Instructions for High Altitude Installations Above 4500 FT.

Similar documents
STOP! Read this notice. STOP! Read before proceeding. These instructions are for gas conversion of the Evergreen boiler only.

CONVERSION TO PROPANE MANUAL M-Series Condensing Boiler. Wall-Mounted, Gas-Fired Boiler

Evergreen Liquid Propane Conversion

Natural Gas & Propane Burners

User manual. Logano GC 124 II. Gas boiler

USER'S INFORMATION MANUAL

WARNING WARNING FOR YOUR SAFETY. Gas Conversion Kit Instructions. Applies to: Model UDAP, UDAS, UDBP, and UDBS Unit Heaters. General and Warnings

Crown Boiler Company

Gas Fired Humidifier. SKG Series Combustion Field Adjustment Instructions. SKG Combustion Field Adjustment Instructions

USER'S INFORMATION MANUAL

SERVICE FACTS WARNING M801-SF-1C. Gas Furnaces Upflow & Downflow Induced Draft 1 Stage Heat Models: DISCONNECT POWER BEFORE SERVICING M801P040AU24AA

Conversion Instructions Logano G234X. Gas boiler. Please read carefully before installing and servicing. Gas boiler

USER S INFORMATION MANUAL

USER'S INFORMATION MANUAL

95M-200. Gas-Fired Direct Vent Modulating Hot Water Boiler. Control Manual And Troubleshooting Guide. P/N , Rev.

USER'S INFORMATION MANUAL

Operating instructions

Operating instructions

Columbia Boiler Company

Using it in an enclosed space can kill you.

Applies to: Models F, B, FE, and BE FOR YOUR SAFETY

Model BW9 Gas-Fired Direct Vent Condensing Water Boiler

USER'S INFORMATION MANUAL

Gas Conversion Kits and Instructions

Control manual and troubleshooting guide

CSD-1 COMMERCIAL BOILER CONTROLS

USER'S INFORMATION MANUAL

X341119P10 Gas Furnace Var. Speed Blower Var. Speed Inducer Two Stage Heat Direct Vent Models:

Q382A,B Pilot Burners

GAS COOKTOP INSTALLATION INSTRUCTIONS

80% and 95% furnace models feature aluminized steel heat exchangers to conduct heat quickly and increase durability.

USER S INFORMATION MANUAL

USER S INFORMATION MANUAL

G61MPV SERIES GAS FURNACE WARNING

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) F-1500T DUAL FUEL CONSTRUCTION HEATER

Operating instructions

Weil-McLain part numbers are found in Weil-McLain Boilers and Controls Repair Parts Lists.

OPERATING INSTRUCTIONS AND OWNER S MANUAL

Outdoor kit. Models: RTG 199HE / RTG 199ME. Installation Instructions

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) F-1000T DUAL FUEL CONSTRUCTION HEATER

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVN/P-400 INDIRECT FIRED SPACE HEATERS

Typical Specifications For: ADVANTUS TM DOMESTIC HOT WATER SUPPLY Models AV(W)0500 AV(W)4000

TO DO IF YOU SMELL GAS

INSTALLATION INSTRUCTIONS # BURNER ASSEMBLY REPLACEMENT

Overview of Gas Range Types

Installation and Maintenance Manual Please retain this manual for future reference.

English, French & Spanish No Color

P.O. Box , Dallas, TX USER'S INFORMATION MANUAL Single-Stage Warm Air Gas Furnaces

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) F-400T DUAL FUEL CONSTRUCTION HEATER

USER'S INFORMATION MANUAL

RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE :$51,1*

Failure to follow these instructions could result in fire or explosion which could cause property damage, personal injury or death.

EL195UHE SERIES GAS FURNACE WARNING WARNING

Installation Instructions

Slant Fin Corp. Installation and Operation Instructions

*Note: For operation at elevations above 2000 ft., appliance rating shall be reduced at the rate of 4 percent for each 1000 ft. above sea level.

Series High Efficiency Gas-Fired Hot Water Direct Vent Condensing Boilers

User s Information Manual

INSTALLATION INSTRUCTIONS

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVN/P-400 INDIRECT FIRED SPACE HEATERS

EL195DFE SERIES GAS FURNACE WARNING

USER'S INFORMATION MANUAL

Installer: Leave this manual with the appliance. Consumer: Retain this manual for future reference.

