Comparative analysis of power supply single speed air mover and an entire electronics enclosure system fan

Similar documents
Ambient (ºF) Temperature Rise Above

Basic Input Data Needed to Develop a High Performance Fan/Blower with Low Noise, Energy Saving and High Efficiency

Important Considerations When Selecting a Fan for Forced Air Cooling. By: Jeff Smoot, CUI Inc

WHITE PAPER: Cooling Industrial Enclosures with Filter Fans

Enclosure Temperature Control

L14 ENVIRONMENTAL CONTROL TECHNICAL DATA

Enclosure Temperature Control

Equipment Layout Manual. For Cooling Towers, Evaporative Condensers & Closed Circuit Coolers

Installation Guide. Dehumidification. Fresh Air Ventilation. Compact Size. Energy Efficient. RXID-AW90A Whole House Dehumidifier

Application Note Heat Transfer Design Team 7 Compact Inverter Jack Grundemann

HEAT TRANSFER ANALYSIS OF 1-USER SERVER THROUGH CFD

Low Profile Layout Guidelines

Series V Layout Guidelines

EqUIPMENT LAYOUT MANUAL

Modeling and Simulation of Axial Fan Using CFD Hemant Kumawat

The Basics of Package/Device Cooling

TC WATER COOLING TOWER UNIT

WHITE PAPER.

Fike set out to develop a better understanding of the power density trends in data centers around the world.

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS FOR PIPE THREAD IMMERSION HEATERS USED IN HAZARDOUS LOCATIONS

ETSI TR V1.3.1 ( )

Fan Selection. and Energy Savings

Guide To Troubleshooting INEFFICIENT COOLING FANS

SKYPAK II, 3 Ton Series, gives you a

Cooling Solutions for High Heat Flux in Dense Packed Servers. Dr. Walter Angelis R&D Manager Aerodynamics Helmut Sebisch Key Account Manager

A GRAPI-IIC MEUCCI or ESTIMATING VENEER!DRYING RATES

APC APPLICATION NOTE #109

ASHRAE JOURNAL ON REHEAT

COMBUSTION AIR SYSTEM

Chapter Eight RESNET Standards

SKYPAK II, 3 Ton Series, gives you a

Microchannel REMOTE AIR COOLED CONDENSER WITH ELECTRONICALLY COMMUTATED AXITOP MOTORS. Technical Bulletin. Products that provide lasting solutions.

b.) Technical Information:

TOWER DRYERS TOTA TOT L VA AL V LUE. TOTA ALUE. TOT L SYSTEMS. AL SYSTEMS.

Series. Packaged Rooftop Units, heat pumps and Outdoor air handling Units. Features:

Factors one should consider while selecting thermal equipment.

Fans for Life! CA-TD0708. The World s Leading Producer of Air Movement Products

Ventilate Your Swine Nursery Building

Thermal Management INDEX. Management. Thermal TM-1

Development of the San Ace Airflow Tester - A Measuring Device for System Impedance and Operating Airflow of Equipment

KOOLTRONIC ENCLOSURE AIR CONDITIONER QUICK SHEET

EHH SERIES DRAW THROUGH FAN COILS CFM

EC Fans Growing in Popularity

TrueAlarm Analog Sensing

Series PACKAGED ROOFTOP UNITS, HEAT PUMPS AND OUTDOOR AIR HANDLING UNITS. Features:

Fan-and-filter units 4.3. Features. Fast assembly. Application diversity and functions

Physical Mechanism of Convection. Conduction and convection are similar in that both mechanisms require the presence of a material medium.

Electric Coils. Blower Coils. Product Information

Technical college/ Baghdad 4th Year Week No. :- 11. The objectives of this lesson are to: Introduction:

Hood Depot Internatioonal, Inc., Phone S. Powerline Road, Deerfield Beach, FL

Features. Figure 1. Recommended Application

Basic Ventilation Considerations for Livestock or Poultry Housing

VEROTEC Electronics Packaging

DFE T ECHNOLOGY. At Conceptronic, the design and management process for reflow soldering systems is called Dynamic Flow Engineering, or DFE.

NOREN Products. Compact Cabinet Coolers

Cooling the Data Center

System Components with ` Emphasis on Packaged Rooftop Application and Installation. Jerry Cohen President Jacco & Assoc.

