Versatec Ultra Series Installation Manual

Similar documents
ARBOR SERIES COMMERCIAL. Arbor Series Installation ti Manual. Water Source/Geothermal Heat Pump R-410A Refrigerant Commercial 0.

Heating and Air Conditioning

Versatec Ultra Series Installation Manual

G Series. G Series 7-25 Tons Installation Manual. Water Source/Geothermal Heat Pump Commercial 7-25 Tons. Installation Information

RK SERIES WATER SOURCE HEAT PUMP 0.75 TON - 6 TON

Versatec Base Series Installation Manual

Versatec Base Series Installation Manual

ARBOR COMPACT SERIES COMMERCIAL. Arbor Compact Series Installation ti Manual

RG Series Commercial Geothermal/Water Source Heat Pump R-410A Refrigerant Tons

ARBOR BASE SERIES COMMERCIAL. Arbor Base Series Installation ti Manual. Water Source/Geothermal Heat Pump R-410A Refrigerant Commercial 0.

Heating and Air Conditioning

Installation, Operation & Maintenance Manual. Geothermal/ Water Source Heat Pump. R-410A Refrigerant Ton. Design Features.

Legend Series Installation Manual

3 Series 300A11 Installation Manual

Envision Commercial Tons Installation Manual

DUAL CAPACITY HEATING COOLING HOT WATER

5 Series 500A11 Installation Manual

INDOOR PACKAGED EQUIPMENT COMMERCIAL WATER SOURCE / GEOTHERMAL HEAT PUMP SERIES RB R-410A TON

Versatec Installation Manual

G Series. G Series Air Coils Installation ti Manual ENCASED/UNCASED AIR COILS. Geothermal/Water Source Heat Pumps R-410A Refrigerant 2-5 Ton

Versatec Installation Manual

Versatec Compact 50 Hz Series Installation Manual

7 Series 700A11 Installation Manual

Heating and Air Conditioning

INSTALLATION, OPERATION, & MAINTENANCE MANUAL

7 Series 700A11 Installation Manual

ARBOR SERIES CONDO. Arbor Condo Series Installation Manual. Water Source/Geothermal Heat Pump R-410A Refrigerant Commercial

7 Series 50Hz 700A11 Installation Manual

Heating and Air Conditioning

5 Series 500R11 Installation Manual

Owner s Manual Therma-Stor II Heat Recovery System

CROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

CAH SERIES INSTALLATION & MAINTENANCE MODELS CAH CAH

G Series Geothermal Indoor Split Heat Pump R-410A Refrigerant 2-6 Tons Single Speed 2-6 Tons Dual Capacity

NAH Series. NAH Series Hydronic Air Handler Installation Manual. Air Handler. Installation Information. Water Piping Connections

Synergy3D Installation Manual

Versatec Variable Speed Installation Manual

Versatec Installation Manual

Installation, Start-Up, and Service Instructions

SPXB-HW Series Single Package Vertical Unit Cooling with Hot Water Heat 1 through 2 tons, up to 47,800 BTUH Heating

INSTALLATION INSTRUCTIONS

Residential Packaged Geothermal Heat Pump

INSTALLATION INSTRUCTIONS

Installation, Start-Up, and Service Instructions

4201 Lien Rd Madison, WI Owner s Manual Therma-Stor III Heat Recovery System. Installation, Operation & Service Instructions

Installation, Start-Up, and Service Instructions

EC SERIES MODEL NOMENCLATURE

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

INSTALLATION INSTRUCTIONS GEO PRIME TANK. (Patent Pending) GPC

TRI-PLATE B INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS PART NO EFFECTIVE MARCH 1, 1983 REPRINT APRIL 16, 1999

Installation Instructions

Cooling/Heat Pump Convertible Air Handlers

RHGN-H: COMMERCIAL AIR HANDLER WITH VARIABLE FREQUENCY DRIVE (VFD) NOMINAL 10 TONS R-410A REFRIGERANT 2-STAGE AIR-FLOW

Installation Instructions

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

INSTALLATION INSTRUCTIONS

J120 STEAM BOOSTER INSTALLATION, OPERATION, AND SERVICE MANUAL J120 STEAM BOOSTER. J120 Steam Booster Manual D

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

AP SERIES VOLTAGE DESIGNATION: 1-208/1/60 & 230/1/60 CABINET CONFIGURATION: VT - VERTICAL HZ - HORIZONTAL CF - COUNTERFLOW

SuperStor Ultra Stainless Steel Storage Tank

Envision Series 30 Ton Installation Manual

Premier Installation Manual

C13-Series Engineering Guide

WM-450-PT WM-900-PT Commercial Wall Mounted Reverse Osmosis

SuperStor Glass Lined Storage Tank

INSTALLATION AND SERVICE OF WATER-SOURCE AND GEOTHERMAL HEAT PUMPS WaterFurnace International

INSTALLATION INSTRUCTIONS TXV Horizontal Slab Coils WLSH

SPXR-A / SPXR-HP-A Series Single Package Vertical Unit Straight Cool and Heat Pump 3/4 through 2 tons, up to 10 kw Electric Heat

AHG**-0B Series Hydronic Air Handling Units

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL FEATURING

Table of Contents. Commercial Horizontal & Vertical Packaged Water-Source Heat Pumps

Installation Instructions

SPXA / SPXA-HP Series Single Package Vertical Unit Straight Cool and Heat Pump 3/4 through 2 tons, up to 10 kw Electric Heat

DOUBLE O-RING GEO-PRIME TANK Non-Pressurized Flow Center System INSTALLATION INSTRUCTIONS. Model: DORGPT-1 NOTE:

Installation. Table of Contents. 1. Description/ Application. Form I-CAUA-CC (04-15) Obsoletes Form I-CAUA-CC (Version C.1)

INSTALLATION MANUAL AFFORDABLE RENEWABLE CLEAN ASTON SERIES OUTDOOR SPLIT HEATING COOLING HOT WATER.

Cooling/Heat Pump Convertible Air Handlers

SV Air Handler. Installation, Operation and Maintenance Manual (2015/01)

ICE AIR Vertical WSHP Technical Manual INSTALLATION

SPXB / SPXB-HP Series Single Package Vertical Unit Straight Cool and Heat Pump 3/4 through 2 tons, up to 10 kw Electric Heat

INSTALLATION MANUAL AFFORDABLE RENEWABLE CLEAN ASTON SINGLE HYDRONIC UNIT GEOTHERMAL HEAT PUMPS

R-410A. NJ-10 thru -20, 4-Pipe Ton, 60 Hertz TABLE OF CONTENTS LIST OF TABLES LIST OF FIGURES

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

INSTALLATION INSTRUCTIONS

MODELS B1PA024, 030 AND 036

GS SERIES. Table of Contents CABINET CONFIGURATION: VT - VERTICAL HZ - HORIZONTAL CF - COUNTERFLOW

INSTALLATION INSTRUCTIONS

Daikin Water Cooling, Heating, and High Capacity Booster Coils

Versatec Variable Speed Ton Installation Manual

AHWG Remote Mount Hot Water Generator Module for TTP Series Outdoor Split Unit

GUIDE SPECIFICATIONS AQUARIUS ii

H&V Products. Table of Contents. Tranquility 27 (TT) Series Tranquility 20 (TS) Series

40LM Hz INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT

AHWG Remote Mount Hot Water Generator Module

Cooling/Heat Pump Convertible Air Handlers

Installation Instructions

ES Series. Installation and Maintenance Manual

INSTALLATION MANUAL AFFORDABLE RENEWABLE CLEAN ASTON SERIES AIR HANDLER GEOTHERMAL HEAT PUMPS

STORAGE TANK INSTALLATION and OPERATION MANUAL

INSTALLATION INSTRUCTIONS

Transcription:

ommercial eothermal/water Source Heat Pump R-40A Refrigerant 0.75-6 Tons Installation Information Water Piping onnections Hot Water onnections Electrical Startup Procedures Versatec Ultra Series Installation Manual Troubleshooting Preventive Maintenance IM200AU 02/

Table of ontents Model Nomenclature........................................................... 4 eneral Installation Information................................................. 5 Dimensional Data............................................................ 6-9 Installing Horizontal Units......................................................0 Hanger Bracket Locations...................................................... Duct System and Water Piping.................................................. 2 ondensate Drain............................................................. 2 Water Quality................................................................. System leaning and Flushing...................................................4 Open Loop round Water Systems..............................................5 Hot Water enerator onnections............................................ 6-7 Freeze Detection..............................................................8 Electrical onnections.........................................................8 Electrical Data............................................................. 9-2 Blower Performance Data...................................................22-27 Wiring Schematics......................................................... 28- ontrols - Aurora Base ontrol.............................................. 4-7 ontrols - FX0 (optional).................................................. 8-42 Unit Startup................................................................. 4 Operating Limits and Operating Parameters..................................... 44 Pressure Drop................................................................ 45 Reference alculations and Legend............................................. 46 Refrigerant ircuit uideline................................................... 46 ompressor and Thermistor Resistance......................................... 47 Heat of Extraction/Rejection Data.............................................. 48 Troubleshooting.............................................................. 49 Startup/Troubleshooting Form...............................................50-5 Preventive Maintenance....................................................... 52 Replacement Procedures...................................................... 52 Service Parts.............................................................. 5-54 Revision uide............................................................... 55

Model Nomenclature U 2 S V 4-6 06 7 T 8 L 9 0 0 0 0 2 A 4 N 5 N 6 A 7 8 N 9 0 20 0 2-22 SS 2 * Model Type U = Versatec Ultra Operation Range S = Single Speed abinet onfiguration V = Vertical H = Horizontal Unit apacity 009, 02, 05, 08, 02 (horizontal), 024, 00, 06, 04 (vertical), 042, 048, 060, 070 Discharge onfiguration T = Top (vertical) E = End (horizontal) S = Side (horizontal) Air onfiguration L = Left R = Right Voltage 0 = 208-20/60/ 2 = 265-277/60/ (009-06) = 208-20/60/ (02-070) 4 = 460/60/ (02-070) 5 = 575/60/ (04-070) Hot Water eneration Option 0 = No HW, No IntelliStart 2 = HW w/o pump, No IntelliStart (V05-070) = No HW, IntelliStart 5 = HW w/o pump, IntelliStart (V08-070) Blower Option 0 = PS Blower = Variable Speed EM Blower (05-070) 2 = High Static VS EM Blower (042-048) = High Static PS Blower (024, 00, 042, 048) 4 = 5-Speed EM Blower (02-070) oax = opper N = upronickel Sound Kit A = None B = Sound Kit (not available on H009-02) NOTES: Phase guard only available on 208-20/60/, 460/60/, and 575/60/ IntelliStart is not available with Phase uard option Vintage * Factory Use Only Non-Standard Option Details SS = Standard Option Drain Pan Options 0 = omposite, No Secondary onnection = omposite, Secondary onnection 2 = Stainless Steel, No Secondary onnection = Stainless Steel, Secondary onnection abinet 0 = Unpainted, in. MERV 4, Filter Rail = Painted, in. MERV 4, Filter Rail 2 = Unpainted, 2 in. MERV, Filter Rail = Painted, 2 in. MERV, Filter Rail 4 = Unpainted, in. MERV 4, Filter Rack 5 = Painted, in. MERV 4, Filter Rack 6 = Unpainted, 2 in. MERV, Filter Rack 7 = Painted, 2 in. MERV, Filter Rack Phase uard N = No Phase uard, No Disconnect D = No Phase uard, Disconnect P = Phase uard, No Disconnect B = Phase uard, Disconnect Air oil/insulation Options = FormiShield/Extended Range 2 = FormiShield/Standard Range = No oating/extended Range 4 = No oating/standard Range ontrols Option A = Aurora TM Base ontrol (AB) 4 = FX0 std. no communication 5 = FX0 w/open N2 om ard 6 = FX0 w/lonworks om ard 7 = FX0 w/bacnet om ard Water ontrol N = None R = Water Flow Regulator (05-070) V = 2-Way Valve (05-070) B = 2-Way Valve w/water Flow Regulator (05-070) Hot as Bypass/Reheat N = None = Hot as Bypass (05-070) R = Hot as Reheat (05-070) B = Hot as Bypass w/hot as Reheat (05-070) Rev.: 06 February 20D 4

