Hitachi Highly. Spezifikation Manual

Similar documents
SUBJECT Model ASH218SV-C8LU SPECIFICATION ASH218SV-C8LU. 1. SCOPE This specification is applied to SHANGHAI HITACHI rotary compressor.

HITACHI ROTARY COMPRESSOR MODEL SG153BG3GC I. SPECIFICATION. This specification is applied to SHANGHAI HITACHI rotary compressor. 2.

Question? 有疑问? Contact Philips 请联系飞利浦 FC6132 FC6130

Rosemount 214C Sensor. Quick Start Guide , Rev BB March 2019

Portable Ionizing Air Gun PIA 型离子风枪 型号 : 94101

PolyBox TM. Edition II. Operation Manual

BT9290. English. 1 Make sure the appliance is switched off and the laser guide is in off position.

所有的资料是按最新出版的产品资料编写而成遥科勒公司保留任何时候不经通知即可改变产品特性尧包装或产品可供类型的权利遥 说明书包括重要的安装内容袁请把这些资料交给用户阅读遥

HC1089 HC Koninklijke Philips N.V. All rights reserved 保留所有权利 (25/9/2017) > 75% 循环再造纸

LEVEL SENSORS & FLOAT SWITCHES

2016 Koninklijke Philips N.V. All rights reserved 保留所有权利 (12/2016) > 75% 循环再造纸 BT9290. >75% recycled paper >75% papier recyclé

CW-5000/ 5200 INDUSTRIAL CHILLER USER MANUAL

COMPRESSOR SPECIFICATIONS

Service Manual. Solar Direct Drive Vaccine Refrigerator / Freezer. Model :HTC-40/110; HTCD-90 Pictures :

美的吸尘器 使用说明书 VACUUM CLEANER OPERATION INSTRUCTIONS MANUAL C5 PRO (C5-L121D) 使用产品前请仔细阅读本说明书 并请妥善保管

Rotary Air-conditioning Compressors Specification

说明书 澳大利亚 ARTUSI KH90A-F1N160 薛孝田 印刷说明 : 2.. 此印刷品自 起开始实施 3. 此印刷品最终成品大小为 A4 纸一半大小 4. 此印刷品黑白印刷 5. 此印刷品要求字迹清晰 不能有漏印 错印 模糊现象 客户名称 产品型号 会签 型号经理

WAT E R S O U R C E H E AT P U M P S

Always there to help you

YVP110 Advanced Valve Positioner. Please use the attached sheets for the pages listed below in the following manuals. IM 21B04C01-01E (10th)

EJX-A and EJA-E Series Differential Pressure and Pressure Transmitters

SUNSTAR 单片机专用电路 TEL: FAX: Features 6 Digit 6 Function LCD Alarm Watch with RGB LE

安装使用说明书. 维格一体化智能座便器 305mm/400mm 坑距 VOGUE INTELLIGENT INTEGRATED TOILET305mm/400mm RI 20127T-M-WK/20128T-M-WK

Código : Motc.PANASC/SANYO-CSB453H8A--6HP-15100fr

Preparation. Name of Each Part. Safety Precautions (Be sure to always follow these precautions) ECLEAR MIST. HCE-HU03 Series. Turning the power on

Kitchen Exhaust Duct (KED) Requirements

DC MOTOR FAN COIL UNIT 直驅無刷电机风机盤管

Rosemount 848T High Density Temperature Measurement Family

Register your product and get support at 在以下网站注册并获得支持

EJX-A and EJA-E Series Differential Pressure and Pressure Transmitters

EJX / EJA-E series. For the description on the applicable page of users manual as shown in the item 1, please use revised information as shown in 2.

compact Bagless Cyclonic Vacuum Cleaner IMPORTANT: Read carefully before assembly and use.