T Mirror Cooling Specifications & Design Revision: -

COOLING SPECIFIER S GUIDE EQUIPMENT PROTECTION SOLUTIONS COOLING

Layout. Guidelines11. Chapter 11: Layout Introduction

GLOBAL FINISHING SOLUTIONS

π H-6621 INDUSTRIAL DEHUMIDIFIER WARNINGS SPECIFICATIONS uline.com WATER REMOVAL ELECTRICAL REQUIREMENTS BUILT-IN ELECTRICAL SAFETY

OPTIMISE VACUUM TO IMPROVE PLANT PERFORMNCE

Selecting Fans and Determining Airflow for Grain Drying and Storage

Adding More Fan Power Can Be a Good Thing

Moisture can be very disruptive to a dust. Preventing moisture problems in your dust collector

Water Tank and Heater

COOLING FOR ELECTRONIC PROCESS CONTROL SYSTEMS IN HOSTILE FACTORY ENVIRONMENTS

FAN POWERED VAV TERMINALS

What is the correct type of fan: Axial, radial, diagonal?

10 Tips on Selecting Cartridge Dust Collection Equipment for Tablet Presses

How to Select and Size Enclosure Thermal Management Systems: White Paper, Title Page. How to Select and Size Enclosure Thermal Management Systems

How Much Energy is Really Being Wasted?

CPC PRODUCT DESCRIPTION

"SAN ACE MC" for Pentium *

INTELLIGENT SUCTION. Upgrade-AtoB

Environmental Specifications for Kaleidescape Components Engineering Bulletin

Line Pressure ( w.c.) Gas Supply Min. Max. Pressure ( w.c.) Natural Gas Propane Gas

Understanding Fan System Effects

Executive Summary 4G WiMax Radio Access Cabinet

Ventilation Techniques. Topic 5 - Audio 53

Technical Development Program

SKYPAK II Heating & Cooling Self Contained Packages

Heat loss via internal drainage vent pipes

AC-046 Peltier-Thermoelectric Air Cooler

Modular Supply Make-Up Air Unit

Space Air Diffusion II

FABRICATING A HEAT PIPE STRUCTURE WITHIN A RADIATING PLATE FOR ELECTRONICS FAN-LESS COOLING

ENSC 388: Engineering Thermodynamics and Heat Transfer

W A T L O W MULTICELL HEATERS MEET YOUR HIGHEST DEMANDS

READ THESE INSTRUCTIONS CAREFULLY AND COMPLETELY BEFORE PROCEEDING WITH THE INSTALLATION.

CUMULUS CUMULUS. Key figures. Construction. Function Integrated chilled beams

Investigation of a Novel Ceiling Panel for Heat and Moisture Control in Buildings

The PA 600LI Heat Recovery Ventilation unit has been designed to serve the following small scale applications

Standards and Guidelines. Presented by: Aric Murray December 12, 2014

ADVANCING HVLS technology through controls and energy efficiency

Challenges and Methods of Estimating a Conceptual HVAC Design

Figure 1-1 Furnace Front Elevation

Appendix A.4.1. Safe Fume Hood User Guide

we make air move Double Inlet Centrifugal Fans (Forward Curved) FBD Series (Square Outlet Metric Size)

Transcription:

Comparative analysis of power supply single speed air mover and an entire electronics enclosure system fan Typical densely packaged electronic systems and power supplies utilize a fan for forced-air cooling. Power supply cooling technology often follows computer electronic thermal solutions such as the following: Thermal vias MOSFET surface mount packaging Power transfer by bonding exposed leads to a thermal plan on printed circuit boards Metalized substrates Isolation materials Laminar bus bars Direct bond copper Isolated metal substrates Glass on epoxy Thick film on ceramic Copper on ceramic Computer systems process information, whereas power supply systems process power. With both systems, electrical energy goes in and physical heat comes out. The need for forced-air cooling should be determined at an early stage in system electronics enclosure design. It is important that the Systems Designer have electrical, mechanical, magnetic, thermal, acoustic and chemical knowledge to design good airflow to heat-generating components. It is also important to allow adequate space and power for the physical cooling solution. The first stage in designing a forced-air cooling system is to estimate the required airflow. The primary variable depends on the heat generated within the enclosure and the maximum temperature rise permitted. AC input power is a good initial estimate of the power dissipated within the enclosure. In estimating the power dissipated within a system, the power dissipation figure used should be a worst-case estimate for a fully loaded system. Airflow calculations using heat dissipation and temperature rise for system impedance characteristics. The required airflow is obtained either by calculation or from a standard graph. The equation for calculating the required airflow through an electronics enclosure is as follows: Q = 1.76 W / TC Where: Q = Airflow required in CFM W = Heat dissipated in watts Tc = Temperature rise above inlet temp C For example, how much CFM air-cooling does a system need that dissipates or consumes 300 Watts, allowing only a 10 degree C rise? The above equation results in 52.8 CFM. This equation can be graphed on the following logarithmic chart (Figure 1) with the vertical axis representing the heat to be removed and the horizontal axis representing the airflow; both axes are logarithmic. The sloping lines define the temperature rise in degrees C. Use the graph by locating the sloping line that represents the permitted temperature rise. Then, locate the point on this line that corresponds to the heat to be removed. The horizontal position of this point shows the airflow required.