eneral Installation Information Safety onsiderations WARNIN: Before performing service or maintenance operations on a system, turn off main power switches to the indoor unit. If applicable, turn off the accessory heater power switch. Electrical shock could cause personal injury. Installing and servicing heating and air conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair or service heating and air conditioning equipment. Untrained personnel can perform the basic maintenance functions of cleaning coils and cleaning and replacing filters. All other operations should be performed by trained service personnel. When working on heating and air conditioning equipment, observe precautions in the literature, tags and labels attached to the unit and other safety precautions that may apply. Follow all safety codes. Wear safety glasses and work gloves. Use a quenching cloth for brazing operations and have a fire extinguisher available. Moving and Storage Move units in the normal up orientation. Horizontal units may be moved and stored per the information on the packaging. Do not stack more than three units in total height. Vertical units may be stored one upon another to a maximum height of two units. Do not attempt to move units while stacked. When the equipment is received, all items should be carefully checked against the bill of lading to be sure all crates and cartons have been received. Examine units for shipping damage, removing the units from the packaging if necessary. Units in question should also be internally inspected. If any damage is noted, the carrier should make the proper notation on the delivery receipt, acknowledging the damage. Unit Location Locate the unit in an indoor area that allows for easy removal of the filter and access panels. Location should have enough space for service personnel to perform maintenance or repair. Provide sufficient room to make water, electrical and duct connection(s). If the unit is located in a confined space, such as a closet, provisions must be made for return air to freely enter the space by means of a louvered door, etc. Any access panel screws that would be difficult to remove after the unit is installed should be removed prior to setting the unit. On horizontal units, allow adequate room below the unit for a condensate drain trap and do not locate the unit above supply piping. are should be taken when units are located in unconditioned spaces to prevent damage from frozen water lines and excessive heat that could damage electrical components. Installing Vertical Units Prior to setting the unit in place, remove and discard the compressor hold down shipping bolt located at the front of the compressor mounting bracket. Vertical units are available in left or right air return configurations. Top flow vertical units should be mounted level on a vibration absorbing pad slightly larger than the base to provide isolation between the unit and the floor. It is not necessary to anchor the unit to the floor (see figure below). Vertical Unit Mounting 2 in. PEX Foam 5

Vertical Dimensional Data Standard filter rails for open return applications Field installed duct flange Deluxe filter rack for ductable return applications A N R S A N Air coil Q Q AESS PANEL B P F AIR OIL SIDE 4 FRONT.4 in (.5 cm) Top View - Right Return M M AIR OIL SIDE FRONT.4 in (.5 cm) Top View - Left Return 4 P F B 2' (6 cm) Alternate Service Access 2' (6 cm) Service Access Left Return (Right Return opposite side) Isometric View - Left Return U T W Air coil Air coil AESS PANEL AESS PANEL V H E D.6 in (4. cm) ondensate /4 in PV glue socket.6 in (4. cm) 5 6 2 8 L J Power supply in (25.4 mm) knockout Low voltage /2" (2.7 mm) knockout L K 8 7 ondensate /4 in PV glue socket.6 in (4. cm) 5 2 E H D.6 in (4. cm) J L 6 8 AESS PANEL 8 7 K L Front View - Right Return Front View - Left Return Right View - Right Return Left View - Left Return 6

Vertical Dimensional Data cont. Overall abinet Water onnections Electrical Knockouts 2 4 5 6 7 8 Vertical Knockout A B D E F H Loop Models J K L Width Depth Height** In Out HW HW ond- Water HW /2 in. /2 in. in. In Out ensate FPT Provisions cond cond cond 009-02 in. 22.5 22.2 2.7 2.6 5.6 N/A N/A 8.8 /2 N/A 7.4.4 5.4 cm. 57.2 56.4 60.2 6.6 4.2 N/A N/A 22.4 2.7 mm N/A 8.8 8.6.7 05-08 in. 22.5 22.2 6.2 2.6 7.6.4 2.9 0.8 /4 0.875 9.4 5.4 7.4 cm. 57.2 56.4 9.9 6.6 9..6 7.4 27.4 9. mm 22.2 mm 2.9.7 8.8 024-00 in. 22.5 26.2 40.2 2.6 7.6.4 4.4 0.8 /4 0.875 0. 6. 8. cm. 57.2 66.5 02. 6.6 9..6.2 27.4 9. mm 22.2 mm 25.7 5.5 20.6 06 in. 22.5 26.2 44.2 2.6 7.6.4 4.4 0.8 /4 0.875 0. 6. 8. cm. 57.2 66.5 2. 6.6 9..6.2 27.4 9. mm 22.2 mm 25.7 5.5 20.6 04 in. 22.5 26.2 44.2 2.6 7.6.4 2.9 0.8 /4 0.875 0. 6. 8. cm. 57.2 66.5 2. 6.6 9..6 7.4 27.4 9. mm 22.2 mm 25.7 5.5 20.6 042-048 in. 25.5.2 44.2 2.6 7.6.4 4.4 0.8 0.875 0. 6. 8. cm. 64.8 79.2 2. 6.6 9..6.2 27.4 25.4 mm 22.2 mm 25.7 5.5 20.6 060 in. 25.5.2 48.2 2.6 7.6.4 4.4 0.8 0.875 0. 6. 8. cm. 64.8 79.2 22.4 6.6 9..6.2 27.4 25.4 mm 22.2 mm 25.7 5.5 20.6 070 in. 25.5.2 52.2 2.6 7.6.4 4.4 0.8 0.875 0. 6. 8. cm. 64.8 79.2 2.6 6.6 9..6.2 27.4 25.4 mm 22.2 mm 25.7 5.5 20.6 Discharge onnection Return onnection* duct flange installed (±0.0 in) using deluxe filter rack (±0.0 in) Vertical M N P Q R S T U V Models Filter Rack Supply Supply Return Return W Width Width Depth Depth Height 009-02 in. 2.2 0.0 0.0 6. 9.4 9.4 2. 8. 0.0.9 cm. 5.6 25.4 25.4 5.5 2.9 2.9 5. 46.0 25.4 4.8 05-08 in. 2.2 4.0 4.0 4. 4. 7.7 2. 8. 20.0.9 cm. 5.6 5.6 5.6 0.4 0.9 9.6 5. 46.0 50.8 4.8 024-00 in. 2.2 4.0 4.0 6. 4.5 7.7 2. 22. 22..9 cm. 5.6 5.6 5.6 5.5.4 9.6 5. 56. 56. 4.8 06 in. 2.2 4.0 4.0 6. 4.5 7.7 2. 22. 26..9 cm. 5.6 5.6 5.6 5.5.4 9.6 5. 56. 66. 4.8 04 in. 2.2 8.0 8.0 4..9.9 2. 22. 26..9 cm. 5.6 45.7 45.7 0.4 9.9 9.9 5. 56. 66. 4.8 042-048 in. 2.2 8.0 8.0 6.6 4.6 6..6 28. 26.0 2.0 cm. 5.6 45.7 45.7 6.8.7 6.0 4. 7.4 66.0 5. 060 in. 2.2 8.0 8.0 6.6 4.6 6..6 28. 0.0 2.0 cm. 5.6 45.7 45.7 6.8.7 6.0 4. 7.4 76.2 5. 070 in. 2.2 8.0 8.0 6.6 4.6 6..6 28. 4.0 2.0 cm. 5.6 45.7 45.7 6.8.7 6.0 4. 7.4 86.4 5. ondensate is /4 in. PV female glue socket and is switchable from side to front. /0/09 *Dimensions for return connections are for the deluxe filter rack that is suitable for ducted return applications and extends.25 in. [8.26 cm] from the unit. The open filter rack, used in non-ducted returns, extends 2.2 in. [5.59 cm] from the unit. **Discharge flange is field installed and extends in. (25.4 mm) from top of cabinet. Vertical Disconnect When using disconnect, do not use dimension L from the standard vertical dimensional data. Use dimension LL from the vertical disconnect dimensional data. Vertical Models LL 009-02 Externally Mounted 05-08 8.8 [47.8] 024-00 4. [6.] 06 5. [8.9] 042-048 4. [6.] 060 4. [6.] 070 4. [6.] Dimensions in inches [cm] 02/06/ Power Supply.8 in. [4.6 cm] Disconnect Location LL Alternative Power Location Disconnect Located on this Side for a Right Return Vertical Shown in Left Return onfiguration 7

Horizontal Dimensional Data Right Return Standard filter rails in. [2.5 cm] knockout 0.5 in. [. cm] knockout Front K.7 in. [5. cm] P.7 in. [5. cm] Standard filter rails Front Left Return AP J E AP MP A RR Front View D AP MP.7.7 2' (6 cm) Service Access J 2' (6 cm) Service Access ondensate "X" PV size End Discharge Deluxe filter rack option shown 2. in. [5.8 cm] N P H FILTER RAK AIR OIL SIDE Right Return End Discharge Side Discharge E D P AP LR Front View Side Discharge Left Return End Discharge ondensate "X" PV size End Discharge Deluxe filter rack option shown P N BLOWER L OUTLET Legend M AP = Alternate Service Panel M L BP P = Blower Service Panel = ontrol Access Panel BLOWER OUTLET 2. in. [5. cm] MP = ompressor Service Panel 2. in. [5. cm] A A K 0.5 in. [. cm] knockout in. [2.5 cm] knockout FILTER RAK AIR OIL SIDE 2. in. [5.8 cm] H P N.5 in. [.8 cm].5 in. [.8 cm] N P BP L M BLOWER OUTLET Right Return Side Discharge AP MP K 0.5 in. [. cm] J knockout Front Front in. [2.5 cm] J knockout 0.5 in. [. cm] K knockout AP MP Left Return Side Discharge BLOWER OUTLET M L BP Air oil Q S T T S Q FILTER RAK ONNETION R Deluxe filter rack option (shown) R FILTER RAK ONNETION Air oil Front Front B Right Return Side View B Left Return Side View 8

