Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

Similar documents
Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

Mechanical System Redesign. Dedicated Outdoor Air System. Design Criteria

State of the art building simulation software... Frenger Radiant chilled beam performance at 1 Shelly St - Sydney

FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney

Visualization of Evaporatively Cooled Heat Exchanger Wetted Fin Area

The Effect of the Ventilation and the Control Mode on the Performance of a VRV System in Cooling and Heating Modes

Chilled beams. TRACE 700 incorporates two chilled beam strategies: passive and active.

Low GWP Refrigerants for Air Conditioning Applications

Low Global Warming Refrigerants For Commercial Refrigeration Systems

Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System

Chilled beam technology overview John Woollett 1, Jonas Åkesson 2 Swegon AB 1,2

Heat Exchanger Shelves For Better Temperature Control Of Food In Open-Type Display Cases

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer

HAP e-help. Modeling Induction Beams in HAP v4.8 QB TIP 001

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System

System Using Exhaust Heat from Residential GHPs

Available online at ScienceDirect. Energy Procedia 78 (2015 )

Clemens Felsmann 1, Jean Lebrun 2, Vincent Lemort 2 and Aad Wijsman 3 ABSTRACT INTRODUCTION METHODOLOGY

Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System

K.F. Fong *, C.K. Lee, T.T. Chow

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

The Use Of Attic Space For Cooling and Dehumidification

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

BOOK 1 OVERVIEW RD2XRT INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Sub-Critical Operation of the CO2 Expander/ Compressor

Available online at Energy Procedia 6 (2011) MEDGREEN 2011-LB

A New Control Approach for a Direct Expansion (DX) Air Conditioning (A/C)System with Variable Speed Compressor and Variable Speed Supply Fan

ENGINEERING BULLETIN. Overview of Chilled Beam Technology. Purpose. Summary. Theory

BOOK 1 OVERVIEW RD2XIN INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

b.) Technical Information:

The Design Of A New Generation Of Twin Screw Refrigeration Compressors

Fifteen Years of Dehumidification Results from Heat Pump Water Heaters

HSPF Calculation of a System Allowing Switching Between a Single-Stage to a Two-Stage Compression System

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) â Summary of Phase II Testing Results

NOVEMBER 2012 THE EUROPEAN EXPERIENCE

Effects of Frost Formation on the External Heat Transfer Coefficient of a Counter-Crossflow Display Case Air Coil

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

The Innovative Green Technology for Refrigerators Development of Innovative Linear Compressor

APPLICATION GUIDE BEAMS

CARRIER edesign SUITE NEWS. Modeling 100% OA Constant Volume Air Systems. Volume 6, Issue 1. Page 1 Modeling 100% OA Constant Volume Air Systems

Experimental Study on the Performance and Oil Return Characteristics of Multi-Split Air- Conditioning System for Medium Size Building

Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area

Daikin Blueprint: Delivering Hot Water with a Chiller

UFAD and Displacement Ventilation. Dan Int-Hout, FASHRAE Chief Engineer Krueger Richardson, Texas

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

Hello, my name is Audra Benzschawel and I m a marketing engineer in the C.D.S. Slide 1 TRACE 700

System Modeling of Gas Engine Driven Heat Pump

7. MECHANICAL SYSTEM DESIGN

Chilled Beams. Getting a Warmer Reception

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

Experimental Study on the Thermal Behavior of a Domestic Refrigeration Compressor during Transient Operation in a Small Capacity Cooling System

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) Summary of Phase I Testing Results

Evaluation of Mechanical Dehumidification Concepts (Part 2)

Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1. Contextual Reminder

Don t Turn Active Beams Into Expensive Diffusers

Performance Comparison of Hydronic Secondary Loop Heat Pump and Conventional Air-Source Heat Pump ABSTRACT 1. INTRODUCTION

Performance Evaluation and Design Optimization of Refrigerated Display Cabinets Through Fluid Dynamic Analysis

Effect of Modification in Refrigerant Passage of an Automotive Air Conditioning Compressor

A study of radiant cooling for a room with daytime application in tropical climate

DADANCO Technical Paper

Humidity Control Systems for Civil Buildings in Hot Summer and Cold. Winter Zone in China

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

nzeb office building

Benefits Offered by Passive Dehumidification Wheel Speed Control

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

The Development Of High Efficiency Air Conditioner With Two Compressors Of Different Capacities

RADIANT COOLING RESEARCH SCOPING STUDY

Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors

seasons in regions with hot, humid climates. For this reason, a dehumidification system with a radiant panel system needs to be developed. In a former

