Quick Start Installation Guide

Similar documents
INSTALLATION MANUAL. Gas-fired Steam Humidifier Nortec GS. IMPORTANT! Read and save these instructions. This manual to be left with the equipment.

_C_EN_1612 INSTALLATION, OPERATION AND MAINTENANCE MANUAL. Blower Pack Condair BP. Humidification and Evaporative Cooling

INSTALLATION, OPERATION AND MAINTENANCE MANUAL. Outdoor Steam Humidifier Nortec EL / RS

NH Series. Installation and Operation Manual

Pressure Steam Humidifiers LS SERIES. humidity.com

Tried, true, and trusted for over 40 years. EL Series Electrode Steam Humidifier. Humidification and Evaporative Cooling. humidity.

SE Series. Installation and Operation Manual

MES2. Installation and Operation Manual

SETC Outdoor. Supplemental Installation and Spare Parts Manual

STEAM DISTRIBUTORS ASD / BSD / CSD. Installation Manual C

RH2+ Installation and Operation Manual

NH Series. Installation and Operation Manual

NH Series Electric Steam Humidifiers

SE Series. Installation and Operation Manual

GS Series. Installation and Operation Manual

Steam Humidifier Models 1150 and 1160

OPERATION AND MAINTENANCE MANUAL. Electrode Steam Humidifier Nortec EL Series

NH Series. Electric Steam Humidifiers. Designed for installation flexibility while maintaining precise humidification control

Pressure Steam Humidifiers. Designed to deliver reliable humidity from facility steam boilers. Live Steam

Steam Humidifier Fan Pack Installation & Maintenance Instructions

Getting Rid of Scale. Nortec RS Series Steam humidifier with patented scale management. Humidification and Evaporative Cooling

"ER" Series Electric Humidifier

Help. Help Software Tutorial. Building a Load Sizing Project with an NH-EL Humidifier and CSD Distributor.

I EN 1811 INSTALLATION MANUAL. Steam humidifier Condair EL. Humidification and Evaporative Cooling

GS Series. Gas Steam Humidifiers. Designed for air handling systems and for areas requiring individual humidification control

SAM-e - Short Absorption Manifold Submittal Drawings

Steam Distribution. Installation Manual. Includes installation instructions for steam distributions ASD/BSD/CSD/RSD/SSD.

READ AND SAVE THESE INSTRUCTIONS

Installation Instructions

Condair CS 2.0/4.0. Resistive Humidifiers INSTALLATION AND OPERATING INSTRUCTIONS. HLK Version HLK EN 1408

XT Series Electrode Steam Humidifier. Installation, Operation, and Maintenance Manual

Installation Instructions

Installation and Operation Guide

SKR series Steam Humidifier Kit N (Patent Pending)

Installation GUIDE VDWU524SS VDWU524WSSS FDWU524WS FDWU524 VDWU324SS FDWU324

Installation Instructions

Installation Instructions

SKR series Steam Humidifier with SDU module (Patent Pending)

Installation, Operation, Maintenance, and Troubleshooting Guide

STS Steam-to-Steam Humidifier

Condair SETC. Steam Exchange Humidifier

Dishwasher Installation Manual

Leading Humidification Innovation... Once Again. Nortec s GS Series Condensing High Efficiency. Humidification and Evaporative Cooling CONDAIR GROUP

LTS Liquid-to-Steam Humidifier. Installation, Operation and Maintenance Manual

Installation, Operation, Maintenance and Troubleshooting Guide

Installation Instructions

Help. Help Software Tutorial. Building a Load Sizing Project with an SETC Humidifier and a mini SAM-e Distributor

READ AND SAVE THESE INSTRUCTIONS

Steam to Steam Humidifier

READ AND SAVE THESE INSTRUCTIONS XTR. Electrode Steam Humidifier. Installation, Operation, and Maintenance Manual