Horizontal Dimensional Data cont. Horizontal Models 009-02 05-02 024-00 06 042-048 060 070 Overall abinet Water onnections Electrical Knockouts 2 J K A B D E H Loop /2 in. cond in. cond Width Depth Height* In Out ondensate Water FPT Low Voltage Power Supply in. 9.2 29.0.9.8 4.8 0.8 /2 4.5 4.5 cm. 48.8 7.7 0.2 4.6 2.2 2.0 2.7 mm.4.4 in. 22.5 42.0 7.2.8 6.8 0.8 /4 7. 7. cm. 57.2 06.7 4.7 4.6 7. 2.0 9.05 mm 8.0 8.0 in. 22.5 42.0 9.2.8 6.8 0.8 /4 9.2 7. cm. 57.2 06.7 48.8 4.6 7. 2.0 9.05 mm 2.4 8.0 in. 22.5 45.0 9.2.8 6.8 0.8 /4 9.2 7. cm. 57.2 4. 48.8 4.6 7. 2.0 9.05 mm 2.4 8.0 in. 25.5 48.0 2.2.8 6.8 0.8 9.2 9. cm. 64.8 2.9 5.8 4.6 7. 2.0 25.4 mm 2.4 2. in. 25.5 5.0 2.2.8 6.8 0.8 9.2 9. cm. 64.8 4.6 5.8 4.6 7. 2.0 25.4 mm 2.4 2. in. 25.5 6.0 2.2.8 6.8 0.8 9.2 9. cm. 64.8 54.9 5.8 4.6 7. 2.0 25.4 mm 2.4 2. Horizontal Models 009-02 05-02 024-00 06 042-048 060 070 Discharge onnection duct flange installed (±0.0 in) Return onnection* using deluxe filter rack option (±0.0 in) PV Size L M N P Q R S T X Supply Width Supply Depth Return Depth Return Height in. 2. 8.0 0.0 2. 5.4 9.4.0.4 /2 cm. 5.8 20. 25.4 5.8 9. 2.9 7.6.6. in. 5.7 0.5 9.4 4.9 2.4 4.5 2.0.4 /4 cm. 4.5 26.7 2.9 2.4 59.4 6.8 5..6.9 in. 6.7 0.5 9.4 4.9 27.4 6.4 2.0.5 /4 cm. 7.0 26.7 2.9 2.4 69.6 4.7 5..8.9 in. 6.7 0.5 9.4 4.9 0.4 6.4 2..5 /4 cm. 7.0 26.7 2.9 2.4 77.2 4.7 5..8.9 in. 4.9.6.2 4.6 5.4 8.6 2.4.5 /4 cm. 2.4 4.5.5.7 89.9 47.2 6..8.9 in. 4.9.6.2 4.6 40.4 8.4 2.4.5 /4 cm. 2.4 4.5.5.7 02.6 46.7 6..8.9 in. 4.9.6.2 4.6 45.6 8.6 2..5 /4 cm. 2.4 4.5.5.7 5.8 47.2 5.8.8.9 *Dimensions for return connections are for the deluxe filter rack that is suitable for ducted return applications and extends.25 in. [8.26 cm] from the unit. The open filter rack, used in non-ducted returns, extends 2.2 in. [5.59 cm] from the unit. ondensate /4 in. PV stub extends from cabinet approximately -/2 in. [8. mm] 07/6/0 Horizontal Disconnect When using disconnect, do not use dimension K from the standard horizontal dimensional data. Use dimension KK from the horizontal disconnect dimensional data. Horizontal Models KK 009-02 Externally Mounted 05-08 8.2 [20.8 ] 024-00 9.2 [2.4] 06 9.2 [2.4] 042-048.2 [28.4] 060 0.2 [25.9] 070.2 [28.4] Dimensions in inches [cm] 02/06/ Disconnect Located on this Side for a Left Return Disconnect Location KK Power Supply 2. in. [5. cm] Horizontal Shown in Right Return onfiguration 9

Installing Horizontal Units Installing Horizontal Units Remove and discard the compressor hold down shipping bolt located at the front of the compressor mounting bracket prior to setting the unit in place. Horizontal units are available with side or end discharge. NOTE: Left (Right) Return Side Discharge cannot be converted to Left (Right) Return End Discharge or vice versa, without additional custom sheet metal parts. Horizontal units are normally suspended from a ceiling by four (009-060 models) or five (070-072 models) /8 in. diameter threaded rods. The rods are usually attached to the unit by hanger bracket kits furnished with each unit. Lay out the threaded rods per the Hanger Bracket Dimensions table. Assemble the hangers to the unit as shown. Securely tighten the brackets to the unit using the weld nuts located on the underside of the bottom panel. When attaching the hanger rods to the bracket, a double nut is required since vibration could loosen a single nut. To allow filter access, install hanger brackets as illustrated in the Hanger Bracket Locations section. The unit should be pitched approximately /4 in. towards the drain in both directions to facilitate the removal of condensate. Use only the bolts provided in the kit to attach hanger brackets. The use of longer bolts could damage internal parts. Some applications require the installation of horizontal units on an attic floor. In this case, the unit should be set in a full size secondary drain pan on top of a vibration absorbing pad. The secondary drain pan prevents possible condensate overflow or water leakage damage to the ceiling. The secondary drain pan is usually placed on a plywood base isolated from the ceiling joists by additional layers of vibration absorbing material. AUTION: Do not use rods smaller than /8 in. diameter since they may not be strong enough to support the unit. The rods must be securely anchored to the ceiling. 0

Hanger Bracket Locations Right Left B D E ompressor Section Air Handler Section F E D ompressor Section Air Handler Section F A /8 Threaded Rod (not supplied) Vibration Isolator Washer Bolt and Lockwasher Hex Nuts (not supplied) Hanger Dimensions Model Hanger Kit Part Number Unit Hanger Dimensions A B 29.8 2.8 8. 009-02 in. 99S500A04 cm [75.7] [55.4] [46.0] 05-02 in. 42.8 25. 2.4 99S500A04 cm [08.6] [6.8] [54.4] 024-00 in. 42.8 25. 2.4 99S500A04 cm [08.7] [6.8] [54.4] 06 in. 45.8 25. 2.4 99S500A04 cm [6.] [6.8] [54.4] 042-048 in. 48.8 28. 24.4 99S500A04 cm [24.0] [7.4] [62.0] 060 in. 5.8 28. 24.4 99S500A04 cm [6.7] [7.4] [62.0] 070 in. 6.8 28. 24.4 99S500A04 cm [57.0] [7.4] [62.0] /0/0 Weight Distribution 009 02 05 08 02 024 00 06 04 042 048 060 070 Model Vertical Shipping Weight Horizontal Shipping Weight Horizontal Weight Distribution Front Back D E F lb. 0 20 46 2 26 25 kg [50] [54] [2] [] [2] [] lb. 5 25 48 24 27 26 kg [52] [57] [22] [] [2] [2] lb. 65 75 67 4 7 6 kg [75] [79] [] [5] [7] [7] lb. 70 80 69 5 8 8 kg [77] [82] [] [6] [7] [7] lb. na 85 7 6 9 9 kg na [84] [2] [6] [8] [7] lb. 20 245 94 47 52 5 kg [04] [] [4] [22] [24] [2] lb. 240 255 98 49 54 5 kg [09] [6] [44] [22] [25] [24] lb. 265 285 0 55 6 59 kg [20] [29] [50] [25] [28] [27] lb. 275 na na na na na kg [25] na na na na na lb. 285 00 5 58 64 6 kg [29] [6] [52] [26] [29] [28] lb. 290 0 9 60 66 65 kg [2] [4] [54] [27] [0] [29] lb. 5 60 8 70 77 75 kg [52] [6] [6] [2] [5] [4] lb. 80 405 56 78 86 84 kg [72] [84] [7] [6] [9] [8] /0/09

Duct System An air outlet collar is provided on vertical top flow units and all horizontal units to facilitate a duct connection. A flexible connector is recommended for discharge and return air duct connections on metal duct systems. Uninsulated duct should be insulated with a minimum of -inch duct insulation. Application of the unit to uninsulated ductwork in an unconditioned space is not recommended as the unit s performance will be adversely affected. If the unit is connected to existing ductwork, check the duct system to ensure that it has the capacity to accommodate the air required for the unit application. If the duct is too small, as in the replacement of heating only systems, larger ductwork should be installed. All existing ductwork should be checked for leaks and repaired if necessary. The duct system should be sized to handle the design airflow quietly and efficiently. To maximize sound attenuation of the unit blower, the supply and return plenums should include an internal duct liner of fiberglass or constructed of ductboard for the first few feet. On systems employing a sheet metal duct system, canvas connectors should be used between the unit and the ductwork. If air noise or excessive airflow is a problem, the blower speed can be changed. Water Piping The proper water flow must be provided to each unit whenever the unit operates. To assure proper flow, use pressure/temperature ports to determine the flow rate. These ports should be located at the supply and return water connections on the unit. The proper flow rate cannot be accurately set without measuring the water pressure drop through the refrigerant-to-water heat exchanger. All source water connections on commercial units are fittings that accept a male pipe thread (MPT). Insert the connectors by hand, then tighten the fitting with a wrench to provide a leakproof joint. When connecting to an open loop (groundwater) system, thread any copper MPT fitting into the connector and tighten in the same manner as described above. ondensate Drain On vertical units, the internal condensate drain assembly consists of a drain tube which is connected to the drain pan, a /4 in. PV female adapter and a flexible connecting hose. The female adapter may exit either the front or the side of the cabinet. The adapter should be glued to the field-installed PV condensate piping. On vertical units, a condensate hose is inside all cabinets as a trapping loop; therefore, an external trap is not necessary. On horizontal units, a PV stub or stainless steel tube is provided for condensate drain piping connection. An external trap is required (see below). If a vent is necessary, an open stand pipe may be applied to a tee in the fieldinstalled condensate piping. Horizontal Drain onnection (omposite Drain Pan) Unit Pitch for Drain /2 or /4 PV oupling Vent (if needed) /2 or /4 PV /2'' Pitch /2 or /4 PV tube stub.5 in..5 in. /8 in. per foot Tube Stub Drain 2

Water Quality In ground water situations where scaling could be heavy or where biological growth such as iron bacteria will be present, a closed loop system is recommended. The heat exchanger coils in ground water systems may, over a period of time, lose heat exchange capabilities due to a buildup of mineral deposits inside. These can be cleaned, but only by a qualified service mechanic, as special solutions and pumping equipment are required. Hot water generator coils can likewise become scaled and possibly plugged. In areas with extremely hard water, the owner should be informed that the heat exchanger may require occasional flushing. Failure to adhere to the guidelines in the water quality table could result in loss of warranty. Units with cupronickel heat exchangers are recommended for open loop applications due to the increased resistance to build-up and corrosion, along with reduced wear caused by acid cleaning. Material opper 90/0 upronickel 6 Stainless Steel ph Acidity/Alkalinity 7-9 7-9 7-9 Scaling alcium and (Total Hardness) (Total Hardness) (Total Hardness) Magnesium arbonate less than 50 ppm less than 50 ppm less than 50 ppm Hydrogen Sulfide Less than 0.5 ppm (rotten egg smell appears at 0.5 ppm) 0-50 ppm Less than ppm Sulfates Less than 25 ppm Less than 25 ppm Less than 200 ppm hlorine Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm hlorides Less than 20 ppm Less than 25 ppm Less than 00 ppm arbon Dioxide Less than 50 ppm 0-50 ppm 0-50 ppm orrosion Ammonia Less than 2 ppm Less than 2 ppm Less than 20 ppm Ammonia hloride Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm Ammonia Nitrate Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm Ammonia Hydroxide Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm Ammonia Sulfate Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm Total Dissolved Solids (TDS) Less than 000 ppm 000-500 ppm 000-500 ppm LSI Index +0.5 to -0.5 +0.5 to -0.5 +0.5 to -0.5 Iron, FE 2 + (Ferrous) Iron Fouling Bacterial Iron Potential < 0.2 ppm < 0.2 ppm < 0.2 ppm (Biological rowth) Less than ppm, above this Less than ppm, above this Less than ppm, above this Iron Oxide level deposition will occur level deposition will occur level deposition will occur Suspended Solids Erosion Threshold Velocity (Fresh Water) NOTES: rains = ppm divided by 7 mg/l is equivalent to ppm Less than 0 ppm and filtered for max. of 600 micron size Less than 0 ppm and filtered for max. of 600 micron size Less than 0 ppm and filtered for max. of 600 micron size < 6 ft/sec < 6 ft/sec < 6 ft/sec 2/22/2

