Operating Manual MS220DA

Similar documents
Operating Manual MS220KA and MSR220KA

Operating Manual MS220VA and MSR220VA

Operating Manual MS220Vi and MSR220Vi

Operating Instructions VLT PTC Thermistor Card MCB 112

Operating Manual TR600

Operating Manual MSF220V(VU)

Operating Guide Safe Torque Off

Inductive slot sensor

DSF xx15.xx xhv Ex-Atex Ex-Atex Certified Two wire Hall Effect Speed Sensor

Operating Guide Safe Torque Off

Technical Data. General specifications. Rated operating distance s n 5 mm

ISOMETER IRDH275BM-7 with coupling device AGH675-7 and AGH675-7MV15

Operating instructions Safety-monitoring module SRB 302X3. 1 About this document

Overload Relay EMT6 Overload monitoring system for machines operating in the EEx e area

Instructions for the fan motor control system with integrated wiring terminals SILVER C

Technical Data. General specifications Switching element function Rated operating distance s n 5 mm

Residual current monitor RCM470LY/RCM475LY. for TN and TT systems (AC and pulsating DC currents)

Technical Data. Dimensions

DSF xx10.xx xhv Ex-Atex Hall Effect Single Channel Speed Sensor

Technical Data. Dimensions

Operating instructions Safety-monitoring module SRB 302X3. 1. About this document. Content

ISOMETER IR1575. Insulation monitoring device for unearthed AC/3(N)AC systems up to 480 V and DC systems up to 480 V

ISOMETER IRDH375. Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems)

Monitoring Relays. 3RN1 Thermistor Motor Protection. For PTC sensors. 7/120 Siemens LV 1 T 2008

1.7 A-ISOMETER IRDH575. RoHS. Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Tel.: Fax:

Datasheet - MZM 100 B ST2-SD2PREM-A

Gas cylinder scale Model GCS-1

INSTRUCTION MANUAL (ATEX / IECEx)

PROTECT SRB 200EXi-1A

1.7. Insulation fault evaluators EDS460/490 EDS461/491

Datasheet - MZM 100 ST-SD2PREM-A

OilSET Installation and Operating Instructions. Oil Separator Alarm Device with SET/DM3AL sensor

Technical Data. General specifications Switching element function DC Dual NC Rated operating distance s n 3 mm

DEB71. Earth Leakage Monitoring Relay. Benefits. Description

Soliphant M with electronic insert FEM52

SCHMIDT LED Measured Value Display MD Instructions for Use

Instructions for the fan motor control system, SILVER C

ISOMETER isomed427p. Application Medical IT system in accordance with IEC , IEC , IEC and DIN VDE

1.7. Insulation fault evaluators EDS460/490 EDS461/491

Insulation fault evaluator EDS460-DG

FUNCTIONAL SAFETY OF ELECTRICAL INSTALLATIONS IN INDUSTRIAL PLANTS BY OTTO WALCH

DTA. Motor thermistor relay. Benefits. Description

Temperature-Relay TR210

MANUAL Overflow sensor NVF-104/34-PF

OPTIBAR DP 7060 Supplementary Instructions

ISOMETER IR425. Insulation monitoring device for unearthed AC/DC control circuits (IT systems)

Remote alarm indicator and test combination MK2430

SITRANS T. SITRANS T Explosion protected temperature sensor. General information. Marking of the degree of protection. Range of uses.

Engineering Guideline. pac- Carriers Type Universal

ISOSCAN EDS460-DG. Insulation fault locator for DC IT systems with high system leakage capacitances

Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Tel.: Fax:

Regulated Ex-Heater HEX with internal controller, HEX with external controller II 3 G II 3 D

Proservo NMS5- / NMS7-

INSTRUCTION MANUAL (ATEX/IECEx/SIL2) BExBG05D-SIL Flameproof Xenon SIL 2 Beacons For use in Flammable Gas and Dust Atmospheres

FUNCTIONAL SAFETY MANUAL

FUNCTIONAL SAFETY MANUAL. Gassonic Observer-H and Observer-i Ultrasonic Gas Leak Detector

Technical Data. General specifications Switching element function Rated operating distance s n 5 mm

SBEx-4 BISTATE SEPARATOR 1, 2, 3 or 4 channels in rail housing (TS35, 22,5mm width)

ISOSCAN EDS460/490 EDS461/491. Insulation fault locators with control and display function for EDS systems (insulation fault location systems)

Safety Temperature Limiter STL 50 Certified to DIN EN (replaces DIN 3440)

Additional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-nA.

