Quantification of Liquid Refrigerant Distribution in Parallel Flow Microchannel Heat Exchanger Using Infrared Thermography

Similar documents
MAL-DISTRIBUTION MODEL OF HEAT EXCHANGERS IN MICRO CHANNEL EVAPORATOR

Numerical Study on the Design of Microchannel Evaporators for Ejector Refrigeration Cycles

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

Experimental and Numerical Study on the Performance of R410A Liquid Recirculation Cycles with and without Ejectors

Investigation of Port Level Refrigerant Flow Mal-distribution in Microchannel Heat Exchanger

Design Optimization of Variable Geometry Microchannel Heat Exchangers

Control Method Of Circulating Refrigerant Amount For Heat Pump System

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Designated vs Non-designated Areas for Condenser Subcooling

Experimental Study of Two-phase Seperators for Vapor Compression Systems in Household Appliances

Performance Comparisons Of A Unitary Split System Using Microchannel and Fin-Tube Outdoor Coils, Part I: Cooling Tests

Experimental Research and CFD Simulation on Microchannel Evaporator Header to Improve Heat Exchanger Efficiency

Visualization of Evaporatively Cooled Heat Exchanger Wetted Fin Area

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Purdue e-pubs. Purdue University

Effects of Oil on atranscritical Carbon Dioxide Air Conditioning Systems some experiences -

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Effect of the Use Pattern on Performance of Heat Pump Water Heater

Experimental and Numerical Study of a Mobile Reversible Air Conditioning Heat Pump System Charge Imbalance when Switching Modes Paper #2569

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants

COMPACT HEAT EXCHANGERS FOR MOBILE CO 2 SYSTEMS

Investigation of Evaporator Performance with and without Liquid Overfeeding

An Experimental Investigation Of Oil Retention Characteristics In CO2 Air-Conditioning Systems

Extremely Low Refrigerant Charge Beverage Display Cooler Technology Using Propane

Performance of CO2 Cycles with a Two-Stage Compressor

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Performance Evaluation and Design Optimization of Refrigerated Display Cabinets Through Fluid Dynamic Analysis

Comparison of Performance of a Residential Air- Conditioning System Using Microchannel and Finand-Tube

DEMONSTRATION OF A MICROCHANNEL HEAT EXCHANGER FOR OPERATION IN A REVERSIBLE HEAT PUMP SYSTEM

Study of R161 Refrigerant for Residential Airconditioning

Numerical Simulation of a New Cooling System for Commercial Aircrafts

Design and Optimization of Capillary Tube- Suction Line Heat Exchangers

Experimental Study on the Performance and Oil Return Characteristics of Multi-Split Air- Conditioning System for Medium Size Building

Effect of Condenser Subcooling of the Performance of Vapor Compression Systems: Experimental and Numerical Investigation

Effect of Modification in Refrigerant Passage of an Automotive Air Conditioning Compressor

Global Journal of Engineering Science and Research Management

Two-Phase Evaporation Pressure Drop Experimental Results for Low Refrigerant Mass Flux

Conceptual Design of a Better Heat Pump Compressor for Northern Climates

Refrigerant Mass and Oil Migration During Start-up Transient

Developing Two-Phase Flow Distribution in Horizontal Headers With Downward Minichannel-Branches

Experimental Study of Fouling Performance of Air Conditioning System with Microchannel Heat Exchanger

Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System

Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Enhancement of Round Tube and Flat Tube- Louver Fin Heat Exchanger Performance Using Deluge Water Cooling

Refrigerant Distribution Effects on the Performance of Microchannel Evaporators

Air-Cooled Heat Exchanger Performance for R410A

Performance Characteristics and Optimization of a Dual-Loop Cycle for a Domestic Refrigerator- Freezer

FROSTING BEHAVIOR OF FIN-TUBE HEAT EXCHANGER ACCORDING TO REFRIGERANT FLOW TYPE

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

Effects of Non-Uniform Refrigerant and Air Flow Distributions on Finned- Tube Evaporator Performance

An Experimental-Numerical Procedure to Characterize Compressor Performance under Cycling Operating Conditions of Refrigerators

The Effect of the Ventilation and the Control Mode on the Performance of a VRV System in Cooling and Heating Modes

Low GWP Refrigerants for Air Conditioning Applications

A fair comparison of CO2 and propane used in light commercial applications featuring natural refrigerants

