P-SERIES SUBMITTAL DATA: PEAD-A12AA7 & PUZ-A12NKA7(-BS) 12,000 BTU/H HORIZONTAL-DUCTED HEAT PUMP SYSTEM Job Name: System Reference: Date: Indoor Unit: Outdoor Unit: PEAD-A12AA7 PUZ-A12NKA7 PUZ-A12NKA7-BS INDOOR UNIT FEATURES Unobtrusive ceiling-concealed design for short-run ductwork. Wide ranging external static pressure Built-in condensate lift mechanism Auto fan speed mode Optional FB Series filter boxes for easy access and service Ideal for residential homes,retail shopping centers, larger classrooms, office complexes, conference ballrooms, fitness centers, and more OUTDOOR UNIT FEATURES Variable speed INVERTER-driven compressor Suction accumulator pre-charged with refrigerant volume for piping length up to 100 ft (70 ft. for A12/18/24/30) 24-hour continuous operation (cooling mode) High pressure protection Fast restart due to bypass valve make it ideal for equipment cooling applications, such as data centers Superior energy and operational efficiency
SPECIFICATIONS: PEAD-A12AA7 & PUZ-A12NKA7(-BS) Model number Indoor unit PEAD-A12AA7 Outdoor unit PUZ-A12NKA7 PUZ-A12NKA7-BS Cooling*1 Maximum Capacity Btu/h 12,000 Rated Capacity Btu/h 12,000 Minimum Capacity Btu/h 5,000 Maximum Power Input W 920 Rated Power Input W 920 Moisture Removal Pints/h 1.80 Sensible Heat Factor 0.83 Power factor % 90.9 Heating at 47 F*2 Maximum Capacity Btu/h 18,000 Heating at 17 F *3 Rated Capacity Btu/h 14,000 Minimum Capacity Btu/h 5,800 Maximum Power Input W 1,520 Rated Power Input W 1,030 Power factor % 91.4 Maximum Capacity Btu/h 10,500 Rated Capacity Btu/h 8,700 Maximum Power Input W 1,130 Rated Power Input W 1,100 Efficiency SEER 21.1 EER *1 13.0 HSPF (IV) 10.2 COP at 47 F *2 3.98 COP at 17 F *3 2.31 ENERGY STAR Certified Electrical Voltage, Phase, Frequency 208 / 230V, 1-phase, 60 Hz Guaranteed Voltage Range V AC 187-253 Voltage: Indoor - Outdoor, S1-S2 V AC 208V / 230 Voltage: Indoor - Outdoor, S2-S3 V DC 24 Voltage: Indoor - Remote controller V DC 12 Recommended Fuse/Breaker Size A 15 Recommended Wire Size (Indoor - Outdoor) AWG 14 Indoor unit MCA A 1.45 MOCP A 15 Yes
SPECIFICATIONS: PEAD-A12AA7 & PUZ-A12NKA7(-BS) Model number Indoor unit PEAD-A12AA7 Indoor unit operating temperature range Outdoor unit PUZ-A12NKA7 PUZ-A12NKA7-BS Fan Motor Full Load Amperage A 1.16 Fan Motor Output W 85 Airflow Rate, Dry CFM 353-424-494 Airflow Rate, Wet CFM 313-384-454 External Static Pressure in.wg 0.14-0.20-0.28-0.40-0.60 Sound Pressure Level db(a) 28-30-34 Drain Pipe Size In. (mm) 1-1/4 (32) Condensate Lift Mechanism, Max. Distance Ft. (m) 27-9/16 (700) Heat Exchanger Type External finish color Plate fin coil Galvanized Unit Dimensions // Grille Dimensions W: In. (mm) 35-7/16 (900) D: In. (mm) 28-7/8 (732) H: In. (mm) 9-7/8 (250) Package Dimensions // Grille Dimensions W: In. 45-5/16 D: In. 34-11/16 H: In. 13-7/16 Unit Weight Lbs. (kg) 58 (26) Package Weight Lbs. 69 Cooling Intake Air Temp (Maximum / Minimum) Heating