FIELD RE-ASSEMBLY FOR FORM 3 AND FORM 7 SHIPMENT MODEL YD CHILLERS - MOD A AND B WITH GRAPHIC CONTROL CENTER AND ELECTRO-MECHANICAL STARTER

Similar documents
CENTRIFUGAL LIQUID CHILLERS MODEL YD (STYLE A) R-134A (COOLING ONLY) WITH OPTIVIEW CONTROL CENTER AND ELECTRO-MECHANICAL STARTER R-134A

CENTRIFUGAL LIQUID CHILLERS YMC 2 MODEL A WITH OPTIVIEW CONTROL CENTER. R-134a. INSTALLATION Supersedes: N1 (611) Form N1 (512) LD14000

MODEL YK M3 M3 G4 THRU YK S6 S4 J2 (STYLE C) R-22 (COOLING ONLY) MODEL YK LB LB G4 THRU YK SE SC J4 (STYLE C) R-134a (COOLING ONLY)

MODEL YK (STYLE G) R-134a or R-531A WITH OPTIVIEW CONTROL CENTER FOR ELECTRO-MECHANICAL STARTER, SOLID STATE STARTER AND VARIABLE SPEED DRIVE

MODELS STEAM YIA-ST-1A1 THRU YIA-ST-14F3 HOT WATER YIA-HW-1A1 THRU YIA-HW-14F3

WATER-COOLED SCREW LIQUID CHILLERS. MODEL YVWA Dual Compressor 50 Hz and 60 Hz Tons kw. R-134a. Issue Date: April 30, 2015

INSTALLATION, OPERATION, MAINTENANCE Supersedes: ICOM2 (1216) Form ICOM2 (318)

MODEL YST UNITS MANUFACTURED AFTER DECEMBER 2006

Installation Manual IM

CENTRIFUGAL LIQUID CHILLERS YMC 2 MODEL A WITH OPTIVIEW CONTROL CENTER. R-134a in

MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: CUSTOMER ORDER NO: PHONE: JCI CONTRACT NO: JOB NAME:

Model REAC / SEAC Self Contained Cooling / Electric Heating Units

Single Package Vertical R-410A A/C & H.P. UNIT MODELS VPC-B, VPP-B, & VPH-B INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

CombiBloc Close-coupled centrifugal pumps

DESCRIPTION. 42 mm. 125 mm

65 MBH through 2890 MBH. LD16237a. June 18, 2015

Single Package Vertical R-22 A/C & HP UNIT MODELS VPC, VPP, & VPH INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

36 & 48 E-Z Cone Fan. Installation & Operator s Instruction Manual (Direct Drive)

WATER-COOLED REFRIGERANT RECOVERY AND RECYCLING UNITS

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

Guide Specifications

EcoVision II Plus Door Upgrade for D6 Kysor Warren Multi-deck Merchandisers

PBS did not observe any paint chips on soil at the school, and no areas of major concern were observed.

Dyna-Star HP, HF, 10:1 Pumps: 120# and 400# Drum Cover and Follower Plate

Installation Instructions

EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST TEL NO: ORDER NO: CONTRACT NO:

Water-Cooled Dual Compressor Screw Chiller

DISTRIBUTION > HOUSING, HVAC > INSTALLATION > AIR INLET HOUSING

MILLENNIUM TM CENTRIFUGAL LIQUID CHILLERS OPERATING & MAINTENANCE Supersedes: Nothing Form O2 (1296)

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

TECHNICAL MANUAL OPERATOR'S, ORGANIZATIONAL, DIRECT SUPPORT AND GENERAL SUPPORT MAINTENANCE MANUAL

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL FEATURING

Installation Instructions

Installation Instruction

INSTALLATION INSTRUCTIONS

Installation Instruction

Installation, Operation, and Maintenance

Installation Instructions

TRIO Compact Gas Barbecue

StarTek West Palm Beach Tech Rates 2018

Installation, Operation, and Maintenance

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION PUMPS

Model CPH Horizontal Water-Cooled Air Conditioning Unit

IOM Installation, Operation, and Maintenance Manual. Magnitude Magnetic Bearing Centrifugal Chillers

INTRODUCTION. NOTE: Read the entire instruction manual before starting the installation. FIRE, EXPLOSION, ELECTRICAL SHOCK HAZARD

Installation, Start-Up and Service Instructions

This label warns for risk of electrical shock when failing to observe.