Shaking Peltier Device

RAS-DX18HDK/RAC-DX18HDK

KMART Corrective Action Plan

Premium Desoldering station with Electric Pump Ref. DIS-D

TSI FMS Particle Monitoring Applications TSI FMS 在线粒子监控系统的应用. 2008, TSI Incorporated

TECHNICAL PRODUCT DATASHEET

FOB NINGBO PORT PRICE: 29,000USD

AIR CONDITIONER WITHOUT OUTDOOR UNIT

CK C O M P R E S S O R

IMPORTANT: Read carefully before assembly and use Techtronic Floor Care Technology Limited. All Rights Reserved.

8 Filtration Systems Air Purifier 8 重過濾空氣清新機 User Manual 產品說明書

HUMIDIFIER SERVICE MANUAL

即熱式電熱水器即热式电热水器. Instantaneous Water Heater 使用說明書

brass material mould. 500USD (2 pcs) Baby safety swab 500USD (2 pcs) Cosmetic swab brass material mould. 500USD (2 pcs) Cosmetic swab

Cooker Hood User Manual

AirFloss Ultra. 5_020_9188_2_DFU-Booklet_A6_v3.indd 1 21/09/16 09:11

SOLARBOX Models 1500e RH and 3000eRH Accelerated xenon light fastness and weathering test chambers

Service Manual. FILE No.HMRSM

矿用电缆 矿 用 电 缆 江苏亨通电力电缆有限公司

M P 1 2 F G C O M P R E S S O R TECHNICAL SPECIFICATIO N

Automated Pressure Steam Sterilizer. Operating Instructions

LATEST HEAT PUMP TECHNOLOGIES IN JAPAN. Waseda University Kiyoshi Saito

Prospects and challenges for sustainable urbanization in China

Modular Air Cooled Chiller/Heat Pump

MultiTemp IV Thermostatic Circulator

Midea Vacuum Cleaner. User Manual VC-35A1Q3

qianlong garden restoration project 乾隆花园修复工程

Hot Air Station without Extractor desk Ref. JTSE-QA

PREVENT ALL INJURIES IN THE KITCHEN. GO HOME SAFE AND HEALTHY.

进入洗手间前须敲门 告知要清洗洗手间的意图 在入口处展示安全告示牌

NE6210CZ NE6210CZ C O M P R E S S O R TECHNICAL SPECIFICATION HUANGSHI DONPER ELECTRICAL APPLIANCE CO., LTD

English (original instructions) 2 中文 ( 简体 ) 7 繁體中文 11 한국어 15. Copyright DeWALT

CJ6240CK COMPRESSOR TECHNICAL SPECIFICATION HUANGSHI DONPER ELECTRICAL APPLIANCE CO., LTD

Contents TERI. Part I Background. Part II Introduction of Research on Flammability of Lower GWP Refrigerantds by TERI.

A New Generation of Active Intrusion Detection System for Physical Protection

APPROVAL SHEET SPECIFICATIONS OF HERMETIC SCROLL COMPRESSOR C-SBR180H16A

Installation Instructions for the MICRO SWITCH VPX Series Valve Position Indicator for Hazardous Locations

CONTENTS. I Description II Specification III Structure IV Mounting and Wiring V Application VI Troubleshooting...

Prof. Dr. Li Ming. Refrigeration technology about solar adsorption, absorption and Photovoltaic

Jiangbei New District, Nanjing ISOCARP Urban Planning Advisory Team Report

Gas Pipeline Locating Leak detection and Safety Assessment

WARNING/CAUTION DESCRIPTION OF COMPONENTS FUNCTION EXPLANATION OPERATION INSTRUCTIONS CONTINUOUS DRAINAGE CAUTIONS MAINTENANCE/EMERGENCY

PAC-10P PAC-15P. 移動座地式冷暖空調 Portable Reverse Cycle Air Conditioner 在使用之前請詳細閱讀 使用說明書 及 保用條例, 並妥為保存

Contents. Precision Lead-free Reflow Oven. Model: AT-R3028

The Home Depot Quality System Audit. * Example Report * North America Latin America

