on the lower heating value 'LHV' of the fuel(s). 2-3. The burners are sized based on the maximum relative humidity case, as listed above. Burners Reformer (Floor Burners Option A) Combustion Systems Round Flame, "Free-Jet" SHEET 2 OF 5

FUEL GAS CHARACTERISTICS OFF GAS CHARACTERISTICS Composition Syn Gas Nat Gas % vol % vol CH4 (methane) 34.30% 94.48% C2H6 (ethane) 2.97% C3H8 (propane) 0.37% C4H10 (butane) 0.05% C5H12 (pentane) 0.01% C6H14 (hexane) 0.08% C5H10 (cyclopen) C6H12 (cyclohex) C2H4 (ethene) C3H6 (propene) C4H8 (butene) C5H10 (pentene) C6H6 (benzene) C5H8 (isoprene) CO2 13.30% 1.03% H2O O2 N2 0.98% SO2 H2S CO 23.70% NH3 H2 28.70% AR Total (vol%) 100% 100% Excess O2 (vol%) 2.86% 3.00% LHV (Btu/scf) 467 921 S.G. 0.64 0.59 TEMP ( F) 70.00 70.00 M.W. 18.65 17.22 FUEL OIL CHARACTERISTICS LHV (BTU/lb) S.G. @ 60 F TEMP ( F) API GRAVITY @ 60 F NITROGEN (wt%) VANADIUM (PPM) SULFUR (wt%) CATALYST PRESENT GENERAL OIL TYPE Burners Reformer (Floor Burners Option A) Combustion Systems Round Flame, "Free-Jet" SHEET 3 OF 5

BASIS OF EMISSIONS INFORMATION Furnace Temperature ( F) 2,200.00 Excess Combustion Air (%) 15% Gas Oil Combustion Air Temperature ( F) 70 Relative Humidity (%) 50% Heat Release for Guarantee (MM Btu/hr) 11.000 to 9.000 LHV EMISSIONS INFORMATION PREDICTED GUARANTEED (ppmv) (#/MMBtu) (ppmv) (#/MMBtu) NOx Syn Gas 17 0.022 45 0.058 NOx Nat Gas 16 0.021 45 0.060 CO - Gas 0 0.000 50 0.039 UHC - Gas 1 0.001 15 0.007 Particulate - Gas 2 0.002 15 0.013 VOC - Gas 0 0.000 15 0.019 EMISSIONS COMMENTS 4-1 The above listed UHC emissions are based upon UHC being defined as free "methane" as the result of incomplete combustion due to the supplied combustion equipment as stated in these data sheets. 4-2 The above listed VOC emissions are based upon VOC being defined as free "propane" as the result of incomplete combustion due to the supplied combustion equipment as stated in these data sheets. 4-3 The above listed Particulate emissions are based upon Particulate being defined as free "ethane" as the result of incomplete combustion due to the supplied combustion equipment as stated in these data sheets. This excludes ash, sand and heavy metals in the fuel oil. 4-4 NOx guarantees are based on the furnace temperature, combustion air temperature, excess combustion air and the fuel gas compositions as specified the Zeeco Burner Data Sheets. 4-5 The emissions guarantees above are for operation between maximum and normal heat release. 4-6 The emissions guarantees as stated above are based upon operation with the % excess air, temperature, furnace temperature, and fuel temperatures as stated in these data sheets. 4-7 See Notes & Clarifications section for more information concerning noise emissions. 4-8 See Notes & Clarifications section for more information concerning the above emissions guarantees. 4-9 Zeeco takes exception to any SOx guarantees since SOx production is based upon the amount of Sulfur in the fuel stream and the equilibrium conditions in the furnace. 4-10 The above listed predictions & guarantees are based on the lower heating value 'LHV' of the fuel(s). 4-11 All ppmv and/or mg/nm3 guarantees are corrected to 3% O2 dry basis. 4-12 All CO, UHC, Particulate and VOC emissions guarantees are based on the furnace local temperature at the burner being above 1100 F (593 C). Burners Reformer (Floor Burners Option A) Combustion Systems Round Flame, "Free-Jet" SHEET 4 OF 5