System leaning and Flushing leaning and Flushing Prior to start up of any heat pump, the water circulating system must be cleaned and flushed of all dirt and debris. If the system is equipped with water shutoff valves, the supply and return runouts must be connected together at each unit location (This will prevent the introduction of dirt into the unit, see Flushing with Water Shutoff Valve Equipped Systems illustration). The system should be filled at the water make-up connection with all air vents open. After filling, vents should be closed. Flushing with Water Shutoff Valve Equipped Systems Return Runout Supply Runout Rubber Hose Runouts Initially onnected Together Mains The contractor should start the main circulator with the pressure reducing valve makeup open. Vents should be checked in sequence to bleed off any trapped air and to verify circulation through all components of the system. As water circulates through the system, the contractor should check and repair any leaks found in the piping system. Drain(s) at the lowest point(s) in the system should be opened for initial flush and blowdown, making sure water fill valves are set at the same rate. heck the pressure gauge at the pump suction and manually adjust the makeup water valve to hold the same positive pressure both before and after opening the drain valves. Flushing should continue for at least two hours, or longer if required, until drain water is clean and clear. The supplemental heater and/or circulator pump, if used, should be shut off. All drains and vents should be opened to completely drain the system. Short-circuited supply and return runouts should now be connected to the unit supply and return connections. Refill the system with clean water. Test the system water for acidity and treat as required to leave the water slightly alkaline (ph 7.5 to 8.5). The specified percentage of antifreeze may also be added at this time. Use commercial grade antifreeze designed for HVA systems only. Environol brand antifreeze is recommended. Once the system has been filled with clean water and antifreeze (if used), precautions should be taken to protect the system from dirty water conditions. Dirty water will result in system-wide degradation of performance, and solids may clog valves, strainers, flow regulators, etc. Additionally, the heat exchanger may become clogged which reduces compressor service life and can cause premature unit failure. In boiler/tower application, set the loop control panel set points to desired temperatures. Supply power to all motors and start the circulating pumps. After full flow has been established through all components including the heat rejector (regardless of season), air vented and loop temperatures stabilized, each of the units will be ready for check, test and start up and for air and water balancing. round Source Loop System heckout Once piping is completed between the unit pumping system and ground loop, final purging and charging of the loop is needed. A high pressure pump is needed to achieve adequate flow velocity in the loop to purge air and dirt particles from the loop itself. Antifreeze solution is used in most areas to prevent freezing. Flush the system adequately to remove as much air as possible; then pressurize the loop to a static pressure of 40-50 PSI (summer) or 50-75 PSI (winter). This is normally adequate for good system operation. Loop static pressure may decrease soon after initial installation, due to pipe expansion and loop temperature change. Running the unit for at least 0 minutes after the system has been completely purged of air will allow for the break-in period. It may be necessary to adjust static loop pressure (by adding water) after the unit has run for the first time. Loop static pressure will also fluctuate with the seasons. Pressures will be higher in the winter months than during the cooling season. This fluctuation is normal and should be considered when charging the system initially. Ensure the pump provides adequate flow through the unit by checking pressure drop across the heat exchanger. Usually 2.25-.0 gpm of flow per ton of cooling capacity is recommended in earth loop applications. 4

Open Loop round Water Systems Typical open loop piping is shown below. Always maintain water pressure in the heat exchanger by placing water control valves at the outlet of the unit to prevent mineral precipitation. Use a closed, bladder-type expansion tank to minimize mineral formation due to air exposure. Insure proper water flow through the unit by checking pressure drop across the heat exchanger and comparing it to the figures in unit capacity data tables in the specification catalog..5-2 gpm of flow per ton of cooling capacity is recommended in open loop applications. Due to only minor differences in flow rate from low to high, only one solenoid valve should be used. The valve should be sized for full flow. Discharge water from the unit is not contaminated in any manner and can be disposed of in various ways, depending on local codes, i.e. recharge well, storm sewer, drain field, adjacent stream or pond, etc. Most local codes forbid the use of sanitary sewer for disposal. onsult your local building and zoning departments to assure compliance in your area. Open System - roundwater Application Unit Supply Aux. Heat Supply Flexible Duct ollar Rubber Bladder Expansion Tank Hot Water enerator onnections Drain Solenoid Valve Flow ontrol Valve (on outlet of Solenoid Valve) Water Out Water In Disconnects (IfApplicable) ompressor Line Voltage Low Voltage to Thermostat and Valve P/T Plugs Vibration Absorbing Pad Strainer Boiler Drains For HX Flushing Shut Off Valves Shut Off Valves (to isolate solenoid valve while acid flushing) 5

Hot Water enerator onnections The heat reclaiming hot water generator coil is of vented double-wall copper construction and is suitable for potable water. To maximize the benefits of the hot water generator a minimum 50-gallon water heater is recommended. For higher demand applications, use an 80-gallon water heater or two 50-gallon water heaters connected in a series as shown below. Electric water heaters are recommended. Make sure all local electrical and plumbing codes are met for installing a hot water generator. A water softener is recommended with hard water (greater than 0 grains or 70 total hardness). Typical Hot Water enerator Installation /4 in. x /4 in. x /2 in. Tee Ball Valve Vent HW Water Out old Water In P/T Relief Valve In Hot Water Out HW Water In Field Installed HW Pump Drain Valve Water Tank Preparation To install a unit with a hot water generator, follow these installation guidelines.. Turn off the power to the water heater. 2. Attach a water hose to the water tank drain connection and run the other end of the hose to an open drain or outdoors.. lose the cold water inlet valve to the water heater tank. 4. Drain the tank by opening the valve on the bottom of the tank, then open the pressure relief valve or hot water faucet. 5. Flush the tank by opening the cold water inlet valve to the water heater to free the tank of sediments. lose when draining water is clear. 6. Disconnect the garden hose and remove the drain valve from the water heater. 7. Refer to Plumbing Installation and Hot Water enerator Startup. Hot Water enerator Installation In Preheat Tank /4 in. x /4 in. x /2 in. Tee Ball Valve HW Water In Vent HW Water Out Field Installed HW Pump old Water In P/T Relief Valve In Drain Valve NOTE: This configuration maximizes hot water generator capability. Hot Water Out P/T Relief Valve AUTION: Elements will burn out if energized dry. Plumbing Installation. Inspect the dip tube in the water heater cold inlet for a check valve. If a check valve is present it must be removed or damage to the hot water generator circulator will occur. 2. Remove drain valve and fitting.. Thread the /4-inch NPT x -/2-inch brass nipple into the water heater drain port. 4. Attach the center port of the /4-inch FPT tee to the opposite end of the brass nipple. 5. Attach the /2-inch copper to /4-inch NPT adaptor to the side of the tee closest to the unit. 6. Install the drain valve on the tee opposite the adaptor. 7. Run interconnecting tubing from the tee to HW water out. 8. ut the cold water IN line going to the water heater. 9. Insert the reducing solder tee in line with cold water IN line as shown. 0. Run interconnecting copper tubing between the unit DHW water IN and the tee (/2-inch nominal). The recommended maximum distance is 50 feet.. To prevent air entrapment in the system, install a vent coupling at the highest point of the interconnecting lines. 2. Insulate all exposed surfaces of both connecting water lines with /8-inch wall closed cell insulation. NOTE: All plumbing and piping connections must comply with local plumbing codes. 6

Hot Water enerator onnections cont. Hot Water enerator Startup. Make sure the power is off to the heat pump. onnect the wire from the hot water generator pump to T on the contactor. 2. lose the drain valve to the water heater.. Open the cold water supply to the tank. 4. Open a hot water faucet in the building to bleed air from the system. lose when full. 5. Open the pressure relief valve to bleed any remaining air from the tank, then close. 6. If so equipped, turn the venting (burping) screw in the center of the pump two (2) turns open (water will drip out), wait until all air is purged from the pump, then tighten the plug. Use vent couplings to bleed air from the lines. 7. arefully inspect all plumbing for water leaks and correct as required. 8. Before restoring electrical supply to the water heater, adjust the temperature setting on the tank. On tanks with both upper and lower elements, the lower element should be turned down to the lowest setting, approximately 00 F. The upper element should be adjusted to 20 F to 0 F. Depending upon the specific needs of the customer, you may want to adjust the upper element differently. On tanks with a single element, lower the thermostat setting to 20 F. 9. After the thermostat(s) is adjusted, replace the access cover and restore electrical supply to the water heater. 0. Make sure that any valves in the hot water generator circuit are open.. Turn on the unit to heating. 2. The HW pump should be running. When the pump is first started, turn the venting (burping) screw (if equipped) in the center of the pump two (2) turns open until water dribbles out, then replace. Allow the pump to run for at least five minutes to ensure that water has filled the circulator properly.. The temperature difference between the water entering and leaving the hot water generator should be 5 F to 5 F. The water flow should be approximately 0.4 gpm per ton of nominal cooling. 4. Allow the unit to heat water for 5 to 20 minutes to be sure operation is normal. AUTION: Never operate the HW circulating pump while dry. If the unit is placed in operation before the hot water generator piping is connected, be sure that the pump wires are disconnected from the contactor. 7

Freeze Detection For Aurora Base ontrol, set SW2-, FP, on the printed circuit board for applications using a closed loop antifreeze solution to 5 F [-9.4 ]. On applications using an open loop/ground water system (or closed loop no antifreeze), set this dip switch to 0 F [-. ], the factory default setting. (Refer to the Dip Switch Field Selection table). For FX0 board, the red wire must be removed from PB2- to change from 0 F [-. ], the factory default setting, to 5 F [-9.4 ]. Electrical onnections eneral Be sure the available power is the same voltage and phase as that shown on the unit serial plate. Line and low voltage wiring must be done in accordance with local codes or the National Electric ode, whichever is applicable. Power onnection onnect the incoming line voltage wires to L and L2 of the contactor for single-phase unit. onsult the Electrical Data tables for correct fuse sizes. 208 Volt Operation All Versatec Ultra Series 208/20 units are factory wired for 20 volt operation. For 208 volt operation, the red and blue transformer wires must be switched on terminal strip PS. AUTION: When installing a unit with an EM blower motor in 460/60/ voltage, a neutral wire is required to allow proper unit operation. Aurora Base ontrol Box FX0 ontrol Box 8

