Study Final Report. Priority Cool Refrigerant Study

Similar documents
1. Packaged Variable Air Volume (VAV) Rooftop Units (RTU) with Hot Water Reheat. 2. Geothermal Heat Pump VAV Rooftop Units with Hot Water Reheat

Introduction to HVAC. American Standard Inc Air Conditioning Clinic TRG-TRC018-EN

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

INSTALLATION INSTRUCTIONS

Executive Summary. Number of Low Number of High Number of Faults , Number of OK

DUAL ZONE CONTROL PANEL Zone Control For Residential Heating/Cooling Systems

A/C Cooling Load calculation and measurement

LGH/LCH WARNING. CAUTION Danger of sharp metallic edges. Can cause injury. Take care when servicing unit to avoid accidental contact with sharp edges.

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

Southwest Air Conditioning

HVAC 101. H V A C S y s t e m s

TECHNOLOGY GUIDE. :: the dawn of a new era in commercial HVAC technology. The all-new Rheem Commercial Renaissance Line featuring:

Technical Development Program. COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1

Designing Energy Efficient Outdoor Air Systems

CARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection.

TECHNICAL GUIDE LISTED. SPLIT-SYSTEM AIR CONDITIONERS 10 SEER R22 60Hz MODELS: AC036X10(3,4) THRU 060 (3 THRU 5 NOMINAL TONS, 3 PH) DESCRIPTION

COMMERCIAL HVAC PACKAGED EQUIPMENT. Split Systems

MHNCCX DX with Hot Water Heat Ceiling Concealed 4-Pipe Heat / Cool Fan Coil 12,000-36,000 BTUH

AIR CONDITIONING. Carrier Corporation 2002 Cat. No

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

TOP-ECO TECHNOLOGY HISTORY

TECHNICAL GUIDE LISTED. SPLIT-SYSTEM AIR CONDITIONERS 10 SEER R22 60Hz MODELS: H*BA-(T,W)036 THRU 076 (3 THRU 6.3 NOMINAL TONS, 3 PH) DESCRIPTION

FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

Installation Manual for ETI AVS Series and NON-ETI Air Handlers with SC or SD Compressor Units and R-410A Refrigerant

Electric Heat Inspection Form Revised September 2012

RSG16**S1M. Split System Air Conditioner 16 SEER

TEST REPORT #4. Travis Crawford Dutch Uselton. Lennox Industries Inc Metrocrest Drive Carrollton, TX 75006

Field Test of Combined Desiccant-Evaporator Cycle Providing Lower Dew Points and Enhanced Dehumidification

Implications of GHP Fan Control Strategies on Humidity Control in Commercial Applications

Frigi Tech International, Inc Prairie Wind Lane,. Houston, Texas T: F:

Ductless Split Systems Wall-mounted, Single Zone Heat Pump

Jr. Tech (JT-1, 2, 3) Knowledge Areas

HVAC Systems What the Rater Needs to Know in the Field CALCS-PLUS

Mechanical Technical Report 1. ASHRAE Standard 62.1 Ventilation Compliance Evaluation

product application data PERFECT HUMIDITY DEHUMIDIFICATION SYSTEM

Building America AC Installation Using CheckMe!

Computing Services Center

Small Commercial Business Energy Audits. Recognizing and addressing the special requirements of the small business market segment.

Refrigeration System Report March 2017

INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012

R-410A Ductless Split Systems. Single Zone, Dual Zone & Multi Zone Air Conditioners & Heat Pumps. Chilled Water Fan Coils

50TM COMBINATION HEATING/COOLING UNITS

MACH N-407 Heat Pump Air-Cooled Chiller

Installation Manual for. Series HWM and Non-ETI HYDRONIC WATER MODULE with SC and SD COMPRESSOR UNITS and R-410 REFRIGERANT

State of the art building simulation software... Frenger Radiant chilled beam performance at 1 Shelly St - Sydney

Service Literature GCS/CHA16 15 and 20 Ton (52.8 and 70.3 kw)

JEFFERSON COLLEGE COURSE SYLLABUS HRA 249 COMMERCIAL REFRIGERATION SYSTEMS. 5 Credit Hours. Prepared by: William Kaune November 30, 2010

Often fellow technicians, co-workers and field personnel CHARGE REFRIGERANT DETERMINING PROPER SYSTEM

IMPORTANT. HOSHIZAKI provides this manual primarily to assist qualified service technicians in the service and maintenance of the icemaker.