BASIS OF SCOPE OF SUPPLY Burner Plenum Burners are supplied with individual, manufactured plenums (windboxes). Plenum General Description Integral, round-shaped air plenum, fabricated construction Material A-1011 Gr 30 Carbon Steel Thickness 10 gauge (3.58 mm) material Internal Insulation / thickness Semi-rigid Mineral Board, Fibrex 1280 1.00 (in) Method of Construction Skip-Welded Construction Inlet Air Control Burners are supplied with air control. Mode of Operation Damper assembly, complete with self-locking handle & position indicator Tight Shutoff for Damper Blades Seal strips not required, 10% air leakage with damper in closed position Mechanism Description Opposed motion, dual carbon steel blades & 304 SS shafts, linked with a quarter gear system Bearing construction Supplied with bearings c/w grease fittings for damper shafts Burner Tile Burner is supplied with a refractory tile assembly. Regen Tile Composition Secondary Tile Composition 60% Al2O3 Needle Construction Required Rated Service Temperature 3000 F (1648 C) Temperature of Pre-firing 500 F (260 C) Noise Attenuation Method Insulated muffler assembly Fuel Delivery System Burners are supplied with a gas tip and manifold assembly, with a single point connection Gas manifold description Manufactured pipe manifold, constructed from schedule 40 carbon steel pipe Gas Tip Material 310 or HK (ASTM A-297) stainless steel Gas Riser Material 1/4" (6.35 mm), schedule 40, 304 stainless steel pipe Fuel Gas Connection 150#, Carbon Steel Flange, RFWN, A-105 Pilot Mixer - Tip Material Carbon Steel and/or Cast Equivalent - 310 SS or Cast equivalent tip Pilot Gas Connection 150#, Carbon Steel Flange, RFWN, A-105 Separate Off Gas Manifold Off Gas Tip Material Off Gas Riser Material Off Gas Connection Oil Tip / Atomizer Material Oil & Steam Connections Painting Requirements Zeeco Standard Carbon Steel Surface Preparation SSPC-SP-2 // ST-2 - Hand Tool Cleaning Primer Red Oxide Primer Primer Thickness One (1) Shop Coat 1st Paint Coat 1st Paint Coat Thk. Top Coat Top Coat Thickness Tile Case Assembly / Mounting Plate Burners are supplied with a tile case assembly Mounting Template - heater floor cutout Lifting Lugs Pressure Taps Required for Windbox Scanner Connection 1" swivel connection, one (1) per burner Ignition / Sight Ports Two (2) ports provided, 2" (50.8 mm), c/w pivoting slide plates Electrical Information Pilot Fittings and Ship Loose Items Pilot Conduit Fittings UL / CSA, Class 1, Div. 2 UV Scanners Burners Reformer (Floor Burners Option A Combustion Systems Round Flame, "Free-Jet" SHEET 5 OF 5

Burner Design Criteria Customer: End User: Jobsite: Heater Tag Number: Type of Heater: Burner Designation: Burner Description: Soperton, Georgia Devol (Radiant Wall Burner) Heating of Product RWSF Radiant Wall, Min-Emissions Revision Table Rev # Issue Description of Revision Rev Date Name 1 4 Revised per Customer Comments - Revised Plant Site Elevation 7-Apr-09 RDR 0 3 Revised to Project S.O. 17928 24-Mar-09 Ryan Roberts B 2 Revised to correct heater identification 11-Feb-09 Jesse S. Chambers A 1 Original Issue. 4-Feb-09 Jesse S. Chambers Burners Devol (Radiant Wall Burner) Combustion Systems Radiant Wall, Min-Emissions SHEET 1 OF 5

