Compliance w/ the 2012 Life Safety Code

Similar documents
CMS Regulatory Update & Survey Trends: Life Safety Code

Agency for Health Care Administration

Agency for Health Care Administration

EC EP 14 All other electrical K-920 equipment in patient care vicinity NFPA , Chapter 10

Agency for Health Care Administration

LIFE SAFETY COMPLIANCE: ADAPTING TO THE 2012 LIFE SAFETY CODE

Chapter 43, Building Rehabilitation allows for degrees of compliance based on the work category such as the extent of work.

CMS Announcement 3/27/2017. Adoption of 2012 Life Safety Code Health Care Facilities Code. Kenneth Daily, LNHA

FIRE SAFETY SURVEY REPORT AMBULATORY SURGICAL CENTERS (ASC) & END STAGE RENAL DISEASE (ESRD) MEDICARE

NFPA 101 and NFPA 99, 2012 Editions Code Update. where art meets engineering

Agency for Health Care Administration

New DATE OF BLDG. PERMIT OR PLAN APPROVAL: SURVEYOR (SIGNATURE) TITLE OFFICE DATE REVIEW AUTHORITY OFFICIAL (SIGNATURE) TITLE OFFICE DATE

The Healthcare Environment Update

FHCA 2014 Annual Conference & Trade Show

Danilo B. Concepcion, CBNT, CCHT-A Operations Manager St. Joseph Hospital Renal Services

Other EC and LS documents may be requested by surveyors, as needed, throughout the survey.

Changes to Environment of Care, Equipment Management, and Life Safety Chapters Related to Life Safety Code Updates

Life Safety Code NFPA 10 NFPA 13 NFPA 25 NFPA 72 NFPA 90A NFPA 110 NFPA 99 THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #7

NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES

NFPA CODE TESTING & INSPECTION. Requirements & Recommendations for. Licensed Florida Hospitals, Ambulatory Surgery Centers,

ASCs & LSC. Alice Epstein, DFASHRM, FNAHQ

Presented by: Brad Keyes, CHSP Senior Consultant Keyes Life Safety Compliance, LLC

Agency for Health Care Administration

2018 Joint Commission Standards What s New in the EC/LS/UM GASHE Annual March Meeting Lake Blackshear Resort

First Aspen Federal Regulation Set: K LSC 2000 Health Existing

Agency for Health Care Administration

Are there any policies regarding outlets that contain USB ports?

Fire & Life Safety Code Compliance. Common Safety Deficiencies and Tips for Compliance for Long Term Care and Skilled Nursing Facilities

Life Safety Code Common Discepancies Course# LSC102. EZpdh.com All Rights Reserved

Building Codes & Standards for Healthcare. Healthcare Construction Certificate - Level 1

Top (15) Life Safety Code Deficiencies and Tips for Compliance (10/01/2011 thru 02/22/2012)

NFPA 99 for Facility Managers

TOPICS IN CODE ENFORCEMENT

4/18/2017. *2012 edition of NFPA 99 has gone through a major overhaul. *This document is now a Code.

THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #5

Agency for Health Care Administration. Eddie Alday Life Safety Code Lead 30 th AHCA Seminar 23 September 2014

The Impact the Reference Standards in the 2012 Edition of NFPA 101 have on the Operation of Health Care Facilities: NFPA 80 and 99

Center for Clinical Standards and Quality /Survey & Certification Group

NFPA 101 Code Update from 2012 Edition to the 2015 Edition

Changes to the 2018 Joint Commission Comprehensive Accreditation Manual for Hospitals (CAMH)

LIFE SAFETY CODE MAINTENANCE MANUAL

Changes to Environment of Care and Life Safety Chapters Related to Life Safety Code Updates

FACILITY MANAGEMENT DEFICIENCIES IN CRITICAL ACCESS HOSPITALS (CAH)

Medical Gas Inspections and Maintenance Programs. HESNI Annual Conference NIU Conference Center May 10-11, 2018 Presented by Mathis Carlson

EC 5.10 FIRE PREVENTION MANAGEMENT

27th Annual AHCA Seminar

FACILITY MANAGEMENT DEFICIENCIES IN ACUTE CARE SETTINGS

Prepublication New Text Jan 2018 Changes to Environment of Care and Life Safety Chapters

To provide the requirements needed for Care Facilities Having 6 or Fewer Clients. This occupancy is classified as an R-3.1.