Installation Instructions Part No , Part No Part No

Specifications Information and Repair Parts Manual 316A-95, 316B-95, 393A-95, 393B A-95 thru 394D-95, 399A-95

KR Series Air Defrost Unit Coolers Operating and Installation Manual

PAC SERIES - 13 SEER SINGLE PACKAGED AIR CONDITIONER (GEN 3, STYLE A)

Installation Instructions

COMPRESSOR SERVICE REPLACEMENT KIT P/N (WCC 500A, 115/60, AIR COOLED)

Model YD Dual Centrifugal Compressor Liquid Chillers Design Level C

Drop-In Refrigeration System

Retrofit Instructions CLEARVIEW DAY COVER CAUTION: Please read this manual completely before attempting to install, operate or service this equipment

Service Data Vickers. Piston Pumps. PVH98/106 Variable Displacement Piston Pump - 11 Design M-2208-S. Revised 05/01/97

Model SWAC Self Contained Cooling/ Hot Water Heating Units UNIT MODEL SWAC - R22 INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

Instruction Manual for HX-DX and HX-DXHP Heat Exchangers 3 / 2017

Installation, Start-Up and Service Instructions

YORK CUSTOM AIR HANDLING UNITS

MODEL URS-1: FACTORY RETROFIT PROGRAM

McQuay. Screw Chiller Water Cooled. WHS Vintage A. Last Manufactured: Replacement Parts List No New 07/2012

PS SERIES PARALLEL RACK SYSTEM GLYCOL CHILLER START UP GUIDE 11/03/2015 Rev 00

PS SERIES PARALLEL RACK SYSTEM GLYCOL CHILLER START UP GUIDE. Master Rack Compressor Sequencer 7/21/2017

Installation Instructions

DLCLRA. INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 TABLE OF CONTENTS

Model KPH Ceiling Mounted, Ducted Condensing Units KPH CEILING MOUNTED, DUCTED CONDENSING UNITS INSTALLATION AND OPERATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS

DLCSRA. INSTALLATION INSTRUCTIONS Outdoor Unit Ductless Split System Sizes 09 to 36 TABLE OF CONTENTS

Installation Instructions

DESIGN STANDARDS SECTION 15600

Service Parts for models UF424 and UN324

IOM Installation, Operation, and Maintenance Manual. Magnitude Magnetic Bearing Centrifugal Chillers

Water Cooled Screw Chiller PFS235C, PFS255C, PFS270C, PFS280C, PFS300C, PFS315C PL

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 PROVEN PERFORMANCE GENERAL FEATURING

Friwa Compact. Operating instructions EN

Disposal Unit (BKSDU) Burger King Shortening. Operation, Service & Parts Manual BURGER KING BKSDU

MODEL DPV VERTICAL AIR CONDITIONING UNITS INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS TXV Coils for Manufactured Housing EMA

TURBO Fiberglass Cone Fan and Grill Fan 48'' Belt Drive. Installation & Operator s Instruction Manual

Service Data Vickers. Piston Pumps. PVH74/81 Variable Displacement Piston Pump - 11 Design M-2207-S. Revised 11/01/97

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer

ICE MAKER POCKET GUIDE. Cornelius Ice Makers Only Starting with Serial Code FA June 1990 Production

Residential Piping and Long Line Guideline

Installation and Operation Manual CLEARVIEW DAY COVER CAUTION: To view a video scan the QR code above

.2 Section Waste Management and Disposal.

COOPER POWER SERIES. Reclosers MN280015EN

Installation Instruction

Cased Aluminum "Convertible" Coils 4TXCB003CC3HC** 4TXCB004CC3HC** 4TXCC005CC3HC** 4TXCC006CC3HC**

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program.