PROPER WALL MOUNTING OF THE SUITMATE

Installation Instructions

Installation Instructions

Installation Instructions. For the 18 Built-In Dishwasher and Front Color Panels

Installation Instructions

READ AND SAVE THESE INSTRUCTIONS

HM700A1000 ELECTRODE STEAM HUMIDIFIER

Installation, Operation, Maintenance and Troubleshooting Guide

XTR Electrode Steam Humidifier. Installation, Operation, and Maintenance Manual

DISHWASHER. Models DW2432 and DW2432SS. Installation Manual. Write Serial Number (on inner door of unit) here:

READ AND SAVE THESE INSTRUCTIONS XT SERIES. Electrode Steam Humidifiers. Installation, Operation, and Maintenance Manual

Steam Humidifier. SK300 Series Installation Instructions and User Manual. SK300-ESL docx

Atomizing Nozzle Humidifiers. Designed for Air Handling Systems, and Manufacturers, Processors and Distributors of Humidity Sensitive Products.

C EN 1707 INSTALLATION MANUAL. Steam humidifier Condair RS. Humidification and Evaporative Cooling

Double Intelligence Two adiabatic humidification methods intelligently combined. Humidification and Evaporative Cooling. humidity.

1.3 REFERENCES A. ANSI/NFPA 70 - National Electrical Code. B. ARI Commercial and Industrial Humidifiers.

READ AND SAVE THESE INSTRUCTIONS VAPORMIST. Electric-to-Steam Humidifier. Installation, Operation, and Maintenance Manual

INSTALLATION INSTRUCTIONS

Installation Instructions

Design Guide Fully Integrated Models 24" and 48"

Vapormist Electric Humidifier. Installation, Operation and Maintenance Manual

Installation Instructions

SCHWAN INSTALLATION GUIDE

Condair CP3mini. Electrode Humidifiers EN 1112

Hoshizaki America, Inc.

Helpful Tip: NOTE:

Installation Instructions

Installation Instructions

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

Installation Instructions

OPERATING AND INSTALLATION MANUAL

DLCLRA. INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 TABLE OF CONTENTS

CRUV. Electric Humidifier. Installation, Operation, and Maintenance Manual

Residential Steam Humidifier

READ AND SAVE THESE INSTRUCTIONS XT SERIES. Electrode Steam Humidifiers. Installation, Operation, and Maintenance Manual

OPERATING AND INSTALLATION MANUAL

Ultra-sorb Models LV and LH

NHRS Series RESISTIVE ELEMENT STEAM HUMIDIFIER. Engineering Manual. Manual No. H

TIDALWAVE I/G POOL PUMP INSTRUCTION MANUAL

INSTALLATION GUIDE KT-CDR2 & KT-CDR3. For COOLDOME ENCLOSURE SERIES

SELF-CONTAINED FLAKER

Dishwasher Installation Instructions DW 24XT/DW 24XV

BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS

Installation, User & Maintenance Guide

INSTALLATION INSTRUCTIONS UNDERCOUNTER DISHWASHERS

VMS-3. Part Number: Ultraviolet Systems VMS-3. Installation, Operation & Maintenance

4201 Lien Rd Madison, WI Owner s Manual Therma-Stor III Heat Recovery System. Installation, Operation & Service Instructions

Installation Instructions T 9822 Gas Dryer. en - US, CA. To prevent accidents

WATLOW IND. WATROD Modular Duct Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date:6/11/2008 Rev: 2

HOSHIZAKI ICE DISPENSING BIN/ WATER DISPENSER MODEL DM-90A SERVICE MANUAL

Transcription:

Quick Start Installation Guide Nortec EL Electrode Steam Humidifier Overview Mounting Installation Requirements Standard Mounting Steam Distribution Installation Requirements Plumbing Water and Drainage Requirements Electrical Installation Requirements External Power Connections Safety Chain and Control Signal Connections Humidification and Evaporative Cooling humidity.com

Overview, ft. 0 ) (m min ) -m in. rm Bno 0 -. ft (, 0 9 9 0 High limit On/Off humidistat (external safety chain) Humidity sensor or modulating humidistat (used for control of the space in the return duct, high limit in the supply duct) On/Off humidistat (used for humidity control) Steam line Electrical disconnect, high voltage supply Drain line Air gap funnel (with optional trap) Water supply Condensate line Steam distributor Air proving switch (external safety chain) Supply air duct Return air duct