Report on First Revisions with Statement June 2014 NFPA 101

2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content

Defend In Place 2012 IFC Overview of Institutional Occupancies

THE HEALTHCARE ENVIRONMENT UPDATE. Anne M. Guglielmo, Engineer Engineering Department The Joint Commission. Copyright, The Joint Commission

JOINT COMMISSION PREPAREDNESS / STATEMENT OF CONDITIONS DRAWINGS WSSHE SOUTHWEST CHAPTER NOVEMBER 19, 2015

NORTH CAROLINA. Downloaded (l) For each nursing unit, or fraction thereof on each floor, the following shall be provided:

Interim Life Safety Measures. Healthcare Construction Certificate - Level 1

Iowa State Fire Marshal

PRINTED: 06/09/2017 FORM APPROVED CENTERS FOR MEDICARE & MEDICAID SERVICES OMB NO (X2) MULTIPLE CONSTRUCTION A. BUILDING 03 - A BUILDING

NFPA 101 Life Safety Code Culture change 2012

New Facilities. Minimum Requirements

2007 CBC & CFC Residential Care Facility Requirements (24 hour care only)

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY

Agency for Health Care Administration

THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #4

2017 CHALLENGING STANDARDS 2018 NEW ELEMENTS OF PERFORMANCE HOSPITAL ENVIRONMENT OF CARE AND

Agency for Health Care Administration

First Revision No NFPA [ Section No ]

K SURVEY FOR DATE OF PLAN APPROVAL SURVEY UNDER

Fire Prevention Program

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

EXAMPLE FIRE PREVENTION AND PROTECTION PLAN WORKSHEET

Schools and the Fire Code A Partnership for Safety

10/25/2018. Facilitators. Emergency Preparedness &Life Safety Code for Administrators. Participant Guide

Agency for Health Care Administration

Taming the Health Care Building Codes NFPA vs. The International and Chicago Building Codes JENSEN & HALSTEAD LTD.

Department of Health Life Safety Code Update

Agency for Health Care Administration

GROUP SR SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES

Ohio Department of Health NFPA 2012 Life Safety Code Tips Sheet

LIFE SAFETY & FIRE PREVENTION MANAGEMENT PLAN

Public Health Fax: Web Site:

Public. Mike Free Health. State of Alabama Department of

GROUP SR SPECIAL (ASSISTED SELF-PRESERVATION) OCCUPANCIES

2017 Accreditation Updates

Riverside County Fire Department Office of the Fire Marshal Market St., Ste. 150, Riverside, CA Ph. (951) Fax (951)

Is the address of your property clearly visible and marked in large numbers that can be easily seen from the street?

Changes to Environment of Care and Life Safety Chapters Related to Life Safety Code Updates

FIRE SAFETY MAINTENANCE INFORMATION for Agricultural Livestock Structures

Residential-based Care Facility R-4 Guideline

FIRE SAFETY SURVEY REPORT 2000 CODE - HEALTH CARE Medicare Medicaid

Agency for Health Care Administration

E25 (D) Automatic controls for general means of egress lighting

Large Family Daycare Guideline

Developing a Healthcare Facility Fire Door Inspection Program

California Fire Code (CFC) Part III contains requirements. Building and Equipment Design Features PART. Chapters 5 through 19

Renovation Program. Renovation Program GENERAL

Crosswalk of 2014 HFAP Standards against HFAP Standards Acute Care Hospital Manual

Changes to Environment of Care and Life Safety Chapters Related to Life Safety Code Updates

Wausau Fire Department Inspection Violation Code Listing (Modified) All Applicable Records

Barrier Management- Defending the Safety of Patients, Visitors, & Staff

Transcription:

Compliance w/ the 2012 Life Safety Code Implications of the 2012 NFPA Code Set for Existing & New ASCs William E. Lindeman, AIA http://www.weldesigns.com Financial Interest Disclosure The presenter provides Health Care Facility consulting services, related to assessment of regulatory compliance & facility design/planning/construction He is on retainer with the Accreditation Association for Ambulatory Health Care as their physical environment consultant He developed and maintains the AAAHC s PEC & Life Safety Code Surveyor Reference documents REALLY IMPORTANT NOTE!! This presentation addresses the most significant changes in ASC physical environment requirements brought on by the CMS adoption of the 2012 NFPA 101 & 99 it is not a comprehensive review of all applicable requirements. The majority of NFPA requirements, that have not significantly changed, are still fundamental to CMS compliance. http:\\www.weldesigns.com 1

CMS adoption of 2012 editions of NFPA 101 & NFPA 99 Federal Register / Vol. 81, No. 86 / May 4, 2016 Effective July 5, 2016 -- first applied to surveys the following November. Defined the distinction between New & Existing ASCs as being the construction start date of the building &/or ASC. Any ASC for which pertinent construction permits were approved -&/orstarted construction before July 5, 2016 are considered to be Existing for the purposes of CMS compliance. 2012 NFPA 101/99 How NFPA documents work By adopting the 2012 editions of NFPA 101 & 99 CMS brought with them all contemporary editions of other NFPA codes and standards referenced within. Such as the CMS-current 2012 ed. of NFPA 101 & 99, are contemporary to the 2011 NFPA 70, the 2010 NFPA 110, etc. All together, conveniently described as the 2012 NFPA Code Set 2012 NFPA 101/99 How NFPA documents work The CMS 2012 NFPA Code Set involves 4 Codes and a more than a dozen Standards; those most prominent in defining compliance for ASCs include: NFPA 101, Life Safety Code NFPA 99, Health Care Facilities Code (including ASHRAE 170 for new construction) NFPA 70, National Electrical Code NFPA 72, National Fire Alarm Code NFPA 25, Standard for ITM of sprinkler systems http:\\www.weldesigns.com 2

NFPA 101 requires both vertical & horizontal fire separations for new ASCs inside new and/or existing buildings. 1-hour minimum separation to any other distinct entity or common area 2-hour minimum to several higher risk occupancies, and most occupancies in nonsprinklered buildings Fire separations require rated assemblies... Exit Door Tactile Signs are provided as follows: Tactile signage stating EXIT located at each exit door requiring an illuminated exit sign. Tactile signage complies with ICC/ANSI including sans serif letters raised 1 / 32 minimum, ½ to 2 inches high, & duplicated in braille Mounted 60 inches above floor on latch side of door NFPA 99 adopts the 2008 ANSI/ASHE/ASHRAE 170 Applies to the construction of new health care facilities, and the altered, renovated, or modernized portions of existing systems or individual components. Space ventilation and pressure relationship requirements maintained even in the event of loss of normal electrical power to Operating rooms http:\\www.weldesigns.com 3

ANSI/ASHE/ASHRAE 170 continued... Multiple heat sources so that failure of any unit does not reduce heating capability (space, water, etc.) Design, materials and construction of HVAC system Filtration requirements by type of space Air change, fresh air, and exhaust by types of space ANSI/ASHE/ASHRAE 170 continued... Pressure relationships for a wide variety of less clean to more clean spaces Required temperature & humidity range (max/min) requirements for a variety of space types Location of air supply relative to O.R. table Filtration requirements by type of space ANSI/ASHE/ASHRAE 170 continued... Air change, fresh air, and exhaust by types of space Pressure relationships for a wide variety of less clean to more clean spaces Required temperature & humidity range (max/min) requirements for a variety of space types Location of air supply relative to O.R. table http:\\www.weldesigns.com 4