TECHNICAL INSTRUCTIONS

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS

SECTION CHILLERS

YCIV Hz & Hz

Installation Operation Maintenance

Installation Instructions

DOLE REFRIGERATING COMPANY 1420 Higgs Road Lewisburg, Tennessee Phone (931)

McQuay. Templifier Scroll Compressor Water Heater. TGZ Vintage A. Replacement Parts List No Revision E 04/2016

Installation Instructions

Transcription:

CENTRIFUGAL LIQUID CHILLERS INSTALLATION INSTRUCTIONS Supersedes: 160.69-NM3 (912) Form 160.69-NM3 (715) FIELD RE-ASSEMBLY FOR FORM 3 AND FORM 7 SHIPMENT MODEL YD CHILLERS - MOD A AND B WITH GRAPHIC CONTROL CENTER AND ELECTRO-MECHANICAL STARTER Issue Date: July 31, 2015

IMPORTANT! READ BEFORE PROCEEDING! GENERAL SAFETY GUIDELINES This equipment is a relatively complicated apparatus. During rigging, installation, operation, maintenance, or service, individuals may be exposed to certain components or conditions including, but not limited to: heavy objects, refrigerants, materials under pressure, rotating components, and both high and low voltage. Each of these items has the potential, if misused or handled improperly, to cause bodily injury or death. It is the obligation and responsibility of rigging, installation, and operating/service personnel to identify and recognize these inherent hazards, protect themselves, and proceed safely in completing their tasks. Failure to comply with any of these requirements could result in serious damage to the equipment and the property in which it is situated, as well as severe personal injury or death to themselves and people at the site. This document is intended for use by owner-authorized rigging, installation, and operating/service personnel. It is expected that these individuals possess independent training that will enable them to perform their assigned tasks properly and safely. It is essential that, prior to performing any task on this equipment, this individual shall have read and understood the on-product labels, this document and any referenced materials. This individual shall also be familiar with and comply with all applicable industry and governmental standards and regulations pertaining to the task in question. SAFETY SYMBOLS The following symbols are used in this document to alert the reader to specific situations: Indicates a possible hazardous situation which will result in death or serious injury if proper care is not taken. Identifies a hazard which could lead to damage to the machine, damage to other equipment and/or environmental pollution if proper care is not taken or instructions and are not followed. Indicates a potentially hazardous situation which will result in possible injuries or damage to equipment if proper care is not taken. Highlights additional information useful to the technician in completing the work being performed properly. External wiring, unless specified as an optional connection in the manufacturer s product line, is not to be connected inside the control cabinet. Devices such as relays, switches, transducers and controls and any external wiring must not be installed inside the micro panel. All wiring must be in accordance with Johnson Controls published specifications and must be performed only by a qualified electrician. Johnson Controls will NOT be responsible for damage/problems resulting from improper connections to the controls or application of improper control signals. Failure to follow this warning will void the manufacturer s warranty and cause serious damage to property or personal injury. 2 JOHNSON CONTROLS

CHANGEABILITY OF THIS DOCUMENT In complying with Johnson Controls policy for continuous product improvement, the information contained in this document is subject to change without notice. Johnson Controls makes no commitment to update or provide current information automatically to the manual or product owner. Updated manuals, if applicable, can be obtained by contacting the nearest Johnson Controls Service office or accessing the Johnson Controls QuickLIT website at http://cgproducts. johnsoncontrols.com. It is the responsibility of rigging, lifting, and operating/ service personnel to verify the applicability of these documents to the equipment. If there is any question regarding the applicability of these documents, rigging, lifting, and operating/service personnel should verify whether the equipment has been modified and if current literature is available from the owner of the equipment prior to performing any work on the chiller. CHANGE BARS Revisions made to this document are indicated with a line along the left or right hand column in the area the revision was made. These revisions are to technical information and any other changes in spelling, grammar or formatting are not included. Unit Installation OptiView TM Operation Shipping Damage Claim Policy ASSOCIATED LITERATURE MANUAL DESCRIPTION FORM NUMBER 160.69-N1 160.69-O2 50.15-NM JOHNSON CONTROLS 3

