Logamax plus. Notice! This manual is available in the English and French language. This manual must be retained for future reference.

Similar documents
Service Instructions. Logamax plus GB kw/100 kw. Condensing gas boiler. For the contractor

Installation instructions

Installation instructions Logamax plus. GB162-L.B. 80 kw GB162-L.B. 100 kw. Read carefully before carrying out installation and maintenance.

/2010 US/CA

EDVRSPV47 EDVRSPV58. Warning: What to do if you smell gas

VSL II QUICK START GUIDE

VSL II QUICK START GUIDE

Operating instructions

Models UBSSC-050 UBSSC-075 UBSSC-100 UBSSC-150 UBSSC-200 UBSSC-299 WALL MOUNTED GAS BOILER INSTALLATION, OPERATION & MAINTENANCE MANUAL

WALL MOUNTED GAS BOILER. INSTALLATION, OPERATION & MAINTENANCE MANUAL Models SSV-050 SSV-075 SSV-100 SSV-150 SSV-200

USER S INFORMATION MANUAL

LGB Gas fired boiler

CONDENSING GAS FIRED BOILER INSTALLATION, OPERATION & MAINTENANCE MANUAL

User s Information Manual

CYLINDER NOT INCLUDED

User s Information Manual Models:

Conversion Instructions Logano G234X. Gas boiler. Please read carefully before installing and servicing. Gas boiler

CONDENSING GAS FIRED FLOOR OR WALL MOUNTED BOILER INSTALLATION, OPERATION & MAINTENANCE MANUAL Model DMG-380

INSTALLATION INSTRUCTIONS

Back to back. Cascade Venting System for RTG 199HE. Basic Set for units 1 and Installation instructions

Models CHB/CCB APPLICATION GUIDE WALL MOUNTED GAS BOILER

Side by side. Cascade Venting System for RTG 199HE. Extension Set for units 3 or Installation instructions

Installation Manual REVOLUTION WATER HEATER. Model VRP-150 VRP-199 VRS-150 VRS-199

Installation Instructions T 9822 Gas Dryer. en - US, CA. To prevent accidents

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVN/P-400 INDIRECT FIRED SPACE HEATERS

SAFETY INFORMATION SAFETY WARNINGS

User s Information Manual Models: 45, ,000 Btu/hr

TO DO IF YOU SMELL GAS

Installation Manual REVOLUTION CONDENSING COMBI-BOILERS. For Your Safety

INSTALLATION INSTRUCTIONS

Installing, Operating & Maintaining MUNCHKIN HIGH EFFICIENCY HEATER with the 925 Controller

HIGH-EFFICIENCY UPFLOW FURNACE INSTALLER'S INFORMATION MANUAL

User s Information Manual

Installation Instructions for use by heating contractor. Vitodens Common Venting System IMPORTANT

Universal Fire Tube Boiler Wall Mount Models

Vent Supplement Ultra-80, -105, -155, -230 & -310

RTG 199 HE INDOOR MODEL. RTG 199 HEN - Natural Gas RTG 199 HEX - Propane (LP Gas) Installation and Operation instructions

Installation and Service Instructions Logano G234X

PVC, CPVC, PP & SS Vent Supplement

USER'S INFORMATION MANUAL

UTICA BOILER. SSV Submittal. Project Name: Project Location: Contractor:

Operating Instructions

NTI TRINITY Ti INSTALLATION AND OPERATION INSTRUCTIONS Ti Boilers and Ti Combi Models VERSION DATE:

UCS 240 CONDENSING GAS FIRED BOILER

GAS COOKTOP INSTALLATION INSTRUCTIONS BEFORE YOU BEGIN. IMPORTANT Save these instructions for local electrical inspector s use.

User s Information Manual

Gas Fired Residential Combi Boiler Floor and Wall Mount Models

User s Information Manual Models:

USER S INFORMATION MANUAL

Residential Gas Condensing Boiler Greenstar ZBR16/21/28/35/42-3A... ZWB28/35/42-3A...

EVO DUO/EVO MICRO HIGH EFFICIENCY WATER HEATERS AND HEATING BOILERS

Installing, Operating & Maintaining MUNCHKIN HIGH EFFICIENCY 399M COMMERCIAL BOILER

USER S INFORMATION MANUAL Model: HSE 125 N/P, HSE 145 N/P Gas-fired, Condensing Boiler and Instantaneous Water Heater

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVN/P-400 INDIRECT FIRED SPACE HEATERS

Columbia Boiler Company

Trinity Lx Model Numbers: Lx Version Date:

Installing, Operating & Maintaining MUNCHKIN VWH HIGH EFFICIENCY HOT WATER SUPPLY BOILER

GB Condensing Gas Boiler

HYBRID WATER HEATER Installation Manual

Installing, Operating & Maintaining MUNCHKIN HIGH EFFICIENCY HEATER with the 925 Controller

C 1050 ES - Natural Gas C 1050 ES - Liquefied Petroleum (LP) Gas

Installing, Operating & Maintaining EVO HIGH EFFICIENCY WATER HEATERS AND HEATING BOILERS

C1050ES Tankless Water Heater

USER'S INFORMATION MANUAL

PRESTIGE Solo. Installation & Maintenance Manual

Installation & Operation Manual Models:

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL FOR CONDENSING GAS STORAGE WATER HEATER BASE MODEL PRIME

High Effi ciency Condensing Stainless Steel Gas Hot Water Supply Boiler Models IEW-199, IEW-399 Installation and operation instructions

Installation and Service Instructions LoganoUS/CA GC 144 II

Aqua Balance. User s Information Manual. WMB-155C Wall Mount Gas-Fired Combination Boiler Heating and Domestic Hot Water

INSTALLATION AND OPERATION MANUAL GAS SKILLETS MODELS: GTS-30 GTS-40

Trinity Lx - WH Model Numbers: Lx200WH - Lx800WH Version Date:

Installation and maintenance instructions

OPERATING INSTRUCTIONS AND OWNER S MANUAL

cod. Doc rev. 3 11/2016 Array AR AR 4000 US INSTALLATION AND OPERATION MANUAL

Trinity Lx Model Numbers: Lx Version Date:

Trinity Tft Model Numbers: Tft Version Date:

INSTALLATION INSTRUCTIONS

Installation and maintenance instructions

cod. Doc rev. 2 07/2016 Array AR AR AR 2000 US INSTALLATION AND OPERATION MANUAL

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVN/P-400 INDIRECT FIRED SPACE HEATERS

User s Information Manual

HIGH EFFICIENCY FIRE TUBE CONDENSING GAS BOILER MODELS CHS-85 through CHS-399

C1210ES Tankless Water Heater

Tankless Water Heater

GB Condensing Gas Boiler

Installing, Operating & Maintaining MUNCHKIN HIGH EFFICIENCY HEATER with the 925 Controller

C 950 / 1050 ES C 950 / 1050 ES - Natural Gas / C 950 / 1050 ES - Liquefied Petroleum (LP) Gas

TL-Pro 175C/199C INDOOR MODEL. TL-Pro 175/199 C - Natural Gas TL-Pro 175/199 C- Propane (LP Gas) Installation and Operation instructions

User s Information Manual

Installation Instructions

710 / 710 ASME (T-M32/ T-M32 ASME) On-Demand Water Heater Installation Manual and Owner s Guide

USER S INFORMATION MANUAL

Common Vent System. Common Vent System

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVN/P-400 INDIRECT FIRED SPACE HEATERS

USER S INFORMATION MANUAL

NAVIEN AMERICA INC FITCH AVENUE IRVINE, CALIFORNIA, USA

Residential Gas Condensing Boiler Greenstar combi 100 p / 151 p ZWB28-3A... ZWB42-3A...

