TECHNICAL DATA. Refer to Approval Chart 1 and FM Design Criteria for FM Approval requirements that must be followed.

Similar documents
standard response Fusible Link Upright sprinkler VK204 (K8.0)

STANDARD RESPONSE FUSIBLE LINK PENDENT SPRINKLER VK008 (K4.2) TECHNICAL DATA 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3. TECHNICAL DATA.

TECHNICAL DATA. Refer to Approval Chart 1 and UL Design Criteria for culus Listing requirements that must be followed.

standard response fusible link sidewall sprinkler VK112 (K5.6)

Microfast quick response Fusible element hsw sprinkler

TECHNICAL DATA. MicrofastHP QUICK RESPONSE FUSIBLE ELEMENT PENDENT HIGH PRESSURE SPRINKLER VK318 (K5.6)

micromatic standard response Upright sprinkler VK100 (K5.6)

MICROMATIC STANDARD RESPONSE CONVENTIONAL SPRINKLER VK118 (K5.6) TECHNICAL DATA

qr fusible element sprinklers (part nos , 13959, 17535, and 17536) 3. technical data Sprinkler 42h March 14, 2013

TECHNICAL DATA. The Web site may include a more recent Frame Casting: Brass UNS-C84400

micromatic standard sprinkler VK003 (K2.8) 3. technical data Page 1 of 7

TECHNICAL DATA. Refer to Approval Chart 1 and Design Criteria for culus Listing requirements that must be followed.

TECHNICAL DATA OBSOLETE

quick response extra-large orifice upright sprinkler vk531 (storage-density/area)

micromatic standard sprinkler VK004 (K4.2) 3. technical data Page 1 of 6

MICROFAST QUICK RESPONSE PENDENT SPRINKLER VK3311 (K4.2) TECHNICAL DATA

QUICK RESPONSE FUSIBLE ELEMENT HSW SPRINKLERS VK308 AND HP VK320 (PART NOS AND 13955) TECHNICAL DATA

QUICK RESPONSE EXTENDED COVERAGE FUSIBLE ELEMENT PENDENT SPRINKLER VK601 (K5.6) TECHNICAL DATA

micromatic Standard response Horizontal Sidewall sprinkler

standard response elo upright sprinkler

MICROMATIC STANDARD RESPONSE CONVENTIONAL SPRINKLER VK120 (K8.0) TECHNICAL DATA

The Viking Corporation s Web site at Rated to 175 psi (12 bar) water working pressure

STANDARD/QR EXTENDED COVERAGE LIGHT HAZARD ELO FUSIBLE ELEMENT PENDENT SPRINKLER VK617 TECHNICAL DATA

MicrofastHP EC/QREC FUSIBLE ELEMENT HSW HIGH PRESSURE SPRINKLER VK613 (K5.6) TECHNICAL DATA

STANDARD/QUICK RESPONSE ECOH ELO FUSIBLE ELEMENT PENDENT SPRINKLER VK537 (K11.2) TECHNICAL DATA

STANDARD/QUICK RESPONSE ECOH ELO FUSIBLE ELEMENT UPRIGHT SPRINKLER VK535 (K11.2) TECHNICAL DATA

MICROFAST SR/QR EXTENDED COVERAGE HSW SPRINKLER VK605 (K5.6) TECHNICAL DATA

microfast and microfasthp quick response horizontal sidewall sprinklers (vk305 & vk319)

MicrofastHP EC/QREC FUSIBLE ELEMENT PENDENT HIGH PRESSURE SPRINKLER VK611 (K5.6) TECHNICAL DATA

MICROFAST QUICK RESPONSE PENDENT SPRINKLER VK302 (K5.6) TECHNICAL DATA

microfast sr/qr extended coverage pendent sprinkler

microfast and microfasthp quick response horizontal sidewall sprinklers (vk305 & vk319)

STANDARD/QR EXTENDED COVERAGE LIGHT HAZARD TECHNICAL DATA ELO FUSIBLE ELEMENT PENDENT SPRINKLER VK617

microfast quick response Pendent sprinkler VK302 (K5.6)

TECHNICAL DATA. Page 1 of 6

STANDARD/quick. Sprinkler 42o. August 8, 2011

MICROMATIC STANDARD RESPONSE PENDENT SPRINKLER VK102 (K5.6) TECHNICAL DATA 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3. TECHNICAL DATA.