Energy Use in Refrigeration Systems

Product Data. Split System Heat Pump B-EN. February A6H6024H1000A

TECHNICAL GUIDE MODELS: H5CE090, H3CE120 & H1CE /2, 10, & 12-1/2 NOMINAL TONS EER DESCRIPTION

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

STATE UNIVERSITY OF NEW YORK COLLEGE OF TECHNOLOGY CANTON, NEW YORK

Air Conditioning Repairs: Maintenance Required

VariCool VAV Engineering Guide

97.501B. Prepared by: (415) Sponsored By: Final Report. Author: Presented at: ASHRAE. Meeting SF Me!

Madeira City Schools Madeira, Ohio. HVAC Assessment. December 2011 (Revised February 2012)

New and Emerging HVAC Technologies. Rod Rhoads, GDS Associates Dave McCullaugh, Mitsubishi Electric Trane HVAC US Dave Binz, Cambridge Engineering

Nominal Capacity 024 = 7 kw (2 tons) 036 = 10.5 kw (3 tons) 048 = 14 kw (4 tons) 060 = 17.5 kw (5 tons)

Displacement Ventilation in Classrooms

Job Name Control Systems Description Date

ELECTRICAL Seminar. B A L A Consulting Engineers, Inc. Edward J. Lynch, PE Vice President, Electrical Department Manager.

VertiCool CLASSIC. Engineering Guide. Effective March Air-Cooled, Water-Cooled, Chilled Water and Water Source Heat Pump

SECTION REFRIGERATION. 1. Reciprocating Compressors (Hermetic). 2. Reciprocating Compressors (Open Drive). 3. Water Cooled Condensing Units.

COMMON WATERSIDE ECONOMIZER APPLICATIONS:

COMcheck Software Version Review Mechanical Compliance Certificate

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

50TM TFF COMBINATION HEATING/COOLING UNITS

Heat Pumps SB SERIES. Vertical Self-Contained Unit Water-Source Heat Pumps (3-18 tons) Features:

Ocean Breeze Split System. General Installation Manual. Ocean Breeze 2951 SE Dominica Terrace Stuart, Florida Tel:

Installation and Operation Guide For

Superheat charging curves for technicians

VertiCool Space Saver 2 to 15 Tons Water-Cooled and Chilled Water Air-Cooled w/remote Condenser

The most energy-efficient commercial split system* Commercial Air Conditioners and Heat Pumps SSB/SPB Models

Radiant Cooling Nonresidential HVAC Stakeholder Meeting #2

TECHNOLOGY GUIDE :: THE DAWN OF A NEW ERA IN COMMERCIAL HVAC TECHNOLOGY. The all-new Ruud Commercial Renaissance Line featuring:

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems

MAC N-407 Air-Cooled Chiller

D-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency

PLP - TERMS AND CONDITIONS Philadelphia Gas Works Residential Parts & Labor Plan Contract

Ruud Achiever Series Dedicated Horizontal Package Heat Pump

Ruud Achiever Series Dedicated Horizontal Package Heat Pump

K*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS*

ADDENDUM 1. Southeast High School Auditorium & Gymnasium HVAC Improvements

Single-Stage. Thermostat Set-Up Guidelines for All-Electric Heat Pumps:

EarthLinked SC Series Compressor Unit R-407C Quik-Start Instructions

TAG: RTU-2B 3B 4B 5B 6B 7B 1E MODEL: QTY. (7) 48TCED14A3A5-0B0A0 PACKAGED GAS/ELECTRIC ROOF TOP UNITS

Heat Pumps SB SERIES. Vertical Self-Contained Unit Water-Source Heat Pumps (3-18 tons) Features:

Application and Installation Bulletin for Master-Bilt Refrigeration Superheat Controller Kit Assembly(A ), 120/208/240/1/60, R404A, LT/MT APPS

COMcheck Software Version Interior Lighting Compliance Certificate

Installation Manual for CCS Cased Coils with SC, SD, SW Compressor Units and R-410A Refrigerant

Civil Engineering Building

SERVICE MANUAL FOR ROOF TOP AIR CONDITIONERS

TEST REPORT #47. System Drop-in Test of R-32 and Refrigerant Blends ARM-71a, HPR2A, L-41-2 and DR-5A in a Five-Ton R-410A Rooftop Packaged Unit

LONG LINE SET APPLICATION R-410A

Inspection Phase Three. Mechanical, Electrical & Plumbing Section 503

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.