Electrical Data PS Motor Model Rated Voltage Voltage Min/Max ompressor M RLA LRA LRA** 009 208-20/60/ 87/25 6.4 4. 2.0 n/a 0.6 4.7 5.7 0/5 265/60/ 28/292 6.7 4. 22.0 n/a 0.6 4.9 6.0 0/5 02 208-20/60/ 87/25 7.7 4.9 25.0 n/a 0.6 5.5 6.7 0/5 265/60/ 28/292 7.0 4.5 22.0 n/a 0.6 5. 6.2 0/5 05 208-20/60/ 87/25 9.2 5.9 29.0 n/a. 7.0 8.5 0/5 265/60/ 28/292 7.8 5.0 28.0 n/a.0 6.0 7.2 0/5 08 208-20/60/ 87/25 0.4 6.7.5 n/a. 7.8 9.5 5 265/60/ 28/292 8.7 5.6 28.0 n/a.0 6.6 8.0 0/5 208-20/60/ 87/25 2.0.5 58. 2.0.2 4.7 8. 0 02 265/60/ 28/292 4.0 9.0 54.0 n/a. 0. 2.4 20 208-20/60/ 87/25.0 7. 55.0.0.2 8. 0. 5 460/60/ 44/506 5.5.5 28.0 6.8 0.6 4. 5.0 0/5 208-20/60/ 87/25 2.0.5 58. 2.0.2 4.7 8. 0 024 265/60/ 28/292 4.0 9.0 54.0 n/a. 0. 2.4 20 208-20/60/ 87/25.0 7. 55.0.0.2 8. 0. 5 460/60/ 44/506 5.5.5 28.0 6.8 0.6 4. 5.0 0/5 208-20/60/ 87/25 2.0.5 58. 2.0.5 5.0 8.4 0 024* 265/60/ 28/292 4.0 9.0 54.0 n/a.5 0.5 2.8 20 208-20/60/ 87/25.0 7. 55.0.0.5 8.6 0.4 5 460/60/ 44/506 5.5.5 28.0 6.8.0 4.5 5.4 0/5 208-20/60/ 87/25 22.0 4. 7.0 26.0.5 5.6 9. 0 00 265/60/ 28/292 7.5.2 60.0 n/a.5 2.7 5.5 25 208-20/60/ 87/25.9 8.9 58.0 4.8.5 0.4 2.6 20 460/60/ 44/506 6.5 4.2 28.0 6.8.0 5.2 6. 0/5 208-20/60/ 87/25 22.0 4. 7.0 26.0 2.2 6. 9.8 0 00* 265/60/ 28/292 7.5.2 60.0 n/a 2.0.2 6.0 25 208-20/60/ 87/25.9 8.9 58.0 4.8 2.2.. 20 460/60/ 44/506 6.5 4.2 28.0 6.8. 5. 6.4 0/5 208-20/60/ 87/25 27.0 7. 96.7 4.0 2.2 9.5 2.8 40 06 265/60/ 28/292 9.0 2.2 72.0 n/a.. 6. 20 208-20/60/ 87/25 20.0 2.8 95.0 57.0 2.2 5.0 8.2 0 460/60/ 44/506 0.0 6.4 45.0 27.0. 7.5 9. 5 208-20/60/ 87/25.0 20.0 5.0 4.0.5 2.5 28.5 45 04 208-20/60/ 87/25 20.0 2.8 95.0 57.0.5 6. 9.5 0 460/60/ 44/506 0.0 6.4 45.0 27.0.8 8.2 9.8 5 575/60/ 57/6 8.5 5.4 8.0 n/a.4 6.8 8.2 0/5 208-20/60/ 87/25.0 20.0 5.0 4.0.5 2.5 28.5 45 042 208-20/60/ 87/25 20.0 2.8 95.0 57.0.5 6. 9.5 0 460/60/ 44/506 0.0 6.4 45.0 27.0.8 8.2 9.8 5 575/60/ 57/6 8.5 5.4 8.0 n/a.4 6.8 8.2 0/5 208-20/60/ 87/25.0 20.0 5.0 4.0 4.6 24.6 29.6 45 042* 208-20/60/ 87/25 20.0 2.8 95.0 57.0 4.6 7.4 20.6 0 460/60/ 44/506 0.0 6.4 45.0 27.0 2. 8.7 0. 5 575/60/ 57/6 8.5 5.4 8.0 n/a.9 7. 8.7 0/5 208-20/60/ 87/25 2.0 2.0 5.0 4.0.5 24.5 29.8 50 048 208-20/60/ 87/25 25.0 6.0 5.0 69.0.5 9.5 2.5 5 460/60/ 44/506 2.0 7.7 50.0 0.0.8 9.5.4 5 208-20/60/ 87/25 2.0 2.0 5.0 4.0 4.6 25.6 0.9 50 048* 208-20/60/ 87/25 25.0 6.0 5.0 69.0 4.6 20.6 24.6 40 460/60/ 44/506 2.0 7.7 50.0 0.0 2. 0.0.9 5 575/60/ 57/6 0.0 6.4 40.0 n/a.9 8. 9.9 5 208-20/60/ 87/25 4.0 26. 50.0 5.0 5.9 2. 8.8 60 060 208-20/60/ 87/25 27.5 7.6 20.0 72.0 5.9 2.5 27.9 45 460/60/ 44/506.0 8. 70.0 42.0.0..4 20 575/60/ 57/6.5 7.4 5.0 n/a.9 9..2 5 208-20/60/ 87/25 47.0 0. 45.0 5.0 5.9 6.0 4.5 70 070 208-20/60/ 87/25 28.0 7. 20.0 72.0 5.9 2.2 27.5 40 460/60/ 44/506 5.0 9.6 70.0 42.0.0 2.6 5.0 20 575/60/ 57/6 2.5 8.0 5.0 n/a.9 9.9.9 5 HAR circuit breaker in USA only * With optional high-static PS motor ** With optional IntelliStart TM 0/2/ NOTE: High-static option not available on all model sizes. 9 Blower Motor FLA Total Unit FLA Min irc Amp Max Fuse/ HAR

Electrical Data cont. 5-Speed EM Motor Model Rated Voltage Voltage Min/Max ompressor M RLA LRA LRA** Blower Motor FLA Total Unit FLA Min irc Amp Max Fuse/ HAR 05 208-20/60/ 87/25 9.2 5.9 29.0 n/a 4. 0.0.5 5 265/60/ 28/292 7.8 5.0 28.0 n/a.6 8.6 9.9 0/5 08 208-20/60/ 87/25 0.4 6.7.5 n/a 4. 0.8 2.5 5 265/60/ 28/292 8.7 5.6 28.0 n/a.6 9.2 0.6 5 208-20/60/ 87/25 2.0.5 58. 2.0 4. 7.6 2.0 0 02 265/60/ 28/292 4.0 9.0 54.0 n/a.6 2.6 4.9 20 208-20/60/ 87/25.0 7. 55.0.0 4..2.0 20 460/60/ 44/506 5.5.5 28.0 6.8 2. 5.6 6.5 0/5 208-20/60/ 87/25 2.0.5 58. 2.0 4. 7.6 2.0 0 024 265/60/ 28/292 4.0 9.0 54.0 n/a.6 2.6 4.9 20 208-20/60/ 87/25.0 7. 55.0.0 4..2.0 20 460/60/ 44/506 5.5.5 28.0 6.8 2. 5.6 6.5 0/5 208-20/60/ 87/25 22.0 4. 7.0 26.0 4. 8.2 2.7 5 00 265/60/ 28/292 7.5.2 60.0 n/a.6 4.8 7.6 25 208-20/60/ 87/25.9 8.9 58.0 4.8 4..0 5.2 20 460/60/ 44/506 6.5 4.2 28.0 6.8 2. 6. 7.4 0/5 208-20/60/ 87/25 27.0 7. 96.7 4.0 4. 2.4 25.7 40 06 265/60/ 28/292 9.0 2.2 72.0 n/a.6 5.8 8.9 0 208-20/60/ 87/25 20.0 2.8 95.0 57.0 4. 6.9 20. 0 460/60/ 44/506 0.0 6.4 45.0 27.0 2. 8.5 0. 5 208-20/60/ 87/25.0 20.0 5.0 4.0 7.6 27.6 2.6 50 04 208-20/60/ 87/25 20.0 2.8 95.0 57.0 7.6 20.4 2.6 0 460/60/ 44/506 0.0 6.4 45.0 27.0 4.0 0.4 2.0 5 208-20/60/ 87/25.0 20.0 5.0 4.0 7.6 27.6 2.6 50 042 208-20/60/ 87/25 20.0 2.8 95.0 57.0 7.6 20.4 2.6 0 460/60/ 44/506 0.0 6.4 45.0 27.0 4.0 0.4 2.0 5 208-20/60/ 87/25 2.0 2.0 5.0 4.0 7.6 28.6.9 50 048 208-20/60/ 87/25 25.0 6.0 5.0 69.0 7.6 2.6 27.6 40 460/60/ 44/506 2.0 7.7 50.0 0.0 4.0.7.6 20 208-20/60/ 87/25 4.0 26. 50.0 5.0 7.6.9 40.5 60 060 208-20/60/ 87/25 27.5 7.6 20.0 72.0 7.6 25.2 29.6 45 460/60/ 44/506.0 8. 70.0 42.0 4.0 2. 4.4 25 208-20/60/ 87/25 47.0 0. 45.0 5.0 7.6 7.7 45.2 70 070 208-20/60/ 87/25 28.0 7. 20.0 72.0 7.6 24.9 29.2 45 460/60/ 44/506 5.0 9.6 70.0 42.0 4.0.6 6.0 25 HAR circuit breaker in USA only 0/2/ ** With optional IntelliStart TM 20