MicrofastHP QUICK RESPONSE HORIZONTAL SIDEWALL HIGH PRESSURE SPRINKLER VK319 (K5.6) TECHNICAL DATA

quick response horizontal sidewall sprinkler vk360 (K8.0)

standard response sprinklers (vk102 & vk202) 3. technical data Specifications: Minimum Operating Pressure: 7 psi (0.5 bar) Sprinkler 11j

micromatic Standard response Horizontal Sidewall sprinkler

TECHNICAL DATA. 2. LISTINGS AND APPROVALS culus Listed: Category VNIV FM Approved: Class 2009 NYC Approved: MEA E, Volume 3

TECHNICAL DATA. Viking Technical Data may be found on UNS-C84400 for Sprinkler VK202.

MICROMATIC STANDARD RESPONSE HORIZONTAL SIDEWALL SPRINKLER VK104 (K5.6) TECHNICAL DATA

STANDARD/QUICK RESPONSE EXTENDED COVERAGE PENDENT SPRINKLER VK602 TECHNICAL DATA

standard response elo upright and pendent sprinklers (storage-density/area)

microfast and microfasthp quick conventional sprinklers

DRY VERTICAL SIDEWALL SPRINKLERS TECHNICAL DATA

QUICK RESPONSE ELO PENDENT SPRINKLER VK377 (STORAGE-DENSITY/AREA) TECHNICAL DATA 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3.

TECHNICAL DATA. 2. LISTINGS AND APPROVALS NOTE: Viking Dry Vertical Sidewall Sprinklers are NOT listed or approved. Sprinkler 103a.

Special Features: For Light Hazard Occupancies Only Designed for Corridor Applications 28 Maximum Width Spacing. 3. technical data

TECHNICAL DATA 2. LISTINGS AND APPROVALS 3. TECHNICAL DATA

microfast quick response extended coverage hsw sprinkler vk606

VK3021 QUICK RESPONSE PENDENT SPRINKLER (K5.6) TECHNICAL DATA

standard/quick response extended coverage light and ordinary hazard elo sprinklers

STANDARD/QUICK RESPONSE CONCEALED PENDENT SPRINKLER VK352-D (K8.0) TECHNICAL DATA

micromatic standard response stainless steel sprinklers

MICROFAST AND MicrofastHP QUICK RESPONSE PENDENT SPRINKLERS TECHNICAL DATA

TECHNICAL DATA. Cover Plate Assembly must be ordered separately:

EC/QREC ORDINARY HAZARD PENDENT SPRINKLER VK572 (K14.0) TECHNICAL DATA

quick response Sprinkler 105a October 25, 2010

ec/qrec ordinary hazard upright and pendent sprinklers vk570 and vk572 (k14.0)

TECHNICAL DATA. Page 1 of 5

TECHNICAL DATA. Viking Technical Data may be found on Maximum Working Pressure: 175 psi (12 Bar).

standard response/ quick response extended coverage

standard response large orifice dry

EC/QREC ORDINARY HAZARD UPRIGHT SPRINKLER VK570 (K14.0) TECHNICAL DATA

Standard response. elo sprinklers

standard/quick response sprinklers (vk302 & vk352) 3. technical data Specifications: Available since Sprinkler 41g May 1, 2009

standard response/qr extended coverage concealed pendent sprinklers vk614 & vk616

TECHNICAL DATA. Viking Technical Data may be found on Pip Cap: Brass UNS-C31400 or UNS-C31600

STANDARD RESPONSE DRY PENDENT STANDARD ORIFICE SPRINKLERS TECHNICAL DATA

standard response dry horizontal sidewall sprinklers

FREEDOM RESIDENTIAL HORIZONTAL SIDEWALL SPRINKLER VK486 (K4.0) TECHNICAL DATA

TECHNICAL DATA. The Viking Corporation s Web site at Frame Casting: Brass UNS-C84400

quick response extended coverage horizontal sidewall sprinkler vk630 (k8.0)