Enhancement of the Separate Sensible and Latent Cooling Air-Conditioning Systems

EFFECT OF OIL IN CIRCULATION ON AUTOMOTIVE A/C COMPONENT AND SYSTEM PERFORMANCE XUAN LIU THESIS

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Energy Transfer Based Test Method Development and Evaluation of Horizontal Air Flow Re- Circulatory Air Curtain Efficiencies

Dae-Hyun Jin. 8/2018-Present Assistant Professor of Mechanical Engineering, Taylor University, USA

Experimental Investigation on Condensation Performance of Fin-and-Flat-Tube Heat Exchanger

Heat Pump Clothes Dryer Model Development

System Modeling of Gas Engine Driven Heat Pump

Experimental Investigation of Closed Loop Oscillating Heat Pipe as the Condenser for Vapor Compression Refrigeration

Effect of Height Difference on The Performance of Two-phase Thermosyphon Loop Used in Airconditioning

Comparison of fin-and-tube interlaced and face split evaporators with flow maldistribution

Application of a hybrid control of expansion valves to a 3-ton large room cooling system

Introduction of Transcritical Refrigeration Cycle Utilizing CO2 as Working Fluid

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) â Summary of Phase II Testing Results

A New Control Approach for a Direct Expansion (DX) Air Conditioning (A/C)System with Variable Speed Compressor and Variable Speed Supply Fan

Pressure drop analysis of evaporator using refrigerants R-22, R-404A and R-407C

Experimental Study on the Performance of Twisted Capillary Tube

Energy Efficiency of Air-to-Air Mini Heat Pump

An Experimental and Theoretical Study on System Performance of Refrigeration Cycle Using Alternative Refrigerants

Experimental Analysis of a Stirling Refrigerator Employing Jet-Impingement Heat Exchanger and Nanofluids

Load Sharing Strategies in Multiple Compressor Refrigeration Systems

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

2. HEAT EXCHANGERS MESA

Noise Reduction Technology With Porous Metal for Refrigerant Two-Phase Flow Through the Expansion Valve

Heat Exchanger Shelves For Better Temperature Control Of Food In Open-Type Display Cases

Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors

Efficiency of Non-Azeotropic Refrigerant Cycle

Keywords: Micro channel condenser, refrigeration system, heat transfer rate, refrigerant Effect.

Evaluation The Effect Of Washing On The Heat Transfer Capacity And Air-Side Flow Resistance Of Air Cooled Condensers

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Optimized Finned Heat Sinks for Natural Convection Cooling of Outdoor Electronics

Development of a Transient Simulation Model of a Freezer Part II: Comparison of Experimental Data with Model

PREDICTION OF THE PRESSURE DROP OF CO 2 IN AN EVAPORATOR USED FOR AIR COOLING ABSTRACT 1. INTRODUCTION 2. EXPERIMENTAL SET-UP AND PROCEDURE

Modeling and Design of an Indirect Air Conditioning System Operating With Low GWP Zeotropic Mixtures

Low Global Warming Refrigerants For Commercial Refrigeration Systems

Development and Application of Micro Channel Heat Exchanger for Heat Pump

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) Summary of Phase I Testing Results

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Experimental Study About An Amount Of Oil Charge On Electric Driven Scroll Compressor For Electric Vehicle

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY

Performance Comparison of R32, R410A and R290 Refrigerant in Inverter Heat Pumps Application

Experimental Investigation Of A New Low- Approach Evaporator With Reduced Refrigerant Charge

Transcription:

Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Quantification of Liquid Refrigerant Distribution in Parallel Flow Microchannel Heat Exchanger Using Infrared Thermography Huize Li University of Illinois at Urbana-Champaign, United States of America, huizeli2@illinois.edu Predrag S. Hrnjak University of Illinois at Urbana-Champaign, United States of America, pega@illinois.edu Follow this and additional works at: http://docs.lib.purdue.edu/iracc Li, Huize and Hrnjak, Predrag S., "Quantification of Liquid Refrigerant Distribution in Parallel Flow Microchannel Heat Exchanger Using Infrared Thermography" (2014). International Refrigeration and Air Conditioning Conference. Paper 1374. http://docs.lib.purdue.edu/iracc/1374 This document has been made available through Purdue e-pubs, a service of the Purdue University Libraries. Please contact epubs@purdue.edu for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html