FIGURE 1 System Impedance Because obstructions in the airflow path cause static pressure within the enclosure, determining the actual airflow needed by a fan mounted in an enclosure is much more difficult than calculating the airflow required. Figure 2 shows the nonlinear relationship between airflow and static pressure for a typical fan. Obstructions should be minimized to achieve maximum airflow. Air guiding devices, in the form of baffles, may be necessary to direct the airflow over the components that need cooling. FIGURE 2

Static Pressure for an Axial Cooling Fan The experimental method of finding airflow through an enclosure is not very accurate and also very timeconsuming. An airflow chamber is required, as shown in Figure 3, and caution must be taken to simulate real application use of the electronics enclosure being tested. FIGURE 3 This article provides the following rules used to estimate airflow resistance: An empty enclosure usually reduces airflow by 5 to 20%. A densely packed enclosure reduces airflow by 60% or more. Most large tower computer electronic enclosures have a static pressure of between 0.05 and 0.15 in. H20. Assuming a dense package, the fan in the previous example should be capable of delivering 80cfm in free air, instead of 52.8 cfm. Most experienced designers are aware that fan manufacturers use the most optimistic statistical figures to represent their products. Intake, Exhaust, and Baffles System Designers have the option of mounting an air-cooling device to: a) Exhaust warm air from the enclosure, or b) Blow cool air into the enclosure. Theoretically, the same volume of air is used to dissipate heat. Depending on the specific real world application, each arrangement has advantages and disadvantages.

Incoming air flows laminarly, which means air drawn into the enclosure, is flowing laminarly. Laminar flow allows for a uniformly distributed airflow in the enclosure. This is important in eliminating stagnant air and possible hot spots. Air exhausted out of an enclosure is turbulent. Heat dissipation in a turbulent airflow could be double that of a laminar flow with the same volumetric flow rate. Thermal-Mechanical Engineers will agree that turbulent airflow is desirable in cooling solutions. The turbulent airflow region near a fan exhaust is limited to a very short distance, depending on the size of the fan. This is why it is desirable to have a heat sink, or the components needing the most cooling, immediately at the fan output. Developing a well-defined airflow path through the entire enclosure is extremely important. Air vent area should be 50 percent larger than the fan opening. This is why most system exhaust fans are placed at the output of a computer or power supply enclosure. Recirculatuion is desirable for very large computer server systems. However, in most small electronic enclosures, air recirculation should be avoided. With small form factor fans, all of the airflow can be lost because of recirculation problems. Baffles, shrouds, or ducting systems are often necessary to eliminate recirculation of the same air and direct air on to or away from hot spots. The airflow path as electricity will always take the path of least resistance. Physical subassemblies and components within the enclosure, such as large capacitors and circuit boards, could be smartly positioned to direct the airflow to places that require cooling. Natural convection cooling should take precedence in electronic enclosure designs. Therefore, a Systems Designer should place warm components above cool components, much the same way heavy components are placed on the bottom of rack systems. Fans used to exhaust heat from an electronics enclosure reduce the pressure within the enclosure and dust is drawn in through all the vents and openings. Dust accumulation can produce many problems. Because exhaust fans tend to operate under hotter conditions exhaust fans can be half the life of an intake fan. A chief recommendation of this article is to use a single systems fan that ventilates an entire electronics enclosure and the power supply is recommended as shown in Figure 4. FIGURE 4

Notice that this system recommendation uses a baffle ducting system, which evacuates hot air from the electronics enclosure while pushing air through the power supply. This design economizes cooling solutions and requires that a single systems designer be responsible for both power supply and electronics system thermal solutions. A variable speed fan is recommended to reduce noise and maximize power efficiency. Notice that most power supply fans simply run at a fixed speed. Applying additional airflow through the power supply will not adversely damage the power supply circuits. With a variable speed fan, the fan circuit automatically controls the speed. JMC has recently patented a software controlled SMBus/I2C OS or BIOS configurable Intellifan. The Intellifan is independent of analog circuitry and imprecise thermistors. As the temperature changes, the fan speed adjusts precisely. Optimum airflow is obtained at all times. Written By: Abe Arredondo Engineering Manager JMC Products aarredondo@jmcproducts.com JMC Products 10315A Metropolitan Drive Austin, Texas 78758 www.jmcproducts.com 800.580.6688