Additional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-d.

Operating Instructions for Limit switch Model: NBK-R NBK-RM NBK-RT NBK-RA

RE-PR3-E-27 3-Phase Panel Mount 27kW

OilSET Installation and Operating Instructions. Oil Separator Alarm Device

Safety in the process industry

Functional safety manual Liquiphant M/S with FEL57 and Nivotester FTL325P

Technical Data. General specifications Switching element function Rated operating distance s n 8 mm

PROZESSAUTOMATION. Manual SEGMENT PROTECTOR R-SP-!12. Zone 1 Zone 2 / Div 2 FNICO

DTA04. Motor thermistor relay. Benefits. Description

GS100-ATEX. Hazardous Areas Infra-Red Beam PULSE MODULATED ACTIVE INFRA-RED BEAM FOR HAZARDOUS AREAS ZONE 1 OR ZONE 2 GENERAL

AO Annunciator Module

Datasheet - MZM 100 ST2-1P2PWREM-A

QFM21... Duct sensors. Symaro. for relative humidity and temperature

Model 144H. Product Data Sheet , Rev DB February Content

Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Phone: Fax:

M2500 Engine Controller Installation Manual

GS100-ATEX. Hazardous Areas Infra-Red Beam PULSE MODULATED ACTIVE INFRA-RED BEAM FOR HAZARDOUS AREAS ZONE 1 OR ZONE 2 GENERAL

INSTRUCTION MANUAL (ATEX/IECEx/SIL2)

OilSET-1000 (12 VDC)

SET Installation and Operating Instructions. Level switch for one sensor

isopv425 and AGH420 Ground Fault Detector for Ungrounded Solar Arrays < 100 kw And Isolation Tester Prior to Array Startup (Grounded and Ungrounded)

Technical Data. Dimensions

Ex SOLENOID / ALARM DRIVER. PRepower 5203B. Table of contents. Applications Safety instructions Technical characteristics...

Danfoss gas detection unit Type GD Heavy Duty

INSTRUCTION MANUAL (ATEX)

Model 144H. Product Data Sheet , Rev DB February Content

SACE PR021/K SIGNALLING UNIT

Datasheet: K-22 LO Sensor

Technical Data. General specifications Switching element function Rated operating distance s n 4 mm

Danfoss gas detection units

AFMS Audible Flow Monitoring System TECHNICAL SPECIFICATION

LINETRAXX RCMA420. Residual current monitor for monitoring AC, DC and pulsed DC currents in TN and TT systems

4) Intrinsic Safety Certification

SAFETY MANUAL. PointWatch Eclipse Infrared Hydrocarbon Gas Detector Safety Certified Model PIRECL

Installation and Operating Instruction

Instructions for the hand-held micro terminal of the fan motor control system, TBLZ-2-75 SILVER C

QFM21... Duct Sensors. Building Technologies HVAC Products. Symaro. for relative humidity and temperature

PEPPERL+FUCHS GmbH

UV Flame Supervision System

Transcription:

ZIEHL industrie elektronik GmbH + Co KG Daimlerstraße 13, D 74523 Schwäbisch Hall + 49 791 504-0, info@ziehl.de, www.ziehl.de Temperature Relays and MINIKA Mains Monitoring Digital Panel Meters MINIPAN Switching Relays and Controls Measuring Transducers Grid- and Plant Protection Operating Manual MS220DA updated: 2015-08-05 Su - Thermal Motor Protection 0102 MS220DA 12030-0701-01 page1 / 12 www.ziehl.de

