HOONEAUTOMAATIKASÜSTEEMID AAR0130 2010 OSA VI-II AUTOMAATNE TULEKAHJUSIGNALIS ATSIOON ( ATS ) ÜLO KALA 1 PÕLEMISE LIIGID PUU PÕLEMINE LAHTISE LEEGIGA 2 PUU PÜROLÜÜS Page 1
PÕLEMISPROTSESS PÕLEMINE ENERGEETILISED PÕLEMISPRODUKTID AINELISED PÕLEMISPRODUKTID SOOJUSÜLEKANNE SOOJUSKIIRGUS MITTELENDUVAD PRODUKTID LENDUVAD PRODUKTID UV LEEGIANDUR ÕHUVOOLUD ULTRAVIOLETT KIIRGUS TUHK VEEAUR, CO, CO2 OPTILINE SUITSUANDUR HELID NÄHTAV KIIRGUS NÄHTAV SUITS TEMPERATUURIANDUR TEMPERATUUR IR LEEGIANDUR INFRAPUNANE KIIRGUS VEDEL JÄÄK IONISATSIOON VÕI SININE SUITSUANDUR PÕLEMISGAASID JA AEROSOOLID 3 SUURSILMUS (BUS/LOOP) Edasine kaabeldus Silmus jääb täielikult töökorda anduri eemaldamisel) ALUS Optilised suitsuandurid Intelligentsed andurid O 2 T fire detector OTG detector (optical/thermo/gas) Temperatuuriandurid Fixed Rate-of-rise Kahekordne reserveeritus esserbus ja lühiseeraldi igas anduris 4 Page 2
SISEKASUTUSE PUNKTANDUR Smoke Detector Heat Detector Black ring LASER Barcode label LIGIKAUDU 95% ANDURIST 5 MODIFIKATSIOONID IQ8Quad (TEMPERATUURI, OPTILINE VÕI GAASIANDUR) IQ8Quad LISATUD VILKUR IQ8Quad HELISIGAAL VASTAVALT EN 54 IQ8Quad SÕNALI NE ETTEPROGRAMMEERITUD TEADE KUIDAS VÄLJUDA ALATES 2011 KA KAAMERA 6 Page 3
KUNI 4 KOMPONENTI KOOS Detector: High-tech SUITSUANDUR Integrated flasher: INTEGREERITUD VILKUR Integrated sounder: SIREEN VAST. EN 54 Integrated speech function: SÕNALISE ALARMI TEATED Tulemas on : SISSEEHITATUD KAAMERA CIF 5 FPS 7 INTEGREERITUD VILKURIGA Alarm Ootel 8 Page 4
Audible signals (Example) Demo Speech outputs Demo Signal component Tone 1 (GB) Tone 2 (GB) Tone 3 (GB) Signal component Phrase 6 Phrase 7 Phrase 8 Phrase 9 Description of signal FP 1063.1 Telecoms BS 5839 Pt1-Tone 1 Alternating signal tone, Fequency 800 / 970 Hz @ 2Hz FP 1063.1 Telecoms BS 5839 Pt1-Tone 2 Alternating signal tone, Frequency 800 / 970 Hz @ 1Hz FP 1063.1 Telecoms BS 5839 Pt1-Tone 3 Cyclic signal tone, Frequency 970 Hz @ 1Hz 0,5 s Description of signal This is a fire alarm. Please leave the building immediately by the nearest available exit. Attention please. This is an emergency. Please leave the building by the nearest available exit. An incident has been reported in the building. Please await further instructions. This is a test message. No action is required. Duration [s] 4,00 4,00 4,00 Duration [s] 5,27 5,82 4,37 3,18 9 Phrase 10 The emergency is now cancelled. We AAR0130 apologise ÜLO for any KALA inconvenience. 2010 4,46 2 JOON või LIINIANDURID IR KIIRANDUR (SAATJA) (VASTUVÕTJA) 100 M LINEAARNE TEMPERATUURIANDUR 10 Page 5
OPTILINE LIINIANDUR IR KIIRANDUR (SAATJA) (VASTUVÕTJA) 100 M 11 PEEGLIGA LIINIANDURID VASTUVÕTJA SAATJA REFLEKTORe hk PEEGEL VASTUVÕTJA SAATJA REFLEKTORe hk PEEGEL 12 Page 6
OPTILISTE LIINIANDURITE PAIGUTUS T max = 12 m T ma1 > 6% Mst Mst MAKSIMAALNE TÖÖKAUGUSKAUGUS 13 6 m OPTILISTE LIINIANDURITE PAIGUTUS T max = 12 m T ma1 < 6% Mst Mst MAKSIMAALNE TÖÖKAUGUSKAUGUS 14 6 m Page 7
LIINIANDURITE PARAMEETRID 15 16 Page 8