Model BW9 Gas-Fired Direct Vent Condensing Water Boiler

USER'S INFORMATION MANUAL

Transcription:

Installation instructions Condensing gas boiler Logamax plus GB- GB-0 GB- GB-60 CAUTION! Before putting the boiler into operation read this manual carefully. DANGER! Improper installation, adjustment, alteration, service or maintenance can cause injury, loss of life or property damage. Refer to this manual. For assistance or additional information consult a qualified installer, service agency or the gas supplier. CAUTION! The operating manual is part of the documentation that is delivered to the installation's operator. Go through the information in this manual with the owner/operator and make sure that he or she is familiar with all the necessary operating instructions. 67069-0.0N Danger: If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life. Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. What to do if you smell gas: Do not try to light any boiler. Do not touch any electrical switch; do not use any phone in your building. Immediately call your gas supplier from a neighbor s phone. Follow the gas supplier s instructions. If you cannot reach your gas supplier, call the fire department. Installation and service must be performed by a qualified installer, service agency or the gas supplier. Notice! This manual is available in the English and French language. This manual must be retained for future reference. 670800 (07/0) US/CA Read carefully before carrying out installation and maintenance.

About these instructions About these instructions These Installation Instructions contain important information for the safe and professional installation, start-up and maintenance of the boiler with boiler capacities, 0, and 60 kw. These Installation Instructions are intended for professional installers, who have the necessary training and experience for working on heating and gas systems. Subject to technical changes Slight changes may be made to the illustrations, process steps and technical data as a result of our policy of continuous improvement. Updating of documentation Please contact us if you have any suggestions for improvements or corrections. Table of contents Safety and general instructions.......................... Designated use.................................. Hazard definitions................................ The following instructions must be observed.......... Observe these instructions for space heating water..... Tools, materials and additional equipment............6 Disposal....................................... Regulations and guidelines............................. Product description................................... Dimensions and connections............................ 7 Packaging and transportation........................... 9. Scope of delivery................................ 9 6 Installation........................................... 9 6. Requirements for the installation room.............. 9 6. Fitting the boiler................................ 9 6. Making the gas connection...................... 0 6. Fitting the heating circuit supply and return pipes... 0 6. Combustion Air and Ventilation Openings.......... 6.6 Installation of the flue gas adapter (included in the scope of delivery).............................. 6.7 Installation of the Exhaust and Air Intake system.... 6.8 Conversion to Propane......................... 8 7 Electrical connections............................... 8 7. External connection board connections........... 8 8 Start-up procedure.................................. 8. Testing for gas leaks........................... 8. Filling the boiler............................... 8. Filling the condensate trap...................... 8. Bleeding the gas supply valve.................... 8. Checking the combustion air/flue gas connection... 8.6 Checking the orifices........................... 8.7 Inlet gas pressure............................. 8.8 Checking and adjusting the gas/air ratio........... 8.9 Carrying out a leak test in operating conditions..... 8.0 Measuring the carbon monoxide content (CO)...... 8. Function testing............................... 8. Measuring the ionization current.................. 8. Testing the Ignition Safety shut off device.......... 8. Installing the casing............................ 8. Informing the owner, handing over the technical documents................................... 9 BC0 basic controller................................. 9. Operating the BC0 basic controller............... 9.. Switching the heating system on and off............ 6 9.. Displaying the operating conditions of the burner and resetting the burner or resetting burner faults... 6 9.. Displaying the heating system status and/or faults... 6 9. Carrying out additional tasks..................... 7 9.. Carrying out a flue gas test....................... 7 9.. Selecting partial load operation (e. g. during flue gas testing)................................... 7 9.. Switching the heating system to manual mode....... 7 9. Configuring the boiler........................... 7 9.. Adjusting the heating capacity.................... 7 9.. Setting the DHW temperature value............... 8 9.. Entering the space heating water temperature....... 8 9.. Setting the pump post-purge period............... 8 0 Shutting down the system............................. 8 0. Shut down the heating system using the control unit.. 8 0. Shutting down the heating system in the event of an emergency................................. 8 Inspection.......................................... 9. Preparing the boiler for inspection................ 9. Visual inspection for general signs of corrosion...... 9. Internal leak testing............................ 9. Measuring the ionization current.................. 9. Measuring the inlet gas pressure.................. 9.6 Checking and adjusting the gas/air ratio............ 9.7 Carrying out a gas leak test in operating conditions... 9.8 Measuring the carbon monoxide content (CO)....... 9.9 Carrying out a pressure test of the heating system.... 9.0 Checking the functioning and the safety of the air intake and flue gas conduit.................... 9. Checking venting systems....................... 9 Maintenance........................................ 9. Cleaning the heat exchanger, burner and condensate trap............................... 9. Checking and adjusting the gas/air-ratio............ Appendix............................................ Operating messages............................. Error messages................................. Technical specifications......................... Reports.............................................. Start-up report................................. Inspection report............................... Maintenance report............................ Spare parts.......................................... 6 Logamax plus GB-/0//60 670800 (07/0)