Adaptibility Analysis of nzeb and Passivhaus in Mixture Climates of China

PMAC202 Branch Circuit Power Meter User Manual V1.0

践行里约 +20 决议, 示范新型城镇化 : 国际人居环境范例新城倡议

Collaborative efforts for sustainable campus 可持续校园建设多方协作机制的初探

PE Series Jaw Crusher P E

丹麦,Fuglsang 美术馆 / Tony Fretton Architects

TOYOLAC PC//ABS Alloy PX10

TRANSPORTATION EXISTING 交通现状

KKKKKKKHud Dapur Panduan Pengguna

Contour TM Screw Compressors

Periuk Nasi Elektrik Kegunaan di Rumah 白米饭 泰国香米 杂粮 快煮 糙米或糯米...25 蛋糕 / 面包...29 汤 / 慢煮...30 使用计时器...31 清洁和保养...32 如何使用可调节式蒸笼 / 屏显代码应对措施...

R-S32EPH R-S32EPHL

"Three Preventions" System Design Based On Single-Chip Microcomputer SCM Control Jiaxiong Wen

Application of Distributed Fiber Optic Sensing Technology in the Transportation Engineering Monitoring

SS IN 1 SMD HOT AIR REWORK STATION

Coils Connectors Bosch Rexroth

Ketuhar Elektrik Terbina Dalam Manual Pengguna. Built-in Electric Oven User Manual 嵌入式电烤箱用户手册

1. TF Hermetic Reciprocating Compressor

InRow Direct-Expansion Air Conditioners

CKF-110. Express Healthy Air Fryer USER MANUAL

GreenUp Lowbay G2 BY288P. Lucia Liu Indoor Segment, PLP Growth Market Feb. 2016

公司願景 業務項目 我們的願景是能為您帶來更加 健康 舒適 便利 的生活環境 水的控制專家 晴立實業 創立於 1993 年 十幾年來致力於排水器及週邊產品之研究與開發 多年來的創新及研發成果獲得多項產品專利, 深受各界的肯定, 於業界亦趨領導地位 為了服務客戶長久以來的支持,

SCB-103. Deluxe Delicacy Cooker USER MANUAL

Transcription:

Hitachi Highly Rollkolbenverdichter Rotary Compressors Spezifikation Manual WHP02250BCN-H6AU RIES GmbH, Rudolf-Diesel-Str. 10, D 64569 Nauheim, GERMANY Phone: +49 6152 9741 0, Fax: +49 6152 9741 21, Email: info@ries-gmbh.de, Website: www.ries-gmbh.de

SUBJECT Model WHP02250BCN-H6AU SPECIFICATION PAGE:1/29 1. SCOPE This specification is applied to SHANGHAI HITACHI Heat pump water heater compressor. 2. SPECIFICATION OF COMPRESSOR 2.1 Model WHP02250BCN-H6AU 2.2 Rated Voltage/Frequency/Phase 208V~230V/60Hz/single 2.3 Application Heat pump water heater 2.4 Refrigerant R-134a 2.5 Compressor Cooling Forced air 2.6 Displacement 2.7 Performance 12.2ml/rev Performance (Voltage 208/220/230V) Item Standard Condition Summer Condition Winter Condition Rated Condition Nominal Heating Capacity Motor input Current COP(see*) Evaporating temp. Condensing temp. 2380W/2400W/2405W 2770W/2790W/2815W 1730W/1750W/1765W 2235W/2250W/2270W 565W/575W/585W 575W/585W/600W 520W/535W/550W 550W/560W/575W 2.80A/2.70A/2.68A 2.85A/2.80A/2.75A 2.60A/2.55A/2.55A 2.70A/2.65A/2.65A 4.21/4.17/4.10 4.80/4.76/4.70 3.32/3.27/3.22 4.06/4.02/3.95 Test Conditions 10 15 0 7.2 55 55 55 54.4 Liquid temp. entering expansion valve. 46.7 46.7 46.7 46.1 Return gas temp. Ambient temp. Wind speed 20 25 10 35 35 35 15 35 2m/s 2m/s 2m/s 2m/s