QUICK RESPONSE EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLER VK630 (K8.0) TECHNICAL DATA

HORIZON STANDARD RESPONSE FLUSH PENDENT SPRINKLER VK400 TECHNICAL DATA

STANDARD/QUICK RESPONSE EXTENDED COVERAGE DRY HORIZONTAL SIDEWALL SPRINKLER TECHNICAL DATA

STANDARD RESPONSE DRY HORIZONTAL SIDEWALL SPRINKLERS TECHNICAL DATA

Form No. F_ Rev 14.1 Page 1 of 6 TECHNICAL DATA

mirage Quick response extended coverage concealed pendent sprinklers (vk632 and vk634)

TECHNICAL DATA STANDARD/QUICK RESPONSE EXTENDED COVERAGE LIGHT HAZARD ELO PENDENT SPRINKLER VK608

TECHNICAL DATA STANDARD/QUICK RESPONSE EXTENDED COVERAGE PENDENT SPRINKLER VK534 (K11.2)

standard response dry horizontal sidewall sprinklers

QUICK RESPONSE DRY CONCEALED PENDENT SPRINKLER VK194 TECHNICAL DATA

quick response sprinkler vk194 Sprinkler 104j January 1, 2011

FREEDOM RESIDENTIAL HORIZONTAL SIDEWALL SPRINKLER VK479 (K3.0) TECHNICAL DATA

quick response ordinary hazard dry hsw sprinklers (8.0K) (VK275, VK277, & VK279)

mirage Quick response concealed pendent sprinkler vk464 (K8.0)

standard response dry horizontal sidewall sprinklers

mirage Quick response concealed pendent sprinkler vk465 (K4.2)

mirage standard response concealed pendent sprinkler vk492 (K5.6)

Standard Spray concealed horizontal sidewall sprinkler VK481

STANDARD RESPONSE DRY PENDENT ELO SPRINKLERS TECHNICAL DATA 1. DESCRIPTION 2. LISTINGS AND APPROVALS

QUICK RESPONSE EXTENDED COVERAGE CONCEALED HSW SPRINKLER VK630 (K8.0) TECHNICAL DATA

FREEDOM RESIDENTIAL PENDENT SPRINKLER VK470 (K3.0) TECHNICAL DATA

TECHNICAL DATA. Viking Technical Data may be found on Minimum Operating Pressure: Refer to the Approval Chart.

TECHNICAL DATA. Refer to the Approval Chart and Design Criteria for C-UL-US-EU Listing requirements that must be followed.

freedom residential horizontal sidewall lead free sprinkler VK4840 (k4.2)

Transcription:

Page 1 of 5 1. DESCRIPTION Viking Standard Response Fusible Link Upright Sprinkler VK109 is a small thermosensitive solder link spray sprinkler available with various finishes and temperature ratings to meet design requirements. The special Polyester coatings can be used in decorative applications where colors are desired. 2. LISTINGS AND APPROVALS FM Approved: Classes 2016 and 2017 Refer to Approval Chart 1 and FM Design Criteria for FM Approval requirements that must be followed. 3. Specifications: Minimum Operating Pressure: 7 psi (0.5 bar) Maximum Working Pressure: 175 psi (12 bar) wwp Factory tested hydrostatically to 500 psi (34.5 bar) Thread size: 15 mm BSP Nominal K-Factor: 5.6 U.S. (80.6 metric**) Glass-bulb fluid temperature rated to -65 F (-55 C) Overall Length: 2-1/4 (58 mm) ** Metric K-factor measurement shown is in Bar. When pressure is measured in kpa, divide the metric K-factor shown by 10.0. Material Standards: Frame Casting: Brass UNS-C84400 Deflector: Brass UNS-C23000 or Copper UNS-C19500 Fusible Link Assembly: Brass UNS-C40500 and UNS-C51000 NOTE: For chrome sprinklers, the fusible link assembly is painted silver for decorative purposes only. Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape Screw: Brass UNS-C36000 Seat: Copper UNS-C11000 Pip Cap Attachement: UNS-C36000 For Polyester Coated Sprinklers: Belleville Spring-Exposed Ordering Information: (Also refer to the current Viking price list.) Viking Technical Data may be found on Viking Standard Response Fusible Link Upright Sprinkler VK109 by first adding the appropriate suffix for the sprinkler finish and then the appropriate http://www.vikinggroupinc.com. The Viking Corporation s Web site at suffix for the temperature rating to the sprinkler base part number. The Web site may include a more recent Finish Suffix: Brass = A, White Polyester = M-/W, Black Polyester = M-/B, edition of this Technical Data Page. Temperature Suffix: 165 F (74 C) = C, 220 F (104 C) = M, 286 F (141 C) = G For example, sprinkler VK109 with a 15mm BSP thread, Brass finish and a 165 F (74 C) temperature rating = Part No. 12971AB Available Finishes And Temperature Ratings: Refer to Table 1. Accessories: (Also refer to the Sprinkler Accessories section of the Viking data book.) Sprinkler Wrenches: A. Standard Wrench: Part No. 10896W/B (available since 2000). D. Wrench for Wax Coated Sprinklers: Part No. 13577W/B* (available since 2006) *A ½ ratchet is required (not available from Viking). Sprinkler Cabinets: A. Six-head capacity: Part No. 01724A (available since 1971) B. Twelve-head capacity: Part No. 01725A (available since 1971) 4. INSTALLATION Refer to appropriate NFPA Installation Standards. (New Page for VK109)