Mounting Installation Requirements. The location of the humidifier depends largely on the steam distribution system. The required minimum clearances are shown on the right. The table below shows the required minimum clearances for a Nortec EL Space humidifier. min.. in (00 mm) 0 in (0 mm). When choosing the location of the humidifier, install it as close as possible to the steam distributor to minimize heat loss through the steam line.. When possible, install the humidifier below the steam distributor. Make sure that the selected location permits proper routing of steam and condensate lines. min. in (9 mm). Allow adequate clearances around the humidifier for ease of maintenance. Although the Nortec EL humidifier requires no side clearance, Nortec recommends minimum clearances of in (0 mm) on the sides. A clearance of in (0 mm) between the humidifier and the ground is required. Observe all local and national installation codes. Nortec is not responsible for any installation code violations. 0 in (0 mm) D W H. Do not mount the humidifier on hot surfaces, or surfaces that can freeze, or near vibrating components, or on the floor. In addition, the mounting surface must be able to withstand temperatures of 0- F (0-0 C) that can be generated during operation of the humidifier.. The humidifier should be mounted on a wall or other suitable surface that offers a sufficiently high load-bearing capacity. min. in (0 mm). The Nortec EL humidifier should be installed in a drip-proof location within buildings, where the ambient temperature is -0 F (-0 C) and the relative humidity is -9% (non-condensing). D D Capacity "A" (minimum) "B" (minimum) lb/h (. kg/h) 9 in (0. m) Minimum Clearamces Nortec EL Space Humidifier 0 lb/h (. kg/h) in (0. m) 0 lb/h (9 kg/h) 0 lb/h (. kg/h) Low Speed in (.9 m) in (0. m) in (.9 m) High Speed 0 lb/h (. kg/h) in (. m) lb/h (.0 kg/h) 9 in (. m) in (. m) 00 lb/h (. kg/h) in (. m) in (. m) B A "A" (minimum) in (0. m) 0 in (. m) in (. m) in (. in) in (.9 m) in (. m) C "B" (minimum) in (0. m) "C" (minimum). in (. m) "D" (suggested) in (0. m) 0 in (0. m)

Mounting continued... Standard Mounting. Locate wooden studs or equivalent support in the mounting surface, and mark the attachment points A and B at the desired position with the help of a level.. Install / in lag bolts (supplied by others) at attachment points A. Use longer screws if going through drywall or other structural material into the mounting surface. Allow the heads of the screws to extend 0. in ( mm) from the mounting surface so that the humidifier can be installed on the bolts.. Remove the door panels from the humidifier.. Carefully raise and install the humidifier onto the installed lag bolts.. Align the humidifier with the help of a level, then tighten the lag bolts.. Install additional lag bolts (supplied by others) into the mounting surface at attachment points B, and fasten securely.. Reinstall the door panels, and fasten them securely. WARNING! Heavy object risk of injury! The small humidifier weighs lb (0 kg), and the large humidifier weights 0 lb ( kg). Use an appropriate lifting device, or request assistance to raise the humidifier into position. X Y Housing Size Small Medium Large.0 in (0 mm). in ( mm).0 in (0 mm) 0. in ( mm).0 in (0 mm). in ( mm) Refer to Mounting the Humidifier in the Installation Manual (Nortec document number 0) for other mounting arrangements, including OSHPD (seismic) mounting arrangement. X X A A A B Y B B Large Nortec EL humidifier shown. Lag bolt