SUBJECT Model WHP02250BCN-H6AU SPECIFICATION PAGE:2/29 * COP= Heating capacity (W) Motor input (W) 2.8 Allowable amount of refrigerant charge 900 g 2.9 Amount of oil charge 270±20 ml(initial) 2.10 Oil NEO32/L22E or equivalent 2.11 Space volume of inner case 900 ml 2.12 Net weight 9.2 kg incl.oil 2.13 Hermetic Terminal 1/4 quick connect type 2.14 Motor Type Permanent Split Capacitor Capacitor 17MFD/450 Volts Locked rotor amps 21 A (230V/60Hz) Approved voltage range Rated Voltage(-10%,+10%) Winding resistance(m/s) 3.56/5.19Ω(at 20 ) 2.15 Starting performance (1) The starting voltage should be as follows. (2) The starting pressure should be balanced between the suction and discharge of the compressor and should be adjusted to the following table. (3) The temperatures of the compressor enclosure should be more than 20 continuously at the following table.

SUBJECT Model WHP02250BCN-H6AU SPECIFICATION PAGE:3/29 TABLE 1 Starting Conditions Spec Motor temperature Pressure Starting voltage Cold-Starting MPa{kgf/cm 2 G} Cold state (room temperature) 0.73{6.38} (V2)** Below 85% of rated voltage Hot-Starting(Standard) Hot state after operated under standard load condition 0.69{6.03} Below 85% of rated voltage Hot-starting(Overload) Hot state after operated under overload condition 0.95{8.61} Below 90% of rated voltage * Nominal heating capacity equals refrigerant capacity adding motor input. Refrigerant capacity and motor input are measured by secondary Refrigerant calorimeter Methods of GB5773by Shanghai Hitachi Electrical Appliances Co.,Ltd. Allowable heating capacity should be more than 95% of the nominal heating capacity and allowable motor input should be less than107% of nominal motor input. **. V 2 means minimum voltage measured between pins of hermetic terminal at the compressor starts. V 2 ***. The suction pressure is measured on the position above the filter of accumulator. Time

SUBJECT 3. PARTS AND DRAWING LIST 零件及图纸清单 Model WHP02250BCN-H6AU SPECIFICATION WHP02250BCN-H6AU 规格书 PAGE:4/29 WHP02250BCN-H6AU Outline dwg. Drawing code Q ty Remarks 4CYCD0064 Dimensioned sketch Wiring diagram SC01D576 Electrical components Motor protector 4CYC00982L 1 B150-145-241E Running capacitor SC01D352H39 * 17µF- 450WV Terminal parts accessories Terminal part assy SC01DA46 Terminal cover SC01DA53 1 Sleeve 4CYC00995 1 Motor Pro. Spring SC01DA45 1 Packing SC01DA54 1 Rubber washer SC01DA63 1 Flange nut SC01D430 1 Mounting accessories Mount assy SC01DA55 Rubber mount SC01DA68 3 *. Out of supply,for reference. 4. CHARACTERISTICS 4.1 Residual moisture 120mg MAX 4.2 Residual impurities 100mg MAX