2147, Page 1 Quantification of Liquid Refrigerant Distribution in Parallel Flow Microchannel Heat Exchanger Using Infrared Thermography Huize LI 1, Pega HRNJAK 1 * 1 University of Illinois at Urbana-Champaign, Mechanical Science and Engineering, Urbana, IL, USA huizeli2@illinois.edu, pega@illinois.edu * Corresponding Author ABSTRACT This paper presents a method to quantify the distribution of liquid refrigerant mass flow rate in parallel flow microchannel heat exchanger from the infrared images. Quantification is achieved by building the relationship between the liquid mass flow rate through each microchannel tube and the air side capacity calculated from the infrared measurement of the wall temperature. After being implemented in a heat exchanger model, the quantification method is validated against experimental data. This method can be used for several types of heat exchangers: evaporators, condensers etc., also it can be applied to various heat exchanger designs: different inlet/outlet locations, different flow configurations etc. 1. INTRODUCTION Microchannel heat exchangers have been widely used in air conditioning and refrigeration systems because of their compactness and enhancement for heat transfer performance. However microchannel heat exchangers suffer from the problem of refrigerant maldistribution, especially for evaporator. The none-uniform distribution of two phase refrigerant in evaporator can significantly deteriorate the heat exchanger performance as well as system efficiency. Many simulation results shows that the capacity degradation due to refrigerant maldistribution ranges from 5% to 23% (Kulkarni et al., 2004; Brix et al. 2009, 2010; Zou et al. 2012). A good quantification of two phase refrigerant distribution is essential for evaluating maldistribution effect on heat exchanger and system performance. Many studies have been done to quantify refrigerant distribution using some intrusive techniques. The main idea is to measure the mass flow rate of liquid and vapor phase through each microchannel tube which branches from a realistic heat exchanger header. Vist (2003) investigated the distribution of two-phase CO 2 and R134a in horizontal heat exchanger headers for upward and downward flow configuration. Strong effect on distribution of vapor fraction at header inlet has been seen in the experiments. An empirical model was developed to describe phase split in the header. Lee et al. (2004) examined the distribution of air-water twophase annular flow in a vertical heat exchanger header. The effect of tube protrusion was examined and the most uniform distribution could be achieved by adjusting the depth of protrusion. Hwang et al. (2007) studied the distribution of R410A and R134a in horizontal heat exchanger headers. They concluded that the refrigerant distribution was largely affected by header inlet location and vapor mass flux. A set of empirical correlations for refrigerant distribution were developed. Lee (2009) investigated the distribution of air-water two phase flow in a vertical header. The distribution at the front part of the header was found to be only affected by the upstream flow regime, while the distribution at the rear part of the header was mainly influenced by the downstream flow configuration due to flow recirculation. The existing T-junction phase split models were found to be working well for the front part of the header but not the rear part. Ahmad et al. studied the two phase HFE 7100 distribution in a horizontal header including both upward and downward flows. The effects of numerous operational and geometrical parameters on distribution were investigated and a map of flow regime in the header was developed. Kim et al. (2011) examined the effect of inlet location on two phase R134a distribution in a horizontal header. Parallel inlet configuration was found to have the worst performance, while normal and vertical inlet configuration yield similar refrigerant distribution. Empirical distribution correlations for all three inlet configurations were formulated, which