Safety and general instructions Safety and general instructions Please observe these instructions in the interest of your own safety.. Designated use The boiler was designed for heating water for a central heating system and generating domestic hot water. The boiler is delivered with a BC0 basic controller and the Universal Automatic Burner Control Unit (UBA ) pre-installed. The boiler can be fitted with a modulating outdoor reset control AM0 (scope of delivery), a room controller RC0 (optional), or an On/Off thermostat or relay panel end switch (accessories).. Hazard definitions The following defined terms are used throughout the documentation to bring attention to the presence of hazards of various risk levels. Notices give important information concerning the operation of the product. DANGER: Indicates the presence of hazards that will cause severe personal injury, death or substantial property damage. WARNING: Indicates the presence of hazards that can cause severe personal injury, death or substantial property damage. CAUTION: Indicates presence of hazards that will or cause minor personal injury or property damage. CAUTION: Risk of electrical shock Indicates presence of hazards due to electric shock. Indicates special instructions on installation, operation or maintenance that are important but not related to personal injury or property damage.. The following instructions must be observed The boiler must only be used for its designated purpose, observing the Installation Instructions. Only use the boiler in the combinations and with the accessories and spares listed. Other combinations, accessories and consumables must only be used if they are specifically designed for the intended application and do not affect the system performance and the safety requirements. Maintenance and repairs must only be carried out by trained professionals. You must report the installation of a condensing gas boiler to the relevant gas utility company and have it approved. You are only allowed to operate the condensing gas boiler with the combustion air/flue gas system that has been specifically designed and approved for this type of boiler. Please note that local permission for the flue system and the condensate water connection to the public sewer system may be required. You must also observe: the local building regulations stipulating the installation rules. the local building regulations concerning the air intake and outlet systems and the chimney connection. the regulations for the power supply connection. the technical rules laid down by the gas utility company concerning the connection of the gas burner fitting to the local gas main. the instructions and standards concerning the safety equipment for the water/space heating system. the Installation Instructions for building heating systems. The boiler must be located in an area where leakage of the tank or connections will not result in damage to the area adjacent to the boiler or to lower floors of the structure. When such locations cannot be avoided, it is recommended that a suitable drain pan, adequately drained, be installed under the boiler. The pan must not restrict combustion air flow. The boiler must be installed such that the gas ignition system components are protected from water (dripping, spraying, rain etc.) during boiler operation and service. The boiler must not be installed on carpeting. Do not restrict or seal any air intake or outlet openings. If you find any defects, you must inform the owner of the system of the defect and the associated hazard in writing. Logamax plus GB-/0//60 670800 (07/0)

Regulations and guidelines DANGER: if flammable gas explodes. Beware if you smell gas: there may be an explosion hazard! Warning: If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury or death. Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other boiler. What to do if you smell gas: Do not try to light any boiler. Do not touch any electrical switch; do not use any phone in your building. Immediately call your gas supplier from a neighbor s phone. Follow the gas supplier s instructions. If you cannot reach your gas supplier, call the fire department. Installation and service must be performed by a qualified installer, service agency or the gas supplier.. Observe these instructions for space heating water Unsuitable heating system water can promote the formation of scale or sludge, which affects system efficiency. It can also cause corrosion and reduce life of the heat exchanger. You must follow Buderus guidelines for boiler water quality. Thoroughly flush the system prior to filling. Use of a Buderus approved boiler cleaner is recommended. Never use salt bedding exchangers to soften the water. Do not use inhibitors or other additives unless approved by Buderus for that purpose! When frost protection of the heating system is desired, only use Buderus-approved Aluminumsafe antifreeze. When using oxygen-permeable pipes, e. g. for floor heating systems, you must separate the system using heat exchangers. The maximum permissible flow rate of the GB- /0 this is GPM (gal./min.)(= l/min.), for the GB- is GPM (= 7 l/min.) and for the GB-60 is 0 GPM (= 76 l/min.).. Tools, materials and additional equipment For the installation and maintenance of the boiler you will need the standard tools for space heating, gas and water fitting. In addition, a handtruck with a fastening belt is useful..6 Disposal Dispose of the boiler packaging in an environmentally sound manner. Dispose of components of the heating system (e. g. boiler or control device), that must be replaced in an environmentally responsible manner. Regulations and guidelines The installation must conform to the requirements of the authority having jurisdiction or, in the absence of such requirements, to the latest edition of the National Fuel Gas Code, ANSI Z.. In Canada, installation must be in accordance with the requirements of CAN/CSA B9., Natural Gas and Propane Installation Code. Where required by the authority having jurisdiction, the installation must conform to the Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-. Install CO detectors per local regulations. Boiler requires yearly maintenance, see maintenance section see chapter Maintenance, page 9. Operating Limits of the boiler Max. boiler temperature: 0 F (0 C) Max. operating pressure: psi ( bar) The hot water distribution system must comply with all applicable codes and regulations. When replacing an existing boiler, it is important to check the condition of the entire hot water distribution system to ensure safe operation. Massachusetts Installations Only (a) For all side wall side horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied: INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gas fitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gas fitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (0) days to comply with the above requirements; provided, however, that during said thirty (0) day period, a battery operated carbon monoxide detector with an alarm shall be installed. Logamax plus GB-/0//60 670800 (07/0)

Product description APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NPA 70 and be ANSI/UL 0 listed and IAS certified. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. the sign shall read, in print size no less than one-half (½) inch in size, GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspections, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 8 CRM.08()(a) through. (b) EXEMPTIONS: The following equipment is exempt from 8 CRM.08()(a) through : The equipment listed in Chapter 0 entitled Equipment Not Required To Be Vented in the most correct edition of NFPA as adopted by the board: and Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes. (c) MANUFACTURES REQUIREMENTS - GAS EQUIPMENT VENTING SYTEM REQUIRED. When the manufacturer of Product Approved side wall horizontally mounted gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for the installation of the equipment and venting shall include: Detailed instructions for the installation of the venting system or the venting system components: and A complete parts list for the venting system design or venting system. (d) MANUFACTURES REQUIREMENTS - GAS EQUIPMENT VENTING SYTEM NOT PROVIDED. When the manufacturer of Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for the venting of flue gases, but identifies special venting systems, the following requirements shall be satisfied by the manufacturer: The referenced special venting systems shall be included with the appliance or equipment installation instructions: and The special venting systems shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions. (e) A copy of all instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or venting design instructions shall remain with the appliance or equipment at the completion of the installation. Product description 6 6 7 7 8 9 0 9 8 9 0 9 7 Fig. 6 6 Logamax plus GB-/0 (left) and GB-/60 (right) 7000-.TD [] Drawer with control unit [] Universal Burner Automat (UBA) [] Control unit BC0 [] Gas valve [] Cover [6] Flue measuring points [7] Parallel flue [8] Burner [9] Latches of which two have locks [0] Sighting glass [] Heat exchanger [] Back cover [] Air intake for the fan [] Fan [] Condensate trap and internal condensate drain flue gas pipe [6] External Connection Board (under the cover) [7] Pressure sensor Logamax plus GB-/0//60 670800 (07/0)

Product description 6 90 00 0 0 0 0 90 0 0 0 70 90 0 9 8 Fig. Basic Controller Logamatic BC0 [] Main switch [] DHW temperature knob ) [] LED DHW status [] Display [] Space heating water temperature knob [6] LED Heating system status [7] Under the cover a RC system controller can be installed [8] LED Burner Operation [9] Service Tool connector [0] Service e button [] Chimney sweep d button [] Reset c button [] Air intake for the fan 7 7000-.TD ) ECO mode means that the temperature inside the hot water tank is 0 F (60 C), with a hysteresis (ΔT) of 8 F (0 C) instead of 9 F ( C) 6 Logamax plus GB-/0//60 670800 (07/0)

