ECS Pre-Engineered Nitrogen Generator. ECS Pre-Engineered Wall Mount Nitrogen Generator PGEN-3/(PGEN-3E) PGEN-5/(PGEN-5E)

Similar documents
ECS Pre-Engineered Nitrogen Generator. ECS Pre-Engineered Wall Mount Nitrogen Generator PGEN-10/(PGEN-10E)

ECS Protector Nitrogen Generator. ECS Protector Nitrogen Generator PGEN-30. Specifications

ECS Protector Nitrogen Generator PGEN-40FK/PGEN-50FK/PGEN-60FK PGEN-40M/PGEN-50M/PGEN-60M

STEP 1: SELECT A NITROGEN GENERATOR STEP 2: SELECT A VENT STEP 3: SELECT MONITORING EQUIPMENT STEP 4: CONTACT ECS

ECS Protector Dry SMART Vent - PSV-D (PSV-DE) Specifications

ECS Protector Dry SMART Vent - PSV-D (PSV-DE) Specifications

NITROGEN-GENERATING SPRINKLER CORROSION INHIBITING SYSTEM

VIZOR Electronic Dry Pipe Accelerator (EDPA) Quick-Opening Device for Dry Pipe Systems General Description

FIRE-PAC SERIES 745 FIRELOCK SYSTEMS

TotalPac X Single interlock SUREFIRE system

Comprehensive corrosion solutions backed by over 115 years of fire sprinkler monitoring. POTTER CORROSION SOLUTIONS

Corrosion in Fire Sprinkler Systems Increasing Your Liability, Increasing Your Costs, and Shortening System Life

N2 BLAST Datasheet Preaction double interlock, Electric/Pneumatic c/w N 2 Blast Nitrogen generating system Self contained unit

TotalPac X Firecycle III Preaction Double interlock system

N2 BLAST Datasheet SUREFIRE double interlock c/w N 2 Blast Nitrogen generating system Self contained unit

N2 BLAST Datasheet Preaction double interlock, Electric/Pneulectric c/w N 2 Blast Nitrogen generating system Self contained unit

Model DV-5 Red-E Cabinet 1-1/2 thru 8 Inch (DN40 thru DN200), 250 psi (17,2 bar) Integrated Preaction Fire Protection Package General Description

POTTER CORROSION SOLUTIONS

FM-200 In-Cabinet Series

EXAMPLES OF HOW TO ORDER

Titus Air Systems. TDD Series. The need for clean and dry compressed air. Energy efficiency

TECHNICAL DATA OBSOLETE

EXAMPLES OF HOW TO ORDER

TECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC RELEASE

TOTALPAC2 Integrated Fire Protection System

DF-340E PROCESS ANALYZERS APPLICATIONS FEATURES

Technical Data. Approvals The 1-1/2 in. to 8 in. (DN40 to DN200) DV-5 Red-E Cabinets are UL Listed and C-UL Listed with the following system types:

Technical Data. Approvals The 1-1/2 thru 8 inch (DN40 thru DN200) DV-5 Red-E Cabinets are UL Listed and C-UL Listed with the following system types:

TECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEUMATIC RELEASE 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3.

PHYSICAL FACILITIES. 1 General. 2 Related Requirements. 5 Quality Assurance. 3 Wiring. 4 Submittals

Installation, Operation, and Maintenance Manual Balston Model 76-01, 76-02, 76-10, and Membrane Air Dryers

Worldwide Contacts.

TECHNICAL DATA. 319a. January 27, 2012

TECHNICAL DATA. model c-2

TECHNICAL DATA OBSOLETE

A. NFPA 2001 Standard for Clean Agent Fire Extinguishing Systems 2004 edition.

CONSTRUCTION REQUIREMENTS

Heatless Desiccant Compressed Air Dryers

Laboratory Enclosed Rotary Screw Air Compressor System with Air Treatment Center Package

Datasheet. Vacuum Double-interlock Preaction System, Electric Release Self contained unit. Features. FIREFLEX VACTEC description

White Paper. Monitoring Corrosion in Water Based Fire Sprinkler Systems (July 2013) By Jeffrey Kochelek V.1.0.0