2147, Page 2 were functions of Reynolds number of the upstream gas in the header. Zou and Hrnjak (2013a, 2013b) performed experimental studies for two phase R134a and R410A distribution in vertical heat exchanger headers. They found that the best distribution was achieved at high flux and low quality. Empirical distribution correlations were developed for both fluids. The intrusive method could provide accurate information of distribution which are the liquid and vapor mass flow rates through each microchannel tube, but none of the aforementioned experiment setups used real microchannel heat exchangers. Some of the experiments were conducted under adiabatic condition. Even for the diabatic cases, it was extremely hard to represent the heat load of each microchannel in a real heat exchanger; also some of the experimental facilities didn t have outlet header, so the outlet header induced maldistribution, which was proved to be very important (Tuo and Hrnjak, 2013), was ignored. Many attempts have been made to quantify two-phase refrigerant distribution through non-intrusive methods. Litch and Hrnjak (1999) related the air exit temperature of a microchannel condenser with the inside refrigerant distribution. Song et al. (2002) used the frosting pattern to identify maldistribution in an outdoor microchannel coil. Infrared (IR) thermography has also been used by many researchers to examine refrigerant distribution, but only qualitative information was obtained (Litch and Hrnjak, 1999; Dschida and Hrnjak, 2008; Qi et al., 2009; Shi et al., 2011; Tuo and Hrnjak, 2012). Bower et al. (2010) proposed a distribution rating parameter which is based on the uniformity of the surface temperature of the heat exchanger. Some quantification of distribution could be acquired from the IR image by using this parameter. Bower et al s method have been adopted by many authors (Tuo and Hrnjak, 2012; Li and Hrnjak, 2013). Non-intrusive method has the advantage of saving time and cost over the intrusive method, but typically uncertain quantitative information about refrigerant distribution is obtained. In this study, an IR thermography based method is proposed to quantitatively estimate liquid refrigerant distribution in parallel flow microchannel heat exchangers. This method is validated against experimental results in conjunction with the heat exchanger model. 2. METHOD DEVELOPMENT 2.1 Heat transfer basis for the quantification method The cooling capacity of an evaporator comes mainly from the latent heat of the liquid refrigerant. So distribution of liquid is more important than vapor. The refrigerant inside of tubes could be either two phase or superheat vapor as shown in Figure 1. Figure 1: Snapshot of a simplified situation in parallel flow heat exchanger From the modeling perspective (finite volume approach), a heat exchanger has several parallel microchannel tubes and each tube is divided into s. The following assumptions are made to simplify the model without losing generality: 1) Uniform temperature and velocity profile of the incoming air; 2) Uniform distribution of refrigerant among parallel ports within the same tube; 3) Uniform wall temperature within each ; 4) No conduction through the fins or wall along tube direction.

2147, Page 3 For each in the two-phase region, because of the uniform wall temperature, the energy balance on the air side can be calculated using the -NTU method: Q C ( T T ) (1) air,, tp min air, in wall, C c m min p, air air (2) 1exp( NTU ) (3) NTU h A C air air (4) min Assuming uniform temperature and velocity profile of the incoming air, constant for each, and Cmin is also constant. A, T,, m air, c, and h air stays air air in p air In the two-phase region, the refrigerant-side capacity is the latent heat of the liquid refrigerant, so the following energy balance equation can be formed in each : Q m i (5) ref,, tp ref, liq, fg For each microchannel tube, refrigerant side capacity in the two phase region is calculated by summing up the capacity of each together: n Q i m i m (6) ref, tube, tp fg ref, liq, fg ref, liq, tube 1 (n is the last of the two phase region) Based on energy balance between refrigerant-side and air-side, n Q Q C ( T T ) ref, tube, tp air, min air, in wall, 1 1 n (7) the ratio of liquid refrigerant mass flow rate through any two microchannel tubes can be calculated as following: ( m ) ref, liq, tube i ni 1 ( Tair, in Twall, ) n j ( mref, liq, tube) j ( Tair, in Twall, ) 1 i j (8) Given the above ratio, liquid refrigerant distribution among parallel microchannel tubes can be fully described by the following equation: ( T T ) air, in wall, ref, liq, tube i 1 i t ube# n j mref, liq, HX Tair, in Twall, 1 1 ( m ) ni ( ) IR camera provides the wall temperature of each. As long as the boundary between single phase region and two phase region can be identified on the IR image of the heat exchanger (see section 2.2), the distribution of liquid refrigerant mass flow rate can be then determined. (9)