Table of contents 1 Application and short description... 3 1.1 Application... 3 1.2 Approvals... 3 1.3 Connection diagram... 3 1.4 Overview of functions... 4 1.5 Block diagram... 4 1.6 Detailed description... 5 2 Important notes... 5 3 Assembly... 6 3.1 Installation... 6 3.2 Putting into operation... 6 3.3 Maintenance and repair... 6 3.4 Warranty... 6 3.5 Trouble shooting... 6 4 Technical data... 7 5 Safety instructions for hazardous areas... 8 5.1 Special remarks for explosive gas atmosphere areas (Zone 1 and Zone 2)... 8 5.2 Special remarks for use in the presence of combustible dust (Zone 21 and Zone 22)... 8 5.3 Safety characteristics of the safety device... 8 5.4 Application of the safety device used with equipment category (EN 50495/VDE 0171-18)... 9 5.5 Wiring... 9 5.6 Resistance and length of sensor circuit wire... 9 5.7 Safe Separation... 9 5.8 Stop function, Stop category 0... 9 5.9 Start and Restart... 10 5.10 Manual resetting... 10 5.11 Proof testing of the safety functions... 10 5.12 Maintenance and repair... 10 6 Installing the MS220DA option in the frequency converter... 11 7 Certificates... 12 MS220DA 12030-0701-01 Seite 2 / 12 www.ziehl.de

1 Application and short description 1.1 Application TMP tripping device MS 220 DA - MCB 112 PTC Relay Option B is designed as a passive option interface for Danfoss Frequency Converter series VLT including Safe Torque Off (STO). The MS 220 DA/MCB 112 will be recognized automatically by the drive. TMP tripping device is according EN 60947-8 (VDE 0660 part 0302). PTC-thermistor sensors according DIN 44081 und 44082(VDE 0660 part 0303) can be connected. The TMP tripping device can be used to protect electrical machines against inadmissible heating due to overload. With ATEX marking it can also be used as protection device for explosion-protected motors in areas with explosive gas atmospheres Zone 1 (refer to marking G) and locations with explosive dust atmospheres Zone 21 (refer to marking D). All functions in the TMP tripping device serve to protect non-explosive-protected motors and explosiveprotected motors in regular operation and in case of failure. 1.2 Approvals EC-Examination Certificate PTB 14 ATEX 3012U Marking see type plate on the device. 1.3 Connection diagram MS220DA 12030-0701-01 Seite 3 / 12 www.ziehl.de

1.4 Overview of functions The TMP tripping device MS 220 DA - MCB 112 PTC Relay Option B includes a tripping stage for PTCthermistor sensors with save potential separation from supply voltage and ground. The tripping function switches of the +24 Volt voltage directly at the Safe StopT37 terminal X44/12 of the drive. The PNP logic output terminal X44/10 signals the status in case of failure. The TMP tripping device works according to the closed-circuit principle. The device trips in case of short-circuit or line interruption. The MS 220 DA needs +24 VDC supply voltage. The serial EEPROM enables the drive to recognize the built-in option module. 1.5 Block diagram Signals from terminal block MCB 112 PTC Thermistor Option B Interface to option A and B Serial EEPROM SPCK MOSI MISO OPTION SELECT 16-pin connector 6 8 10 11 13 SPI BUS 3,3 V 5 V 1 2 5 7 9 +5 V GND T1 X44/1 PTC INPUT 24 V T2 X44/2 8,2 V 15 16 +24 V T37 LOGIC OUT X44/12 X44/10 PNP LOGIC OUT NC NC NC NC 3 4 12 14 MS220DA 12030-0701-01 Seite 4 / 12 www.ziehl.de

1.6 Detailed description 1) Shortcut 2) Attention! Tripping will not be saved and it is not protected against zero voltage. A current monitors continuously the resistance of the sensors. In cold state, the resistance is < 250 Ω per sensor (sensor circuit < 1.5 kω). The output to terminal X44/12 is high = 1. The resistance of the sensor rises rapidly at nominal response temperature TNF. At a resistance of 3 4 kω output to terminal X44/12 changes to low = 0. The devices also switch off in the case of sensor or line short-circuit (< approx. 20 Ω) or sensor or line interruption. It switches on automatically when the temperature has decreased approx. 5 C. Depending on the number of sensors the following tripping and release temperatures will be achieved with respect of TNF (nominal response temperature of the sensors): Trip temperature Release temperature 3 sensors in series TNF + 5 K TNF 5 K 6 sensors in series TNF TNF 20 K 2 Important notes To use the equipment flawless and safe, transport and store properly, install and start professionally and operate as directed. Only let persons work with the equipment who are familiar with installation, start and use and who have appropriate qualification corresponding to their function. They must observe the contents of the instructions manual, the information written on the equipment and the relevant security instructions for the setting up and the use of electrical units. The equipments are built according to EN 60947 and checked and leave the plant according to security in perfect condition. To keep this condition, observe the security instructions with the headline Attention written in the instructions manual. Ignoring of the security instructions may lead to death, physical injury or damage of the equipment itself and of other apparatus and equipment. If, in any case the information in the instructions manual is not sufficient, please contact our company or the responsible representative. Instead of the industrial norms and regulations written in this instructions manual valid for Europe, you must observe out of their geographical scope the valid and relevant regulations of the corresponding country. Attention! Safety Circuits according to EN 60204. The equipment must not be used alone for functions, when an automatic start must be avoided. MS220DA 12030-0701-01 Seite 5 / 12 www.ziehl.de