Electrical Data cont. Variable Speed EM Motor Model Rated Voltage Voltage Min/Max ompressor M RLA LRA LRA** Blower Motor FLA 05 208-20/60/ 87/25 9.2 5.9 29.0 n/a 4.0 9.9.4 5 265/60/ 28/292 7.8 5.0 28.0 n/a 4. 9. 0. 5 08 208-20/60/ 87/25 0.4 6.7.5 n/a 4.0 0.7 2.4 5 265/60/ 28/292 8.7 5.6 28.0 n/a 4. 9.7. 5 208-20/60/ 87/25 2.0.5 58. 2.0 4.0 7.5 20.9 0 02 265/60/ 28/292 4.0 9.0 54.0 n/a 4.. 5.4 20 208-20/60/ 87/25.0 7. 55.0.0 4.0. 2.9 5 460/60/ 44/506 5.5.5 28.0 6.8 4. 7.6 8.5 0/5 208-20/60/ 87/25 2.0.5 58. 2.0 4.0 7.5 20.9 0 024 265/60/ 28/292 4.0 9.0 54.0 n/a 4.. 5.4 20 208-20/60/ 87/25.0 7. 55.0.0 4.0. 2.9 5 460/60/ 44/506 5.5.5 28.0 6.8 4. 7.6 8.5 0/5 208-20/60/ 87/25 22.0 4. 7.0 26.0 4.0 8. 2.6 5 00 265/60/ 28/292 7.5.2 60.0 n/a 4. 5. 8. 25 208-20/60/ 87/25.9 8.9 58.0 4.8 4.0 2.9 5. 20 460/60/ 44/506 6.5 4.2 28.0 6.8 4. 8. 9.4 0/5 208-20/60/ 87/25 27.0 7. 96.7 4.0 4.0 2. 25.6 40 06 265/60/ 28/292 9.0 2.2 72.0 n/a 4. 6. 9. 0 208-20/60/ 87/25 20.0 2.8 95.0 57.0 4.0 6.8 20.0 0 460/60/ 44/506 0.0 6.4 45.0 27.0 4. 0.5 2. 5 208-20/60/ 87/25.0 20.0 5.0 4.0 4.0 24.0 29.0 45 04 208-20/60/ 87/25 20.0 2.8 95.0 57.0 4.0 6.8 20.0 0 460/60/ 44/506 0.0 6.4 45.0 27.0 4. 0.5 2. 5 208-20/60/ 87/25.0 20.0 5.0 4.0 4.0 24.0 29.0 45 042 208-20/60/ 87/25 20.0 2.8 95.0 57.0 4.0 6.8 20.0 0 460/60/ 44/506 0.0 6.4 45.0 27.0 4. 0.5 2. 5 208-20/60/ 87/25.0 20.0 5.0 4.0 7.0 27.0 2.0 50 042* 208-20/60/ 87/25 20.0 2.8 95.0 57.0 7.0 9.8 2.0 5 460/60/ 44/506 0.0 6.4 45.0 27.0 6.9. 4.9 20 208-20/60/ 87/25 2.0 2.0 5.0 4.0 4.0 25.0 0. 50 048 208-20/60/ 87/25 25.0 6.0 5.0 69.0 4.0 20.0 24.0 40 460/60/ 44/506 2.0 7.7 50.0 0.0 4..8.7 20 208-20/60/ 87/25 2.0 2.0 5.0 4.0 7.0 28.0. 50 048* 208-20/60/ 87/25 25.0 6.0 5.0 69.0 7.0 2.0 27.0 40 460/60/ 44/506 2.0 7.7 50.0 0.0 6.9 4.6 6.5 20 208-20/60/ 87/25 4.0 26. 50.0 5.0 7.0. 9.9 60 060 208-20/60/ 87/25 27.5 7.6 20.0 72.0 7.0 24.6 29.0 45 460/60/ 44/506.0 8. 70.0 42.0 6.9 5.2 7. 25 208-20/60/ 87/25 47.0 0. 45.0 5.0 7.0 7. 44.6 70 070 208-20/60/ 87/25 28.0 7. 20.0 72.0 7.0 24.9 29.4 45 460/60/ 44/506 5.0 9.6 70.0 42.0 6.9 6.5 8.9 25 HAR circuit breaker in USA only 0/2/ * With optional HP EM motor ** With optional IntelliStart TM Total Unit FLA Min irc Amp Max Fuse/ HAR AUTION: When installing a unit with a variable speed EM blower motor in 460/60/ voltage, a neutral wire is required to allow proper unit operation. 2

Blower Performance Data Standard PS Motor Model 009 Blower Spd Blower Size Motor hp Airflow (cfm) at External Static Pressure (in. wg) 0 0.05 0.0 0.5 0.20 0.25 0.0 0.5 0.40 0.45 0.50 0.60 0.70 0.80 0.90.00 50 55 500 485 470 450 40 405 85 55 0 - - - - - H MH 475 460 450 45 420 405 85 65 45 20 00 - - - - - 6 x 8 /0 ML* 45 420 40 95 80 65 45 25 00 - - - - - - - L 70 55 40 25 0 290 275 - - - - - - - - - H 50 55 500 485 470 450 40 405 85 55 0 - - - - - 02 MH* 475 460 450 45 420 405 85 65 45 20 00 - - - - - 6 x 8 /0 ML 45 420 40 95 80 65 45 25 00 - - - - - - - L 70 55 40 25 0 290 275 - - - - - - - - - H 875 860 845 80 820 805 790 770 750 725 700 - - - - - 05 M 9 x 7 /6 760 750 740 70 720 70 700 680 660 640 620 - - - - - L 60 620 60 600 590 580 570 560 550 520 490 - - - - - H 875 860 845 80 820 805 790 770 750 725 700 - - - - - 08 M 9 x 7 /6 760 750 740 70 720 70 700 680 660 640 620 - - - - - L 60 620 60 600 590 580 570 560 550 520 490 - - - - - H 020 990 960 90 900 870 850 80 800 770 690 - - - - - 02 M 9 x 7 /5 960 840 820 800 780 760 740 720 690 670 - - - - - - L 720 700 680 650 640 620 600 580 570 550 - - - - - - H 065 045 00 005 975 950 925 900 870 85 800 - - - - - 024 M 9 x 7 /5 880 865 850 80 85 795 775 750 725 700 670 - - - - - L 805 790 780 765 745 725 70 685 660 60 600 - - - - - H 240 220 200 75 50 0 080 055 00 975 920 840 70 - - - 00 M 9 x 7 / 095 085 080 060 045 020 995 960 925 885 850 785 675 - - - L 860 860 855 850 850 845 845 825 805 775 750 680 - - - - H 60 40 20 290 260 220 85 0 080 045 00 90 855 - - - 06 M 9 x 7 /2 205 90 70 45 20 085 050 05 980 940 900 845 - - - - L 070 060 050 05 020 995 970 940 90 875 840 780 - - - - H 655 65 65 590 570 55 500 425 50 270 85 080 970 - - - 04 M 0x0 /2 470 455 445 425 40 80 50 285 240 205 70 905 - - - - L 50 40 0 0 090 050 00 970 90 900 865 800 - - - - H 705 685 665 645 625 595 565 50 500 450 405 260 40 - - - 042 M 0 x 0 /2 485 475 465 445 40 40 90 50 5 260 20 0 00 - - - L 80 65 50 5 20 090 060 00 000 965 920 855 - - - - H 90 90 885 860 80 790 750 70 665 620 580 280 25 - - - 048 M 0 x 0 /2 580 565 550 55 525 505 485 445 40 0 25 0 00 - - - L 80 70 60 40 20 00 080 050 020 970 90 875 - - - - H 260 20 200 2270 2240 225 290 260 20 2095 2060 985 920 855 - - 060 M x 0 265 20 2095 2070 2050 200 200 985 965 90 900 850 775 700 - - L 965 940 920 900 885 870 855 825 800 780 760 720 625 50 - - H 2450 245 2420 295 270 240 20 2280 2250 2225 2200 2040 2000 950 - - 070 M x 0 225 290 270 255 240 220 2095 2070 2045 205 990 940 876 795 - - L 2005 990 975 960 950 940 925 90 890 865 845 780 70 565 - - Factory settings are in Bold 7/6/0 Airflow values are with dry coil and standard filter For wet coil performance first calculate the face velocity of the air coil (Face Velocity [fpm] = Airflow [cfm] / Face Area [sq ft]). Then for velocities of 200 fpm reduce the static capability by 0.0 in. wg, 00 fpm by 0.08 in. wg, 400 fpm by 0.2in. wg. and 500 fpm by 0.6 in. wg. Optional High Static PS Motor Model 024 00 042 Blower Spd Blower Size Motor hp Airflow (cfm) at External Static Pressure (in. wg) 0 0.05 0.0 0.5 0.20 0.25 0.0 0.5 0.40 0.45 0.50 0.60 0.70 0.80 0.90.00 H 240 220 200 75 50 0 080 055 00 975 920 840 70 - - - M 9 x 7 / 095 085 080 060 045 020 995 960 925 885 850 785 675 - - - L 860 860 855 850 850 845 845 825 805 775 750 680 - - - - H 40 20 00 270 240 200 60 5 070 025 985 880 - - - - M 9 x 7 /2 85 75 65 0 095 065 05 000 965 920 880 795 - - - - L 050 040 00 05 000 980 960 925 895 855 85 - - - - - H 2095 2080 2060 2020 980 950 920 880 840 780 725 550 5 20 - - M 0 x 0 /4 960 940 920 890 865 80 800 760 725 670 620 45 00 - - - L 800 780 760 740 725 695 670 625 585 525 465 00 200 - - - H 2095 2080 2060 2020 980 950 920 880 840 780 725 550 5 20 - - 048 M 0 x 0 /4 960 940 920 890 865 80 800 760 725 670 620 45 00 - - - L 800 780 760 740 725 695 670 625 585 525 465 00 200 - - - Factory settings are in Bold 7/6/0 Airflow values are with dry coil and standard filter For wet coil performance first calculate the face velocity of the air coil (Face Velocity [fpm] = Airflow [cfm] / Face Area [sq ft]). Then for velocities of 200 fpm reduce the static capability by 0.0 in. wg, 00 fpm by 0.08 in. wg, 400 fpm by 0.2in. wg. and 500 fpm by 0.6 in. wg. * Setting for 265 V operation. 22

Setting Blower Speed - PS HIH MEDIUM LOW AUTION: Disconnect all power before performing this operation. FAN SPEED WIRE PS BLOWER MOTOR BODY 2