2147, Page 4 2.2 Procedure of applying the quantification method First, IR image is smoothed using an algorithm for total variation minimization. The difference between the IR images before and after smoothing can be seen in Figure 2. Temperature scale is the same in the smoothed image as in the raw IR image which is adjusted to be narrowest possible. Figure 2: Comparison of IR image before and after smoothing After obtaining the smoothened IR image, a transition line is drawn to identify the two-phase zone. In each tube with liquid at the inlet and superheated exit, there will be a certain location at which the last drop of liquid refrigerant evaporates. The which starts from that location is defined as the transition. It is assumed to have saturated single phase vapor refrigerant at the inlet. When heat exchanger model is not available, the pressure at the transition can be estimated as the average of evaporator inlet and outlet pressures, also average mass flow rate which equals to the total mass flow rate divided by the tube number is used to calculate the refrigerant-side heat transfer coefficient. m1 m2...= mi=... mn (9) m m + m i l, i v, i (10) Based on the air-side and refrigerant-side thermal resistances, the wall temperature of the transition in each tube can be then determined. The locations with the calculated temperature in the IR image define the transition line (red line in Figure 4). When higher calculation accuracy is required, the mass flow rate at each transition location can be determined through an iterative process using heat exchanger models. In the first iteration, average mass flow rate which is corresponding to uniform distribution case is used to calculate the transition temperature. The resultant transition line will be used to determine liquid mass flow rate through each tube using the IR quantification method introduced in section 2.1. In the heat exchanger model (Li and Hrnjak (2013) is chosen in this study), the working fluid flows along different paths, each of them consisting of one microchannel tube and the corresponding distances in the inlet and outlet header as shown in Figure 3. Because each path starts from the evaporator inlet and ends at the outlet, the pressure drop should be the same. The two-phase refrigerant distribution in the inlet header is originally described by an empirical quality distribution function. Among available distribution functions, we have initially chosen Jin (2006) (modified by Tuo et al. (2012)) which assigns the inlet quality for each microchannel tube. This quality distribution function is now replaced by the information of liquid refrigerant distribution ( m li, ) acquired by the IR quantification method. Knowing the liquid mass flow rates distribution ( m li, ), the vapor mass flow rate through mv, mv... mv i..., m v n ) can be determined using the following pressure drop (function of each tube (,1,2,, mli, and m vi, refrigerant. ) equality relationship along each flow path and the mass conversation equation of the vapor Pst P nd... P th (11) 1 path 2 path n path mv,1 mv,2... mv, n x minlet (12)

2147, Page 5 1 2 3 i Outlet i-th flow path Inlet 1 2 3 i n Figure 3: Configuration of microchannel heat exchanger m, m... m... m ), new transition line is identified. Iteration will Using the newly calculated mass flow rates ( 1 2 i n stop when mass flow rates reach convergence. The resultant transition line is shown as the blue line in Figure 4. If more precision is needed in the model, actual pressure at the transition location will be determined iteratively instead of assumed to be the average of inlet and outlet pressures. Comparing these two transition lines, it can be found that in the most superheated tubes, the blue line is located above the red line because these tubes receive less than average mass flow rates, resulting in lower refrigerant-side heat transfer coefficient and higher transition wall temperature; In the least superheated tubes, the blue line is below the red line, because the mass flow rates through these tubes are higher than average, contributing to a higher refrigerant-side heat transfer coefficient and lower transition wall temperature. Even though the red line is determined using average mass flow rate (no need for heat exchanger model), it can still provide a reasonable estimation which makes the quantification method easier to apply. Figure 4: Determination of transition line 3. METHOD VALIDATION The newly proposed quantification method of liquid refrigerant distribution is integrated into Li and Hrnjak s (2013) heat exchanger model as introduced in section 2.2. The new model is validated against Bielskus s (2011) experimental data. A microchannel evaporator taken from a mid-size, major brand vehicle was used in his study. The experiments were conducted under three indoor/outdoor conditions (25 /25, 35 / 35, 40 /40 ) and four different superheats at compressor inlet (5, 10, 15, 20 ). Since Li and Hrnjak s model is inherited from an

2147, Page 6 experimentally validated (using Bielskus s (2011) data) model developed by Tuo et al. (2012), the comparison of the simulation results with experimental data presents the validation of the method. The inlet and outlet location of the heat exchanger is indicated on the top left part in the following two figures. Figure 5 shows the comparison of the simulated surface temperature (using modified Jin s distribution function and IR quantification method) and experimental results under the same indoor temperature but different superheats at the compressor inlet. The case of 35 indoor temperature is used as an example. Tair=35 Tsup=5 Tair=35 Tsup=10 Tair=35 Tsup=15 Tair=35 Tsup=20 Simulation (quantification method) Simulation (empirical function) Experiment Figure 5: High similarity of the shape of the superheated zones in experiment and simulation validates the IR quantification method presented Tair=25 Tsup=5 Tair=35 Tsup=5 Tair=40 Tsup=5 Simulation (quantification method) Simulation (empirical function) Experiment Figure 6: Same as in Figure 6 but for different conditions