3 Assembly 3.1 Installation The TMP tripping device MS 220 DA - MCB 112 PTC Relay Option B is intended to be used in Danfoss series VLT Drives with Safe Torque Off (STO). PTC-thermistor sensors are connected directly to the terminals T1, T2. The lines of Safe Stop 37 and Logic Out are to be routed separately. Attention: Routed lines must keep enough distance to sensor lines and other mainstream lines.! Attention! Observe Safety instruction and references for putting into operation! 3.2 Putting into operation The correct function of the TMP tripping device has to be tested by simulation of the sensor resistance at terminals T1, T2. This test can additionally be done with maintenance services: Short circuit test: resistance 20 Ω in parallel to sensor terminals T1, T2 Line interruption test: disconnect sensor line at terminal T1 or T2 Temperature test: increase resistance 50 1500 Ω up to 4000 Ω. The tripping function will be stated at the drive display and can be reseted manually when the failure is removed. Please notice the admissible ambient conditions -> Technical data. 3.3 Maintenance and repair The devices are maintenance-free. Only the manufacturer may accomplish repairs. We recommend an examination within the regular maintenance periods of the plant, in which the equipment is installed. 3.4 Warranty The guarantee presupposes the observance of this operating instruction (safety and start-up instructions). 3.5 Trouble shooting The resistance within the sensor circuit must have a value 50 Ω < R < 1500 Ω. The voltage at terminals T1, T2 must be < 2.5 VDC when PTC-thermistor sensors are connected and the temperature is below TNF. The TMP tripping device must shut down when the sensor circuit is open. The voltage at terminals T1,T2 must be < 9 VDC. MS220DA 12030-0701-01 Seite 6 / 12 www.ziehl.de

4 Technical data Power supply Rated supply voltage Us Tolerance voltage Us Power consumption DC 24 V DC 21 28 V < 1 W PTC-thermistor connection X44/1 + X44/2 Standard DIN 44081/ DIN 44082 Numbers Set with 3 6 PTCs in series Cut-out-point 3.3 kω 3.65 kω 3.85 kω Reclosing point 1.7 kω 1.8 kω 1.95 kω Collective resistance cold sensors 1.65 kω Terminal voltage (sensors) 2.5 V at R 3.65 kω, 9 V at R = Terminal current (sensors) 1 ma Short circuit 20 Ω R 40 Ω Power consumption 2 mw Safe Stop T37, X44/12 Output Logic Voltage Level Voltage Current Logic Out, X44/10 Output Logic Voltage Level Voltage Current PNP-Transistor 0 24 VDC Low = 0, PNP < 4 VDC HIGH = 1, PNP > 20 VDC 60 ma PNP-Transistor 0 24 VDC Low = 0, PNP < 5 VDC HIGH = 1, PNP > 10 VDC 10 ma Testing conditions Standards EN 60947-8, EN 50178 Rated Impulse voltage 6000 V Over voltage category III Contamination level 2 Rated insulation voltage Ui 690 V Safe separation up to Ui 500 V Environmental conditions Rated ambient temperature range Ta -20 C... +55 C Rel. Humidity 5 95 %, without condensation EMC Immunity industry standard EN 61000-6-2 EMC Emission industry standard EN 61000-6-4 Vibration resistance 10 10000 Hz 1,14 g Shock resistance 50 g Housing Form 130B4065 PA 6 Dimensions (H x B x T) mm 82.5 x 69.5 x 29.5 Line connection, solid wire 1 x 0,5 1,5 mm 2 (AWG 20 AWG 16 solid wire) Insulation strip length 8.5 9.5 mm Protection class EN 60529 IP 20 Weight approx. 50 g Subject to technical modifications MS220DA 12030-0701-01 Seite 7 / 12 www.ziehl.de

