COnDEnSInG BOIlERS TAU UNIT OIL USER parameters manual

Similar documents
RVS43.. RVS63.. AVS75.. AVS37.. QAA75.. QAA78.. QAA55.. Albatros2 Boiler controllers User manual. Building Technologies HVAC Products

INSTRUCTION FOR THE USER THC V E OIL BLU

RVS46.. AVS75.. AVS37.. QAA75.. QAA78.. QAA55.. Albatros 2 Zone controller User Manual. Building Technologies HVAC Products

RVS43.. RVS63.. AVS75.. AVS37.. QAA75.. QAA78.. QAA55.. Albatros2 Boiler controller User Manual. Building Technologies HVAC Products

RVS13... RVS53... AVS75... AVS37... QAA75... QAA78... QAA55... Albatros2 Boiler controllers User Manual. Building Technologies HVAC Products

Albatros 2 CHP Controller User Manual OEM. RVC32.4x0. Building Technologies HVAC Products

QAA Room Unit for Boiler Control with OpenTherm Interface Basic Documentation. Siemens Building Technologies Landis & Staefa Division

user s instructions MH-water heater

Operating Manual for professional installers. LMS Controller. 02/2011 Art. Nr

Albatros 2 Solar compact controller User manual RVA Building Technologies

Albatros2 Boiler Controllers User Manual RVS13.. RVS53.. Siemens Schweiz AG HVAC Products. Edition 1.0 Controller series A CE1P2383en

Albatros 2 CHP Controller User Manual RVC Siemens Schweiz AG HVAC Products. Edition 0.15 Controller series Z CE1UsManCHP1en 16 September 2008

Operating instructions

ProCon 16, 31, 47, 75, 77 & HT. RVA 46. Zone Controller Commissioning Data.

Albatros2 Heat pump controller User Manual RVS AVS AVS AVS AVS Building Technologies

ADI LT CONDENSING LOW TEMPERATURE BOILER

user s instructions MH-water heater

Operating Instructions Heating Controllers RVL479, RVL480, RVL481, RVL482

Chappee Moorea Condensing Boiler kw

G2484. Installation. - Control panel (in the panel front, on the inner wall, or on a DIN rail)

RVL471 Heating and Domestic Hot Water Controller Basic Documentation

Heating and D.h.w. Controller RVL482 Basic Documentation

1 DOCUMENT REVISION SOFTWARE VERSION BASIC DESCRIPTION BASIC OVERVIEW OF HYDRAULIC DIAGRAMS HYDRAULIC DIAGRAMS...

Boiler controller Lambdatronic S 3200

ProCon Boiler Controller Commissioning Quick Reference Guide

Room Unit for Boiler Control QAA User manual. Building Technologies. With OpenTherm Interface

ADI CD CONDENSING BOILER

M116 / M450 USER AND MAINTENANCE MANUAL FOR MODULATING-CONTROL BOILER WITH GAS BURNER EQUIPPED FOR NATURAL GAS. Type : B23 ATLANTIC 2000

Type summary Albatros 2

Boiler controller S-Tronic Plus

RVP360 and RVP361 Heating controllers for 2 heating circuits and d.h.w. Basic Documentation

Operating Instructions

Operating instructions

ProCon 16, 31, 47 & 75. RVA 63 Boiler and Circuit Controller Commissioning Data.

RVP340 Heating controller for 1 heating circuit RVP350 and RVP351 Heating controllers for 1 heating circuit and d.h.w. Basic Documentation

Installation and Operating Manual for the ProCon E 26 Wall Mounted Condensing Boiler Range

Installation and Operating Manual. Merlin 5064 V3. System Manager

Modulating clock thermostat

CONTROL PANEL. RIELLOtech PRIME ACS INSTALLATION, OPERATION AND MAINTENANCE MANUAL

multimatic Operating instructions AT, BE (de), CH (de), DE VRC 700f/4

Safety. DANGER Indicates potentially fatal situations. WARNING Indicates possible danger to life and limb.