Transcription:

Refrigerant Study Study Final Report Prepared for: Greenway Solutions Company, Inc. 120 Bethpage Road, Suite 304 Hicksville, New York 11801 Prepared by: WSP Flack + Kurtz 512 Seventh Avenue New York, NY 10018 May 24, 2012 Project No. N12.43430.00

Executive summary This report demonstrates the energy savings potential of hydrocarbon based refrigerant over standard R22 refrigerant. Side by side tests run in both real world settings and a laboratory setting show significant energy savings in the refrigerant compressor electrical loads. While fan loads remain constant, the thermodynamic properties appear to improve performance on the air side of the refrigerant cycle with lower evaporator temperatures and higher moisture removal (latent load). Compressor energy savings for each test is shown below; Test Case #1 Lab test 10% Test Case #2 Field test 18 to 19% Test Case #3 Field test 24% The air handler in the lab test removed 27% more moisture from the air in a lab test. It must be noted that refrigerant has not been registered with the U.S. Environmental Protection Agency (EPA). Similar hydrocarbon refrigerants have not been accepted for use in HVAC systems. These alternative refrigerants are acceptable in commercial refrigeration systems. 1

I. Purpose of the Report The purpose of this report is to define the test results for comparing standard R22 refrigerant energy performance and hydrocarbon based replacement refrigerant in a side by side study. The testing was performed on air conditioners in a simulated laboratory test, and in a real world side by side comparison. II. Systems Tested For the lab tests, integrated testing was performed on a set of two matching direct expansion (DX) units located in the same space in this project. A data acquisition system was installed to monitor and collect data during the field test. For the field testing, two matching roof top units were used serving offices spaces on the same floor of a commercial office building in Melville. III. Team Data Team Member Company Contact Info. Lab Owner Air Control Supply Bob Mecca 516-241-2242 Engineering Provider Client WSP Flack + Kurtz 512 Seventh Avenue New York, NY 10018 Paul Meyer, PE, CEM, LEEP AP, GBE paul.meyer@wspfk.com Office (212) 951-2662 Fax (212) 689-7489 Cell (917) 596-3191 Refrigerants, Inc Robert Conway 631-553-8538 Mechanical Contractor Apollo HVAC Corp Rudy Holesek 631-242-8787 IV. Laboratory Test Case #1 A laboratory test simulation was performed on two identical DX split units. The heat load was generated in the space with a separate heat source. Flack + Kurtz scheduled functional tests through the contractor and owners. Flack + Kurtz witnessed and documented the integrated testing of the split units according to the approved Test Plan. The Mechanical Contractor executed the tests. The test location was the training room at Air Control Supply, 1580 Lakeland Ave, Bohemia, NY 11716. 2

The room conditions were: Room size: 22-9 L x 20-5 W x 18 H Ceiling: None installed (exposed /insulated roof deck) Glass: None (no exterior windows) Outside Doors: (1) metal man door Outside Walls: (1) approximately 20 x 16 Interior lighting: approximately 1.25 wpf The equipment under test was: Quantity (2) Amana 2-ton air cooled condensing units R-22 (specs attached) (2) Amana 2-ton air handlers R-22 (specs attached) (2) Honeywell programmable thermostats The test room had (1) Payne 45,000 btuh warm air furnace to supply sensible heat load into room. An unconditioned warehouse adjacent to the lab space supplied both sensible and latent heat load thru a large transfer grill. Refrigeration piping of identical size and length was used to connect both systems The condensing units were located on grade side by side immediately outside the space on the North side of the building. The air handlers were located side by side on the inside of the North wall for minimum refrigeration pipe run. Suction and liquid line pressure gauges were installed inside for data monitoring. The air handlers drew air from the testing room across the evaporator coils and discharged the air out of the building. Room air was made up by a transfer opening from adjoining warehouse space. The warehouse space was not conditioned. The testing took place from October 13 to 24 th, 2011. The test procedure: The data acquisition M & V sensors were calibrated and verified as accurate. Both units were charged with standard R-22 according to factory procedures. The units were run side by side to establish a baseline and to prove that the units performed identically. The data acquisition system was run during this phase of the testing. The units did draw the same power. Please see the appendices for this data. The Apollo technicians evacuated unit #1 using standard EPA procedures for refrigerant reclaimation. The unit #1 test system was charged with HC22a/502a refrigerant according to empirical data and manufacturers recommendations. Amount of the original R22 removed was 4 lbs 7 oz. The amount of HC22a/502a installed was 3