5 Safety instructions for hazardous areas! Attention! Safety instruction and references for putting into operation please read carefully! 5.1 Special remarks for explosive gas atmosphere areas (Zone 1 and Zone 2) The increased danger within hazardous areas requires the careful attention of the safety instructions and references for putting into operation. Observe the national safety rules and regulations for prevention of accidents as well as the European Standard EN 60079-14 (Explosive atmospheres - Part 14: Electrical installations design, selection and erection). Installation, electrical connection and commissioning to be carried out by trained service personnel only. Inappropriate behaviour can cause heavy personal damage and damages to property. The response of the thermal motor protection must directly switch off the motor, also when used together with converters. This must be realized in the logic section or configuration in the converter. The MS 220 DA may be installed only outside potentially explosive atmospheres for the protection of explosive-protected motors. Within potentially explosive atmospheres the equipment (VLT and MS 220 DA) is to be provided with a pressurized enclosure according EN 60079-1 (Explosive atmospheres - Part 1: Equipment protection by flameproof enclosures "d"). 5.2 Special remarks for use in the presence of combustible dust (Zone 21 and Zone 22) The increased danger within hazardous areas of combustible dust requires the careful attention of the safety instructions and references for putting into operation. Observe the national safety rules and regulations for prevention of accidents as well as the European Standard EN 60079-14 (Explosive atmospheres - Part 14: Electrical installations design, selection and erection). Installation, electrical connection and commissioning to be carried out by qualified service personnel only. Inappropriate behaviour can cause heavy personal damage and damages to property. The MS 220 DA may be installed only outside potentially explosive atmospheres for the protection of explosive-protected motors. Within potentially explosive atmospheres the equipment is to be provided with a dust proofed enclosure according to EN 60529. 5.3 Safety characteristics of the safety device Safety Integrity Level SIL (EN 61508) and safety-related parameters Operating mode Hardware architecture Fault tolerance HFT low demand mode 1001 0 SIL 2 Safety Integrity Level MS220DA MTBF SFF SD SU DD DU Ta = 40 C 179 years 78 % 2,35E-07 3,73E-08 0 7,69E-08 MS220DA Proof Test Interval T1 1 year 3 years 5 years 10 years Ta = 40 C PFDavg 3,37E-04 1,01E-03 1,68E-03 3,37E-03 Observe proof test interval according EN 60079-17 for electrical equipment 3 years. The data of the functional safety stated above are valid for an ambient temperature of 40 C. Data for additional ambient temperatures can be obtained on request. MS220DA 12030-0701-01 Seite 8 / 12 www.ziehl.de

5.4 Application of the safety device used with equipment category (EN 50495/VDE 0171-18) This standard describes the minimum requirements of safety integrity level and fault tolerance of a safety device in the application together with the category of the Equipment Under Control (EUC). Equipment under control EUC Category 2 (2G, 2D) EPL = Gb, Db Category 3 (3G, 3D) EPL = Gc, Dc Safety Device No safety device SIL 1 SIL 2 Zone 1, Zone 21 Zone 0, Zone 20 Zone 0, Zone 20 Zone 2, Zone 22 Zone 1, Zone 21 Zone 0, Zone 20 The tripping relay thus is suitable as safety device for Equipment Under Control (EUC) Category 3 (HFT = 0) in Zone 1 and Zone 21 and for Equipment Under Control (EUC) Category 2 (HFT = 1) in Zone 0 and Zone 20. The combined equipment shall comply with the relevant standards EN 60079 respectively EN 61241 according to the categories to match. 5.5 Wiring The lines of the sensor circuit are to be routed as separate control lines. The use of lines of the supply cable or other mainstream lines is not permissible. If extreme inductive or capacitive stray effects are to be expected by parallel cables of the power installation, shielded control lines should be used. 5.6 Resistance and length of sensor circuit wire The line resistance within the sensor circuit may not exceed a value of 20 Ω. Maximum of permissible length for sensor circuit lines: Wire cross section Wire length 1.5 mm 2 2 x 800 m 1.0 mm 2 2 x 500 m 0.75 mm 2 2 x 300 m 0.5 mm 2 2 x 250 m With commissioning and after modification of the plant the sensor resistance must be checked with a suitable measuring instrument. With a resistance < 50 Ω the sensor circuit is to be examined for shortcircuit. Attention! Check PTC s only with measuring voltages of < 2.5 V. 5.7 Safe Separation PTC-thermistor circuit (T1, T2) has a safe separation to low-voltage electric circuits PELV (Safe Stop T37, Logic Out and Interface). -> Technical data. 5.8 Stop function, Stop category 0 A stop function released by the protection device must transfer the machine after manipulation of this function as fast as possible into a safe condition. The stop function must have top priority. In case of failure the MS220DA motor protection causes a stop command at the Safety Stop terminal T37 and the drive directly stops the engine. Stop function is Safe Torque Off (STO). MS220DA 12030-0701-01 Seite 9 / 12 www.ziehl.de