RVA Cascade Controller for modulating gas-fired Boilers Basic Documentation

Operating instruction. Remote control station WCM-FS /

Operating instructions

Heating Controller SDC. District Heating Controller DHC 43 OPERATING INSTRUCTIONS

Operation manual FR EN NL DE IT. intended for professionals and end users. To be saved for future consultation

British Gas 330+ High Efficiency Condensing Boiler. Instructions for Use. To b e l e f t w i t h t h e u s e r. British Gas Service Tel:

USER'S INFORMATION MANUAL

User Instructions For TopTronic RS-30

Installation and Operating Manual. Merlin IO 5064 V4 with BM-T. System Manager

Heating Controller SDC Remote Heating Controller DHC

Operating Instructions for use by heating contractor. VITOTRONIC r 100 VITOTRONIC r 300-K IMPORTANT

PROGRAMMABLE 7-DAY THERMOSTAT

RVL472. Heating Controller. Building Technologies HVAC Products. Series C. including d.h.w. heating

CONDENSING BOILERS TAU UNIT OIL 35 G OIL 55 G INSTALLATION, MAINTENANCE AND SYSTEM MANAGEMENT MANUAL

Heating Controller SDC Remote Heating Controller DHC

Operating Instructions

BM Programming Module. For the heating engineer Installation instructions

HMC300. Control unit. Operating Instructions. EMS plus (2014/10) O

1. COMMISSIONING OF THE BOILER en DESCRIPTION FUNCTION BUTTON DESCRIPTION SYMBOL DISPLAY

Service instructions. FM443 solar module. Function module. For contractors. Read carefully prior to commissioning or service

RVL481. Heating Controller. including d.h.w. heating

BeSMART Thermostat. EN Thermostat Manual

Operating Instructions

Multi Boiler Guide. Kit #

District heating controller for two heating circuits and d.h.w. according to Siemens specifications:

Condensing Boiler RS100 Controller Training Program

RVL471. Heating controller. G2524en. Installation Instructions. 1 Installation. 2 Commissioning

Operating instructions THETA control unit for heating contractors. ROTEX control unit: - THETA 23R - THETA RS - THETA HEM1

User Manual for model

RF ELECTRONIC PROGRAMMABLE ROOM THERMOSTAT, 7 DAY

USER MANUAL ACQUAHOME 32 B BLU

Installation and Operating Manual for the ProCon HT & HTP 150 & 225 Floor Standing Condensing Boiler Range. **RVS Controlled**

/2010 US/CA

multimatic Operating instructions Operating instructions For the operator AT, BE (de), CH (de), DE VRC 700f/4 Publisher/manufacturer Vaillant GmbH

E8 Controller and BCM for Modulex EXT GF-136-C USER MANUAL. Installation, Operation & Maintenance

Heating Controller SDC Remote Heating Controller DHC

Grant Aerona³. Air to Water High Efficiency Heat Pump Range. User Instructions

E System Manager Operating instructions

Technical Data Manual

USER'S INFORMATION MANUAL

CONDENSING BOILERS TAU UNIT OIL 28 B FLEX INSTALLATION AND MAINTENANCE MANUAL

USER'S INFORMATION MANUAL

Service Instructions for use by heating contractor

1 DOCUMENT REVISION CONTROL ELEMENTS... 9

Stokvis R600-LMS Boiler Gas-Fired Floor Standing Condensing

RVD120, RVD140 Controllers for district heating and d.h.w. Basic Documentation

Self-learning Room Temperature Controller

ALFEA. Commissioning & Services

INSTALLATION, OPERATION AND MAINTENANCE MANUAL

Installation and servicing instructions

RVA /109. Heating Circuit ZONE Controller. Instructions for the INSTALLER

DESIGN & TECHNICAL MANUAL

Operating Instructions. VITODENS r 200 Series With Vitotronic 200 HO1B Controls WARNING WARNING IMPORTANT

INSTALLATION, TECHNICAL ASSISTANCE CENTRE AND SYSTEM MANAGEMENT MANUAL THC V E OIL BLU

User Manual RBS 24. for model CE series ENERGY. Wall mounted instantaneous combi boiler room sealed chamber