Dimensions and connections Dimensions and connections 0" (00 mm) " (00 mm) 6." (8 mm)." (9 mm) " (60 mm)." ( mm)." (0 mm) A B " (00 mm) 0." (6 mm) 8" (7 mm)." (0 mm) 7." (90 mm) " (7 mm) C 6" (0 mm) D E F G.8" (6 mm) 8.7" (7 mm)." ( mm) " (7 mm) 6" (0 mm) 6" (0 mm) " (7 mm) > 6" (0 mm) > " (00 mm) 7000-.TD Fig. Dimensions and connections for boiler GB-/0 (dimensions in inches) [A] (AA) Flue gas connection (inside diameter ") [B] (LA) Air intake (inside diameter ") [C] (WB) Wall bracket [D] (GAS) diameter Gas connection, ¾" NPT [E] (AKO) Condensate water outlet, Ø." (Ø mm) outside [F] (VK) Supply, Ø.0" ) (Ø. mm) [G] (RK) Return, Ø.0" ) (Ø. mm) Observe the lateral minimum distances of the boiler (" = 00 mm) and the necessary distances (" = 600 mm) at the front and " (00 mm) at the top for removing the casing and for servicing. Closet clearances are: " (00 mm) to the right, " (00 mm) at the top and 6" (0 mm) to the left. ) One Ø.0" (Ø. mm) inside x " NPT threaded compression fitting is delivered enclosed with boiler packaging Logamax plus GB-/0//60 670800 (07/0) 7

Dimensions and connections 0" (00 mm) " (00 mm) " (00 mm) 6." (8 mm) 0." (6 mm)." (9 mm) 8" (7 mm)." (0 mm) 7." (90 mm)." (900 mm)." ( mm)." (0 mm) A B 9.7" (6 mm) C 6" (0 mm) D E F G.8" (6 mm) 8.7" (7 mm)." ( mm) " (7 mm) 0.7" (6 mm) " (7 mm) > 6" (0 mm) > " (00 mm) 7000-.TD Fig. [A] [B] [C] [D] [E] [F] [G] Dimensions and connections for boiler GB-/60 (dimensions in inches) (AA) Combustion air (LA) Air intake (WB) Wall bracket (GAS) Gas connection, ¾" NPT (AKO) Condensate water outlet, Ø." (Ø mm) (VK) Supply, Ø.0" ) (Ø. mm) (RK) Return, Ø.0" ) (Ø. mm) Observe the lateral minimum distances of the boiler (" = 00 mm) and the necessary distances (" = 600 mm) at the front and " (00 mm) at the top) for removing the casing and for servicing. Closet clearances are: " (00 mm) to the right, " (00 mm) at the top and 6" (0 mm) to the left. ) One Ø.0'' (Ø. mm) inside x '' NPT threaded compression fitting is delivered enclosed with boiler packaging 8 Logamax plus GB-/0//60 670800 (07/0)

Packaging and transportation Packaging and transportation. Scope of delivery The boiler is delivered fully assembled. When receiving the delivery, check if the packaging is intact. Check that all the items listed in fig. are included in the delivery. 9 8 7000-.TD Fig. Items supplied with unit ( box) [] Boiler with casing [] Wall bracket [] Technical documents including: User's Instructions ), Installation Instructions, wall mounting template and Servicing Instructions [] Compression fittings (x) [] GB Boiler manifold including: low loss header, pressure relief valve, tridicator, DHW connections, Grundfos -8 -speed boiler circulator, supply and return shutoff ball valves [6] AM0 with outdoor sensor [7] Propane conversion kit [8] Flue gas adapter [9] Boiler connection kit, including the DHW sensor 6 7 6 Installation 6. Requirements for the installation room DANGER: Install the heating system in a frost-free room. Do not store any flammable materials or liquids in the immediate vicinity of the boiler. Never use any chlorinated detergents or halogenated hydrocarbons (e. g. in spray cans, solvents and detergents, paints, adhesives). Do not allow too much dust to collect on the boiler. 6. Fitting the boiler Observe the installation clearances of the combustion air/flue gas system. To protect the connection orifice you must not remove the styrofoam bottom panel. Do not lift the boiler by the drawer. Do not remove the transport safety clamps ( fig. 6) from the drawer at this time. Protect the boiler and the combustion air/flue gas orifice against pollution during installation. Remove the packaging materials and dispose of them. Use the mounting template to mark the drill holes. Install the wall bracket taking into account the necessary service clearances. Remove the transport safety clamps ( fig. 6). 7000-6.TD Fig. 6 Removing the transport safety clamps Use the radiator key to unlock the two latches a quarter turn ( fig. 7, []). Open the latches ( fig. 7, []). Remove the casing by lifting it upwards and then pulling it forwards ( fig. 7, []); do not hold the casing by the latches....... ) The user s instructions (in a special format) is located in the boiler drawer Fig. 7 Removing the casing 7000-7.TD Logamax plus GB-/0//60 670800 (07/0) 9

6 Installation Hold the boiler by the rear boiler casing and place it on the wall bracket. Level out the boiler. 6. Making the gas connection DANGER: Only carry out work on gas lines if you are licensed for such work. Determine proper size gas pipe for the installation using table and table. Do not forget the pipe fitting losses and observe proper size of the fittings. Length of Gas Volume Capacity (ft / hr) ) pipe (feet) ¼" " ¼ " ½ " 0 78 0,060,600 0 90 0 70,00 0 8 90 890 0 0 00 760 0 0 670 7 9 7 60 00 79 60 0 80 0 6 0 0 80 Table Gas Pipe Capacity for different pipe sizes ) Maximum pipe capacity in ft/hr, based on a specific gravity of.60 ( mbar) and a inlet gas pressure of inches W.C. ( mbar) or less and a pressure drop of inches W.C. (0 mbar) Steel pipe diameter in inches Equivalent length for Pipe Fittings in feet Type of pipe fitting 90 -Elbow Tee (flow thru branch) Gate valve Gas cocks Equivalent length in feet ¾.. 0...6. 0.6.60 ¼. 6.9 0.8. ½.0 8.0 0.9.0 Table Equivalent length for pipe fittings in feet Install the ¾" gas cock on the gas connection. Connect the gas pipe to the gas cock ( fig. 8, []) so that it is free from any strain When installing the gas supply connection, it must comply with local regulations or, if such regulations do not exist, with the National Fuel Gas Code, ANSI Z.. In Canada, the gas supply connection must comply with local regulations or, if such regulations do not exist, with CAN/CSA B9., Natural Gas and Propane Installation Code. A sediment trap must be provided upstream of the gas controls. 6. Fitting the heating circuit supply and return pipes To protect the entire heating system we require installing a WYE strainer in the return circuit. When retrofitting the boiler to an existing heating system this filter is required. Install shut-off valves immediately before and after the dirt particle filter to allow the filter to be cleaned. Fit a filling and drain cock in the heating system supply pipe if required. Also fit an adequately sized safety valve in the system that meets all applicable codes and regulations. When using oxygen-permeable pipes, e. g. for radiant floor heating systems, you must separate the system using heat exchangers. Buderus recommends hydraulically isolating snowmelt systems using heat exchangers. Thoroughly flush all pipes and radiators. Use of a Buderus approved boiler cleaner is recommended. Refer to the installation template for the pipe connection dimensions. Fit the compression fittings ( fig. 9, [] and []) first to the Hydronic set ( fig. 0, and ) and then to the boiler. 0 6 9 8 7 Fig. 8 Making the gas connection 7000-8.TD Fig. 9 Pump manifold installation [] Compression fitting (heating system supply pipe) [] Compression fitting (heating system return pipe) 7000-9.TD 0 Logamax plus GB-/0//60 670800 (07/0)