User s Manual for FT SERIES THE

Typical Specifications For: ADVANTUS TM DOMESTIC HOT WATER SUPPLY Models AV(W)0500 AV(W)4000

VF/VG700 Jumbo. Construction Heater. Installation and Maintenance Manual

prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE TSG-PRESTIGE Date revised: 11/10/08

Gas-Fired Natural Draft Hot Water Boilers INSTALLATION INSTRUCTIONS These instructions must be affixed on or adjacent to the boiler

Product Data. 95% AFUE Single Stage Furnace Upflow / Downflow / Horizontal. ama ! WARNING

USER'S INFORMATION MANUAL

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER

EL195UH SERIES GAS FURNACE WARNING

User s Information Manual

Raptor 320HB & 399HB Submittal Sheet

INSTALLATION GUIDE Dual Fuel Ranges

USER S INFORMATION MANUAL

prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE TSG-SOLO-9/04

*DD2B060A9V3VA *DD2B080A9V3VA *DD2C100A9V5VA *DD2D120A9V5VA

EL296UHV SERIES GAS FURNACE WARNING WARNING

MODELS BT- 80 AND 100

PRODUCT SPECIFICATIONS 1 *UH2B080A942VA

Replacement parts. WM97+ gas-fired water boiler Boiler Manual. OBTAIN PARTS ONLY THROUGH WEIL-McLAIN THE BOILER CONTAINS CERAMIC FIBER MATERIALS

LGB Gas fired boiler

WARNING FIRE OR EXPLOSION HAZARD.

PROBLEM CAUSE SOLUTION

BC Series II OIL-FIRED CAST IRON BOILER INSTALLATION, OPERATION & MAINTENANCE MANUAL FOR US AND CANADIAN SALES

WARNING FIRE OR EXPLOSION HAZARD.

TECHNICAL GUIDE MODELS: P*DH GAS-FIRED CONDENSING / HIGH EFFICIENCY DOWNFLOW / HORIZONTAL FURNACES 91 AFUE DESCRIPTION WARRANTY FEATURES

Sunpak Infrared Heater. Model S34 TSR

Engineering Bulletin. Gas Heat. for M-Series and T-Series Climate Changer Air Handlers CLCH-PRB010-EN. March 2004

MANUAL WARNING FIRE OR EXPLOSION HAZARD. SL280UHNV SERIES WHAT TO DO IF YOU SMELL GAS:

CYLINDER NOT INCLUDED

MGC GAS-FIRED HOT WATER BOILERS. Models MGC-8D MGC-8DP MGC-9D MGC-9DP INSTALLATION, OPERATION & MAINTENANCE MANUAL

Installation and Service Instructions LoganoUS/CA GC 144 II

THERMAX Efficiency Monitor

MCC SERIES II GAS-FIRED HOT WATER BOILERS

User s Information Manual Galaxy GG/GX Series, Sentry S/SX Series and Sentinel SE Series Gas Boilers with Continuous Burning Pilot

THC 85N / 175N INDUSTRIAL / COMMERCIAL SPACE HEATER

Carbon monoxide (CO) is a colorless, odorless gas that is the product of incomplete combustion of carbon-based fuels.

Aqua Balance. Boiler Manual WMB-80/120/155. Wall Mount Gas-Fired Condensing Boilers Combi and Heating Only Models. Quick Start Guide Pages 3 & 4

Transcription:

Instructions for High Altitude Installations Above 4500 FT. If installing Boiler sizes 080 OR 180, do not attempt to convert 080 for use with LP at altitudes above 2000 ft (610 m). Also, do not attempt to convert 180 for use with LP gas at altitudes above 7800 ft (2377 m). Attempts to do so may result in unreliable operation, property damage, personal injury, or loss of life due to carbon monoxide (CO) poisoning. These instructions apply only to altitudes from 4501 to 10200 ft. (1350 to 3109 m). These instructions contain specific information to set up your Boiler to ensure proper operation. LP Conversions - Boiler setup from factory is configured for use with natural gas installed from 4501 to 10200 ft (1350 to 3109 m) above sea level only. For conversion to LP at altitudes from 4501 to 10200 ft (1350 to 3109 m), follow the High Altitude Start-Up Instructions for LP section in this supplement. This conversion shall be performed by a qualified service agency in accordance with the manufacturer s instructions and all applicable codes and requirements of the authority having jurisdiction. If the information in these instructions is not followed exactly, a fire, explosion, or production of carbon monoxide may result causing property damage, personal injury, or loss of life. Installation is not proper and complete until the operation of the converted appliance is checked as specified in the manufacturer s instructions supplied. DANGER These instructions include a procedure for adjusting the air-fuel mixture on this Boiler. This procedure requires a combustion analyzer to measure the CO 2 (or Oxygen) and Carbon Monoxide (CO) levels in flue gas. Adjusting the air-fuel mixture without a proper combustion analyzer could result in unreliable Boiler operation, personal injury, or death due to carbon monoxide poisoning. Asphyxiation Hazard. The outlet pressure for the gas valve has been factory set and requires no field adjustment. This setting is satisfactory for both natural gas and LP. Attempting to adjust the outlet pressure may result in damage to the gas valve and cause property damage, personal injury, or loss of life due to carbon monoxide (CO) poisoning. Failure to set up Boiler in accordance with these instructions could result in production of high amounts of Carbon Monoxide which could result in death, serious injury, and/or reduced component life. 107284-01 - 9/16 1