Operating and Installation Manual VRC 430f. Weather compensator controller with radio transmission. For the operator / for the heating engineer

Control Products & Systems OEM

Aqua Balance. AquaBalance TM CONTROL MODULE QUICK START GUIDE LEGEND

RF Programmable Room Thermostat User Instructions

Transcription:

CONDENSING BOILERS TAU UNIT OIL USER parameters manual 1

CONTENTS List of end user level parameters 3 Setting functioning parameters 6 -- Time programs 6 -- Heating circuits 6 -- Room temperature 7 -- Heating curve 7 -- Setting dhw parameters 8 Error/maintenance codes 9 -- Maintenance code 11 The following symbols are used in this manual: b = Identifies actions that require caution and adequate preparation. a = Identifies actions that you MUST NOT do. This manual, Code 20100565 Rev. 0 (05/15) is made up of 12 pages. 2 USER

List of end user level parameters LIST OF END USER LEVEL PARAMETERS Operating line User level Function Default value Min Max Unit Time of day and date 1 E Hours/minutes - 00:00 23:59 hh:mm 2 E Day / month - 1,01 31,12 dd.mm 3 E Year - 2004 2099 yyyy Operator unit 20 E Language German German - - - 29 E Units ( C,bar F,PSI) C,bar - - - 32 E Basic setting Compatible - - - 39 E Commissionig menù (On Off) Off - - - Time prog heating circuit 1 500 E Mo - Su Mo - Fr Sa - Su Mo Tu We Th Fr Sa Su Mo - Su - - - 501 E 1st phase on 6:00 00:00 24:00 hh:mm 502 E 1st phase off 22:00 00:00 24:00 hh:mm 503 E 2nd phase on 24:00 00:00 24:00 hh:mm 504 E 2nd phase off 24:00 00:00 24:00 hh:mm 505 E 3rd phase on 24:00 00:00 24:00 hh:mm 506 E 3rd phase off 24:00 00:00 24:00 hh:mm 516 E Default values No Yes No - - - Time prog heating circuit 2 520 E Mo - Su Mo - Fr Sa - Su Mo Tu We Th Fr Sa Su Mo - Su - - - 521 E 1st phase on 6:00 00:00 24:00 hh:mm 522 E 1st phase off 22:00 00:00 24:00 hh:mm 523 E 2nd phase on 24:00 00:00 24:00 hh:mm 524 E 2nd phase off 24:00 00:00 24:00 hh:mm 525 E 3rd phase on 24:00 00:00 24:00 hh:mm 526 E 3rd phase off 24:00 00:00 24:00 hh:mm 536 E Default values No Yes No - - - Time program 3/HC3 540 E Mo - Su Mo - Fr Sa - Su Mo Tu We Th Fr Sa Su Mo - Su - - - 541 E 1st phase on 6:00 00:00 24:00 hh:mm 542 E 1st phase off 22:00 00:00 24:00 hh:mm 543 E 2nd phase on 24:00 00:00 24:00 hh:mm 544 E 2nd phase off 24:00 00:00 24:00 hh:mm 545 E 3rd phase on 24:00 00:00 24:00 hh:mm 546 E 3rd phase off 24:00 00:00 24:00 hh:mm 556 E Default values No Yes No - - - Time program 4/DHW 560 E Mo - Su Mo - Fr Sa - Su Mo Tu We Th Fr Sa Su Mo - Su - - - 561 E 1st phase on 6:00 00:00 24:00 hh:mm 562 E 1st phase off 22:00 00:00 24:00 hh:mm 563 E 2nd phase on 24:00 00:00 24:00 hh:mm 564 E 2nd phase off 24:00 00:00 24:00 hh:mm 565 E 3rd phase on 24:00 00:00 24:00 hh:mm 566 E 3rd phase off 24:00 00:00 24:00 hh:mm 576 E Default values No Yes No - - - Time program 5 600 E Mo - Su Mo - Fr Sa - Su Mo Tu We Th Fr Sa Su Mo - Su - - - USER 3