Selected Laboratory Energy Efficiency Measures

product application data PERFECT HUMIDITY DEHUMIDIFICATION SYSTEM

GUIDANCE AND TOOLS FOR CHILLED CEILINGS COMBINED WITH A WET COOLING TOWER

EFFECT OF SATURATION EFFICIENCY OF DIRECT EVAPORATIVE COOLER ON INDOOR CONDITIONS AND THERMAL COMFORT IN A SMALL OFFICE ROOM OF A BUILDING

NEW FEATURES IN THE CARRIER HOURLY ANALYSIS PROGRAM v4.80

Recovery of Waste Thermal Energy in U.S. Residential Appliances

SIMULATION ANALYSIS OF BUILDING HUMIDITY CONTROL AND ENERGY CONSUMPTION FOR DIFFERENT SYSTEM CONFIGURATIONS USA

Development of R744 Two Stage Compressor for Commercial Heat Pump Water Heater

EADQUARTERS. Technical Report One. Stephanie Kunkel Mechanical Option

Residential ventilation concepts based on the idea of displacement airflow distribution

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1

Chilled Ceilings / Beams Working Principles & Applications

Purdue e-pubs. Purdue University

Design and Research of the Digital VRV Multi- Connected Units With Three Pipes Type Heat Recovery System

Performance Characteristics and Optimization of a Dual-Loop Cycle for a Domestic Refrigerator- Freezer

Noise Reduction Technology With Porous Metal for Refrigerant Two-Phase Flow Through the Expansion Valve

Radiant Exchange in Stratified Environments: Considerations and Challenges for Hourly Energy Simulation of UFAD, DV, and Radiant Cooling Systems

High Efficiency R-134a Compressor for Domestic Refrigerator

Do All DOAS Configurations Provide the Same Benefits?

Optimisation of cooling coil performance during operation stage for improved humidity control

Radiant Heating & Cooling for Commercial Buildings

VENTILATIVE COOLING CONTROL STRATEGIES APPLIED TO PASSIVE HOUSE IN ORDER TO AVOID INDOOR OVERHEATING

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

White Paper Dehumidification in Humid Climates - A Theoretical Case Study

Radiant Cooling Nonresidential HVAC Stakeholder Meeting #2

Chilled Beams in Labs Eliminating Reheat & Saving Energy on a Budget

High-Performance VAV Systems

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants

Transcription:

Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2014 Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates Janghyun Kim Ray W. Herrick Laboratories, School of Mechanical Engineering, Purdue University, United States of America, kim1302@purdue.edu James E. Braun jbraun@purdue.edu Athanasios Tzempelikos ttzempel@purdue.edu Follow this and additional works at: http://docs.lib.purdue.edu/ihpbc Kim, Janghyun; Braun, James E.; and Tzempelikos, Athanasios, "Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates" (2014). International High Performance Buildings Conference. Paper 107. http://docs.lib.purdue.edu/ihpbc/107 This document has been made available through Purdue e-pubs, a service of the Purdue University Libraries. Please contact epubs@purdue.edu for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html

3254, Page 1 Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates Janghyun KIM 1*, James E. BRAUN 1,2, Athanasios TZEMPELIKOS 1,2 1 Ray W. Herrick Laboratories, School of Mechanical Engineering, Purdue University, 140 S. Martin Jischke Dr., West Lafayette, IN 47907, USA kim1302@purdue.edu, jbraun@purdue.edu, ttzempel@purdue.edu 2 School of Civil Engineering, Purdue University, 550 Stadium Mall Dr., West Lafayette, IN 47907, USA * Corresponding Author ABSTRACT This study considers a cooling system retrofit for a commercial building in different climates by introducing a passive chilled beam system. A typical single duct VAV system, widely used in large office buildings, was considered as a baseline scenario; a combination of the air system and passive chilled beams was considered as a retrofit scenario. The retrofit with minimum modifications in this study includes installations of (1) multiple passive chilled beam units, (2) additional pumps and a closed water loop for the passive chilled beam units and (3) a heat exchanger where the chilled beam s water loop exchanges heat with the return side of the chilled water loop. The results showed total energy savings up to 22% for climates where the sensible load is much higher than the latent load. 1. INTRODUCTION Reducing energy consumption in buildings is an important part of reducing global energy usage and environmental impact. It has been reported by the International Energy Agency (IEA, Energy technology perspectives 2012) that the global energy demand in buildings will be doubled in 2050 due to the rising number of residential and commercial buildings in response. More than two-thirds of existing buildings are expected to remain until 2050. Therefore, significantly reducing energy use in the building sector requires retrofitting existing buildings with advanced technologies. Furthermore, modeling of these technologies is a critical part of assessing their economics towards realizing success in the marketplace. Passive chilled beams can be considered passive systems, which rely only on radiation and natural convection for sensible heat transfer and do not employ active fans; while active systems include forced air movement with fan operation to enhance air flow and convective heat transfer. Typically, latent load requirements are handled separately using a dedicated outdoor air system (DOAS) that conditions only the ventilation air. Compared to conventional all-air systems, this can lead to reduced overall cooling requirements: a significant benefit of passive systems. Since the amount of air carried to the space can be reduced significantly, there is also less fan energy consumption compared to conventional systems. Furthermore, the reduction of air flow allows downsized ductwork. The cooling load can be further reduced by taking advantage of the improved comfort associated with radiant cooling of occupants, which can allow a somewhat higher zone temperature for the same comfort level. Furthermore, higher radiant surface temperatures (above the dew point of the air) lead to higher operating temperatures than those of conventional cooling systems, and improved energy efficiency for chillers. It is also possible to couple the radiant cooling system with energy storage within the building thermal mass, to allow load shifting and reductions in peak load. Energy modeling tools are important for designing building systems and for assessing new technologies such as passive ceiling cooling systems. To evaluate both thermal comfort and energy saving aspects of passive chilled beams, the model should accurately take into account the primary heat transfer mechanisms of radiation and natural convection which are strongly coupled to the specific characteristics and conditions within the spaces where they are