Intake Air Temp (Maximum / Minimum) F 90 DB, 73 WB / 66 DB, 59 WB F 82 DB / 50 DB Outdoor unit MCA A 11 MOCP A 28 Fan Motor Full Load Amperage A 0.5 Fan Motor Output W 46 Airflow Rate CFM 1,590 Refrigerant Control Defrost Method Heat Exchanger Type Electronic Expansion Valve Reverse Cycle Cross fin Sound Pressure Level, Cooling*1 db(a) 44 Sound Pressure Level, Heating*2 db(a) 46 Compressor Type Compressor Model INVERTER-driven twin rotary SNB092FNCM
SPECIFICATIONS: PEAD-A12AA7 & PUZ-A12NKA7(-BS) Model number Indoor unit PEAD-A12AA7 Outdoor unit operating temperature range Outdoor unit PUZ-A12NKA7 PUZ-A12NKA7-BS Compressor Rated Load Amps A 7 Compressor Locked Rotor Amps A 12 Compressor Oil Type // Charge oz. FV50S // 12 External finish color Ivory Munsell 3Y 7.8/1.1 Base pan heater Unit Dimensions W: In. (mm) 31-13/16 + 7/16 (809+62) n/a D: In. (mm) 11-3/16 (300) H: In. (mm) 24-13/16 (630) Package Dimensions W: In. 37-1/16 D: In. 16-3/16 H: In. 27-7/16 Unit Weight Lbs. 93 (42) Package Weight Lbs. 104 (47) Cooling *5 Intake Air Temp (Maximum / Minimum) Heating Intake Air Temp (Maximum / Minimum) F 115 DB / 0* DB F 70 DB, 59 WB / 12 DB, 10 WB Thermal Lock-out / Re-start Temperatures** F 8 / 12 DB Refrigerant Type R410A Charge Lbs, oz 4 lbs, 7 oz Piping Gas Pipe Size O.D. (Flared) In.(mm) 1/2 (12.7) Liquid Pipe Size O.D. (Flared) In.(mm) 1/4 (6.35) Maximum Piping Length Ft. (m) 100 (30) Maximum Height Difference Ft. (m) 100 (30) Maximum Number of Bends 15 AHRI Rated Conditions *1 Cooling (Indoor // Outdoor) F 80 F DB, 67 F WB // 95 F DB, 75 F WB *2 Heating at 47 F (Indoor // Outdoor) F 70 F DB, 60 F WB // 47 F DB, 43 F WB *3 Heating at 17 F (Indoor // Outdoor) F 70 F DB, 60 F WB // 17 F DB, 15 F WB Conditions *4 Heating at 5 F (Indoor // Outdoor) F 70 F DB, 60 F WB // -4 F DB, -5 F WB Notes *Wind baffles required to operate below 23 F DB in cooling mode. PUZ with wind baffle: 0 F - 115 F. **System cuts out in heating mode to avoid thermistor error and automatically restarts at these temperatures
SPECIFICATIONS: PEAD-A12AA7 & PUZ-A12NKA7(-BS) SEACOAST PROTECTION External Outer Panel: Phosphate coating + Acrylic-Enamel coating Fan Motor Support: Epoxy resin coating (at edge face) Separator Assembly; Valve Bed: Epoxy resin coating (at edge face) Blue Fin treatment is an anti-corrosion treatment that is applied to the condenser coil to protect it against airborne contaminants. Notes:
ACCESSORIES: PEAD-A12AA7 & PUZ-A12NKA7(-BS) Filter Box with Filters (MERV 13) PEAD-A12AA7 3-Pole Disconnect Switch (30A/600V/UL) [fits 2" X 4" utility box] Drain Pan Level Sensor (Control for indoor unit shut off to prevent drain pan overflow) FBM2-2 TAZ-MS303 DPLS2 Advanced Blue Diamond Mini-Condensation pump w/ Resevoir & Sensor (110V) X87-711 - 110 Advanced Blue Diamond Mini-Condensation pump w/ Resevoir & Sensor (208/230V) X87-721 - 208/230 Extension Cord for Blue Diamond Pump C13-103 MegaBlue Blue Diamond Condensate