5.9 Start and Restart A restart may take place automatically only if no dangerous condition can be present. The MS 220 DA motor protection switches on automatically when the engine has cooled down. If automatically restart is programmed additional measures are required to prevent a restart of the engine in case of risk of a dangerous situation. 5.10 Manual resetting After introducing a stop by the protection device this must be maintained, until the manual resetting mechanism is operated and safe conditions for a restart are given. The manual resetting may only be possible, if all safety functions and protection devices are effective. 5.11 Proof testing of the safety functions The safety function must be tested within regular intervals. It is recommended to test once annually or within the maintenance cycle of the plant. For recurring examinations of electrical systems in hazardous areas the inspection period must be kept within 3 years. One fault is recognized by the safety test. One fault between safety tests can cause the loss of protection. The following must be tested additionally to recurring examinations with maintenance services: Short circuit test: resistance 20 Ω in parallel to sensor terminals T1, T2 Line interruption test: disconnect sensor line at terminal T1 or T2 Temperature test: increase resistance 50 1500 Ω to 4000 Ω The tripping function will be stated at the drive display and can be reseted manually when the failure is removed. If an error is detected no restart must be induced until the error is cleared. 5.12 Maintenance and repair The devices are maintenance-free. Only the manufacturer may accomplish repairs. EN 60079-17 Explosive atmospheres - Part 17: Electrical installations, inspection and maintenance have to be observed. MS220DA 12030-0701-01 Seite 10 / 12 www.ziehl.de

6 Installing the MS220DA option in the frequency converter Observe the instructions in the Operating Instructions of the VLT Drive including Safe Torque Off (STO).! Attention! Before start, disconnect the supply voltage to the frequency converter! Do never install an option card into the frequency converter while in operation! The MS220DA option is exclusively intended for use in option slot B. - Remove LCP control unit, terminal cover and standard frame (see Photo 1 or 2). - If necessary, wire the terminal block with terminal 39-55 first. Photo 1 Photo 2 Photo 3 Photo 4 - Insert the MS 220 DA option into slot B. (see Photo 3) - The plastic cover must point downwards. - Connect the motor resistor (thermistor) to terminals T1 and T2 of the MS 220 DA. Open jumper 12-37 on the frequency converter and connect terminal X44/12 on the MS 220 DA with terminal 37 (Safe Stop) on the frequency converter (see Photo 4). Only then can the VLT Drive be safely shut down in the case of malfunction. The output on terminal X44/12 of the MS 220 DA must always be wired into the chain MS220DA 12030-0701-01 Seite 11 / 12 www.ziehl.de

on the Safe Stop input on terminal 37 on the frequency converter in order to ensure shutdown of power in case of malfunction. - Continue the necessary wiring of the MS 220 DA. See connection diagram in section 1.3. - Afterwards, remove the gaps for slot B from the deeper frame supplied, and reinsert the frame, terminal cover, and the LCP control unit. (see Photos 5 or 6) Photo 5 Photo 6 - Close the device with the cover or with the enclosure cover in order to restore the enclosure to its initial condition. - Restore the supply voltage to the frequency converter.! Attention! Depending on the programmed parameters, the motor may start after the supply voltage is restored! - Configure new additional functions in the corresponding parameters.! Attention! The operator or electrical installer is responsible for proper earthing and adherence to all applicable national and local safety regulations! MG33.AK.02_FC300_Operating Instructions MG33.V3.02_Operating instructions www.danfoss.com 7 Certificates EC-Examination Certificate and EC-Declaration of Conformity can be downloaded from the web-site www.ziehl.de www.danfoss.com MS220DA 12030-0701-01 Seite 12 / 12 www.ziehl.de