NOMENCLATURE YD XF XA J2 CA A MODEL EVAPORATOR CODE XF, XH YF, YG, YH, ZF, ZG, ZH AF, AG, AH CONDENSER CODE XA, XB, XC, XD, YA, YB, YC, YD, ZA, ZB, ZC, ZD, AA, AB, AC, AD POWER SUPPLY - for 60 Hz 5 for 50 Hz COMPRESSOR CODE J1, J2, J3, J4, J5 MOTOR CODE 60 Hz 50 Hz CW CX CY CZ CA CB DA DB DC DD DE DF DH DJ DESIGN LEVEL 5CS 5CT 5CU 5CV 5CW 5CX 5DA 5DB 5DC 5DD 5DE 5DF 5DG 5DH 5DJ YD XH XD J2 DA B MODEL EVAPORATOR CODE KB, KC, KD, K2, K3, K4 HB, HC, HD, H2, H3, H4 GB, GC, GD, G2, G3, G4 FB, FC, FD, F2, F3, F4 EB, EC, ED, E2, E3, E4 DB, DC, DD, D2, D3, D4 CB, CC, CD, C2, C3, C4 BB, BC, BD, B2, B3, B4 COMPRESSOR CODE J1, J2, J3, J4, J5, J7 CONDENSER CODE KB, KC, KD, KE, K2, K3, K4, K5 HB, HC, HD, HE, H2, H3, H4, H5 GB, GC, GD, GE, G2, G3, G4, G5 FB, FC, FD, FE, F2, F3, F4, F5 EB, EC, ED, EE, E2, E3, E4, E5 DB, DC, DD, DE, D2, D3, D4, D5 CB, CC, CD, C2, C3, C4 BB, BC, BD, BE, B2, B3, B4, B5 POWER SUPPLY for 60 Hz 5 for 50 Hz MOTOR CODE 60 Hz 50 Hz CW CX CY CZ CA CB DA DB DC DD DE DF DH DJ DK DL DESIGN LEVEL 5CS 5CT 5CU 5CV 5CW 5CX 5DA 5DB 5DC 5DD 5DE 5DF 5DG 5DH 5DJ 5DK 5DL 4 JOHNSON CONTROLS

LIST OF FIGURES FIGURE 1 - Front View Of Assembled Unit...7 FIGURE 2 - Form 7 Shipment...8 FIGURE 3 - Rigging Compressor/Motor Assembly...9 FIGURE 4 - Re-Assembly...10 FIGURE 5 - System Piping... 11 FIGURE 6 - System Piping... 11 FIGURE 7 - Liquid Line Re-Assembly...12 FIGURE 8 - Oil Pump Housing...13 JOHNSON CONTROLS 5

THIS PAGE INTENTIONALLY LEFT BLANK. 6 JOHNSON CONTROLS

GENERAL This instruction explains the procedure to be used for reassembling the Model YD Chiller shipped disassembled (Shipping Form 3 and 7). Chillers MUST be field reassembled under the supervision of a Johnson Controls representative. For Installation Instructions other than unit assembly, refer to Form 160.69-N1 or N2. FORMS OF SHIPMENT Form 3 Driveline Separate From Shells Shipped as three major assemblies. Unit first factory assembled, refrigerant piped, wired and leak tested; then dismantled for shipment. Close-coupled compressor/open motor assemblies are removed from shells and skidded. Evaporator/condenser is not skidded. All wiring essential with the compressors is left on them, and all conduit is left on the shells. All openings on the compressors and shells are closed and charged with dry nitrogen (2 to 3 PSIG). Miscellaneous packaging of the Control Center, oil eductor filter, tubing, water temperature controls, wiring, oil, isolators, etc. Refrigerant charge shipped in appropriate cylinders. Form 7 Split Shells Shipped as four major assemblies. Unit first factory assembled, refrigerant piped, wired and leak tested; then dismantled for shipment. Close-coupled compressor/open motor assemblies removed from shells and skidded. Evaporator and condenser shells are separated at tube sheets and are not skidded. Refrigerant lines between shells are flanged and capped; tube sheets are also bolted, requiring no welding. MOTOR COMPRESSOR COMPRESSOR MOTOR CONDENSER VSOP PANEL GRAPHIC CONTROL CENTER EVAPORATOR LD09115 Figure 1 - FRONT VIEW OF ASSEMBLED UNIT JOHNSON CONTROLS 7

All wiring essential with the compressors is left on them. All wiring harnesses on shells are removed. All openings on the compressors and shells are closed and charged with dry nitrogen (2 or 3 PSIG). Miscellaneous packaging of Control Center, oil eductor filter, tubing, water temperature controls, wiring, oil, isolators, etc. Refrigerant charge shipped in appropriate cylinders. When more than one chiller is involved, the major parts of each unit will be marked to prevent the mixing of assemblies (Piping and Wiring Drawings to be furnished by YORK). INSPECTION DAMAGE SHORTAGE The unit shipment should be checked on arrival to see that all major pieces, boxes and crates are received. Each unit should be checked on the trailer or rail car when received, before unloading, for any visible signs of damage. Any damage or signs of possible damage must be reported to the transportation company immediately for their inspection. YORK will not be responsible for any damage in shipment of at job site or loss of parts. (Refer to Shipping Damage Claims, Form 50.15-NM). When received at the job site, all containers should be opened and contents checked against the packing list. Any material shortage should be reported to YORK immediately (refer to Shipping Damage Claims, Form 50.15-NM). DATA PLATES A unit data plate is mounted on the Control Center assembly of each unit, giving unit model number; design working pressure; water passes; refrigerant charge; serial numbers; and motor power characteristics and connection diagrams. A Control Panel data plate, which includes control panel part number and serial number is also included. CONDENSER COOLER 5/8" X 2-1/2" BOLTS, LOCKWASHERS, & HEX NUTS LD03865 Figure 2 - FORM 7 SHIPMENT 8 JOHNSON CONTROLS