ANALOOG TEMPRATUURI LIINIANDUR NEG. TEMP. KOEF.MATERJAL VASKSOON KAABEL KAITSEKEST PVC 17 DIGITAALNE TEMPRATUURI LIINIANDUR 18 Page 9
TUNNELITE DIGITAALNE TEMPERATUURIANDUR 19 TEMPERATUURID TUNNELIPÕLENGUL 20 Page 10
FIIBEROPTILINE TEMPERATUURISENSOR 21 FIIBER SENSORI TÖÖPÕHIMÕTE 22 Page 11
RUUMIANDURID VIDEO SUITSUANDUR LEEGIANDUR 23 VIDEO SUITSUANDUR KAITSTUD ALA enkooder 24 Page 12
SUITS MÄRGATUD EELALARM SUITS LEEK MÄRGATUD 25 LEEGIANDURID UV LEEDIANDURID - LEEGI UV KIIRHUSELE IR LEEGIANDURID - KUUMUSE MUUTUSELE SOOVITATAV MONTAAZIKÕRGUS ON 2 X OBJEKTI KÕRGUS 26 Page 13
27 SÄDEMEANDURID 28 Page 14
SÄDEMEANDURIGA TULETÕKESTUSSÜSTEEM SÄDEMEL ANDURITE VAHEL RAKENDUB KIIRE SULGEMEHHANISM MIS ISOLEERIB OHTLIKU KANALI OSA 29 PROOVIVÕTU ANDURID 30 Page 15
RAKENDUSKIIRUS ALGSTAADIUM ILMA NÄHTAVA N SUITSUTA NÄHTAV SUITS LEEGI TEKE INTENS. KUUMUS STAGE 1 STAGE 2 STAGE 3 BEAM STAGE 4 SPRINKLER PHOTO FLAME SUITSU TIHEDUS ION 31 AEG PROOVIVÕTUSÜSTEEMI EHITUS PROOVIVÕTU TORU VESDA LaserPLUS 88 32 Page 16
OLULISELT VARASEM HOIATUS NÄHTAVAT SUITSU POLE NÄHTAV SUITS LEEK INTENSIIVNE KUUMUS STAGE 1 STAGE 2 STAGE 3 BEAM STAGE 4 SPRINKLER PHOTO FLAME SUITSU TIHEDUS ION 33 AEG EELHÄIRE I EELHÄIRE II TULI TUNDLIKKUS KUNI 10 000 X SUUREM KUI TAVALISEL SUITSUANDURIL PAIGALDUS RIPPLAELE KAPILLAARTORU PROOVIVÕTUTORU MINIATUURNE PROOVIVÕTU PUNKT RIPPLAGI PEIDETUD PROOVIVÕTU PUNKT 34 Page 17
ANDURITE VÕRDLUS 35 ALARMISEADMED ANDUR KOOS INTEGREERITUD VÄLKLAMBI,SIREENI,JA SÕNALISE ALARMIGA, ERALDI ALARMSEADE KOOS INTEGREERITUD VÄLKLAMBI,SIREENI,JA SÕNALISE ALARMIGA 36 Page 18
MINIMAALNE HELITUGEVUS EN 54-3, OSA 4.6.2 NURK 15 45 75 105 135 165 DIN TOON 81 db 89 db 94 db 94 db 89 db 81 db Madal toon 730 Hz 81 db 90 db 95 db 95 db 90 db 81 db Keskmine 830 Hz toon 80 db 85 db 90 db 90 db 85 db 80 db Kõrge toon 970 Hz 82 db 91 db 96 db 96 db 91 db 82 db 37 38 VÕIMALIKUD TOONID Tone No. Frequency / Tone type 1) 1. Signal tone 730Hz tone, 1 Hz intermittent 2. Signal tone 730Hz tone, 2 Hz intermittent 3. Signal tone 830Hz tone, 1 Hz intermittent 4. Signal tone 830Hz tone, 2 Hz intermittent 5 Signal tone 970Hz tone, 1 Hz intermittent 6. Signal tone 970Hz tone, 2 Hz intermittent 7. Signal tone Alternating tone 730/830 Hz, 1Hz impulse 8. Signal tone Alternating tone 730/830 Hz, 2 Hz impulse 9. Signal tone Alternating tone 970/830 Hz, 1Hz impulse 10. Signal tone Alternating tone 970/830 Hz, 2 Hz impulse 11. Signal tone Continuous tone 730 Hz 12. Signal tone Continuous tone 830 Hz 13. Signal tone Continuous tone 970 Hz 14. Signal tone Signal tone according to DIN 33404-3 Page 19
NÕUDED ALARMISEADMETELE EELNEVALT TULEB MÕÕTA MÜRATASET PAIGALDUSKOHAS. ALRMSEADME HELITUHEVUS PEAB OLEMA VÄHEMALT 65 db JA KKÕIGIS RUUMI PUNKTIDES PEAB HELITUGEVUS OLEMA VÄHEMALT10dB KÕRGEM TAUSTAST TULEB MÕÕTA KA ALARMSEADME HELITUGEVUST PAIGALDUSKOHAS ALARMSIGNAAL PEAB OLEMA SELGELT TAUSTAST ERISTATAV 39 HELIRÕHU MUUTUS EEMALDUMISEL 92dB 1m 72dB 10m ~ -20dB ALARMSEADME POOLT TEKITATAV HELIRÕHK ON ANTUD 1 M KAUGUSEL SEADMEST KAUGUSE SUURENEMISEL 2 KORDA VÄHENEB HELIRÕHK 6 db (freefield measurement). 40 Page 20