Corrosion Dry Air Pak

GASS Module. User Manual. Gas Analysis Sampling System PERMA PURE

MX 200. MX-200 Technical Specifications FEATURES:

Compressed Air. Filtration. Balston Membrane Nitrogen Generators. 157 Parker Hannifin Corporation

Becoming an Expert on Dry-pipe, Preaction, and Deluge Sprinkler Systems

DV-5 Red-E Cabinet Integrated Deluge Fire Protection Package. General Description. Technical Data. Page 1 of 6 AUGUST 2018 TFP1300. Worldwide Contacts

Technical Data. Working Pressure Range 20 to 250 psi (1,4 to 17,2 bar)

Model DV-5 Red-E Cabinet 1-1/2 thru 8 Inch (DN40 thru DN200), 250 psi (17,2 bar) Integrated Deluge Fire Protection Package General Description

Datasheet. Dry-pipe Vacuum Sprinkler System, Electric Release Self contained unit. Features. FIREFLEX VACTEC description

DRY-PAK INDUSTRIAL AIR DRYER Installation and Instruction Manual

TCR. Features: TISSUE CULTURE

Waveguide Dehydrators

TECHNICAL DATA. Factory Mutual Approval is pending for the system as a whole.

TCC-34. Features: TISSUE CULTURE

TECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEU-LECTRIC RELEASE

SECTION COMPRESSED AIR SYSTEM. A. Pipe and pipe fittings, including valves, unions and couplings.

SPECIFICATION: ECS SERIES CLEAN AGENT FIRE SUPPRESSION SYSTEM

TRI-PLATE B INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS PART NO EFFECTIVE MARCH 1, 1983 REPRINT APRIL 16, 1999

SECTION AIR COMPRESSORS AND ACCESSORIES

LABORATORY ULTRA ZERO AIR GENERATOR. ZAC-ULT Series USER MANUAL

Laboratory Open Scroll Air Compressor System with Premium NFPA Controls

PMT200A SERIES DEHYDRATOR USER MANUAL. Bulletin AE01B-A NOV 05

Model DDX Deluge Valve

Dry Air Pac ENGINEERED COMPRESSED AIR DRYING SYSTEMS FOR COLD STORAGE/ FREEZER ROOM DRY PIPE SPRINKLER SYSTEMS

MX 200. MX-200 Technical Specifications FEATURES:

TPR. Features: TALL PLANT

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

MANUFACTURED with high-quality components and innovative techniques. DESIGNED for economical, trouble-free performance and long-life reliability

PORTABLE DEW POINT MONITOR

Laboratory Open Scroll Air Compressor System with Premium NFPA Controls Rev. 06/27/14

FLEXIBLE, AFFORDABLE, HIGH SPECIFICATION OXYGEN GAS ANALYSIS DESIGNED FOR DEMANDING HAZARDOUS AREA PROCESS CONTROL APPLICATIONS.

Refrigerated Air Dryers

MST, INC. MODEL 2002 CARBON MONOXIDE MONITOR OWNER S MANUAL

SPECIFICATION: Kidde Engineered Fire Suppression System Designed for use with 3M Novec 1230 Fire Protection

Reciprocating Simplex and Duplex Tank Mount Compressor Systems Rev. 08/23/12


MST, INC. MODEL 2002 OXYGEN MONITOR (AMBIENT-TYPE) OWNER S MANUAL

ENGINEERING SPECIFICATIONS FOR FM-200 CLEAN AGENT INDIRECT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS

UltraDry s Features and Benefits

150-3,000 scfm AEHD Series. Desiccant Air Dryers AEHD Series. Externally Heated Desiccant Air Dryer 150-3,000 scfm. Front Page

TECHNICAL DATA 1. SYSTEM DESCRIPTION 2. SYSTEM OPERATION 3. INSTALLATION. Page 1 of 5

Desiccant Drying DRYPOINT XC. efficient low dew point heatless desiccant drying. Truth in Compressed Air.