Operating line level User Function Default value Min Max Unit 601 E 1st phase on 6:00 00:00 24:00 hh:mm 602 E 1st phase off 22:00 00:00 24:00 hh:mm 603 E 2nd phase on 24:00 00:00 24:00 hh:mm 604 E 2nd phase off 24:00 00:00 24:00 hh:mm 605 E 3rd phase on 24:00 00:00 24:00 hh:mm 606 E 3rd phase off 24:00 00:00 24:00 hh:mm 616 E Default values No Yes No - - - Holidays heating circuit 1 641 E Period 1 Period 8 Period 1 1 8-642 E Start --.-- 01.01 31,12 dd.mm 643 E End --.-- 01.01 31,12 dd.mm 648 E Operating level Frost protection Reduced Frost protection - - - Holidays heating circuit 2 651 E Period 1 Period 8 Period 1 1 8-652 E Start --.-- 1,01 31,12 dd.mm 653 E End --.-- 1,01 31,12 dd.mm 658 E Operating level Frost protection Reduced Frost protection - - - Holidays heating circuit 3 661 E Period 1 Period 8 Period 1 1 8-662 E Start --.-- 1,01 31,12 dd.mm 663 E End --.-- 1,01 31,12 dd.mm 668 E Operating level Frost protection Reduced Frost protection - - - Heating circuit 1 700 E Operating mode Protection Automatic Reduced Comfort Comfort - - - 710 E Comfort setpoint 20,0 OL 712 OL 716 C 712 E Reduced setpoint 16 OL 714 OL 710 C 714 E Frost protection setpoint 4,0 4 OL 712 C 720 E Heating curve slope 1,50 0,10 4,00-730 E Summer/winter heating limit 18 - - - / 8 30 C Cooling circuit 1 901 E Operating mode Off Automatic Automatically - - - 902 E Comfort setpoint 24,0 15 40 C 907 E Release 24h/day Time progr HC Time program 5 24h / day - - - Heating circuit 2 1000 E Operating mode Protection Automatic Reduced Comfort Automatically - - - 1010 E Comfort setpoint 20,0 OL 1012 OL 1016 C 1012 E Reduced setpoint 16 OL 1014 OL 1010 C 1014 E Frost protection setpoint 10,0 4 OL 1012 C 1020 E Heating curve slope 1,50 0,10 4,00-1030 E Summer/winter heating limit 18 - - - / 8 30 C Heating circuit 3 1300 E Operating mode Protection Automatic Reduced Comfort Automatically - - - 1310 E Comfort setpoint 20,0 OL 1312 OL 1316 C 1312 E Reduced setpoint 16 OL 1314 OL 1310 C 1314 E Frost protection setpoint 10,0 4 OL 1312 C 1320 E Heating curve slope 1,50 0,10 4,00-4 USER

Operating line level User Function Default value Min Max Unit 1330 E Summer/winter heating limit 18 - - - / 8 30 C Domestic hot water DHW 1600 E DHW operating mode Off On On - - - Optg mode selection Eco 1601 O None Instantaneous water heater DHW storage tank None - - - Inst water heater + st tank Service / special operation 7120 E Economy mode Off On Off - - - 7130 E Chimney sweep function Off On Off - - - 7140 E Manual control Off On Off - - - Diagnostics, heat generation 8526 E 24-hour yield solar energy 0 0 999,9 kwh 8527 E Total yield solar energy 0 0 9999999.9 kwh 8570 E Hours run solid fuel boiler 0 0 65535 h USER 5