3254, Page 2 installed. However, it is also possible to partially analyze the aspect of decoupling sensible and latent loads for passive chilled beam applications with simplified models. Since the capital cost of passive chilled beam systems is the major barrier of introducing the system into the market place, this study focuses on passive chilled beams as a retrofit option with minimum modification of the original cooling system. The study considers energy savings associated with decoupling of sensible and latent loads for the same zone temperature setpoints, but does not consider benefits of improved thermal comfort that may result. 2. BUILDING ENERGY MODEL DESCRIPTION The details and parameters of the simulation model are described in the following sections. The model was implemented in TRNSYS software (TRNSYS, 2004). 2.1 Climatic data Different climatic zones were considered that have different ambient humidity levels (marine, dry and moist) and five different latitudes (zone 1 to 5) based on the U.S. climate zone map in ANSI/ASHRAE Standard 90.1 (ASHRAE, 2013). Based on this classification, eleven different cities were selected (Figure 1) to import TMY 2 weather data into the simulation. Since the study focuses on the cooling system s performance, zone 6 and higher were not considered. Detailed definitions of each climate zone can be found in ANSI/ASHRAE Standard 90.1 (ASHRAE, 2013). 2.2 Building Envelope Parameters The building envelope model was developed based on construction drawings of one of the new Living Lab offices in the Ray W. Herrick Laboratories at Purdue University (West Lafayette, Indiana) as shown in Figure 2. Table 1 includes details of the envelope components. Although the actual office is equipped with a double façade, the model is applied with a regular double-glazed window to focus more on the relative performance of the two cooling system alternatives. The office has a 117 m 2 floor area with the height of 4.6 m. North, east and bottom side of the space is adjacent with other spaces in the building and south and west wall are exposed to the ambient. The window to wall ratio is about 50% of the South wall. 2.3 Internal Gains Figure 1: Eleven cities representing the different climate zones

3254, Page 3 Figure 2: Exterior view and plan of the studied office space Internal gains schedules for occupancy, lighting and plug loads were adopted from ASHRAE Standard 90.1 (ASHRAE, 2010) as shown in Figure 3. These schedules represent typical load profiles of commercial building. 2.4 Conventional Air System A typical single duct VAV system, which is widely used in large office buildings (Thornton et al., 2011), was considered as the cooling system for the baseline scenario. As shown in Figure 4 (a), the system includes a cooling coil, supply and return fan and an economizer. The preheating coil, reheating coil and VAV box were not included in this study to simplify the approach for the consideration of a summer cooling season. The chilled water source for the cooling coil is provided from a water cooled chiller which is driven by electricity and a variable speed pump was used to provide chilled water from the chiller to the cooling coil. The control sequence of the air system is basically to meet the space sensible load requirement while latent load is mostly covered in the same cooling process at the cooling coil. The speed of the supply fan (Fan 1) is controlled to meet the room temperature setpoint (23.9 o C) and the speed of the pump (Pump 1) at chilled water loop is controlled to meet the cooling coil outlet air temperature setpoint (13 o C). The return fan (Fan 2) is assumed to be synchronized with the supply fan s operation. The chiller is controlled to provide 7 o C outlet temperature whenever the cooling signal is on. The economizer is controlled based on temperature difference between room setpoint and outdoor air. Type Roof Raised Floor External Wall Internal Wall Table 1: Specification of Envelope Components Thickness Layer Description m Insulation 0.1 Concrete 0.038 Concrete 0.3 Air 0.102 Gypsum Board 0.013 Insulation 0.105 Stucco 0.025 Gypsum Board 0.016 Air 0.184 Gypsum Board 0.016 U-Value W/m 2 K 0.221 0.086 0.358 0.136 Window Double pane, Low-e, IGU - 1.43