High Altitude Start-up Instructions for Natural Gas 1. Install Boiler in accordance with the Installation, Operating and Service Instructions manual supplied with the Boiler. Follow all instructions in Section XI (Start-up and Checkout) up through Step 14. Skip Step 10. 2. Verify the gas inlet pressure is between the ranges shown in Table 4 with all gas appliances (including the Boiler) both on and off. 3. Perform a combustion test. Boilers are equipped with a screw cap in the vent adapter. Be sure to replace this cap when combustion testing is complete. Check CO 2 (or O 2 ) and CO at both high and low fire. The Boiler may be temporarily locked into high or low fire as follows: a. From the home screen, press and hold both the LH and RH buttons for 3s. The screen will change to Diagnostic Mode and show the flame signal (Figure 12.7 in the Installation, Operating and Service Instructions manual). b. Press the RH ( Next ) button 5 times to advance to the high fire ( HF ) screen. c. To set the Boiler in low fire from the high fire screen, press the LH button 6 more times. d. To return to automatic firing control from either the HF or LF screens, press the LH ( Done ) button. The Boiler will return to automatic modulation from either screen after 15 minutes if no buttons are pressed. e. At both high and low fire, CO readings should be less than 200PPM air-free. Acceptable CO 2 and O 2 ranges are shown in Table 3. Adjust the throttle at high fire if flue gases are not in range: To reduce the CO 2 (increase the O 2 ), turn throttle clockwise. To increase the CO 2 (reduce the O 2 ), turn throttle counter-clockwise. Make adjustments in increments of 1/8 to 1/4 turn and allow Boiler at least a minute to respond to each adjustment before making another. The CO level will be at its lowest somewhere in the CO 2 range shown in Table 3. Consult factory if it is not possible to reduce CO level below 200PPM air free within the range of CO 2 shown for the fuel and altitude at which the Boiler is being used. Final readings should be taken with all doors and covers in place. 4. Follow all instructions in Section XI (Start-up and Checkout) from Steps 17 to 20. 5. Apply the High Altitude Installation Label for Canadian Installations adjacent to the Rating Plate Label, if applicable. This label is provided in the Instructions Packet supplied with the Boiler. High Altitude Start-up Instructions for LP 1. Install Boiler in accordance with the Installation, Operating and Service Instructions manual supplied with the Boiler. Follow all instructions in Section XI (Start-up and Checkout) up through Step 9. 2. Set the throttle to its preliminary setting for LP. To do this: a. Turn the throttle (Figure 1) clockwise until it stops (several full turns). b. Turn the throttle counter-clockwise the exact number of turns shown in Table 2. 3. Follow all instructions in Section XI (Start-up and Checkout) from Steps 11 through 14. Note: If the Boiler does not light on the first try for ignition, allow the Boiler to make at least four more attempts to light. If the Boiler still does not light, turn the throttle counterclockwise in 1/8 increments, allowing the Boiler to make at least four tries for ignition at each setting, until the Boiler lights. 4. Verify the gas inlet pressure is between the ranges shown in Table 4 with all gas appliances (including the converted Boiler) both on and off. 5. Perform a combustion test. Boilers are equipped with a screw cap in the vent adapter. Be sure to replace this cap when combustion testing is complete. Check CO 2 (or O 2 ) and CO at both high and low fire. The Boiler may be temporarily locked into high or low fire as follows: a. From the home screen, press and hold both the LH and RH buttons for 3 seconds. The screen will change to Diagnostic Mode and show the flame signal (Figure 12.7 in the Installation, Operating and Service Instructions manual). b. Press the RH ( Next ) button 5 times to advance to the high fire ( HF ) screen. c. To set the Boiler in low fire from the high fire screen, press the LH button 6 more times. d. To return to automatic firing control from either the HF or LF screens, press the LH ( Done ) button. The Boiler will return to automatic modulation from either screen after 15 minutes if no buttons are pressed. 2