Setting functioning parameters Setting functioning parameters Time programs A number of programs are available for setting the CONTINUOUS COMFORT and REDUCED COMFORT operating modes for central heating and DHW. On and off times can be set in common for groups of days (MO-FR or SA-SU) or for each day individually. HC1 HC2 Line no. Default setting Preimpostazione HC3 4/DHW 5 500 520 540 560 600 Mo - Su Mo - Fr Sa - Su Mo... Su 501 521 541 561 601 1st phase on 6:00 Mo - Su 502 522 542 562 602 1st phase off 22:00 503 523 543 563 603 2nd phase on 24:00 504 524 544 564 604 2nd phase off 24:00 505 525 545 565 605 3rd phase on 24:00 506 526 546 566 606 3rd phase off 24:00 All programs can be reset to their default (factory) settings. Each program has a line for restoring default settings. HC1 HC2 Line no. Default setting Preimpostazione HC3 4/DHW 5 516 536 556 576 616 Default values No Heating circuits Various functions are available for each individual heating circuit. The operating mode for circuits 1 and 2 is selected directly by means of the button on the control panel. The operating mode of circuit 3/P is selected by means of parameter 1300. Line no. Description Default setting 700-1000-1300 Operating mode Protection Automatic Reduced Comfort The various setpoints are entered on the corresponding lines of the table. Automatic HC1 Line no. Description Default setting HC2 HC3 710 1010 1310 Comfort setpoint 20.0 712 1012 1312 Reduced setpoint 16 714 1014 1314 Frost protection setpoint 4.0 716 1016 1316 Comfort setpoint max 35.0 6 USER

Room temperature Room temperature can be set to different setpoints, according to operating mode. The following figure illustrates the relationships between the various room temperature setpoints. TRKmax TRK TRR TRF 0 2 4 6 8 10 12 14 16 18 20 22 24 26 C TRKmax Comfort setpoint max TRK Comfort setpoint TRR Reduced setpoint TRF Frost protection setpoint In protection mode, room temperature is not allowed to fall below the setpoint in order to stop the system freezing. Heating curve Heating curve slope The heating curve is used to generate temperature setpoints according to prevailing weather conditions. The heating curve can be adapted by a number of settings according to user requirements. HC1 Line no. Description Default setting HC2 HC3 720 1020 1320 Heating curve slope 1.5 721 1021 1321 Heating curve displacement 0.0 726 1026 1326 Heating curve adaption Off Increase slope: You can use this function to increase heating flow temperature, especially in low outside temperatures. Reduce slope: You can use this function to reduce heating flow temperature, especially in high outside temperatures. CHARACTERISTIC HEATING CURVE SLOPE TFlow temperature C 100 90 80 70 60 50 40 30 4 3,5 3 2,75 2,5 2,25 2 1,75 1,5 1,25 1 0,75 0,5 0,25 20 10 0-10 -20-30 C Outside temperature USER 7

Setting dhw parameters Setpoints Line no. Description Default setting 1610 Nominal setpoint 55 1612 Reduced setpoint 40 Domestic hot water can be heated to different setpoints. These are activated on the basis of the selected operating mode and take the storage cylinder to different temperatures. TWWR TWWN TWWmax TWWR DHW reduced setpoint TWWN DHW nominal setpoint TWWmax DHW nominal setpoint maximum 0 10 20 30 40 50 60 70 80 90 100 C DHW charging begins when DHW temperature drops below the switching differential setpoint (parameter 5024) and stops again when the DHW temperature reaches the nominal setpoint. 8 USER

Error/maintenance codes Error/maintenance codes When the alarm symbol n warns of an error, press the button (6) to display a description. The message on the display describes the cause of the error. Error 30: Flow sensor 1 6 b If one of these alarms appears, contact r's Technical Assistance Service or an authorised heating engineer to restore the normal functioning of the boiler. Error list Error code Description 0 No error 10 Outside sensor 20 Boiler sensor 1 25 Boiler sensor solid fuel 26 Common flow sensor 28 Flue gas sensor 30 Flow sensor 1 31 Flow temperature 1 cooling, sensor error 32 Flow sensor 2 38 Flow sensor primary controller 40 Return sensor 1 43 Solid fuel boiler return sensor 46 Return temperature cascade sensor error 47 Common return temperature sensor error 50 DHW sensor 1 52 DHW sensor 2 57 DHW circulation sensor 60 Room sensor 1 65 Room sensor 2 68 Room sensor 3 70 Buffer storage tank sensor 1 71 Buffer storage tank sensor 2 72 Buffer storage tank sensor 3 73 Collector sensor 1 74 Collector temperature 2 sensor error 76 Special sensor 1 81 LPB short-circuit/comm 82 LPB address collision 83 BSB short-circuit 84 BSB address collision 85 Radio communication 98 Extension module 1 99 Extension module 2 100 2 clock time masters USER 9