3254, Page 4 Figure 3: Specification of internal gains The minimum outdoor air requirement (0.4 ACH) is applied to the system based on ANSI/ASHRAE Standard 62.1 (2010), thus even when outdoor air is not favorable, the economizer still includes the minimum outdoor air to the supply air stream. A thermostat was used to control the cooling signal with ±1 o C deadband from the room temperature setpoint and a night setback schedule was applied besides the occupied hours (8 a.m. to 5 p.m.) for the room temperature setpoint (+4 o C). 2.5 Passive Chilled Beam System In this case, the same air system is used for dehumidification and multiple passive chilled beams, connected to a separate water loop as shown in Figure 4 (b), are employed to satisfy the main sensible cooling load. The separate water loop for the chilled beams is coupled with the air system's cooling coil by a heat exchanger. The use of the heat exchanger allows variation of the pump speed (Pump 3) at the passive chilled beam's water loop to meet the sensible load requirement. The air system's chilled water loop also utilizes variable speed capability to meet the latent load requirement. As shown in the Figure 4 (b), two additional water pumps (Pump 2 and 3) are included over the conventional air system's configuration. The additional water pump and a bypass loop were added prior to the cooling coil to allow sufficient chilled beam cooling capacity. However, the temperature inlet to the passive chilled beams is controlled to avoid condensation. The cooled water was provided to each passive chilled beam unit individually, providing the same inlet temperature to each unit, as it is usually applied in practical design. Figure 4: HVAC system layout of conventional and retrofit scenarios

3254, Page 5 Figure 5: Performance characteristics of fan, pump and passive chilled beam The control sequence of the passive chilled beam system is to meet the latent load requirement with the air system while the passive chilled beam system covers the remaining sensible load. While the chiller and the pump (Pump 1) within the chilled water loop are controlled with the same sequence as in the conventional air system's scenario, the speed of the supply fan (Fan 1) is controlled to meet the humidity setpoint (0.01 kg water /kg air ) in the space. One additional pump (Pump 2) in the cooling coil's bypass loop is controlled to provide 9 o C water temperature to the heat exchanger whenever there is a cooling requirement at the passive chilled beam. While the air system is controlled based on the latent load requirement, the coil cooling rate will generally not be sufficient to maintain the temperature of the space at the setpoint of 23.9 o C during summer. Thus, the passive chilled beams output is controlled to meet the temperature setpoint. Nominal water temperature (13 o C) and mass flow rate (0.1 kg/s) were used for the passive chilled beams operation, while the number of passive chilled beam units was used as a variable to calculate the maximum required number of passive chilled beams needed in the space. A humidistat was used to control the cooling signal with ±0.001 kg water /kg air deadband from the room humidity ratio setpoint and a night setback schedule was applied besides the occupied hours (8 a.m. to 5 p.m.) for the room humidity ratio setpoint (+0.003 kg water /kg air ). 2.6 HVAC Components Water cooled chiller, fan, pump and passive chilled beam models are incorporated in the building energy model. The performance of these components needs to be estimated to correctly evaluate the effect of a retrofit scenario. The water cooled chiller s performance was predicted with one of the models from the TRNSYS library (Type 666). A normalized performance map was used to calculate the power of the chiller from different conditions of rated capacity, rated COP, water mass flow rate, chilled water leaving temperature and cooling water inlet temperature. Performance of the fan and pump were applied based on actual measurements. Supply flow rate and power consumption of the fan and the pump were directly coupled by using the affinity laws for the fan and a 2 nd order polynomial for the pump as shown in Figure 5 (a) and (b). A regression model available for the passive chilled beam (based on the experimental measurements) was used (DOE 2.1E Manual, 2013). The surface fit shown in Figure 5 (c) was used to calculate the heat extraction rate of the passive chilled beam based on water mass flow rate and temperature difference between indoor air temperature and water inlet temperature. 3. RESULTS The components described in the previous section were incorporated in TRNSYS to conduct transient simulations of both the conventional air system scenario and the retrofit passive chilled beam scenario for the cooling season (July and August) in all 11 climatic zones. A 15-min time step was used in the simulation. Total energy consumption per unit floor area for all cases are shown in Figure 6. The most significant part of the savings comes from the fan s reduced energy consumption due to reduced coil loading. In every climate, more than 70% of the fan energy was saved in the retrofitted scenario. The required supply air flow is significantly less because the coil meets a much smaller load when controlled based on latent requirements rather than for sensible load. Furthermore, fan power depends on the cube of the air flow leading to substantial savings. As shown in Figure 7, the fan energy consumption is driven by the sensible load profile in the conventional system, while in passive chilled beam