Piped Medical Gas System requirements based on 4 categories of Risk; but definitions and appendix examples effectively limit ASCs to Category 1 or 2 piped medical gas systems Difference between Category 1 & 2 piped gas systems similar to that between Levels 1 & 2 in 2000 code set; i.e. the alarm system requirements Piped Medical Gas System requirements Proscriptive requirements for design & installation of patient gases AND support gases Many requirements go to component level All Category 1 sources are duplexed or greater Category 2 manifold supplies are duplexed or greater Piped Medical Gas System requirements Expanded alarm system monitoring and panel display requirements Local alarms required at exterior medical gas manifold sources, and interior reserves for them Local alarms required at all motor driven sources of gas of vacuum http:\\www.weldesigns.com 5

Essential Electrical System (EES) requirements based on 4 categories if Risk; but definitions and appendix examples effectively limit ASCs to Category 1 or 2, meaning Type 1 EES or Type 2 EES. Type 1 almost identical to 2000 code set requirements; i.e., what hospitals had to have Type 2 almost identical to Type 1, except larger systems permitted to have one fewer transfer switch &/or 1 less distribution panel EES requirements... No more Type 3 & very unlikely battery systems will be practical if even possible All patient care electrical receptacles must be hospital grade General care areas/patient positions must have at least 8 electrical receptacles Critical care areas/patient positions must have at least 14 electrical receptacles Electrical System O.R.s must have at least 36 electrical receptacles Circuit breaker cabinets not located in public access areas Optional loads on an EES require a separate & subservient transfer switch http:\\www.weldesigns.com 6

Electrical System Self-contained battery-powered emergency lights required where deep sedation or general anesthesia used, at new transfer switch locations, at interior generator sets, & at central battery-source equipment locations Fire Alarm Systems Remote supplementary power supplies require dual sources of power, and smoke detection if in areas not continuously staffed http:\\www.weldesigns.com 7

(exist g & new) Approved Supervised Automatic Sprinkler System requirements have always been driven by NFPA 13. Now NFPA 101 upped the ante with a requirement that all supervision must be electrical -- as opposed to supervision of the water supply by securing valves in the open position with chains and locks (as still permitted by NFPA 13) -- and could extend beyond monitoring the reliability of the water supply. Construction & Overall Fire Protection Building construction requirements have not changed, relative to protecting a single story Vs. a multi-story building that houses an ASC The NFPA 101 definition of what determines the number of stories in a building has changed, such that some previous one story buildings with a basement now qualify as multi-story buildings -- requiring better fire protection throughout. Exiting/Egress Existing egress that passes through intervening rooms require new exit signs and doors with minimum 32 inch clearance when open 90 O No portion of exit egress is permitted through a hazardous area, storeroom, workroom, kitchen, or toilet room http:\\www.weldesigns.com 8

Hazardous area protection Doors to storage locations with flammable, or otherwise hazardous, contents require automatic closing or self closing doors CMS is allowing existing ASCs to reach compliance before July 5, 2017. New (additional?) medical gas signs: Medical Gases NO Smoking or Open Flame Positive Pressure Gases NO Smoking or Open Flame Room May Have Insufficient Oxygen Open Door and Allow Room to Ventilate Before Entering Electrical System Receptacles in pediatric care spaces or where pediatric patients may access them are listed as tamper-resistant or provided with a listed tamper-resistant cover New O.Rs. are wet areas unless ASC demonstrates otherwise through qualified risk assessment; risk assessment required in all facilities. http:\\www.weldesigns.com 9

Electrical System Patient care electrical receptacles in areas of changed use/classification must be hospital grade. New electrical receptacles in patient care areas areas must be hospital grade. Existing electrical receptacles requiring maintenance or replacement must be replaced with hospital grade receptacles Fire Protection Systems When fire alarm system is out of service for more than 4 hours in a 24 hour period, the local AHJ is notified and the building is either evacuated or placed under a fire watch When the fire sprinkler system is impaired or is anticipated to be impaired for more than 10 hours, in any given 24 hour period, a designated Impairment Coordinator must initiate one of three responses. http:\\www.weldesigns.com 10