1 lb. 10 oz. One of the primary reasons for lower energy consumption of Priority Cool is the lower gas volume requires less compressor work. Both units were operated under load and operating parameters were recorded using data acquisition system. On the initial test day the outdoor weather conditions was heavy rain. The high humidity allowed for the testing of moisture removal capacity between the two refrigerants. Simultaneous condensate water collections were taken from both condensate drains. The (unit #1) discharged 14 fluid ounces of water. The R22 (unit #2) discharged 11 fluid ounces of water. The unit removed 27% more moisture from the conditioned air. Test was run for 6 consecutive days with data collection. Data is available in the appendices for review. Metering/Monitoring variables of the two HVAC units: (i) (ii) (iii) (iv) (v) (vi) (vii) (viii) (ix) (x) Inside Space Temperature Outdoor Temperature Thermostat settings for each space and unit Supply air temperature Return air temperature Total kwh Electrical Demand Refrigerant Low side pressure Refrigerant High side pressure Hours of operation Team Member Responsibilities Mechanical Contractor i) Performed all recommended installation requirements on both split units. This included checking refrigerant charge, condenser and evaporator coils, filters and fans. Provided documentation that installation was completed and copies of the O&M manuals. ii) iii) iv) Reclaimed the original R22 refrigerant from one of the split units using all required EPA procedures. Evacuated the refrigerant circuit with a vacuum pump. Charged the unit with the recommended amount of Priority Cool refrigerant according to the manufacturer s instructions. v) Documented the services performed. Flack + Kurtz 1) Witnessed the contractor responsibilities shown above. Performed site inspection of split units after installation of Priority Cool refrigerant. Verified correct operation. Insured that all required installations had been performed on both test units. 4

2) Verified data acquisition was recording correct values. 3) Analyzed recorded data and compared energy usage of both units. 4) Performed periodic field observation of DX units. 5) Issued this final engineering report. Typical screen shot of the data acquisition system- 5

V. Field Test Case #2: b. The RXR owned building at 68 South Service Rd. Melville, New York was used for a side by side field test of refrigerant. A 75-ton rooftop heat/cool unit was chosen for the test. The unit was a Trane Model #SFHFC754H777C9BD8D11ABCE0G00L00RT0Y8600, Serial # C05B01224. The unit was charged with R-22 refrigerant and was manufactured in 2006. The unit operates with (6) scroll compressors with circuits #1 and #2. Each circuit consists of (1) 15-ton and (2) 10-ton compressors. This unit serves a general office environment of the first floor that was fully occupied. The total area covered of the floor under test was 62,650 sq.ft., with 31,325 sq.ft. served by each RTU. On August 17, 2011 the return air was measured at 74F db, the supply air was 55F db, and the outdoor temperature was 82F db. In this test the entire unit was not shut down in an effort to not cause discomfort to the building occupants. Each circuit was independently shut down and the existing R-22 refrigerant was recovered. Each circuit was evacuated for a period of 45 minutes and the refrigerant was installed. The amount of existing R-22 recovered was 80 lbs in circuit #1 and 79 lbs on circuit #2. Priority Cool refrigerant installed was 37 lb-6 oz in circuit #1 and 36 lbs-3 oz in circuit #2, both weighed by the same electronic scale. The compressor amperage in circuit #1 while running with the existing R-22 was measured at 26.3, 16.4 and 17.4 respectively on the 460 volt 3 phase circuits. After was installed the compressor amperage was measured at 21.1, 13.3 and 13.9 respectively. This was a decrease of over 19%. The compressor amperage in circuit #2 while running with the existing R-22 was measured at 25.5, 16.9 and 17.2 respectively. After was installed the compressor amperage was measured at 21.4, 13.6 and 13.5 respectively. This was a decrease of over 18%. After stabilizing both circuits the supply air temperature leveled off at 52F db with a return air temperature of 76F db. The supply air temperature of was 3F lower than the original R22. We continued to monitor the performance of this test unit and a second 75-ton rooftop unit serving the general office area at this location. The test unit serves the south half of the building s first floor and the comparison R22 unit serves the north half of the same floor. The compressor amperage continued to be the same spread of between 15% and 19% throughout the test period of 2 months. The amount of condensate generated was not measured in this test. Note that these 75-ton units are both Variable Air Volume (VAV) units with Variable Frequency Drives. The loads vary due to VAV throttling so the comparative amperage readings were taken during the morning pull-down cycle when the loads were at a maximum. This test unit remains in operation with refrigerant to date. 6