Error code Description 102 Clock reserve missing 103 Communication error 105 Maintenance message 109 Boiler temperature supervision 110 Lockout by SLT 117 Water pressure too high 118 Water pressure too low 121 Flow temperature HC1 122 Flow temperature HC2 123 Flow temperature too low 126 DHW charging supervision 127 Legionella temperature 131 Fault burner 140 Invalid LPB address 141 LPB not configured 142 No LPB device 146 Sensor/controlling element config 171 Alarm contact 1 active 172 Alarm contact 2 active 174 Alarm contact 4 active 176 Water pressure 2 too high 177 Water pressure 2 too low 178 Temperature limiter heating circuit 1 179 Temperature limiter heating circuit 2 207 Error, cooling circuit 217 Sensor error common message 218 Pressure supervision common message 241 Flow sensor, solar sensor error 242 Return sensor, solar sensor error 243 Swimming pool temperature sensor error 320 DHW charging temperature sensor error 321 Instantaneous DHW heater outlet temperature sensor error 322 Upper pressure limit 3 (crossed) 323 Critical lower pressure limit 3 (crossed) 324 BX same sensors 325 BX/extension module same sensors 326 BX/mixing valve group same sensors 327 Extension module same function 328 Mixing valve group same function 329 Extension module / mixing valve group same function 330 Sensor BX1 no function 331 Sensor BX2 no function 332 Sensor BX3 no function 333 Sensor BX4 no function 334 Sensor BX5 no function 335 Sensor BX21 no function 336 Sensor BX22 no function 337 Sensor BX1 no function 338 Sensor BX12 no function 339 Collector pump Q5 missing 340 Collector pump Q16 missing 341 Collector sensor B6 missing 342 Solar DHW sensor B31 missing 343 Solar integration missing 344 Solar controlling element buffer K8 missing 345 Solar controlling element swimming pool K18 missing 346 Solid fuel boiler pump Q10 missing 347 Solid fuel boiler comparison sensor missing 348 Solid fuel boiler address error 10 USER

Error code Description 349 Buffer return valve Y15 missing 350 Buffer storage tank address error 351 Primary controller / system pump address error 352 Pressureless header address error 353 Cascade sensor B10 missing 354 Special sensor 2 357 Flow temperature cooling circuit 1 monitoring 365 Q34 instantaneous heating error 366 Room temperature Hx sensor error 367 Relative room humidity Hx sensor error 371 HC3 flow temperature 373 Expansion module 3 388 DHW sensor no function When the h symbol appears, a maintenance alarm is present or the boiler has entered a special operating mode. Press button (6) for further information. Line no. Description 7040 Burner hours interval 7041 Burner hrs since maintenance 7042 Burner starts interval 7043 Burn starts since maint 7044 Maintenance Interval 7045 Time since maintenance Attention 3: Maintenance interval exceeded 6 As soon as the number of burner operating hours or the number of burner starts exceeds the values set here, an alarm message is displayed. Maintenance code Maintenance code Description 1 Burner hours run exceeded 2 Burner starts exceeded 3 Maintenance interval exceeded 5 Water pressure heating circuit too low (pressure dropped below lower limit 1) 18 Water pressure 2 heating circuit too low (pressure dropped below lower limit 2) 10 Replace battery of outside sensor USER 11

Cod. 20100565 RIELLO S.p.A. 37045 Legnago (VR) Tel. 0442630111 - Fax 0442630371 - www.riello.it As part of the company s ongoing commitment to perfecting its range of products, the appearance, dimensions, technical data, equipment and accessories may be subject to variation.