Steam Distribution Installation Requirements. Use steam line made of copper or stainless steel tube exclusively, or use a Nortec steam hose for short distances. Steam line made of any other material may adversely affect the operation of the humidifier, and will void the warranty. Refer to the table below for steam line sizing.. To prevent excessive backpressure in the steam cylinder, the steam line must not have any restrictions.. The steam line must run straight up from the humidifier minimum in (00 mm) before any bends.. The steam line must have a constant slope minimum upslope of 0, or minimum downslope of.. Do not merge steam lines, except at the steam distributor. Use a Nortec adaptor designed for the purpose.. Insulate the steam line with minimum in ( mm) pipe insulation.. Support the steam line so there is no load on the humidifier.. Install condensate lines at all low points and horizontal-to-vertical transitions in the steam line. The condensate line should always connect to a full size Tee connector, and have a minimum constant downslope of.. The trap should be located minimum in (00 mm) below the connector, and have a minimum height of in (00 mm). 9. Use / in (9. mm) Nortec condensate hose, or / in (. mm) Med-L copper tube or / in (9. mm) stainless steel tube for condensate traps. 0. Install condensate traps every ft (. m) in the steam line.. Upon completion of installation, purge the steam and condensate lines to remove any contaminants or construction material.. Prime the condensate traps with water. Refer to Steam Line Connections in the Installation Manual for other details. in (00 mm) in (0 mm) 0 o Minimum Upslope Minimum Downslope ½ in ( mm) o in (00 mm) Min. in (00 mm) in (00 mm) in ( mm). o Minimum Downslope in (. m) Min. in (00 mm) in (00 mm) in ( mm). o Minimum Downslope in (. m) Steam Line Sizing Model Maximum Equiv. Length MED-L Copper Tube Stainless Steel Tube Steam Losses EL00 ft ( m) / in EL00 ft (. m) (0 mm) EL00 ft ( m) EL00 ft (. m) EL00 ft ( m) -/ in EL0 ft ( m) (0 mm) EL00 EL0* EL00* 0 ft ( m) -/ in (0 mm) / in 0.09 wall ( mm. mm wall) -/ in 0.0 wall ( mm. mm wall) -/ in 0.0 wall ( mm. mm wall) 0.0 lb/h/ft (0.09 kg/h/m) 0. lb/h/ft (0. kg/h/m) WARNING! Risk of serious injury or damage to equipment! Restrictions in the steam line can cause excess build-up of backpressure which can result in serious burn injuries or damage to equipment. Backpressure should not exceed. in HO (. kpa). Nortec Steam Hose EL00- EL00 0 ft ( m) P/N 0 / in ( mm) 0. lb/h/ft (0. kg/h/m) EL00- EL00 0 ft ( m) P/N 0 -/ in ( mm) 0. lb/h/ft (0. kg/h/m) * Use a single steam line for each steam cylinder. Do not combine lines except at a distributor, and only if using the steam cylinders in parallel. Refer to the Installation Manual for over-sized steam lines for longer steam runs.

Plumbing Water and Drainage Requirements. All water supply and drain connections must be installed to local plumbing codes.. The water supply line should be minimum / in (. mm) in diameter, with a shutoff valve and a union fitting.. The water supply to the humidifier must be cold potable drinking water (and not RO or DI water). The conductivity of the water should be 0-00 micro-seimens/cm (hardness 0- gpg, when Silica is between 0- ppm, 0- gpg when Silica is between - ppm; Silica content above ppm is not recommended). ph should be between and... The water supply should be filtered to μm (optional, but recommended), surge-free and pressure regulated to 0-0 psig (0-0 kpa). Water temperature should be -0 F (-0 C).. The air gap funnel should be located away from the control cabinet to keep any rising steam from damaging the electrical components in the cabinet. The drain piping should have a minimum internal diameter of / in ( mm).. The flexible bent hose exiting the humidifier should be connected to a drain line with a minimum internal diameter of / in ( mm) and secured with clamps.. The drain line should be as short as possible, and have a constant minimum downslope of in/ in (. ) to the funnel without touching its sides or bottom. Use stainless steel or plastic pipe suitable for temperatures up to F (00 C).. Drain lines from large humidifiers with dual steam cylinders must empty into separate air gap funnels before connecting to the drain. Combined drain line minimum. in ( mm) I.D. 9. Upon completion of installation, flush the water supply and drain lines to clear out any debris in the lines. Check the strainer in the fill valve to ensure it is clear of all debris. Refer to Water Connections in the Installation Manual for other details. CAUTION! Risk of damage to the plastic threads of the fill valve. Handtighten the NPT adaptor to the fill valve. 9 0 Drain canal, -/ in (0 mm) O.D. Hose clamp (supplied) Flexible bent hose (supplied) Drain line, minimum / in ( mm) I.D. Water supply line, minimum / in (. mm) Adaptor, / BSPP to / in NPT (supplied) Inlet, fill valve (/ in BSPP plastic threads) Air gap funnel (and optional trap) 9 Shutoff valve 0 Filter, μm (optional, but recommended) Union fitting