e. Allow Boiler to operate for approximately 5 minutes before taking combustion readings. At both high and low fire, CO readings should be less than 200PPM air-free. Acceptable CO 2 and O 2 ranges are shown in Table 3. Adjust the throttle at high fire if flue gases are not in range: To reduce the CO 2 (increase the O 2 ), turn throttle clockwise. To increase the CO 2 (reduce the O 2 ), turn throttle counter-clockwise. Make adjustments in increments of 1/8 to 1/4 turn and allow Boiler at least a minute to respond to each adjustment before making another. The CO level will be at its lowest somewhere in the CO 2 range shown in Table 3. Consult factory if it is not possible to reduce CO level below 200PPM air free within the range of CO 2 shown for the fuel and altitude at which the Boiler is being used. Final readings should be taken with all doors and covers in place. 6. Cycle Boiler at least five times at the final throttle setting to ensure burner ignites without delay and without noise. 7. Follow all instructions in Section XI (Start-up and Check-out) from Steps 17 to 20. 8. A sheet of yellow labels is provided in the Instructions Packet supplied with the boiler for boilers converted from natural to LP gas. Select the model from this sheet of labels and apply them as follows: a. Apply the Rating Plate Label adjacent to the rating plate. b. Apply the Gas Valve Label to a conspicuous area on the gas valve. c. Apply the Boiler Conversion Label to a conspicuous surface on, or adjacent to, the outer boiler jacket. Fill in the date of the conversion and the name and address of the company making the conversion with a permanent marker. 9. Apply the High Altitude Installation Label for Canadian Installations adjacent to the Rating Plate Label, if applicable. This label is provided in the Instructions Packet supplied with the boiler. Figure 1a: Gas Valve Detail (80MBH Thru 120MBH) 3

Figure 1b: Gas Valve Detail (150MBH, 180MBH) Table 2: Starting Number of Throttle Turns For Conversion To LP Gas Boiler Size # Counterclockwise Turns (From Fully Closed) 080 100 3 120 4 150 5-3/4 180 6-1/2 Throttle adjustments shown in Table 2 are approximate. The final throttle setting must be found using a combustions analyzer. Leaving the Boiler in operation with a CO level in excess of 200PPM air-free could result in injury or death from carbon monoxide poisoning. Leaving the Boiler in operation with a CO 2 level outside of the range shown in Table 3 could also result in injury or death from carbon monoxide poisoning, even if the Boiler is operating at an air-free CO level below 200PPM during this adjustment procedure. If the throttle is very far out of adjustment on the rich (counter-clockwise) side, the Boiler burner may be running at 0% excess air or even with a air deficiency. Operating the Boiler in this condition may cause property damage, personal injury or loss of life. Under these conditions, most combustion analyzers used in the field will show 0% O 2 and a very high (over 1000PPM) CO. Combustion readings will also appear to be unresponsive to throttle adjustment. If the Boiler appears to be operating under this condition, turn the throttle screw clockwise until the flame lengthens significantly and is mostly blue. Then, slowly turn the throttle counter-clockwise, using a combustion analyzer to achieve the required CO 2 as described in these instructions. 4

Table 3: Boiler Altitude Adjustments 4501-10200 Ft. (1350-3109 m) Boiler Size Fuel Acceptable Combustion Readings Measured Measured Max CO % CO 2 % O 2 (PM Air-Free) Approximate Derate per 1000 Ft. 4501-7800 ft. * (1350-2377 m) 7801-10200 ft. ** (2377-3109 m) 80 100 120 150 180 NG 8.7-9.1 4.9-5.6 200 0.0% 3.1% LP NG 8.5-9.3 4.5-6.0 200 0.0% 3.1% LP 9.9-10.2 5.4-5.8 200 0.9% 3.1% NG 8.8-9.3 4.5-5.4 200 0.0% 3.1% LP 9.9-10.2 5.4-5.9 200 0.5% 3.1% NG 8.6-9.3 4.5-5.8 200 0.4% 3.1% LP 9.8-10.3 5.2-6.0 200 1.2% 3.1% NG 8.5-9.1 4.9-6.0 200 1.9% 3.1% LP 9.9-10.2 5.4-5.8 200 2.4% * Derate is referenced from sea level. ** Derate is referenced from 7800 ft. Example: 1) 150 Boiler Size using natural gas installed at 6000 ft. Total derate = (0.4% x 6.0) = 2.4% 2) 150 Boiler Size using natural gas installed at 8800 ft. Total derate = (0.4% x 7.8) + (3.1% x 1.0) = 6.22% Table 4: Acceptable Gas Inlet Pressure Range Fuel Inlet Pressure (in w.c.) 4501-10200 Ft. Nat. Gas 4.0-14.0 LP 11.0-14.0 Table 5: High Altitude Specific Parameters Boiler Size 080 100 120 150 180 PIM High Altitude Repair Kit Part Number 107394-01 107394-02 107394-03 107394-04 107394-05 Altitude 4501-10200 Ft. Maximum Heat Rate (RPM) 6200 7500 7050 7300 7200 Minimum Heat Rate (RPM) 1800 2000 1800 2000 1900 Absolute Maximum Heat Rate (RPM) 7720 7680 7132 7300 7385 Minimum Light-off Rate (RPM) 3500 3500 3500 3500 3500 Maximum Light-off Rate (RPM) 4000 4000 4000 4000 4000 5