2147, Page 7 Figure 6 shows the comparison of the simulated surface temperature and experimental results under the same compressor inlet superheat but different indoor temperatures. The 5 superheat condition is chosen as a show case. From Figure 5 and Figure 6, it can be seen that the shape of the superheat region calculated using IR quantification method is smoother and more similar with the experimental results than the ones calculated using empirical distribution functions. The high similarity of the shape of the superheat regions between simulations (using IR quantification method) and experiments indicates accurate estimation of refrigerant distribution among parallel microchannels. The simulated surface temperature is found to be consistently lower than the experimental results for 2-3. Good agreement (±5%) between simulated and measured capacity shown in Figure 7 provides additional assurance of the fidelity of the model with IR quantification method. Figure 7: Capacity validation 4. APPLICATION This quantification method can be applied to various heat exchanger designs. Since refrigerant maldistribution is less important in condenser (Pottker and Hrnjak, 2012), the following examples only focus on evaporators. Figure 8 shows the liquid refrigerant distribution inside of a microchannel heat exchanger with inlet and outlet on the opposite side. For the IR image on the left side, liquid mass flow rate fraction calculated using the IR quantification method is presented on the right side in blue. The red line indicates the liquid mass flow rate distribution using empirical distribution function developed by Jin (2006) (modified by Tuo et al. (2012)). The similarity of two liquid refrigerant distribution profiles indicates that far simpler and less costly IR quantification method provides even slightly better results. Figure 9 illustrates that the quantification method is cable of providing good estimation of liquid refrigerant distribution regardless of the inlet and outlet locations. Figure 10 demonstrates that this method can also handle the estimation of liquid refrigerant distribution in the heat exchanger with vertical headers and horizontal tubes.

2147, Page 8 Figure 8: Example for heat exchanger with inlet and outlet on the opposite side Figure 9: Example for heat exchanger with inlet and outlet on the same side Figure 10: Example for heat exchanger with vertical header and horizontal tube The existence of flooded tubes in a heat exchanger creates limitation for this method. The quantification of liquid refrigerant distribution is based on the premise that all the liquid has turned into vapor at the end of the two phase region. So this method has difficulties working in situations like the first pass in a multiple circuits evaporator or the last pass in a multiple circuits condenser where many flooded tubes exist (shown in Figure 11). Limitation Figure 11: Limitation of the quantification method

2147, Page 9 5. CONCLUSIONS In this study, an IR thermography based method is proposed to quantify liquid refrigerant distribution in parallel flow microchannel heat exchangers. After being implemented in a heat exchanger model, this method is validated against experimental data. Good agreement has been achieved between simulation and experiment for surface temperature and capacity. This quantification method is non-contacting and none-intrusive, thus is easy to apply. It can be used to evaluate the refrigerant distribution in operating heat exchangers under various conditions. The paper demonstrates the application of the methods to different heat exchanger orientations and designs. Authors are currently working on application of this method to develop more general correlation/process to predict refrigerant distribution among parallel microchannels. NOMENCLATURE A area (m 2 ) C heat capacity (kjkg -1 K -1 ) heat exchanger effectiveness ( ) h heat transfer coefficient (kwm -2 K -1 ) i specific enthalpy (kjkg -1 ) m mass flow rate (kgs -1 ) NTU number of transfer units ( ) P pressure (kpa) Q capacity (kw) T temperature (K) U heat exchanger effectiveness ( ) Subscript air air side f fluid g gas HX heat exchanger in inlet l liquid min minimum p pressure path path ref refrigerant tp two phase tube tube v vapor REFERENCES Kulkarni, T., Bullard, C. W., Cho, K., 2004, Header design tradeoffs in microchannel evaporators, Appl. Therm. Eng., 24, 759 776. Brix, W., Kaern, M. R., Elmegaard, B., 2009, Modeling refrigerant distribution in microchannel evaporators, Int. J. Refrig., 32, 1736 1743. Brix, W., Kaern, M. R., Elmegaard, B., 2010, Modeling distribution of evaporating CO2 in parallel minichannels, Int. J. Refrig., 33, 1086 1094. Zou, Y., Tuo, H., Hrnjak, P. S., 2012, Two-phase refrigerant maldistribution in the vertical header and its effect on the heat exchanger performance as evaporator in the heat pump mode, Proceedings of ASME 2012 International Mechanical Engineering Congress and Exposition, Houston, TX.