Installation 6 [] Di electric union [] DHW return " FPT [] Low loss header [6] Tridicator [7] System return ½ MPT [8] System supply ½ MPT [9] Drain valve [0] DHW supply " FPT [] Relief valve Connect the expansion tank to the system. Connect the pipes so that they are free from strain. Connecting boiler with DHW tank Connect the external hot-water tank according to the Installation instructions of the hot-water tank and fittings concerned. Piping examples The following illustrations are two Installation examples. The following illustrations are simplified conceptual illustrations only. Piping and field components must be field verified. Fig. 0 is a schematic representation of fig. 9. DANGER: If this boiler is installed in a closed water supply system with an external indirect DHW tank, such as one having a backflow preventer in the cold water supply line, means shall be provided to control thermal expansion. Contact the water supplier or local plumbing inspector on how to control this situation. Relief valve The indirect DHW tank must have a temperature and pressure relief valve installed. The relief valve shall comply with the Standard for Relief Valves and Automatic Gas Shutoff Devices for Hot Water Supply Systems, ANSI Z.-CSA.. Install the relief valve according fig. 0. The relief valve must comply with following specifications: dimensions: height ¼ inch (7. mm), width inch (0.8 mm); 0 Psi ( bar) discharge pressure; discharge is ¾ inch (9. mm) female in diameter. WARNING: No valve is to be placed between the relief valve and the tank. Discharge of the relief valve must be conducted to a suitable place for disposal when relief occurs and no reducing coupling or other restriction may be installed in the discharge line. GB For the maximum permissible flow rate of the DHW pump see section., page. 0 9 8 7000-0.TD Fig. 0 Schematic representation of the boiler with the hydronic set [] Flue gas [] Air intake [] Pump manifold [] DHW return " FPT [] Low loss header [6] PT gauge (pressure and temperature gauge) [7] System return ½ MPT [8] System supply ½ MPT [9] Drain valve [0] Pump manifold shut-off valve [] DHW supply " FPT PT 6 7 6 0 Fig. GB Schematic representation of the boiler with the hydraulic set connected to an optional hot water tank with one or multiple zones including one pump and zone valves [] Flue gas [] Air intake [] Optional DHW tank [] Primary pump [] Shut-off valve [6] PT gauge (pressure and temperature gauge) [7] Zone valve PT Additional DHW Tank 6 7 8 9 7000-.TD Logamax plus GB-/0//60 670800 (07/0)

6 Installation [8] Radiant [9] Additional zones [0] Shut-off valve [] Zones [] Secondary pump [] Drain valve [] Low loss header [] DHW pump [6] Pressure relief valve 0 Fig. Primary boiler pump must have an internal check valve. GB Schematic representation of the boiler with the Hydronic set connected to an optional hot water tank with one or multiple zones and zone pumps [] Flue gas [] Air intake [] Optional DHW tank [] Primary pump [] Shut-off valve [6] PT gauge (pressure and temperature gauge) [7] Zone pump [8] Radiant [9] Additional zones [0] Shut-off valve [] Zones [] Drain valve [] Low loss header [] DHW pump [] Pressure relief valve Additional DHW Tank 7000-.TD Low Water Cut-Off (LWCO) and External Manual Reset High Limit A hot water boiler installed above radiation level or as required by the Authority having jurisdiction, must be provided with an external Low Water Cut-Off (LWCO) and/or an External Manual Reset High Limit device, either as a part of the boiler or at the time of boiler installation. Contractor to furnish and install LWCO and Manual Reset High Limit devices as required by local codes. Do not install any type of value or check valve in between boiler and LWCO or Manual Reset High Limit. PT 6 7 8 9 Refer to the manufacturer s instructions when installing LWCO and Manual Reset High Limit. LWCO is installed external to the boiler and must be located above the highest point of the boiler heat exchanger. Manual Reset High Limit remote sensing bulb must be located in the boiler supply. In a cascade each boiler must be equipped with its own LWCO and Manual Reset High Limit. Remove the plug and connect a " Tee at the back of the boiler manifold. Connect a " well for the Manual Rest High Limit probe [6] at the horizontal end. Install a " stand pipe that reaches above the highest point of the boiler heat exchanger at the vertical connector of the Tee. Install a second Tee with an automatic air vent [] at the top and a LWCO [] just below. Wire the LWCO [NC] and the Manual Reset High Limit [NC] normally closed dry contacts in series with EV pins and on the boiler, which will shut off the burner when the connection is interrupted. Fig. NC GRY RED LT. BLU FW EV DWV NC 6 Low Water Cut-Off views (Note: Power supply to LWCO and external high limit not shown for clarity.) [] Automatic air vent [] Low Water Cut-Off [] Manual Reset High Limit [] DHW Return [] DHW Supply [6] Manual Reset High Limit probe 7000-.TD Logamax plus GB-/0//60 670800 (07/0)