Blower Performance Data cont. 5-Speed EM Motor Model Motor Speed Motor Tap Blower Size Motor HP Airflow (cfm) at External Static Pressure (in. wg) 0 0.05 0.0 0.5 0.20 0.25 0.0 0.5 0.40 0.45 0.50 0.60 0.70 0.80 0.90.00 High 5 95 895 880 865 850 80 85 805 795 775 750 70 695 640 - - Med High 4 805 785 765 750 740 725 705 685 665 655 65 605 55 - - - 05 Med 9 x 7 /2 725 75 700 680 660 65 65 600 585 560 55 485 - - - - Med Low 2 695 675 650 60 60 590 575 550 525 490 455 - - - - - Low 655 600 550 50 508 490 475 45 95 50 - - - - - - High 5 95 895 880 865 850 80 85 805 795 775 750 70 695 640 - - Med High 4 805 785 765 750 740 725 705 685 665 655 65 605 55 - - - 08 Med 9 x 7 /2 725 75 700 680 660 65 65 600 585 560 55 485 - - - - Med Low 2 695 675 650 60 60 590 575 550 525 490 455 - - - - - Low 655 600 550 50 508 490 475 45 95 50 - - - - - - High 5 980 960 940 90 920 905 890 875 860 840 820 800 745 - - - Med High 4 890 878 865 845 825 8 800 785 770 75 75 70 665 - - - 02 Med 9 x 7 /2 80 85 800 788 775 755 75 72 70 690 670 640 600 - - - Med Low 2 780 760 740 70 665 65 640 620 600 585 570 - - - - - Low 625 59 560 55 50 495 480 455 40 40 90 - - - - - High 5 980 960 940 90 920 905 890 875 860 840 820 800 745 - - - Med High 4 890 878 865 845 825 8 800 785 770 75 75 70 665 - - - 024 Med 9 x 7 /2 80 85 800 788 775 755 75 72 70 690 670 640 600 - - - Med Low 2 780 760 740 70 665 65 640 620 600 585 570 - - - - - Low 625 59 560 55 50 495 480 455 40 40 90 - - - - - High 5 40 0 280 240 200 70 40 095 050 05 980 900 800 - - - Med High 4 0 5 00 085 070 057 044 022 000 970 940 870 780 - - - 00 Med 9 x 7 /2 00 005 980 965 950 95 920 900 880 870 860 80 750 - - - Med Low 2 960 945 90 95 900 885 870 855 840 825 80 790 740 - - - Low 790 765 740 725 70 690 670 660 650 60 60 580 500 - - - High 5 70 45 20 285 250 220 90 58 25 085 045 960 - - - - Med High 4 265 25 240 220 200 75 50 20 090 05 05 - - - - - 06 Med 9 x 7 /2 60 4 25 00 085 070 055 040 020 000 - - - - - Med Low 2 0 095 080 065 050 08 025 008 990 980 970 - - - - - Low 825 80 780 770 760 740 720 705 690 670 650 - - - - - High 5 840 825 80 790 770 745 720 700 680 660 640 600 570 50 480 - Med High 4 70 7 695 670 645 62 600 575 550 55 520 480 440 90 50-04 Med x 0 60 60 590 56 55 5 490 470 450 425 400 70 0 290 - - Med Low 2 550 520 490 465 440 45 90 70 50 0 0 260 220 80 - - Low 80 40 00 275 250 225 200 75 50 25 00 00 980 820 - - High 5 840 825 80 790 770 745 720 700 680 660 640 600 570 50 480 - Med High 4 70 7 695 670 645 62 600 575 550 55 520 480 440 90 50-042 Med x 0 60 60 590 56 55 5 490 470 450 425 400 70 0 290 - - Med Low 2 550 520 490 465 440 45 90 70 50 0 0 260 220 80 - - Low 80 40 00 275 250 225 200 75 50 25 00 00 980 820 - - High 5 2060 2045 200 205 2000 970 940 925 90 890 870 80 800 750 740 - Med High 4 880 860 840 825 80 785 760 740 720 705 690 640 60 570 55-048 Med x 0 790 770 750 70 70 685 660 640 620 600 580 550 50 460 - - Med Low 2 670 650 60 605 580 555 50 50 490 470 450 40 70 40 - - Low 40 405 80 5 25 0 280 255 20 20 90 0 070 925 - - High 5 2400 260 20 25 200 2290 2285 2275 2265 2250 220 2200 265 20 2080 200 Med High 4 280 260 240 20 220 205 2090 2075 2060 2045 200 2000 960 90 890 850 060 Med x 0 2080 2050 2020 200 2000 985 970 955 940 925 90 870 840 800 760 720 Med Low 2 90 920 90 89 875 86 850 8 85 798 780 740 700 660 620 590 Low 750 75 720 698 675 658 640 620 600 58 565 525 490 450 40 50 High 5 2400 260 20 25 200 2290 2285 2275 2265 2250 220 2200 265 20 2080 200 Med High 4 280 260 240 20 220 205 2090 2075 2060 2045 200 2000 960 90 890 850 070 Med x 0 2080 2050 2020 200 2000 985 970 955 940 925 90 870 840 800 760 720 Med Low 2 90 920 90 89 875 86 850 8 85 798 780 740 700 660 620 590 Low 750 75 720 698 675 658 640 620 600 58 565 525 490 450 40 50 Factory settings are in Bold 0/2/ Airflow values are with dry coil and standard in. filter ISO/AHRI rating point on the US*070 will require moving the red wire on the motor to high speed (tap 5) and disconnecting the tan wire from tap 5. Setting Blower Speed - 5-Speed EM 5-speed EM blower motors have five (5) speeds of which three () are selectable on single speed and four (4) are selectable on dual capacity. 5-Speed EM Motor onnections AUTION: Disconnect all power before performing this operation. 24

5-Speed EM onstant Torque Motors The 5-speed EM is a onstant Torque EM motor and delivers air flow similar to a PS but operates as efficiently as an variable speed EM motor. Because it s an EM Motor, the 5-speed EM can ramp slowly up or down like the variable speed EM motor. There are 5 possible speed taps available on the 5-speed motor with # being the lowest airflow and #5 being the highest airflow. These speed selections are preset at the time of manufacture and are easily changed in the field if necessary. 5-Speed EM Benefits: - High efficiency - Soft start - 5 speeds with up to 4 speeds on-line - Built in logic allows air flow to change with, Y, Y2 and W signals - Super efficient low airflow continuous blower setting () If more than one tap are energized at the same time, built in logic gives precedence to the highest tap number and allows air flow to change with, Y, Y2 and W signals. Each of those 5 speeds has a specific Torque value programmed into the motor for each speed selection. As static pressure increases, airflow decreases resulting in less torque on the rotor. The motor responds only to changes in torque and adjusts its speed accordingly. The 5-speed motor is powered by line voltage but the motor speed is energized by 24VA. Power onnection - /6 in. quick connects - Line (orange wire) to L, round (green wire) to, Line 2 (for 208V-20V units) to N (brown wire). Signal onnection - /4 in. quick connects - ommon to, 24VA to Taps #-5. Applying 24VA power between any of the motor taps -5 (/4 in. quick connects) and common will signal the motor to run and regulate torque at the programmed level. The tap input voltage must be in the range 2-VA. The 5-speed EM will have less variation over the operating static pressure range versus a PS motor as well as a significant watts reduction due to the high motor efficiency. Thermal Protection - Motor is electronically protected. Locked Rotor Amps - If motor speed decreases below a programmed stall speed, the motor will shut down and after a delay period, the control will attempt to restart the motor. The 5-speed EM speed tap selections are as follows: The blue wire should be placed on the speed tap desired for the () continuous blower setting factory wired to Tap. The red wire should be placed on the speed tap desired during compressor operation (Y signal) factory wired to Tap or 4. The gray wire is not factory wired to the motor and is tied to the wire harness. It is field connected and can be used with ht/2cl thermostats or IntelliZone to deliver the required air flow for the Y2 signal. The tan wire should be placed on the speed tap desired for auxiliary heat (W signal) factory wired to Tap 5. 25

Blower Performance Data cont. Variable Speed EM Motor Model Max esp 05 0.50 08 0.50 02 0.50 024 0.50 00 0.50 06 0.50 04 0.50 042 0.50 042 w/hp* 0.75 048 0.50 048 w/hp* 0.75 060 0.75 070 0.75 Airflow DIP Switch Settings 2 4 5 6 7 8 9 0 2 00 400 500 600 700 L M H 00 400 500 600 700 800 L M H 400 500 600 700 800 900 000 00 200 L M H 400 500 600 700 800 900 000 00 200 L M H 400 500 600 700 800 900 000 00 200 L M H 600 700 800 900 000 00 50 225 00 L M H 650 750 850 950 050 50 250 25 75 475 550 600 L M H 650 750 850 950 050 50 250 25 75 475 550 600 L M H 800 000 00 00 500 600 800 L M H 650 750 850 950 050 50 250 25 75 475 550 600 L M H 800 000 00 00 500 600 800 L M H 750 900 000 200 400 600 700 850 2000 2200 200 2400 L M H 800 950 00 00 500 750 950 200 200 L M H /0/09 Factory settings are at recommended L-M-H DIP switch locations. Shaded regions are recommended for best performance. It is acceptable to operate outside of this area as long as the WSHP operates within the guidlines of the Operating Limits table and orrection Factor tables. Lowest and Highest DIP switch settings are assumed to be L and H respectively. FM is controlled within ±5% up to the maximum esp. Max esp includes allowance for wet coil and standard filter 26

Setting Blower Speed - Variable Speed EM - Aurora ontrols Setting Blower Speed - Variable Speed EM The AB board s Yellow onfig LED will flash the current variable speed EM blower speed selections for low, med, and high continuously with a short pause in between. The speeds can also be confirmed with the AID Tool under the Setup/EM Setup screen. The variable speed EM blower motor speeds can be field adjusted with or without using an AID Tool. Variable Speed EM Setup with an AID Tool cont. EM SPEED INFO LOW SPEED: MED SPEED: 5 HIH SPEED: 7 Selecting YES will enter variable speed EM speed setup, while selecting NO will return to the previous screen. Variable Speed EM Setup without an AID Tool The blower speeds for Low ( only), Med (Y), and High (Y2/Aux) can be adjusted directly at the Aurora AB board which utilizes the push button (SW) on the AB board. This procedure is outlined in the Variable Speed EM onfiguration Mode portion of the Aurora Base ontrol System section. Variable Speed EM Setup with an AID Tool A much easier method utilizes the AID Tool to change the airflow using the procedure below. First navigate to the Setup screen and then select EM Setup. This screen displays the current variable speed EM settings. It allows the technician to enter the setup screens to change the variable speed EM settings. hange the highlighted item using the and buttons and then press the button to select the item. WANT TO HANE? YES OPTION NO ENTER Variable Speed EM Speed Setup - These screens allow the technician to select the low, medium, and high blower speed for the variable speed EM blower motor. hange the highlighted item using the and buttons. Press the button to select the speed. EM SPEED INFO 2 < LOW 4 5 6 7 8 9 0 2 EM SPEED INFO 2 LOW 4 5 < MED 6 7 8 9 0 2 EM SPEED INFO 2 LOW 4 5 MED 6 7 8 9 0 2 < HIH OPTION ENTER OPTION ENTER OPTION ENTER After the high speed setting is selected the AID Tool will automatically transfer back to the EM Setup screen. Setting Blower Speed - Variable Speed EM - FX0 ontrols Variable speed EM blower motors have 2 selectable speeds and are factory set for optimum performance. To change speeds, using a Medium User Interface (MUI) enter the MAINT menu to adjust the 2 soft switches. When applicable, the speed settings may also be adjusted through the Building Automation System (BAS). AUTION: Disconnect all power before performing this operation. 27