3254, Page 6 Figure 6: Total energy consumption in different climatic zones configuration it is driven by the latent load. Since the latent load is smaller than the sensible load in every climate considered in this study, fan energy can always be saved. As shown in Figure 6, chiller energy can also be saved in climatic zones A and B with savings ranging from 9 to 17%. However, there are insignificant savings in marine zones (C). The chiller savings are the result of decoupling of the sensible and the latent load. Since the conventional air system is operated based on the sensible load only, dehumidification is driven by the profile of the sensible load, which, in certain climates, might provide excess dehumidification to the space. Figure 8 (a) shows the excess dehumidification (latent load on cooling coil) for the conventional scenario compared to Figure 8 (b) for the retrofitted scenario. It also shows that almost the same magnitude of the sensible load is met by the cooling coil in the conventional scenario and by the cooling coil and the passive chilled beam in the retrofitted scenario. Thus, since the chiller s power is driven by both sensible and latent loads as depicted in Figure 7, the total load on the chiller which is the total magnitude of the bars in Figure 8 is reduced in most climatic zones in the retrofitted scenario. The total energy savings in different climatic zones (calculated from Figure 6) are shown in Figure 9. Variable energy savings are due to the difference between the magnitude of the sensible and latent loads. Compared to the humid climates (A), dry regions (B) will have less latent load but they might have either higher sensible load (2B and 5B) or lower sensible load (3B and 4B). Marine regions (C) have both less sensible and latent load compared to humid regions. Thus, compared to humid regions, climatic zone 2B and 5B will have higher energy savings since excess dehumidification will increase according to higher sensible load, while the actual latent load will decrease in dryer regions. The savings due to excess dehumidification are depicted in Figure 10: in the conventional scenario, the cooling system will be driven by the profile of the sensible load. If the actual latent load is less than the Figure 7: Driving force of each component in both scenarios

3254, Page 7 dehumidification provided by the cooling system, the difference between excess dehumidification and the actual latent load, shown in Figure 10 (b), can be saved in the retrofitted scenario since the load is decoupled and met separately by the air system and passive chilled beam system. Thus, it will be favorable to apply the passive chilled beam system in regions where the sensible load is high and the latent load is low. Figure 8: Load on each component Figure 9: Total energy saving in each climate Figure 10: Excess dehumidification in conventional air system which can be saved with the chilled beam configuration.

3254, Page 8 4. CONCLUSIONS The following conclusions were found in considering a passive chilled beam system as a retrofit option: Total energy savings between 8 to 24% in humid and dry climate zones. Passive chilled beams as a retrofit option was not favorable in marine regions. Substantial fan energy can be saved in every climate (~70%) depending on the magnitude of the latent load. Chiller energy can be saved in both humid and dry regions. REFERENCES ASHRAE, ANSI/ASHRAE Standard 90.1 2010: Energy Standard for Building Except Low-Rise Residential Buildings, ASHRAE, Atlanta, GA, 2010 ASHRAE, ANSI/ASHRAE Standard 90.1 2013: Energy Standard for Building Except Low-Rise Residential Buildings, ASHRAE, Atlanta, GA, 2013 ASHRAE, ANSI/ASHRAE Standard 62.1 2010: Ventilation for Acceptable Indoor Air Quality, ASHRAE, Atlanta, GA, 2010 DOE 2.1E Manual. Accessed February 18, 2013. http://simulationresearch.lbl.gov/dirsoft/21e_update2.pdf Energy Technology Perspectives 2012. 2012. Scenarios and Strategies to 2050. Paris: International Energy Agency (IEA). Thornton, B.A. et al., 2011, Achieving the 30% Goal: Energy and Cost Savings Analysis of ASHRAE Standard 90.1-2010, Pacific Northwest National Laboratory (PNNL-20405) TRNSYS, 2004. A Transient System Simulation Program, Version 17. University of Wisconsin. Available from: <http://sel.me.wisc.edu/trnsys/> ACKNOWLEDGEMENT The authors would like to acknowledge Donghun Kim and Jie Cai for their preliminary work on the Living Lab envelope model and experimental data measurements.