Installation 6 6. Combustion Air and Ventilation Openings Provisions for combustion and ventilation air must be made in accordance with section., Air for Combustion and Ventilation, of the National Flue Gas Code, ANSI Z., or Sections 7., 7. or 7. of CAN/CGA B9, Installation Codes, or applicable provisions of the local building codes. CAUTION: BOILER DAMAGE AND OPERATIONAL FAILURES! Due to insufficient or lacking openings for combustion air and/or ventilation of the boiler room. Provisions for combustion air and ventilation are always required, regardless whether the combustion air is taken from the outside (sealed combustion) or inside (non sealed combustion for combustion). Insufficient ventilation of the boiler room can lead to high air temperatures. This can result in boiler damage. Make sure that intake and exhaust openings are sufficiently sized and no reduction or closure of openings takes place. When the problem is not resolved, do not operate the boiler. Please note these restrictions and its dangers to the operator of the boiler. Where communicating with the outdoors through vertical ducts, each opening shall have a minimum free area of square inch per,000 Btu/hr of total input rating of all equipment in the enclosure. Where communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of square inch per,000 Btu/hr of total input rating of all equipment in the enclosure. Where ducts are used, they shall be of the same cross-sectional area as the free area of the opening to which they connect. 6.6 Installation of the flue gas adapter (included in the scope of delivery) Before installing the exhaust and air intake system, it is necessary to remove the transport safety device and to install the flue gas adapter. Before installing the exhaust and air intake system, it is necessary to remove the transport safety device and to install the flue gas adapter. Remove the transport safety device with the two screws ( fig. ). CAUTION: BOILER DAMAGE! Due to contaminated air. Boiler must be clear and free from combustible materials, gasoline and other flammable vapors and liquids, and corrosive liquids and vapors. Never use chlorine and hydrocarbon containing chemicals (such as spray chemicals, solution and cleaning agents, paints, glues etc) in the vicinity of the boiler. Do not store and use these chemicals in the boiler room. Avoid excessive dust formation and build-up. When one expects contaminated combustion air (near swimming pools, chemical cleaning operations and hair salons), sealed combustion operation is recommended. 7000-.TD Fig. Removing the transport safety device Remove the protective cap from the internal condensate bypass pipe. Place the flue gas adapter and connect the internal condensate bypass pipe ( fig. ). DANGER: FIRE DANGER! Due to flammable materials or liquids. Do not store flammable materials and liquids in the immediate vicinity of the boiler. All Air from Inside the Building (non sealed combustion) The closet shall be provided with two permanent openings communicating directly with an additional room(s). The total input of all gas utilization equipment installed in the combined space shall be considered in making this determination. Each opening shall have a minimum free area of square inch per,000 Btu per hour of total input rating of all gas utilization equipment in the confined space, but no less than 00 square inches. One opening shall commence within inches (0 mm) of the top, and one opening shall commence within inches (0 mm) of the bottom of the enclosure. The minimum dimension of air openings shall be not less than inches (7 mm). Where directly communicating with the outdoors, each opening shall have a minimum free area of square inch per,000 Btu/hr of total input rating of all equipment in the enclosure. Fig. Placing the flue gas adapter 7000-.TD Logamax plus GB-/0//60 670800 (07/0)

6 Installation Screw on the flue gas adapter using 6 screws ( fig. 6). [] " (00 mm) over maximum snow level or " (600 mm) whichever is greater [] Intake " (80 mm) [] "." (80 8. mm) Fig. 6 Connecting the flue gas adapter 6.7 Installation of the Exhaust and Air Intake system Consult local and state codes pertaining to special building code and fire department requirements. Adhere to national code requirements. Observe the listed maximum lengths of vent system, which are boiler model dependent. The maximum permissible lengths are listed in table, page 8. An optional concentric vent/air intake body ( fig. 7 and 8) can be used for the installation of a vertical venting system as well as for a horizontal venting system. The concentric vent/air intake body can be ordered by Buderus Hydronic Systems, part no. BRYKGAVTO60CV. Other optional vent kits are: 8-00-97 Plastic Vent Kit Fig. 8 Horizontal venting system (sealed combustion) [] Exhaust " (80 mm) [] Intake " (80 mm) [] " max. (60 mm max.) [] "." (80 8. mm) The boiler can also be operated with separate air intake and exhaust piping ( fig. 8 and fig. 9). 7000-7.TD Fig. 7 Vertical venting system (sealed combustion) [] Exhaust " (80 mm) [] 0"- 0" min. (0 mm - 0 mm min.) 7000-9.TD 7000-0.TD Fig. 9 Horizontal venting system (non sealed combustion only) - Situation [] Exhaust " (80 mm) [] Intake " (80 mm) [] "." (80 8. mm) The termination shall be at least ft (,0 mm) for the U.S. and 6 ft (,80 mm) for Canada away from a gas utility gauge, service regulator or the like (for non sealed combustion applications only). Logamax plus GB-/0//60 670800 (07/0)

Installation 6 The termination shall terminate at least ft (,0 mm) below, ft (,0 mm) horizontally from, or ft (0 mm) above any door, window, or gravity air inlet into any building. Vent must be at least inches (0 mm) above grade, anticipated snow line or roof surface (Canada 8'' (7 mm) minimum) ( fig. 0). Vent termination must be at least 7 ft (, mm) above a public walkway ( fig. ). Vent must be ft (9 mm) above any forced air intake within 0 ft (,00 mm) ( fig. ). Do not extend exposed vent pipe outside the building beyond recommended distance. Condensate could freeze and block vent pipe. Vent should terminate at least ft (9 mm) away from adjacent outside walls, inside corners and ft ( mm) below roof overhang ( fig. ). It is not recommended to terminate vent above any door or window, condensate can freeze causing ice formations. It is allowed to use a chimney as a supply channel, only when there are no other boilers or fireplaces which are using the chimney also as air supply or drainage. Fig. 0 Vent and air pipe position () of a sealed combustion system [] Intake [] " (00 mm) minimum [] " (60 mm) minimum [] Exhaust 7000-7.TD ' ( mm) 7' ( mm) ' (0 mm) ' (0 mm) ' (0 mm) ' (0 mm) (0 mm) ' ' ' (9 mm) (0 mm) ' (9 mm) (0 mm) ' Fig. Vent position of a system with combustion air supply from the room (non-room sealed) [] At least ft (0 mm) above grade and snow line [] Exhaust terminal must be at least ft (9 mm) above forced air inlet within 0 ft (00 mm) [] Forced air inlet [] Gravity air Inlet 7000-8.TD Logamax plus GB-/0//60 670800 (07/0)