Pump (110-230V) X87-835 Remote Sensor (extensible) Connector Cable for Remote Display Connector for CN32 (remote ON/OFF) Connector for CN24 (Back up heating) Connector for CN30 (LLC) Remote Operation Adapter (with wire terminals for remote ON/OFF and operation status/ error) External fan / Heater control relay adapter Backlit, wall-mounted, wireless Wireless adapter BACnet and Modbus Interface Wall-mounted, Wired Wired remote controller T-STAT Interface Wired remote controller Signal Receiver Wireless Remote Controller Wireless Signal Receiver Wire for Remote ON/OFF with CN32 connector Lockdown Bracket for wireless, hand-held, remote controllers *1 Unable to use with wireless remote controller PAC-SE41TS-E PAC-SA88HA-EP PAC-725AD-E (10pcs) PAC-SE55RA-E PAC-SE56RA-E PAC-SE57RA-E PAC-SF40RM-E *1 CN24RELAY-KIT-CM3 MHK1 PAC-USWHS002-WF-1 PAC-UKPRC001-CN-1 PAC-YT53CRAU-J PAR-32MAA-J PAC-US444CN-1 PAR-32MAA PAR-SA9CA-E PAR-FL32MA-E PAR-FA32MA-E PAC-715AD RCMKP1CB PUZ-A12NKA7(-BS) Air Outlet Guide Front Wind Baffle Drain socket Centralized Drain Pan M-NET Converter PAC-SJ07SG-E WB-PA PAC-SJ08DS-E PAC-SG63DP-E PAC-SJ19MA-E
ACCESSORIES: PEAD-A12AA7 & PUZ-A12NKA7(-BS) PUZ-A12NKA7(-BS) Control/Service Tool PAC-SK52ST Wall mounting bracket (powder-coated steel) QCWB2000M-1 Wall mounting bracket (316 Series Stainless Steel) QCWBSS M-NET control adapter for Building Management System PAC-SF83MA-E Outdoor Unit Mounting Pad 16" x 36" x 3" ULTRILITE1 Outdoor Unit 3-1/4 inch Mounting Base - Pair (Plastic) DSD-400N MiniSplit Mounting Stand-Single Fan models - 12" QSMS1201M MiniSplit Mounting Stand-Single Fan models - 18" QSMS1801M MiniSplit Mounting Stand-Single Fan models - 24" QSMS2401M 1/4 x 1/2 x 15' / 1/2" Lineset (Twin-Tube Insulation) MLS141212T-15 1/4 x 1/2 x 30' / 1/2" Lineset (Twin-Tube Insulation) MLS141212T-30 1/4 x 1/2 x 50' / 1/2" Lineset (Twin-Tube Insulation) MLS141212T-50 1/4 x 1/2 x 65' / 1/2" Lineset (Twin-Tube Insulation) MLS141212T-65 1/4 x 1/2 x 100' / 1/2" Lineset (Twin-Tube Insulation) MLS141212T-100
DIMENSIONS: PEAD-A12AA7 & PUZ-A12NKA7 (-BS) PEAD-A12AA7 HWE16080 21 40(1-5/8) Outlet air side view H±3(H±1/8) 40(1-5/8) 23(15/16) 40(1-5/8) 122(4-13/16) (DUCT) 178(7-1/16) 100(3-15/16) 33(1-5/16) 15(5/8) 58(2-5/16) J±3(J±1/8) Opposite piping side view Drain pipe(o.d ø32(1-1/4)) (Emergency drain) Bottom 20(13/16) D(Duct) 30(1-3/16) 100(3-15/16)X(E-1)=F 100(3-15/16) 200(7-7/8) Top 2XE-ø2.9(1/8) Top view Air outlet 378(14-15/16) 153(6-1/16) Fresh air intake ø100(3-15/16) knock out hole Note 4 3-ø2.9(1/8) mount hole ø125 120 (4-15/16) 120 135 (5-3/8) Air inlet A 41(1-5/8) 217(8-9/16) 250(9-7/8) B(Suspension bolt pitch) 23(15/16) C Inlet air side view 18(3/4) 210(8-5/16) Unit:mm(in.) 10(7/16) Model J 1Gas pipe 2Liquid pipe PEAD-A12,18AA7 62 ø12.7 ø6.35 (2-1/2) (1/2) (1/4) PEAD-A24,30AA7 66 ø15.88 ø9.52 (Suspension bolt pitch) (2-5/8) (5/8) (3/8) 57(2-1/4) 643(25-3/8) PEAD-A36,42AA7 732(28-7/8) 