MODEL A-316 CARBON MONOXIDE (CO) MONITOR AND ALARM FOR COMPRESSED AIR TESTING

User Manual / Care Instructions

DISHWASHER INSTALLATION INSTRUCTIONS

Chargebuster Ion Gun Installation, Operation and Maintenance

Centro-Matic Automated Lubrication Systems System Controls

TotalPac 3 Firecyle III Deluge Remote controlled system

USER GUIDE. Dental Compressed Air System. Installation and Maintenance Manual For 1000 CM Series with C1 Control

FireFlex DUAL Double Interlock, Self-contained system

PROdry. High Inlet. Temperature. refrigerated. compressed air. dryers. Contents. For Sales & Service please contact:

AMENDMENTS TO THE BUILDING AND FIRE CODE FOR THE CITY AND COUNTY OF DENVER

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVO-200 INDIRECT FIRED SPACE HEATERS

DIVISION 21 FIRE SUPPRESSION SECTION FIRE PROTECTION SPECIALTIES

INGERSOLLrAND AIR COMPRESSORS CAUTION: HMD SERIES AIR DRYERS MODELS 18 THROUGH 385 OPERATORS/ INSTRUCTION MANUAL REPLACEMENT PARTS

vsource GAS SOURCE SYSTEMS

ENSPECO Recovery/ Recycle/ Evacuate/ Recharge

INSTALLATION INSTRUCTIONS

OPEN SPRINKLER SYSTEM

Transcription:

ECS Pre-Engineered Wall Mount PGEN-3/(PGEN-3E) PGEN-5/(PGEN-5E) Specifications For use under U.S. Patents 8,720,591, 9,144,700 and 9,186,533 Cabinet Dimensions: Weight Temperature Range: Power Supply: Power Consumption: 24.5 (W) X 36.5 (H) X 9.25 (D) (622mm (W) X 927mm (H) X 235mm (D)) 125 lbs (57kg) 40 F - 105 F (5 C - 40 C) 120v/1 phase/60hz (dedicated circuit) (230v/1 phase/50hz (dedicated circuit)) 6 Amps Nitrogen/air connection: ½ NPT Female Drain connection: ¼ NPT Female FM Approved UL 508A Listed Industrial Control Panel Ordering Information Stock Number: Replacement Filters: Replacement Membrane: PGEN-3(E)/PGEN-5(E) PGEN-FKW (annual maintenance) PGEN-MW (20 year expected service life) General Description The ECS Pre-Engineered Wall Mount Nitrogen Generators are designed for use in facilitating the Dry Pipe Nitrogen Inerting (DPNI) process for controlling oxygen corrosion in dry and preaction fire sprinkler systems. The ECS s are designed for plug and play performance in a typical dry or preaction fire sprinkler system. The ECS Pre-Engineered s can be used to provide DPNI for single or multiple zones depending on the number of systems, the volume of the largest system and the cumulative volume of all systems being supplied. The ECS s are designed to nitrogen inert all of the zones being served within 14 days. Thereafter, the ECS s continue to automatically provide supervisory nitrogen gas sufficient for pressure maintenance of the fire sprinkler system(s). The ECS s facilitate the patented fill and purge breathing process in the fire sprinkler system when paired with a venting device installed on the sprinkler riser such as the ECS Protector Manual Vent (PAV-D) or the ECS Protector Dry SMART Vent (PSV-D/DE). ECS Pre-Engineered PGEN-3/(3E)/PGEN-5/(5E) 1