6 Installation All vent pipes must be glued, except for the flue gas adapter ( fig., []) which is screwed into place and the first connection to the flue gas adapter ( fig., []). Installed you can slide the pipe onto the adapter, properly supported and the exhaust pipe must be pitched a minimum of a ¼ inch per foot back to the boiler. This allows the condensate to drain away. Fix the screws ( fig., []), this is obliged for Canada. Use materials approved by the authority having jurisdiction. In the absence of such authority, PVC and CPVC pipe must comply with ASTM D78, F or D66. Cement and primer must comply with ASTM D6 or F9. For Canada, use CSA or ULC certified PVC or CPVC pipe, fittings and cement. Below are approved examples of vertical and horizontal venting installation Place pipe supports every feet ( mm) of horizontal run, beginning with support near boiler. Periodic cleaning of the vent terminal and air-intake screens is mandatory. Fig. Vent pipes 7000-6.TD All combustion air and vent pipe materials and fittings must comply with the following: Item Material United States Canada Vent or air pipe PVC schedule 0 PVC-DWV ANSI/ASTM D78 ANSI/ASTM D66 CSA or BH Gas venting and CPVC schedule 0 ANSI/ASTM F systems, fitting ULC S66 ) ABS-DWV ANSI/ASTM D66 certified only schedule 0 Pipe PVC ANSI/ASTM D6 cement/ CPVC ANSI/ASTM F9 primer ABS ANSI/ASTM D Table ) Components of the certified vent systems must not be interchanged with other vent systems or unlisted pipe fittings Plastic components, and specified primers and glues of the certified vent system must be from a single system manufacturer and not intermixed with other system manufacturer's vent system parts. Use of cellular core PVC (ASTM F89), cellular core CPVC, or Radel (polyphenolsulfone) in venting systems shall be prohibited. Covering non-metallic vent pipe and fittings with thermal insulation shall be prohibited. A minimum clearance of feet horizontally from and in no case above and below, unless a -foot horizontal distance is maintained, from electric gauges, gas gauges, regulators and relief equipment. Fig. Vertical parallel venting system (sealed combustion) - Situation 7000-.TD [] Exhaust " (80 mm) [] 0"- 0" min. (0 mm - 0 mm min.) [] " min. (60 mm min.) [] " (00 mm) over maximum snow level or " (600 mm) whichever is greater [] Intake " (80 mm) 6 Logamax plus GB-/0//60 670800 (07/0)

Installation 6 7000-.TD Fig. 6 Horizontal parallel venting system (sealed combustion) Fig. Horizontal venting system (sealed combustion) - Situation [] Exhaust " (80 mm) [] "." (80 8. mm) [] Intake " (80 mm) 7000-.TD [] Exhaust " (80 mm) [] " minimum [] Intake " (80 mm) [] " (00 mm) minimum 7000-.TD Fig. Vertical parallel venting system (sealed combustion) - Situation [] Exhaust " (80 mm) [] " (00 mm) over maximum snow level or " (600 mm) whichever is greater [] " min. (60 mm min.) [] Intake " (80 mm) [] "." (80 8. mm) Fig. 7 Vertical venting system (non sealed combustion only) 7000-.TD [] "." (80 8. mm) [] Exhaust " (80 mm) [] 0"- 0" min. (0 mm - 0 mm min.) [] " (00 mm) over maximum snow level or " (600 mm) whichever is greater [] Intake Logamax plus GB-/0//60 670800 (07/0) 7

7 Electrical connections CAUTION: Vent connectors serving appliances vented by natural draft shall not be connected into any portion of mechanical draft systems operating under positive pressure. For Direct venting properly reassemble and reseal the vent and air-intake systems. 6.8 Conversion to Propane To convert the boiler to propane, following the instructions in the Propane, Conversion Kit Instruction manual. Available kits page 6 Spare parts, []. Fig. 8 7000-6.TD Vertical exhaust and horizontal intake venting system (sealed combustion) [] "." (80 8. mm) [] Exhaust " (80 mm) [] 0"- 0" min. (0 mm - 0 mm min.) [] " (00 mm) over maximum snow level or " (600 mm) whichever is greater [] Intake " (80 mm) Do not exceed the total equivalent venting length of 00 feet (0,80 mm) (GB-/0/) and 60 feet (8,88 mm) (GB- 60) maximum requirement each for the intake and exhaust piping. See table for the Friction Loss Equivalent in piping and fittings. 7 Electrical connections Devices such as pumps, outdoor sensor and -way valve are all connected to the external connection board. The electrical connections to the boiler must be made in accordance with all applicable local codes and the latest revision of the National Electrical Code, ANSI/NFPA-70. Installations should also conform with CSA C. Canadian Electrical Code Part if installed in Canada. 7. External connection board connections Make all electrical connections inside the external connection box. Remove the cover of the external connection box ( fig. 9). Fittings or Piping Equivalent feet m degree elbow 0.9 90 degree elbow. plastic pipe per foot 0.0 concentric vent kit 0.9 Table Friction Loss Equivalent in piping and fittings Example: When you end up using x -elbows and the concentric vent kit, then the total venting length may not exceed 88 feet (6.8 m) (GB-/ 0/) or 8 feet (.6 m) (GB-60). x -elbow = x ft (0.9 m) = 9 ft (.7 m) concentric vent kit = ft (0.9 m) Total friction loss equivalent = ft (.6 m) Total venting length for this example is: GB-/0/ = 00 ft (0.8 m) - ft (.6 m) = 88 feet (6.8 m) GB-60 = 60 ft (8.9 m) - ft (.6 m) = 8 feet (.6 m). The minimum covering wall thickness is " ( mm). The maximum covering wall thickness is 6" (06 mm). Fig. 9 Removing the cover from the external connection box 7000-8.TD DANGER: Connecting incoming power The boiler must be electrically grounded in accordance with local codes, or in absence of local codes, with the National Electrical Code, ANSI/INFPA 70 and/or the CSA C., Electrical Code. 8 Logamax plus GB-/0//60 670800 (07/0)

Electrical connections 7 Install a 0V cable to the boiler ( fig. 0, []). Lead the cable through the cable guide ( fig. 0, []). Fig. 0 External connection board Terminals 6 ( fig. ) are low-voltage connections and terminals 7 0 ( fig. ) are 0 Volt connections. 6 Fig. Connections to external connection board [Pos] Abbr. Color Component [] RC orange RC room controller connection or for an AM0 or other module [] FA blue Outdoor-temperature sensor [] WA green Potential-free On/Off thermostat [] FW gray DHW temperature sensor [] EV red External switching contact, potential-free for floor heating safety etc. [6] DWV green Connection for external -way valve [7] PK green Primary loop pump 0 V 60 Hz [8] PS gray DHW tank pump 0 V 60 Hz [9] PZ lilac DHW recirculating pump 0 V 60 Hz [0] Netz white Main power connection 0 V 60 Hz.. 7000-9.TD 7 8 9 0 7000-0.TD EV terminal (external switching contact) This terminal can be used for example for the safety switch of floor heating. This protects the floor heating against too high boiler water temperatures (external manual reset high limit). The boiler is shut down when the external switching contact is opened. The normally closed contacts of a LWCO will shut down burner operation but allow the pump to continue to operate in case of a low water condition. DWV Terminal for connection of an external -way valve (not used). PK Connector for the primary loop pump 0 V 60 Hz. PS Connector for the DHW tank pump 0 V 60 Hz. PZ Connector for the DHW recirculating pump 0 V 60 Hz. NETZ Main power connector 0 V 60 Hz (-% +0%). 0-volt connections CAUTION: Make sure that the power consumption of each of the terminals 7 9 ( circuit diagram) does not exceed 0 W or Amp. CAUTION: Label all wires prior to disconnection when servicing. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing. CAUTION: RISK OF ELECTRIC SHOCK. Once the main power supply is on then there is 0V on terminals 7 0 (can only be used with the correct configuration of the control unit and specific system hydraulics), if the main switch of the BC0 basic controller is switched on. RC terminal Connector for installation of an RC controller for indoor reset operation or a module like the AM0. FA terminal This is the terminal where you connect the outdoor temperature sensor. Only necessary for outdoor weather responsive operation. WA terminal For connection of a potential free thermostat or relay panel end switch. FW Connection for an external DHW tank sensor. Logamax plus GB-/0//60 670800 (07/0) 9