s s s s s s Electrical Installation Requirements. All wiring must only be done by a licensed electrician in accordance with the wiring diagram (refer to the Installation Manual), and local and national codes.. An external dedicated fused disconnect switch must be installed close to the unit to allow for power interruption during servicing and/ or maintenance. The fusing must not exceed the maximum circuit protection shown on the specification label. The optional internal fusing is not a substitute for an external disconnect switch.. The humidifier should only be connected to primary power (main power) after all installation work has been completed.. All cables must enter the control cabinet in the humidifier through appropriate cable glands or grommets, and must be properly secured to prevent fraying, or become a tripping hazard. DANGER! Risk of electric shock! The Nortec humidifier is mains powered, and should only be wired by a licensed electrician. CAUTION! Risk of damage to electronic components in the control cabinet due to ESD (electrostatic discharge). Refer to ANSI/ESD-S0.0 for appropriate measures to prevent damage to electronic components. Refer to Electrical Connections in the Installation Manual for other details. External Power Connections Single-phase L L L X0 External Three-phase L L L X0 External External fused disconnect switch Terminal block, power supply (XO) Internal primary fuse, optional

+ Electrical continued... Safety Chain and Control Signal Connections. If a blower pack is installed, then connect it to terminal points and 9 on the low voltage terminal strip. Make sure that no other wires are connected to these terminal points. If using multiple blower packs, make sure that they are connected in series. Install a jumper between terminal points and 9 if a blower pack is not used.. Connect external monitoring devices (for example, high limit humidistat, air proving switch, etc.) in series to terminal points and on the low voltage terminal strip. Install a jumper between terminal points and if external monitoring devices are not used (not recommended).. Connect an external humidity sensor input or direct demand modulating input to terminal points and on the low voltage terminal strip. Do not connect multiple modulating signals to the same modulating input on the humidifier. If necessary, a second modulating signal can be connected to terminal point and, using terminal point as common. Note: If the cable shielding is already connected to a potential or a grounded conductor, do not connect it to terminal point.. If a V On/Off humidistat is used, connect the input to the terminal points and on the low voltage terminal strip. When connecting a V On/Off humidistat, set the jumper JP on the driver board to V (so that terminal point will output VDC).. If an external On/Off input is used to control the humidifier, connect it to connector X on the driver board. CAUTION! Risk of damage to internal component. DO NOT apply voltage to low voltage terminal strip terminal points and through the contacts of the external On/Off devices. LV Blower pack GND 0/ Vdc (+) Limit signal (+) Control signal (-) Signal Safety loop 9 External Δp φ max V JP 0V Modulating demand or humidity sensor signal (additional) Modulating demand or humidity sensor signal V On/Off humidistat (jumper JP must be set to V) High limit humidistat Air proving switch Jumper Low voltage terminal strip Blower pack

Notes

Printed in Canada -A_0 All information contained in this Quick Start Guide is for general information purposes only. For complete Nortec installation/operation recommendations for your Nortec equipment, please refer to the installation manual for your specific system, accessories, and components. All electrical connections must be installed in accordance with local and national electrical code requirements by a licensed electrician. All water supply and drain line connections must be installed in accordance with local plumbing codes by a licensed plumber. Nortec does not accept any liability for installations of humidity equipment installed by unqualified personnel or the use of parts/ components/equipment that are not authorized or approved by Nortec. USA Commerce Park Drive, Ogdensburg, NY -09 Canada 0 Fenton Road, Ottawa, Ontario KT T..NORTEC nortec@humidity.com humidity.com