Impaired Fire Sprinkler Systems Evacuate entire building -OR- Establish fire watch: notify all building occupants, mitigate risks that could start or worsen a fire, extinguish small fires, and insure integrity of life safety design and systems -OR- Establish a temporary supply of water for the sprinkler system. Hazardous area protection ABHR considerations now part of NFPA 101, and slightly less restrictive than prior CMS requirements... ABHR now allowed to include aerosol dispensers up to 18 oz. Total allowed quantity of ABHR fluids now exclude one dispenser per room where installed ABHR dispensers Do not release contents without purposeful activation Touch free models require activation within 4 inches of sensing device Touch free activation releases only enough solution for proper hand sanitation regardless of time object is in activation zone Dispensers designed to avoid accidental or malicious activation http:\\www.weldesigns.com 11

Medical gases: Required detail of Med Gas system ITM determined by it s Category Classification Routine maintenance programs developed (i.e., written and followed) for each/all piped gas and vacuum systems and/or system components Category 2 Medical gas systems: The facility has an emergency plan for loss of Medical Air The facility has an emergency plan for loss of medical-surgical vacuum The facility has an emergency plan for loss of WAGD Electrical System Requirements for plug strip use now part of NFPA 99 less restrictive than the CMS categorical waiver (no UL rating requirements); but CMS s position related to that is as yet unknown ASC sets and follows policies for routine testing and maintenance of patient care electrical equipment. Required at minimum when new & after maintenance http:\\www.weldesigns.com 12

Electrical System New patient care receptacle testing now address pull-retention force of the grounding blade alone Generator set engine jackets heated as specified by the manufacturer Annual load bank of diesel generators, when required, is for 90 minutes Generator sets tested for full duration or 4 hours, whichever is less, every 36 months. Electrical System Some types of sealed batteries now permitted for generator sets; but require supplemental testing Specific testing and maintenance parameters for main and feeder circuit breakers, main feed insulation resistance, generator set starting batteries, and minimum documentation thereof Type 3 EES (existing systems only) Inspection testing and maintenance of battery-based alternate sources of power per NFPA 111. Interior finishes The total combined area of bulletin boards, posters, and paper attached to walls does not exceed 20% of the wall surface they are attached to. http:\\www.weldesigns.com 13

Fire Alarm Systems Documentation of new system acceptance testing on specific NFPA 72 form FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION Records of completion for all fire alarm systems are continuously updated to reflect changes to system over time Fire Alarm Systems Allowances for automated testing of fire alarm system Maintenance is performed in accordance with manufacturer s recommendations Documentation (paper or electronic) of inspection testing & maintenance are retained for at least one year following the next periodic ITM activity Smoke & Fire Separation Sealing of new penetrations in fire-rated surfaces must utilize a firestop system or device tested in accordance with ASTM814 or ANSI/UL 1479, with some exceptions that are little if any better. Annual functional testing of fire door and window assemblies by individuals with understanding of the operating components of the type of door being subject to testing. http:\\www.weldesigns.com 14

Portable Fire Extinguishers Allowances for specific water-type extinguishers to substitute for 2-A or 4-A types 10/20-B rated extinguishers required within a 30/50 foot travel distance of any point in a room or area (i.e., smoke compartment) containing more than 5 gals of flammable liquids. Must be located along normal paths of travel Portable Fire Extinguishers Allowances for electronic monitoring for monthly inspection Any extinguisher removed from use for service or maintenance are immediately replaced with a like-rated unit for the duration of the service/maintenance Hydrostatic testing of rechargeable extinguishers on 5-12 year interval as applicable to the specific type Building Services Smoke & fire dampers inspected and tested after installation, after 1 year & every 4 years thereafter Furnishings and Decorations Mobile trash and soiled linen collection carts > 32 gal. are never left unattended outside of rooms protected as hazardous areas http:\\www.weldesigns.com 15

IMPORTANT REMINDER!! This presentation addressed the most significant changes in ASC physical environment requirements brought on by the CMS adoption of the 2012 NFPA 101 & 99 it was not a comprehensive review of all applicable requirements. The majority of NFPA requirements, that have not significantly changed, are still fundamental to CMS compliance. Compliance w/ the 2012 Life Safety Code Implications of the 2012 NFPA Code Set for Existing & New ASCs William E. Lindeman, AIA http://www.weldesigns.com http:\\www.weldesigns.com 16