Page 2 of 5 5. OPERATION During fire conditions, the heat-sensitive fusible link disengages, the pip cap and spring are released, and the waterway is opened. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire. 6. INSPECTIONS, TESTS AND MAINTENANCE Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. AVAILABILITY The Viking Standard Response Fusible Link Upright Sprinkler VK109 is available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. GUARANTEE For details of warranty, refer to Viking s current list price schedule or contact Viking directly.

Page 3 of 5 Sprinkler Temperature Classification TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES Sprinkler Nominal Temperature Rating 1 Maximum Ambient Ceiling Temperature 2 Bulb Color Ordinary 165 F (74 C) 100 F (38 C) None Intermediate 220 F (104 C) 150 F (65 C) White High 286 F (141 C) 225 F (107 C) Blue Sprinkler Finishes: Brass, Chrome, White Polyester, and Black Polyester 1 The sprinkler temperature rating is stamped on the deflector. Footnotes 2 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. Protective Sprinkler Cap Wrench Flat Figure 1: Standard Sprinkler Wrench 10896W/B

Page 4 of 5 Sprinkler Base Part Number 1 SIN Approval Chart 1 (FM) Standard Response Upright Sprinkler VK109 Maximum 175 PSI (12 bar) WWP Thread Size Nominal K-Factor Overall Length FM Approvals 3 NPT BSP U.S. metric 2 Inches mm Standard Orifice (Refer also to Design Criteria below.) 12971 VK109 -- 15 mm 5.6 80.6 2-1/4 58 A1 Approved Temperature Ratings A - 165 F (74 C), 220 F (104 C), and 286 F (141 C) Approved Finishes 1 - Brass, White Polyester 4, and Black Polyester 4 Footnotes 1 Base part number is shown. For complete part number, refer to Viking s current price schedule. 2 Metric K-factor shown is for use when pressure is measured in bar. When pressure is measured in kpa, divide the metric K-factor shown by 10.0. 3 This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals. 4 Other colors are available on request with the same Approvals as the standard colors. FM Approval Requirements: DESIGN CRITERIA - FM (Also refer to Approval Chart 2.) Sprinkler VK109 is FM Approved as a standard response Non-Storage upright sprinkler as indicated in the FM Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (including Data Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling. NOTE: The FM installation guidelines may differ from culus and/or NFPA criteria. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page SR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable.

Page 5 of 5 Sprinkler wrench 13577W/B** must be used for installing wax coated sprinklers. Step 1: Carefully slide the wrench sideways around the deflector, ensuring engagement with the sprinklger wrench flats. Wax Coated Upright Sprinkler ** A 1/2 ratchet is required (not available from Viking) Step 2: Carefully press the wrench downward and ensure engagement with the sprinkler wrench flats. Figure 2: Wrench 13577W/B for Wax Coated Sprinklers (New Page for VK109)