HEAT PUMP WATER HEATER COMPRESSOR CRITERIA FOR LONG LIFE SYSTEM 1. SYSTEM DESIGN LIMITATIONS PAGE:5/29 1.1 Power source and Voltage Voltage applied to hermetic terminal should be within the range mentioned in this specification. In the case of three phase, the phase imbalance should be within 3% among the compressor terminals. The phase imbalance should be calculated according to the follow formula. (V)max-(V)mean the phase imbalance= 100% (V)mean (V)max:Maximum voltage among the three terminals.(v) (V)mean:average voltage among the three terminals.(v) 1.2 Operating Temperatures and Pressures The operating temperatures and pressures of the compressor should be within the range shown in the table 2 and graph 1. 1.3 Operating and Shut-off Period The compressor should be operated continuously at least for 5 minutes after being turned ON. 3 minutes shut-off time should be ensured at least until restarting. 1.4 Oil Back and height of the oil level Oil should be returned continuously to the compressor and not kept in the refrigeration system. Oil level of compressor should be higher than 7.5 mm from the lubricating piece fixed on the end of the crankshaft. Compressor must not be started operated under a dual-layer separate status. However, in case of foaming situation, the height of this foam does not mean the height of the oil level. If you do not keep the oil level, the oil shortage will occur, and influence the reliability of compressor. (Please check the oil level in the compressor with the sight glass we supply.)

HEAT PUMP WATER HEATER COMPRESSOR CRITERIA FOR LONG LIFE SYSTEM PAGE:6/29 There should be superheated gas returned to the compressor under all normal operating conditions. Item Table 2 Operating Envelope Discharge pressure 2.63{25.79} MAX MPa{kgf/cm 2 G} (condensing temperature :80 ) ( see graph 1) Suction Pressure 0.11~0.67 {0.12~5.83} (Evaporation Temperature :- 25 ~25 ) MPa{kgf/cm 2 G} Compressor case bottom temp 99 or below and 6 degrees higher than condensing temperature Motor winding temp. Voltage±10% 127 MAX Motor winding temp. under locked-rotor condition under stable condition: OLR Average OFF 165 MAX Temp Highest Accumulator temp Highest 190 MAX Average OLR time Higher than outlet pipe of evaporator ON

HEAT PUMP WATER HEATER COMPRESSOR CRITERIA FOR LONG LIFE SYSTEM PAGE:7/29 Condensening Temperature( ) 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 P7 P1 P6 P5 P2 P4 P3-35 -30-25 -20-15 -10-5 0 5 10 15 20 25 30 Evaporating temperature( ) Graph 1 图 1 P1 P2 P3 P4 P5 P6 P7 Condensing temperature 80 25 10 10 52 70 80 Evaporation Temperature 25 25 10-25 -25-15 5 1.5 Discharge pipe temperature Discharge pipe temperature is measured at a distance 300mm from the surface of compressor and should be less than 110. The tip of the thermocouple is fixed by soldering when measuring discharge pipe temperature.furthermore, soldering point is covered with urethane foam to prevent the effect of wind.

HEAT PUMP WATER HEATER COMPRESSOR CRITERIA FOR LONG LIFE SYSTEM PAGE:8/29 1.6 Temperature of Shell Bottom The Temperature of compressor shell Bottom must be 6 degrees higher than the corresponding saturated temperature of discharge pressure under normal operating conditions. 1.7 Avoid refrigerant migration The refrigerant migration to compressor shell should be avoided during the heat pump water heater system shut down periods, It s suggested that the electric heating belt should be used around the shell bottom when necessary. 1.8 Allowable Incline The allowable incline should be less than 5 during operation. 1.9 Pipe Vibration The displacement of the pipes, which connect from the compressor to otherparts of the refrigerator systems, should be less than 0.8mm(1/32 )when the compressor is operating at rated frequency +10Hz/ -10Hz and voltage range of rated ±10%. Displacement in excess of 0.8mm(1/32 ) will require changing tube length and/or routing. 1.10 Connecting Tube Design In designing and routing tubing that connect from the compressor to the other parts of the air conditioner, following should be considered. Moving tubes to the moving parts; minimum clearance 12.7mm(1/2 ) Moving tubes to non-moving parts; minimum clearance 9.5mm(3/8 ) Moving tubes never touch to lead wire. 2. PROCESS LIMITATIONS 2.1 The degree of vacuum in the refrigerating system should be less than 20Pa {150 10-3 mmhg}at room temperature just before charging refrigerant. The quantity of water should be less than 0.15ml.