32(1-5/16) Drain pump 700(27-9/16) 238(9-3/8) Drain pipe Unit:mm(in.) 2Refrigerant piping(liquid) 10(7/16) (Integral lift pump outlet) Model A B C D E F G H (O.Dø32(1-1/4)) Top PEAD-A12,18AA7 900 (35-7/16) 954 (37-9/16) 1000 (39-3/8) 860 (33-7/8) 9 800 (31-1/2) 858 (33-13/16) 72 (2-7/8) PEAD-A24,30AA7 1100 1154 1200 1060 1000 1058 11 (43-5/16) (45-7/16) (47-1/4) (41-3/4) (39-3/8) (41-11/16) 78 PEAD-A36,42AA7 1400 1454 1500 1360 14 1300 1358 (3-1/8) (55-1/8) (57-1/4) (59-1/16) (53-9/16) (51-3/16) (53-1/2) 2X2-ø2.9(1/8) Control box Bottom Terminal block(transmission) 1Refrigerant piping (gas) Terminal block(power source) (5-3/8) 136 (2-11/16) 67 Piping side view 356(14-1/16) Drain pipe(o.dø32(1-1/4))(gravity drain) 21(7/8) G Unit:mm(in.) Note 1.Use an M10 screw for the suspension bolt (field supply). 2.Keep the service space for maintenance at the bottom. 3.This drawing is for PEAD-A24 30 36 42 AA7 models,which have 2 fans. PEAD-A12 18AA7 models have 1 fan. 4.If the inlet duct is used,remove the air filter (supplied with the unit), then install the filter (field supply) at the suction side. 5.Heat air to 0 C (32 F) or higher when taking fresh air with a fresh air intake. Air filter PEAD-A12, 18, 24, 30, 36, 42AA7 INDOOR UNIT
DIMENSIONS: PEAD-A12AA7 & PUZ-A12NKA7 (-BS) 6 OUTLINES AND DIMENSIONS PUZ-A12NKA7(-BS) PUZ-A12NKA7 PUZ-A18NKA7 PUY-A12NKA7 PUY-A18NKA7 PUZ-A12NKA7-BS PUZ-A18NKA7-BS PUY-A12NKA7-BS PUY-A18NKA7-BS Unit: mm<in> 48<1-29/32> 404.5<15-15/16> Air intake Installation bolt pitch 500<19-11/16> drain hole ø 42 2-U Shaped notched holes (Foundation Bolt M10<W 3/8>) Air intake 300<11-13/16> 330<13> 360<14-3/16> 630 <24-13/16> Handle for moving 320<12-5/8> 22.3 <29/32> 8.5<11/32> 154.5 <6-3/32> Air discharge 310 <12-7/32> 40 <1-19/32> 32.5<1-9/32> 2-10 21 oval hole (Foundation Bolt M10 <W 3/8>) 22 <7/8> 23.2<15/16> Terminal connection Left... Power supply wiring Right... Indoor/Outdoor wiring 2- ø 22.2<7/8> 1/2 conduit hole 809 <31-7/8> 62 <2-15/32> 492<19-3/8> Earth terminal Service panel 164.5<6-1/2> 99.5<3-15/16> Service port 43 Service panel for charge plug Connection for liquid pipe FLARE ø 6.35 (1/4F) 35 Connection for gas pipe FLARE ø 12.7 (1/2F) 185.5 <7-5/16> Free space around the outdoor unit (basic example) Basically open 100mm<3-15/16> or more as long as no obstacle is placed on the rear and right-and-left sides of the unit FOUNDATION BOLTS Please secure the unit firmly with 4 foundation (M10<W3/8>) bolts. (Bolts, washers and nut must be purchased locally). <Foundation bolt height> Min.100mm <3-15/16> Min.350mm <13-25/32> Max. 18 mm<23/32> FOUNDATION Min.500mm <19-11/16> Min.100mm <3-15/16> PIPING-WIRING DIRECTION Piping and wiring connection can be made from the rear direction only. 2 sides should be open in the right, left and rear side. OCH636 14 1340 Satellite Boulevard. Suwanee, GA 30024 Toll Free: 800-433-4822 www.mehvac.com FORM# PEAD-A12AA7 / PUZ-A12NKA7(-BS) - 201701