GENERAL INFORMATION Customer Name End User Name Jobsite Soperton, Georgia FURNACE DATA / SITE CONDITIONS Furnace Tag Number Devol (Radiant Wall Burner) Plant Site Elevation Above Sea Level, ft 500 1 Type of Furnace Heating of Product Ambient Air Temperature ( F) 70 Refractory Thickness, in 12 Minimum Relative Humidity 0% Heater Steel Thickness, in 0.25 Normal Relative Humidity 50% Type of Draft Induced Maximum Relative Humidity 100% Direction of Firing Wall Heater Height (to convective sec.), ft 20.0 Mounting Direction Horizontal Wall Heater Width (ft) 4.5 Heater Length, ft 20.0 PROCESS DATA Gas Maximum Heat Release (MM BTU/hr) 1.250 Available Combustion Air dp (in H2O) 0.500 Normal Heat Release (MM BTU/hr) 1.100 Combustion Air Temperature ( F) 70 Minimum Heat Release (MM BTU/hr) 0.450 Furnace Temperature ( F) 1850 Turndown 2.78 Combustion Test Available Fuel Pressure (psig) 30 Design Excess Air 15% GENERAL BURNER DESCRIPTION Burner Model / Size RWSF 4 Flame Shape Round Flame Burner Description Radiant Wall, Min-Emissions Maximum Predicted Flame Length (ft) Number Required 36 Maximum Predicted Flame Width (ft) Oil Gun Model / Size N/A Pilot Model JM-1S Atomizing Media N/A Pilot Ignition Method Manual Ignition Atomizing Type N/A Pilot Heat release (Btu/hr) 90,000.00 Available Atomizing Pressure (psig) N/A Pilot Operating Pressure (psig) 10 Atomizing Media Rate (# / # fuel) N/A Pilot Fuel Natural Gas Flame / Ionization Rod Provided None NOISE DATA (SINGLE BURNER BASIS) Predicted @ 63 Hz (db) 85 Predicted @ 2000 Hz (db) 72 Predicted @ 125 Hz (db) 89 Predicted @ 4000 Hz (db) 74 Predicted @ 250 Hz (db) 82 Predicted @ 8000 Hz (db) 72 Predicted @ 500 Hz (db) 86 Guar. Noise Level @ 3 ft from burner, dba 85 Predicted @ 1000 Hz (db) 76 GENERAL BURNER COMMENTS 2-1. The above noise emissions are "Sound Pressure Level". 2-2. The above heat releases are based on the lower heating value 'LHV' of the fuel(s). 2-3. The burners are sized based on the maximum relative humidity case, as listed above. Burners Devol (Radiant Wall Burner) Combustion Systems Radiant Wall, Min-Emissions SHEET 2 OF 5

FUEL GAS CHARACTERISTICS OFF GAS CHARACTERISTICS Composition Syn Gas Nat Gas % vol % vol CH4 (methane) 34.30% 94.48% C2H6 (ethane) 2.97% C3H8 (propane) 0.37% C4H10 (butane) 0.05% C5H12 (pentane) 0.01% C6H14 (hexane) 0.08% C5H10 (cyclopen) C6H12 (cyclohex) C2H4 (ethene) C3H6 (propene) C4H8 (butene) C5H10 (pentene) C6H6 (benzene) C5H8 (isoprene) CO2 13.30% 1.03% H2O O2 N2 0.98% SO2 H2S CO 23.70% NH3 H2 28.70% AR Total (vol%) 100% 100% Excess O2 (vol%) 2.86% 3.00% LHV (Btu/scf) 467 921 S.G. 0.64 0.59 TEMP ( F) 70.00 70.00 M.W. 18.65 17.22 FUEL OIL CHARACTERISTICS LHV (BTU/lb) S.G. @ 60 F TEMP ( F) API GRAVITY @ 60 F NITROGEN (wt%) VANADIUM (PPM) SULFUR (wt%) CATALYST PRESENT GENERAL OIL TYPE Burners Devol (Radiant Wall Burner) Combustion Systems Radiant Wall, Min-Emissions SHEET 3 OF 5