RE-ASSEMBLY The following is a step-by-step procedure to be used to assemble the chiller. Refer to Installation Instruction, Form 160.69-N1 or N2 for other instructions. Form 7 Shipment (See Figure 2 on page 8) 1. Locate the evaporator and condenser shells in their final position. 2. Bolt the tube sheets together as shown in Figure 2 on page 8. Note that the outside surfaces of the tube sheets must be flush. FORM 3 AND FORM 7 SHIPMENT 1. Level the shells in both directions. The longitudinal alignment of the shell should be checked by placing a level on the top of the shell, next to the discharge connection. The transverse alignment should be checked by placing a level on the tops of both end sheets. Refer to Installation Instruction, Form 160.69-N1 or N2 for additional instructions to level the unit. After the shell is leveled, wedge and shim each corner of the shell to solidly support it while assembling the other parts. 2. Lift a compressor/motor assembly and remove the packing materials (refer to Figure 3 on page 9 for rigging). Carefully lower the compressor/motor assembly on to the supports on the condenser and evaporator. Fasten with the proper hardware. Do not tighten the bolts until all connections are made to the compressor. 3. Bolt the suction lines between the compressors and the evaporator using the proper gaskets and hardware, see Figure 4 on page 10. 4. Install the isolation valves between the compressors and the condenser using proper gaskets and hardware, see Figure 4 on page 10. 5. Connect the oil drain lines between the compressors oil drain flanges and oil pump housing flanges. Be sure to install the proper gaskets and hardware, see Figure 4 on page 10 and Figure 7 on page 12. 6. Complete the refrigerant liquid piping beneath the evaporator and condenser. Be sure the fill piece, orifice plate, gaskets and hardware are properly installed, see Figure 6 on page 11. 7. Tighten all hardware installed from the previous steps 2 thru 8. 8. Assemble the Control Center to unit. 9. Assemble the VS Oil Pump Control Panel. 10. Install the refrigerant piping and oil return system filters. 11. Pressure test. NOTE: Relief valves must be plugged (or capped) (refer to Form 160.69-O2). 12. Evacuate and charge with refrigerant (refer to Form 160.69-O2). 13. All Units Complete installation and finally level the unit per Installation Instruction, Form 160.69-N1 or N2. LD02140 Figure 3 - RIGGING COMPRESSOR/MOTOR ASSEMBLY JOHNSON CONTROLS 9

CONDENSER Motor Compressor #1 Gasket Gasket Isolation Valve with Actuator Gasket O-Ring Oil Pump Housing Gasket EVAPORATOR O-Ring O-Ring Oil Drain Line Compressor #2 Gasket O-Ring Oil Drain Line Flexible Metal Braided Elbow Assembly Compressor Support Gasket VSOP Panel Figure 4 - RE-ASSEMBLY LD09430 10 JOHNSON CONTROLS

Isolation Valve with Actuator Compressor #2 Isolation Valve with Actuator Compressor #1 VSOP Panel LD09431 Figure 5 - SYSTEM PIPING Compressor #2 Compressor #1 VSOP Panel Figure 6 - SYSTEM PIPING LD09433 JOHNSON CONTROLS 11

Figure 7 - LIQUID LINE RE-ASSEMBLY LD09435

Figure 8 - OIL PUMP HOUSING LD09442

P.O. Box 1592, York, Pennsylvania USA 17405-1592 800-861-1001 Subject to change without notice. Printed in USA Copyright by Johnson Controls 2015 www.johnsoncontrols.com ALL RIGHTS RESERVED Form 160.69-NM3 (715) Issue Date: July 31, 2015 Supersedes: 160.69-NM3 (912)