7 Electrical connections Earth 0 VAC Function module Operating switch Mains supply 0 VAC 60 Hz white L N PE L N Grid High Voltage Circulating pump 0 VAC, max. 0 VA lilac L N PE PZ DHW circulator 0 VAC, max. 0 VA Boiler circulator 0 VAC, max. 0 VA grey green L N PE L N PE 6 6 PS PK External -way valve External switch contact Potential-free e.g. for floor heating DHW sensor On/Off temperature control, potential-free Outdoor-temperature sensor Modulating room controller white red grey green blue orange DWV EV FW WA FA RC BC0 connector Bus Function module External connection for specialist servicing company 8 7 6 8 6 7 6 0 9 8 7 6 6-pole connector (0 VAC) 6 Connection box UBA.0 6 9 79 77 6 6 6 7 7 6 7 8 7 60 8 8 7 6 6 L N L PE N 6 7 0 9 0 VAC Function module 0 VAC 0 VAC 0 VAC 0 VAC 6-pole connector Pin 6 Pin N PE L N 0 L VAC KIM M Pin 8 8 Pin Hot surface ignitor Gas burner fitting Transformer Fan unit 6 7 8-pole connector Earth Supply sensor Safety-temperature sensor Return sensor P Pressure sensor Ionization 0 VAC 0 VAC 0 VAC 0 VAC VAC 0 VAC VRAC VRAC 9 8 70 6 6 8 90 8 7 79 76 9 6 7 8-pole connector (AC 0, 0, and 0 V) PE N L 69 68 67 7000-.TD Fig. Electric circuit diagram 0 Logamax plus GB-/0//60 670800 (07/0)

Start-up procedure 8 8 Start-up procedure There are several steps involved in starting up the boiler. A. B. C. D...... 6. 7. 8. 9. 0.... FOR YOUR SAFETY READ BEFORE OPERATING WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life. This appliance does not have a pilot. It is equipped with an ignition device which automatically lights the burner. Do not try to light the burner by hand. BEFORE OPERATING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor. WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance. Do not touch any electric switch; do not use any phone in your building. Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instruction. If you cannot reach your gas supplier, call the fire department. Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not push in or turn by hand, don't try to repair it, call a qualified serv ice technician. Force or attempted repair may result in a fire or explosion. Do not use this appliance if any parts have been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water. OPERATING INSTRUCTION STOP! read the safety information above on this label. Turn off all electric power to the appliance. Set the thermostat or other operating control to lowest setting. This appliance is equipped with an ignition device which automatically lights the burner. Do not try to light the burner by hand. Close main gas shut off valve. Wait () minutes to clear out any gas. Then smell for gas. Including near the floor. If you smell gas, STOP! Follow "B" in the safety information above on this label. If you don't smell gas, go to the next step. Open main shut off valve. Set the thermostat or other operation control to desired setting. Turn on all electric power to the appliance. If the appliance will not operate, follow the instruction "To Turn Off Gas To Appliance" and call your service technician or gas supplier. TO TURN OFF GAS TO APPLIANCE Turn off all the electric power to the appliance if service is to be perf ormed. Set the thermostat or other operating control to lowest setting. Close main gas shut off valve. 708.7A - 7B Fig. 7000-.TD Logamax plus GB-/0//60 670800 (07/0)

8 Start-up procedure 8. Testing for gas leaks Prior to start-up of the boiler you must check the external tightness of the gas supply valve and confirm this in the start-up report. WARNING: Cover endangered positions before leak testing. Do not spray the leak testing agent onto cables, plugs or electrical connection lines. Do not allow it to drip onto them either. DANGER: Leaks may be caused to pipes and screw connections during commissioning and maintenance activities. Carry out a proper leak test. Only use approved leak detection agents for leak detection. Disconnect the heating system from the power supply. Check the exterior tightness of new conduit sections up to and including the direct sealing point on the gas burner fitting. The maximum test pressure allowed on the input of the gas burner fitting is inch W.C. ( mbar). 8. Filling the boiler Set the main switch to a. [p/0.0 appears in the display of the BC0 telling you that there is no system pressure. Fill the heating system to a pressure of around 0 psi (. bar). Observe the space heating water requirements as described in paragraph. on page. Fig. Filling water into the condensate trap Fill with water and refit the condensate trap in reverse order. WARNING: Danger of fatal accident due to poisoning. If the condensate trap is not filled with water, flue gas can escape and put people's lives at risk. 8. Bleeding the gas supply valve Loosen the screw plug on the testing nipple for the gas connection and venting ( fig., []) by two turns and fit a hose. 7000-.TD Observe the pressure on the BC0 or the P/T gauge in the pump manifold for the heating circuit. The fill pressure of the system should be at least the required inlet pressure for the expansion tank plus 7. psi (0. bar). The minimum pressure is psi (.0 bar) (on a cold system). The maximum pressure is psi (.0 bar) (if the heating medium temperature is at its highest possible level). If this pressure is exceeded, the pressure relief valve will open. If a relief valve discharges periodically, this may be due to thermal expansion in a closed water supply system. Contact the water supplier or local plumbing inspector on how to correct the situation. Never plug the relief valve. For first time start up it is necessary to set the DHW temperature knob h and the space heating water temperature knob i to the desired setting ( 9.. and 9..). Factory setting is 0. WARNING: There is a hot water scald potential if the BC0 is set too high. 8. Filling the condensate trap Make sure that you fill the condensate trap with water. This is to prevent exhaust gases from entering the room. Remove the condensate trap ( fig. ) by disconnecting the connection to the heat exchanger and the connection to the condensate bypass pipe. Fig. Bleeding the gas supply conduit Slowly open the gas shut-off valve. Run the gas that is discharged through a water bath. Close the gas shut-off valve when no more air is released. Remove the hose and tighten the screw plug again. 8. Checking the combustion air/flue gas connection Check the following points: Is the prescribed combustion air/flue system used? Have the instructions for configuring the flue system as specified in the relevant Installation instruction for the flue gas system been observed? 8.6 Checking the orifices 7000-.TD CAUTION: The burner must only be commissioned if the correct orifices are fitted ( table ). Convert the burner fitting to another gas type if required ( chapter 6.8 Conversion to Propane, page 8). Logamax plus GB-/0//60 670800 (07/0)