BASIS OF EMISSIONS INFORMATION Furnace Temperature ( F) 1,850.00 Excess Combustion Air (%) 15% Gas Oil Combustion Air Temperature ( F) 70 Relative Humidity (%) 50% Heat Release for Guarantee (MM Btu/hr) 1.250 to 1.100 LHV EMISSIONS INFORMATION PREDICTED GUARANTEED (ppmv) (#/MMBtu) (ppmv) (#/MMBtu) NOx Syn Gas 25 0.033 65 0.084 NOx Nat Gas 24 0.032 65 0.087 **Emissions guarantees are made without the pilot in operation. CO - Gas 0 0.000 50 0.039 UHC - Gas 1 0.001 15 0.007 Particulate - Gas 2 0.002 15 0.013 VOC - Gas 0 0.000 15 0.019 EMISSIONS COMMENTS 4-1 The above listed UHC emissions are based upon UHC being defined as free "methane" as the result of incomplete combustion due to the supplied combustion equipment as stated in these data sheets. 4-2 The above listed VOC emissions are based upon VOC being defined as free "propane" as the result of incomplete combustion due to the supplied combustion equipment as stated in these data sheets. 4-3 The above listed Particulate emissions are based upon Particulate being defined as free "ethane" as the result of incomplete combustion due to the supplied combustion equipment as stated in these data sheets. This excludes ash, sand and heavy metals in the fuel oil. 4-4 NOx guarantees are based on the furnace temperature, combustion air temperature, excess combustion air and the fuel gas compositions as specified the Zeeco Burner Data Sheets. 4-5 The emissions guarantees above are for operation between maximum and normal heat release. 4-6 The emissions guarantees as stated above are based upon operation with the % excess air, temperature, furnace temperature, and fuel temperatures as stated in these data sheets. 4-7 See Notes & Clarifications section for more information concerning noise emissions. 4-8 See Notes & Clarifications section for more information concerning the above emissions guarantees. 4-9 Zeeco takes exception to any SOx guarantees since SOx production is based upon the amount of Sulfur in the fuel stream and the equilibrium conditions in the furnace. 4-10 The above listed predictions & guarantees are based on the lower heating value 'LHV' of the fuel(s). 4-11 All ppmv and/or mg/nm3 guarantees are corrected to 3% O2 dry basis. 4-12 All CO, UHC, Particulate and VOC emissions guarantees are based on the furnace local temperature at the burner being above 1100 F (593 C). Burners Devol (Radiant Wall Burner) Combustion Systems Radiant Wall, Min-Emissions SHEET 4 OF 5

BASIS OF SCOPE OF SUPPLY Burner Plenum Burners are supplied with individual, manufactured plenums (windboxes). Plenum General Description Integral, round-shaped air plenum, fabricated construction Material A-1011 Gr 30 Carbon Steel Thickness 10 gauge (3.58 mm) material Internal Insulation / thickness Semi-rigid Mineral Board, Fibrex 1280 1.00 (in) Method of Construction Bolted Construction Inlet Air Control Burners are supplied with air control. Mode of Operation Primary and secondary register assemblies Tight Shutoff for Damper Blades Mechanism Description Screw - type primary register & slide plate register ass'y - CS Bearing construction Supplied with bearings c/w grease fittings for damper shafts Burner Tile Burner is supplied with a refractory tile assembly. Regen Tile Composition Secondary Tile Composition 60% Al2O3 Needle Construction Required Rated Service Temperature 3000 F (1648 C) Temperature of Pre-firing 500 F (260 C) Noise Attenuation Method Insulated muffler assembly Fuel Delivery System Burners are supplied with a single fuel gas connection Gas manifold description Gas Tip Material 310 or HK (ASTM A-297) stainless steel Gas Mixer Material 304 Stainless Steel Fuel Gas Connection 150#, Carbon Steel Flange, RFWN, A-105 Pilot Mixer - Tip Material Carbon Steel and/or Cast Equivalent - 310 SS or Cast equivalent tip Pilot Gas Connection Separate Off Gas Manifold Off Gas Tip Material Off Gas Riser Material Off Gas Connection Oil Tip / Atomizer Material Oil & Steam Connections Painting Requirements Zeeco Standard Carbon Steel Surface Preparation SSPC-SP-2 // ST-2 - Hand Tool Cleaning Primer Red Oxide Primer Primer Thickness One (1) Shop Coat 1st Paint Coat 1st Paint Coat Thk. Top Coat Top Coat Thickness Tile Case Assembly / Mounting Plate Burners are supplied with a tile case assembly Mounting Template - heater floor cutout Lifting Lugs Pressure Taps Required for Windbox Scanner Connection Ignition / Sight Ports One (1) port provided, 2" (50.8 mm), c/w pivoting slide plate Electrical Information Pilot Fittings and Ship Loose Items Pilot Conduit Fittings UV Scanners Burners Devol (Radiant Wall Burner) Combustion Systems Radiant Wall, Min-Emissions SHEET 5 OF 5