VI. Field Test Case #3: Another field test was performed on July 6, 2011 at the Apollo HVAC offices at 225 North Fehrway, Bay Shore, New York on a 5-ton rooftop heat/cool unit. The unit under test was a Rheem Model #RKKA-A060CK13E, Serial #2A5643ADAAF349911631, using R-22refrigerant and operates on 208 volt 3 phase power, the unit was manufactured in 1999 and uses a scroll compressor. This unit serves a general office environment. The return air was measured as 72F db, the supply air was 51F db, and the outdoor temperature was 84F db. The unit was shut down and the existing R-22 was recovered. The unit was evacuated for a period of 30 minutes and the refrigerant was installed. The amount of existing R-22 recovered was 8 lb-0 oz and the Priority Cool refrigerant installed was 3 lb-4 oz both weighed by the same electronic scale. The unit compressor amperage while running with R-22 was measured at 18.5 amps and after was installed the compressor amperage was measured at 13.9 amps. This was a decrease in compressor amperage of over 24%. The supply air temperature dropped from 51F db to 48F db. Apollo continues to monitor the performance of the test unit and a second 5-ton rooftop unit serving the general office area at this location. The test unit serves the perimeter zone and the comparison unit serves the interior zone. The compressor amperage continued to be the same spread of between 20% and 24% throughout the summer test period of 2 months. In addition, the condensate drain water was measured and there was approximately 25% more moisture being removed by the unit. This test unit remains in operation with refrigerant to this date. 7

Appendices 8

Lab test data Energy Test 10-19 10-23 AC-1 AC-2 Hours 119 119 KWH Savings KWH 146.47 163.22 16.75 KWH Delta Savings Savings $30.77 $34.28 $3.51 Date Time KWH Daily KWH KWH Daily KWH Daily KWH Savings Daily % Comp Loads S-R C % Delta 10/19/2011 12:00 PM 0.05 0.03 12 Hours 10/19/2011 11:45 PM 13.33 13.28 15.52 15.49 2.21 14.27% AC-1 AC-2 4.10 4.10 0.00% 10/20/2011 12:00 AM 13.61 15.86 24 Hours 4.23 3.84 9.22% 10/20/2011 11:45 PM 40.92 27.31 46.44 30.58 3.27 10.69% 5.10 5.96 14.43% 3.74% 10/21/2011 12:00 AM 41.22 46.77 24 Hours AC-1 Measured Amps 10/21/2011 11:45 PM 70.06 28.84 77.95 31.18 2.34 7.50% Volts Amps Watts KWH 202 5.1 1030.2 1.0302 10/22/2011 12:00 AM 70.38 78.31 24 Hours 24 Hour X KWH= 24.7248 10/22/2011 11:45 PM 100.64 30.26 112.06 33.75 3.49 10.34% AC-2 Measured Amps 10/23/2011 12:00 AM 100.97 112.41 24 Hours Volts Amps Watts KWH 10/23/2011 11:45 PM 131.59 30.62 146.28 33.87 3.25 9.60% 202 5.96 1203.92 1.20392 24 Hour X KWH= 28.89408 10/24/2011 12:00 AM 131.89 146.64 11 Hours 10/24/2011 1:00 PM 147.94 16.05 164.75 18.11 2.06 11.37% Fan Measured Amps Volts Amps Watts KWH 202 0.56 113.12 0.11312 Total HWH 146.36 162.98 16.62 10.20% 24 Hour X KWH= 2.71488 9

RXR office field test datamodel RTU-1A #SFHFC754H777C9BD8D11ABCE0G00L00RT0Y8600 68 South Service Road serial #C05B01224 Melville, NY 11747 75 tons 85 lbs r-22 per circuit Circuit #1 Compressor "A" m#csha150k0d00 s#05c10005 15 ton Compressor "B" m#csha100k0e00 S#05C07016 10 ton Compressor "C" m#chsa100k0e00 s#05c09060 10 ton R-22 recovered 80 lbs HC-22a recharged 38 lbs (44% rated charge) R-22 270/65 pressures 84 deg OAT suction temp 58 deg Comp "A" 24.3 amps Comp "B" 14.9 amps Comp "C" 15.8 amps HC-22a 210/65 pressures 82 deg OAT suction temp 57 deg Comp "A" 22.1 amps Comp "B" 14.3 amps Comp "C" 14.9 amps Circuit #2 Compressor "A m#csha150k0d00 S#05C10002 15 TON Compressor "B" m#csha100k0e00 s#05c09054 10 TON Compressor "C" m#csha100k0r00 s#05c09055 10 TON R-22 recovered 75 lbs HC-22a recharged 36 lbs (42% rated charge) R-22 281/68 pressures 82 deg OAT suction temp 58 deg Comp "A" 24.5 amps Comp "B" 14.9 amps Comp "C" 15.2 amps HC-22a 250/66 pressures 84 deg OAT suction temp 56 deg Comp "A" 21.5 amps Comp "B" 14.2 amps Comp "C" 14.5 amps Note: 2nd stage condenser coil needs cleaning 10

11