2147, Page 10 Vist, S., Pettersen, J., 2004, Two-phase flow distribution in compact heat exchanger manifolds, Exp. Thermal Fluid Sci., 28, 209-215. Lee, J. K., Lee, S. Y., 2004, Distribution of two-phase annular flow at header-channel junctions, Exp. Thermal Fluid Sci., 28, 217-222. Hwang, Y., Jin, D.H., Radermacher, R., 2007, Refrigerant distribution in minichannel evaporator manifolds, HVAC&R Res., 13 (4), 543-555. Lee, J.K., 2009, Two-phase flow behavior inside a header connected to multiple parallel channels, Exp. Thermal Fluid Sci., 33, 195-202. Kim, N.H., Kim, D.Y., Byun, H.W., 2011, Effect of inlet configuration on the refrigerant distribution in a parallel flow minichannel heat exchanger, Int. J. Refrig., 34, 1209 1221. Zou, Y., Hrnjak, P. S., 2013, Experiment and visualization on R134a upward flow in the vertical header of microchannel heat exchanger and its effect on distribution, Int. J. Heat Mass Transfer, 62,124-134. Zou, Y., Hrnjak, P.S., 2013, Refrigerant distribution in the vertical header of the microchannel heat exchanger - measurement and visualization of R410Aflow, Int. J. Refrig., 36, 2196-2208. Tuo, H.F., and P. Hrnjak, 2013, Effect of the header pressure drop induced flow maldistribution on the microchannel evaporator performance, Int. J. Refrig., 36, 2176-2186. Litch, A. D., and Hrnjak, P. S., 1999, Condensation of Ammonia in Microchannel Heat Exchangers, ACRC Report No. CR-22, University of Illinois at Urbana-Champaign. Song, S., Bullard, C.W., Hrnjak, P.S., 2002, Frost deposition and refrigerant distribution in microchannel heat exchangers, ASHRAE Trans., 108 (2), 944 953. Dschida, M., Hrnjak, P.S., 2008, Evaluation of Microchannel Heat Exchangers for a Residential Mini-Split Type Air-Conditioning/Heat Pump System, ACRC Report No. CR-67, University of Illinois at Urbana-Champaign. Qi, Z.G., Chen, J.P., and Radermacher, R., 2009, Investigating performance of new mini-channel evaporators, Appl. Therm. Eng., 29(17-18), 3561-4567. Shi, J.Y., Qu, X.H., Qi, Z.G., and Chen, J.P., 2011, Investigating performance of microchannel evaporators with different manifold structures, Int. J. Refrig., 34(1), 292-302. Tuo, H.F., Bielskus, A., and Hrnjak, P.S., 2011, Effect of flash gas bypass on the performance of R134a mobile airconditioning system with microchannel evaporator,, SAE Int. J. Materials and Manufacturing, 4(1), 231-239. Bowers, C.D., Hrnjak, P.S., 2010, Quantification of Refrigerant Distribution and Effectiveness in Microchannel Heat Exchangers Using Infrared Thermography, International Refrigeration and Air Conditioning Conference, Paper 1016. Tuo, H.F., and Hrnjak, P. S., 2012, Flash gas bypass in mobile air conditioning system with R134a, Int. J. Refrig., 35(7), 1869-1877. Tuo, H.F., Bielskus, A., and Hrnjak, P. S., 2012, Experimentally Validated Model of Refrigerant Distribution in a Parallel Microchannel Evaporator, SAE Int. J. Materials and Manufacturing, 5(2), 365-374. Li, H.Z., and Hrnjak, P.S., 2013, Effect of lubricant on two-phase refrigerant distribution in microchannel evaporator., SAE Int. J. Materials and Manufacturing, 6(3), 231-239. Jin, D., 2006, Investigation on refrigerant distribution in evaporator manifolds, Doctoral Dissertation, University of Maryland, College Park, MD. Pottker, G., and Hrnjak, P.S., 2012, Designated vs Non-designated Areas for Condenser Subcooling, International Refrigeration and Air Conditioning Conference, Paper 1332. ACKNOWLEDGEMENT The authors thankfully acknowledge the support provided by the Air Conditioning and Refrigeration Center at the University of Illinois at Urbana-Champaign.