The ECS Pre-Engineered is a self-contained wall mounted unit that includes the following components: Steel enclosure cabinet with membrane type nitrogen generator (no nitrogen gas storage) and manual bypass Power supply - 120v/1 phase/60hz (230v/1 phase/50hz) Single point nitrogen/air discharge ½ NPT Oil less air compressor Hour Run Meter Cycle Counter The ECS includes the following function Indications: Bypass Alarm - Nitrogen generator is in the By-Pass mode (Flashing Indicator) Leak Monitoring - Nitrogen generator running excessively (Audible Signal) Operating Performance Model Number Min. Supply Air (SCFM) Total System Capacity (Gallons) The ECS includes the following monitoring outputs: System Power (Digital Output) Bypass Mode Alarm (Digital Output) Nitrogen Generation Mode (Digital Output) Nitrogen Supply Line Pressure (Analog Output) Leak Monitoring (Digital Output) The ECS is designed to be used in conjunction with the following components as part of the complete ECS Dry Pipe Nitrogen Inerting (DPNI) system: Air maintenance device with on board adjustable regulator (recommend Victaulic Series 757, Tyco Model AMD 1 or Reliable Model A-2) Riser-mounted ECS Protector Manual Vent (PAV-D) or ECS Protector Dry SMART Vent (PSV-D/DE) ECS Protector SMART Gas Analyzer (SGA-1/1E) one per nitrogen generator is recommended ECS In-Line Corrosion Detector (ILD-X) monitoring at least one system is recommended Single System Capacity @ 40 psig (Gallons) Single System Capacity @ 20 psig (Gallons) Sound Level dba @ 10 PGEN-3 2.5 675 215 540 56 PGEN-5 3.3 950 265 590 57 Model Number Min. Supply Air (L/min) Total System Capacity (Liters) Single System Capacity @ 2.8 bar (Liters) Single System Capacity @ 1.4 bar (Liters) Sound Level dba @ 3m PGEN-3E 71 2,555 814 2,044 56 PGEN-5E 94 3,596 1,003 2,233 57 Capacity based on NFPA 13 30-minute fill requirement of largest single system Nitrogen Quality N 2 Purity at Discharge: 98% or greater (maximum of 2.0% oxygen) N 2 Pressure at Discharge: Min of 15 psig (1 bar); Max of feed air pressure minus 15 psig (1 bar) N 2 Water Dew Point: Typically less than 70ºF ( 57ºC) Note: When connecting an ECS Protector to an existing dry pipe/preaction fire sprinkler system, the existing fire sprinkler system(s) must be limited to a maximum leak rate of less than 3 psig (2 bar) within a 24 hour period, per system. ECS Pre-Engineered PGEN-3(3E)/PGEN-5(5E) 2

Installation Instructions Installation of the ECS requires five (5) steps: Step 1: Step 2: 1. Mount the cabinet on the wall in the appropriate location within the riser room 2. Bring the dedicated power supply lines to the NEMA4 power supply box in the cabinet 3. Plumb the nitrogen/air supply line to the trim work on the dry or preaction zones being served 4. Plumb the drain line to floor drain or building exterior 5. Connect Nitrogen generator output signals to BMS or fire alarm system, where applicable Mounting the Wall Mounted The ECS is designed to be mounted directly to the wall at the installation location. Several factors should be considered in choosing the proper mounting location for the nitrogen generator: Access to the power supply (dedicated circuit as per above) Access to the sprinkler riser being supplied from the nitrogen generator Clearance at the front of the unit to open the cabinet door Ability to support cabinet weight at mounting location - 125 lbs (57kg) The nitrogen generator cabinet assembly includes a mounting rail for wall mounting using standard anchors. Power Supply The requires a dedicated power supply line that ties into a single point in the generator cabinet. 120v/1 Phase 60 Hz Connections (230/1 Phase 50 Hz Connections) L1 N G Step 3: Plumb the Nitrogen/Air Supply Line The nitrogen/air discharge plumbing from the is to be connected directly to the dry or preaction valve trim work as per standard fire sprinkler compressed air supply lines using ½ black steel, galvanized steel or copper piping. The requires an in-line Air Maintenance Device (AMD) that is equipped with an on board field adjustable pressure regulator for each zone being served. The preferred AMD is the Victaulic Series 757. ECS Pre-Engineered PGEN-3(3E)/PGEN-5(5E) 3

Note: Step 4: Step 5: When both dry pipe and preaction fire sprinkler systems are connected to one nitrogen generator, additional equipment may be required if the fire sprinkler systems operate at different supervisory gas pressures. Plumb the Condensate Drain Line The ECS Protector will occasionally discharge a small amount of condensate water from the coalescing filters inside the cabinet. It is recommended that the 1/4 drain connection be plumbed to a floor drain or building exterior. When plumbing to a drain is not feasible an evaporative collection chamber can be used. System Signals and Monitoring, where used The nitrogen generator cabinet has two (2) system signals and five (5) outputs that can be monitored by the facility s BMS or fire alarm system. The nitrogen generator is operating in the bypass mode which is activated when the bypass valve is in the fast fill position to fast fill the fire sprinkler system and the air supplied directly from the air compressor has reached a pressure of 20 psig (1.4 bar). (Flashing amber light) The nitrogen generator is equipped with a leak monitor audible signal which is activated when the nitrogen generator runs excessively. (Audible signal) The nitrogen generator cabinet includes system monitoring signals which can be monitored through a building monitoring system, if desired: Loss of Power (Form C contacts) Bypass Mode Alarm (Form C contacts) Nitrogen Generation Mode (Form C contacts) Nitrogen System Supply Line Pressure (Analog Signal) Leak Monitoring (Form C contacts) Nitrogen Generation Monitoring Output By-Pass Alarm Monitoring Output Power Monitoring Output Leak Monitoring Output ECS Pre-Engineered PGEN-3(3E)/PGEN-5(5E) 4