HEAT PUMP WATER HEATER COMPRESSOR CRITERIA FOR LONG LIFE SYSTEM PAGE:9/29 2.2 Prevent moisture from entering into the enclosed unit system. When the moisture entered into the unit with refrigerant R134a, the refrigerant oil and the organic compound material presented in the hermetic motor will possibly decompose on the affecting of water. It will result in the capillary depositing and the reducing of insulation resistance. It is necessary to install a dryer to dehumidify the residual moisture mixed in the refrigerant in the cycling system. The specially defined device for drying and filtering of HFC-R134a is advised. 2.3 The weight of foreign particles on the inside surface of the heat exchanger tubes should be less than 0.05g/m 2. Metallic dust should not be permitted to enter the refrigerating system. This value means the weight of foreign particles filtered after washing inside surface of the heat exchanger tubes with R-11. Prevent the impurities from entering into the enclosed unit system. When the impurities entered into the enclosed system, it will damage the moving mechanism parts and result in the capillary depositing. 2.4 Eliminate all system contaminants such as trichlorethylene, alkalies,soap,acid,oil & washing fluid used at machining the heat exchanger tubes. 2.5 Purge parts with dry nitrogen or dry air to remove remains in parts (dust, detergent,etc.) before assembly of system.. Time for purging :over one second for pipe ;over three seconds for heat exchanger. Purging pressure: 0.9±0.1MPaG.Dew point of dry air: Below-20 C. 为把部品内的残留物 ( 灰尘, 清洗剂等 ) 除去, 在组装系统的部品前, 要用干燥氮气或干燥空气吹净部品 吹的时间 : 管件要在 1 秒以上, 热交换器要在 3 秒以上 吹气压力 :0.9±0.1MPaG, 干燥空气露点 :-20 C 以下.

HEAT PUMP WATER HEATER COMPRESSOR CRITERIA FOR LONG LIFE SYSTEM 热泵热水器专用压缩机使用基准 PAGE:10/29 Dry nitrogen should be charged in compressor before assembly of system. Welding should be finished within one minute after charge of nitrogen. Dry nitrogen needs to be charged again and weld if over one minute. Always purge the compressor with dry nitrogen during assembly of system. 在系统组装时, 先往压缩机里充入干燥氮气 充入氮气后, 在 1 分钟内完成焊接 如果超过 1 分钟, 须再次充入干燥氮气焊接 在系统装配时要经常用干燥氮气吹净压缩机 2.6 The motor winding temperatures should be less than 149 in process of manufacturing the refrigerating system. The temperature of the hermetic terminal body should be less than 177. 在制造制冷系统时, 电机绕线的温度应小于 149, 密封接线柱体温度小于 177 2.7 The compressor should be operated for more than 20 seconds within 15 minutes after charging refrigerant into the system so proper lubrication results. 在充注制冷剂之后的 15 分钟内, 压缩机必须运转 20 秒以上, 以保证适当的润滑 3. MISCELLANY 其它 3.1 The pipe and hermetic pins attached to the compressor should not be bent. 与压缩机连接的管道及密封接线柱销子不得弯曲 3.2 The compressor should never be operated while under vacuum;otherwise, internal arcing can cause damaging parts. 压缩机不得在真空情况下运行, 否则内部的弧形电流将损坏内部零件 3.3 The compressor should not be operated to form a vacuum and to absorb air. 压缩机不得自身抽真空及空运转 3.4 The compressor should not be left opened in the atmosphere for more than 5 minutes. 压缩机不得在空气中持续打开 5 分钟以上 When the air entered into the unit system with refrigerantr134a, it will expedite the deterioration of the oil and result in the capillary depositing and the reducing of insulation resistance. 应避免空气进入系统 当使用 R134a 冷媒的系统里混入过多的空气时, 将促使冷冻机油分解和裂化, 从而成为毛细管堵塞和压缩机绝缘不良的原因 3.5 The electric pulse should not be applied to the hermetic terminals when the compressor is under vacuum. 当压缩机处于真空状态下, 不应向密封接线柱上加电脉冲

HEAT PUMP WATER HEATER COMPRESSOR CRITERIA FOR LONG LIFE SYSTEM PAGE:11/29 3.6 The compressor should be kept in the clean place with low-moisture. 3.7 The compressor must not be applied for transportation equipment, such as automobiles, trains, ships, and others. 3.8 The compressor should not be splashed with water intentionally. 3.9 Use the refrigerant of specified brand. When the refrigerant not specified used, it will possibly cause trouble of the performance and reliability of the compressor by the impurities in the refrigerant. 3.10 Refrigerant should be charged from the end of condenser of refrigerating systems. Never charge refrigerant to the compressor directly. 3.11 Compressor mounting 压缩机防振构造 Rubber grommets are designed soft to provide the noise isolation and to lessen vibration energy transmission.stud bolt should be designed to provide sufficient clearance for noise and vibration isolation and to prevent compressor from coming off its mount. 3.12 The first starting voltage supplied to the refrigerating system should be more than the starting voltage mentioned TABLE 1(page 3). The refrigerant can not dissolve in the oil at the beginning because of the high viscidity of the oil. 3.13 The compressor should be kept out of the corrosive atmosphere such as in a chemicals storage, beside a hot spring and so on.

HEAT PUMP WATER HEATER COMPRESSOR CRITERIA FOR LONG LIFE SYSTEM PAGE:12/29 3.14 The lead wires should be connected to hermetic terminals without being touched on the surface of the compressor. 3.15 The fuse or/and breaker should be equipped in the main circuit. 3.16 The oil should be returned continuously to the compressor and not stayed in the refrigerating system. 3.17 There should be adequate clearance between the OD26-under-surface of Bolt -Head and the upper surface of rubber grommets. 3.19 To avoid water and impurity into the refrigeration system and make sure no leakage of refrigerant during the operating course. It s required to direct the erector and maintenance man of air-conditioner.

Check upon Delivery PAGE:13/29 1. Basis for Checking upon Delivery The Performance test will be carried out in accordance with this compressor specification. The Safety Performance in accordance with GB4706.1 Safety of household and similar electrical appliances General requirements and GB 4706.17 Safety of household and similar electrical appliances Particular requirements for motor-compressor. 2. Rule for Checking upon Delivery If come across any quality problem, please notify the company in written form within 30 days after the arrival of the cargo, the company shall exchange exactly the number of the products, otherwise they shall be regarded as being up to standard.

14/29

15/29

16/29

17/29

18/29

19/29

20/29

21/29

22/29

23/29

24/29

25/29

26/29

27/29

28/29 Heizleistung / Capacity (W) 4500 4000 3500 3000 2500 2000 1500 ( ) 40 50 55 60 70 Kondensationstemp / Cond. Temp. 1000 500 0-15 -10-5 0 5 10 15 20 25 Verdampfungstemp. / Evaporationg Temp.( C) Leistungsaufnahme / Motor input (W) 800 700 600 500 400 ( ) 70 60 55 40 30 Kondensationstemp / Cond. Temp. 300 200-15 -10-5 0 5 10 15 20 25 Verdampfungstemp. / Evaporationg Temp.( C)

29/29 Stromaufnahme / Current (A) 4.00 3.50 3.00 2.50 2.00 1.50 ( ) 70 60 55 50 40 Kondensationstemp / Cond. Temp. 1.00-15 -10-5 0 5 10 15 20 25 Verdampfungstemp. / Evaporationg Temp.( C) Massenstrom / Flux (kg/h) 80 70 60 50 40 ( ) 40 50 55 60 70 Kondensationstemp / Cond. Temp. 30 20 10-15 -10-5 0 5 10 15 20 25 Verdampfungstemp. / Evaporationg Temp.( C)