ECS PRE-ENGINEERED NITROGEN GENERATION SYSTEM (typical installation schematic) Maintenance of the The nitrogen generator cabinet contains two (2) separate cartridge filters. It is recommended that each of the filter cartridges be replaced as part of an annual preventative maintenance program. In some environments it may be necessary to replace filters more frequently. The filter replacement kit for the nitrogen generator is part number PGEN-FKW. When maintained properly the nitrogen separation membrane will provide up to 20 years of service life. The membrane replacement part number is PGEN-MW. Cartridge Filter Exchange Procedure Preliminary Steps (taking the nitrogen generator out of service) 1. Turn the power supply to the unit off 2. Close the regulated and fast fill valves on fire sprinkler system s air maintenance device(s) 3. Turn the bypass valve in the nitrogen generator to the fast fill position 4. The is designed to depressurize the inlet piping through the permeate of the nitrogen separation membrane when the nitrogen generator automatically shuts off ECS Pre-Engineered PGEN-3(3E)/PGEN-5(5E) 5

Coalescing Filter Cartridge Exchange Procedure The two filters with the condensate drain tube extending from the bottom of the filter housing are coalescing filters. To replace the filter cartridges follow Step 1 through Step 6. Filter Cartridge Clear Drain Tube Step 1: Step 2: Step 3: Grasp the ¼ clear drain tube on the bottom of the filter housing with the right hand. With the left hand, push upward on the grey retaining ring on the filter housing outlet fitting. This motion will allow for the ¼ clear drain tube to be removed from the fitting. Gently pull the ¼ clear drain tube downward out of the fitting and let it hang. Once the ¼ clear drain tube has been disconnected, the filter housing bowl may be unscrewed from the top portion of the filter housing which is connected to the internal system piping. Once the filter housing bowl has been removed, the filter cartridge inside is removed by first unscrewing the black retaining disc at the base of the cartridge and then pulling down on the cartridge. Discard the old filter cartridge and replace it with the appropriately marked filter cartridge from the maintenance kit by pushing up so that it fits snugly onto the receiving stepped cylinder in the upper part of the filter housing. Screw the black retaining disc back onto the central metal threaded rod. Important: HAND TIGHTEN ONLY! ECS Pre-Engineered PGEN-3(3E)/PGEN-5(5E) 6

Step 4: Step 5: Step 6: Step 7: Replace the filter housing bowl by screwing it onto the filter housing top. Important: HAND TIGHTEN ONLY! Reconnect the ¼ clear drain tube into the fitting on the filter housing bowl. Make sure that it fully seats in the fitting and is retained snugly. Repeat Step 1 through Step 5 for the remaining coalescing filter. The can now be placed back into service. Filter Cartridge Black Disc Return the to Service 1. Turn the power supply to the unit on 2. Open the regulated valve on fire sprinkler system s air maintenance device(s) ECS Protector Optional Monitoring Equipment ECS Protector Handheld Gas Analyzer (PHGA-1): portable handheld gas analyzer includes one-button calibration and enables user to measure nitrogen concentration at nitrogen generator cabinet or gas sampling ports on ECS venting devices ECS Protector SMART Gas Analyzer (SGA-1/1E): permanently installed near an ECS Protector Manual/SMART Vent to continuously report nitrogen gas concentration to a building information or management system; includes digital display and provides 0-5V DC or 4-20mA output signals ECS In-Line Corrosion Detector (ILD-X): installed in-line within the fire sprinkler system piping at locations most susceptible to corrosion; provides either a local push-button test/indicator or control panel monitoring ECS Pre-Engineered PGEN-3(3E)/PGEN-5(5E) 7

8