2 VERSATE ULTRA SERIES INSTALLATION MANUAL Wiring Schematics Aurora Base ontrol 208-20/60/ PS with IntelliStart ompressor rn P PS Blower Motor H M L Brn Wht ap Airflow Settings White S Blue Blue R Black ap Red Tan Pink T2 T L2 L Black Black (95) Red Pink Blue Black reen (9) Note round Neutral Disconnect L Run Winding Active Start Winding ommon Winding L Soft Start Unit Power Supply 208-20/60/ Black RB Black Red (97) L2 L2 Note 2 Red 208V L L Blue 20V Black Transformer 24V Yellow Black/White Resistor RB RV FD T LP HP RV Note Isolation Valve White (2) Black () Violet (4) Black (5) Orange (0) Orange (02) Yellow Yellow Blue (07) Blue (08) Black (09) Black (0) 2 Red (5) reen (50) White (52) Red (5) Note P2 P DH W Y2 Y O/B R LO P9 R F F 2 2 2 HI LO ES LS ALM AL A OM A NO A N LO R O/B Y Y2 W DH Accessory Relay Operation SW2-4 SW2-5 ycle with Blower On On ycle with ompressor Off Off Water Valve Slow Open On Off Outdoor Air Damper Off On R F K5 K6 reen LED4 RS485 NET Aurora Timing Events Event Normal Mode Test Mode Random Start Delay 5 to 80 seconds second ompressor On Delay 5 seconds < second ompressor Minimum On Time 2 minutes 5 seconds ompressor Short ycle Delay 4 minutes 5 seconds Blower Off Delay 0 seconds 2 seconds Fault Recognition Delay High Pressure Less than second Less than second Start-Up Bypass Low Pressure 2 minutes 0 seconds Fault Recognition Delay Low Pressure 0 seconds 0 seconds Start-Up Bypass Low Water/Air oil Limit 2 minutes 0 seconds Fault Recognition Delay Low Water/Air oil Limit 0 seconds 0 seconds Fault Recognition Delay ondensate Overflow 0 seconds 0 seconds Thermostat all Recognition Time 2 seconds 2 seconds Auxiliary Heat Staging Delay 5 minutes 20 seconds Emergency Heat Staging Delay 2 minutes 7.5 seconds Water Valve Slow Open Delay 90 seconds 90 seconds Reheat Delay 0 seconds 0 seconds P8 JW2 LED5 RS485 NET K4 R A- B+ P7 K2 K RS485 EXP P5 Aurora Base ontrol (AB) REV REV FP FP FP2 FP2 LPS LPS HPS HPS P4 SW R A- B+ P6 N/A O EH EH2 P Brown (2) ondensate K Status Y Fault R PWM P Off On FP 5 F/0 F FP2 5 F/0 F 2 RV B/O Acc Dip 4 Acc Dip 2 5 Dual/Single 6 L Pulse/ontinuous 7 Reheat/Normal 8 SW2 Aurora LED Flash odes Slow Flash second on and second off Fast Flash 00 milliseconds on and 00 milliseconds off Flash ode 00 milliseconds on and 400 milliseconds off with a 2 second pause before repeating Random Start Delay Status LED (LED, reen) Fast Flash onfiguration LED (LED2, Yellow) Fast Flash Fault LED (LED, Red) Fast Flash Status LED (LED, reen) onfiguration LED (LED2, Yellow) Fault LED (LED, Red) Normal Mode ON No Software Overide Flash EM Setting Normal Mode OFF ontrol is Non-Functional OFF DIP Switch Overide Slow Flash Input Fault Lockout Flash ode Test Mode Slow Flash EM onfigure Mode Fast Flash High Pressure Lockout Flash ode 2 Lockout Active Fast Flash Reset onfigure Mode Off Low Pressure Lockout Flash ode Dehumidification Mode Flash ode 2 Low Air oil Limit Lockout - FP2 Flash ode 4 Reserved Flash ode Low Water oil Limit Lockout - FP Flash ode 5 Reserved Flash ode 4 Reserved Flash ode 6 Load Shed Flash ode 5 ondensate Overflow Lockout Flash ode 7 ESD Flash ode 6 Over/Under Voltage Shutdown Flash ode 8 Reserved Flash ode 7 Reserved Flash ode 9 Reserved Flash ode 0 Air/Water oil Limit Sensor Error Flash ode onfig Y FM R F Black/White Yellow Optional, factory installed unit mounted disconnect. 2 Swap blue and red leads for 208V operation. Optional, factory installed internal isolation valve. L Factory Low Voltage Wiring Factory Line Voltage Wiring Field Low Voltage Wiring Field Line Voltage Wiring Optional Block D Voltage PB Traces Field Zone Sensor Wiring Internal Junction Quick onnect Terminal Field Wiring Lug round Relay ontacts N.O., N.. apacitor Fuse ompressor ontactor O ondensate Overflow Sensor ES Emergency Shutdown HP High Pressure Switch LP Low Pressure Switch FD Freeze Detection Sensor F Fuse Notes: Legend T Y R Thermistor Relay oil Switch - ondensate Overflow Switch - High pressure Switch - Low pressure Polarized connector SW Push button SW2 DIP package 8 position RB Blower Relay RV Reversing Valve oil Light Emitting Diode - reen Light Emitting Diode - Yellow Light Emitting Diode - Red 97P87-02 /08/0 28

L T 2 VERSATE ULTRA SERIES INSTALLATION MANUAL Wiring Schematics cont. Aurora Base ontrol 460/60/ 5-Speed EM T T Note 4 Red T2 Black Phase uard Monitor (PM) L L2 L L T Yellow T2 L2 L T Unit Power Supply 460/60/ Black (7) White (8) Red (9) Note reen (9) round Neutral Disconnect Black (95) L L Yellow (96) L2 L2 Red (97) L L reen Note 5 Blue 460V Black Brown Orange N 5-Speed EM Blower Motor PM Y-OUT Y Yellow Transformer 24V Black/White 5 4 2 Note 5 Yellow (9) Black/White (92) ray (0) Tan () Note 6 Red (2) Blue () RV Resistor FD LP HP Black (5) RV Note 2 Isolation Valve 2 Red (5) reen (50) White (52) Red (5) Note 2 P2 P R ES LS ALM AL LO O/B Y2 W DH DH W Y2 Y O/B R LO P9 R F F 2 HI A OM A NO A N R Y F K5 K6 LED4 RS485 NET P8 JW2 LED5 RS485 NET K4 R A- B+ P7 Violet (4) K2 Black (5) K 2 LO 2 RS485 EXP P5 Aurora Base ontrol (AB) R A- B+ P6 N/A O EH REV REV FP FP FP2 FP2 LPS LPS HPS HPS K Orange (0) SW Orange (02) EH2 Yellow P Yellow Status Y Blue (07) Fault R P4 FP 5 F/0 F FP2 5 F/0 F RV B/O Acc Dip Acc Dip 2 Dual/Single L Pulse/ontinuous Reheat/Normal Blue (08) Black (09) onfig Y Black (0) Off PWM FM P SW2 R F On 2 4 5 6 7 8 Black/White Yellow 5-Speed EM Low Voltage onnections Model TAP- TAP-2 TAP- TAP-4 TAP-5 05 Blue Red ray 08 Blue Red ray 02 Blue Red ray 024 Blue Red ray 00 Blue Red ray 06 Blue Red ray 04 Blue Red ray 042 Blue Red ray 048 Blue Red ray 060 Blue Red ray 070 Blue Red ray Notes: - Optional, factory installed unit mounted disconnect. 2 - Optional, factory installed internal isolation valve. - Optional, factory installed phase guard. 4 - Optional, factory installed phase guard. The yellow transformer wire shall be connected directly to the PU board, if this option is not installed. 5 - Refer to the 5-Speed EM Low Voltage onnection Table. 6 - Wire is provided with the unit but not connected to the 5-Speed EM. Legend Accessory Relay Operation SW2-4 SW2-5 ycle with Blower On On ycle with ompressor Off Off Water Valve Slow Open On Off Outdoor Air Damper Off On Aurora Timing Events Event Normal Mode Test Mode Random Start Delay 5 to 80 seconds second ompressor On Delay 5 seconds < second ompressor Minimum On Time 2 minutes 5 seconds ompressor Short ycle Delay 4 minutes 5 seconds Blower Off Delay 0 seconds 2 seconds Fault Recognition Delay High Pressure Less than second Less than second Start-Up Bypass Low Pressure 2 minutes 0 seconds Fault Recognition Delay Low Pressure 0 seconds 0 seconds Start-Up Bypass Low Water/Air oil Limit 2 minutes 0 seconds Fault Recognition Delay Low Water/Air oil Limit 0 seconds 0 seconds Fault Recognition Delay ondensate Overflow 0 seconds 0 seconds Thermostat all Recognition Time 2 seconds 2 seconds Auxiliary Heat Staging Delay 5 minutes 20 seconds Emergency Heat Staging Delay 2 minutes 7.5 seconds Water Valve Slow Open Delay 90 seconds 90 seconds Reheat Delay 0 seconds 0 seconds reen Brown (2) ondensate Aurora LED Flash odes Slow Flash second on and second off Fast Flash 00 milliseconds on and 00 milliseconds off Flash ode 00 milliseconds on and 400 milliseconds off with a 2 second pause before repeating Random Start Delay Status LED (LED, reen) Fast Flash onfiguration LED (LED2, Yellow) Fast Flash Fault LED (LED, Red) Fast Flash Status LED (LED, reen) onfiguration LED (LED2, Yellow) Fault LED (LED, Red) Normal Mode ON No Software Overide Flash EM Setting Normal Mode OFF ontrol is Non-Functional OFF DIP Switch Overide Slow Flash Input Fault Lockout Flash ode Test Mode Slow Flash EM onfigure Mode Fast Flash High Pressure Lockout Flash ode 2 Lockout Active Fast Flash Reset onfigure Mode Off Low Pressure Lockout Flash ode Dehumidification Mode Flash ode 2 Low Air oil Limit Lockout - FP2 Flash ode 4 Reserved Flash ode Low Water oil Limit Lockout - FP Flash ode 5 Reserved Flash ode 4 Reserved Flash ode 6 Load Shed Flash ode 5 ondensate Overflow Lockout Flash ode 7 ESD Flash ode 6 Over/Under Voltage Shutdown Flash ode 8 Reserved Flash ode 7 Reserved Flash ode 9 Reserved Flash ode 0 Air/Water oil Limit Sensor Error Flash ode Factory Low Voltage Wiring Factory Line Voltage Wiring Field Low Voltage Wiring Field Line Voltage Wiring Optional Block D Voltage PB Traces Field Zone Sensor Wiring Internal Junction Quick onnect Terminal L Field Wiring Lug round Relay ontacts N.O., N.. apacitor Fuse ompressor ontactor O ondensate Overflow Sensor ES Emergency Shutdown HP High Pressure Switch LP Low Pressure Switch FD Freeze Detection Sensor F Fuse T Y R SW Push button SW2 DIP package 8 position RB Blower Relay RV Reversing Valve oil PM Phase uard Monitor RH Reheat Valve oil Thermistor Relay oil Switch - ondensate Overflow Switch - High pressure Switch - Low pressure Polarized connector Light Emitting Diode - reen Light Emitting Diode - Yellow Light Emitting Diode - Red 97P89-07 /8/2 29

P VERSATE ULTRA SERIES INSTALLATION MANUAL Wiring Schematics cont. FX0 ontrol 208-20-265/60/ PS rn PS Blower Motor H M L D09 D08 D07 D0 D05 D04 D0 D02 D0 20 9 8 7 6 5 4 2 0 Note 9 reen (9) Black (95) Red (97) round Neutral Disconnect L L L2 L2 L L Unit Power Supply 208-20-265/60/ - + - + - + - + 6 9 8 7 6 5 4 2 ROUND 24VA om A4 A A5 A A2 A5 Johnson FX-0 Wht Brn White Black (7) RB 24VA J8 O 2 5VD K Brown (60) 24 AI Brown (6) 25 - AI5 + - AI4 + AI6 26 27 28 29 0 A24 A4 2 AI2 5VD 4 A25 A2 AI 5 6 A22 A2 LED 7 5VD 8 A A A2 Black Yellow (50) J2 9 PWM2 K 40 PWM2 om Note 6 ray (68) 4 PWM J7 P Transformer Yellow (5) PB2 Black/White (6) reen/yellow (7) Black (5) Yellow (50) Blue (0) 2 ompressor S Blue R ap Black Red Blue (55) White (62) FD White/Blue (62) Black (6) DA 0 4 5 Red () Black (4) Brown () Violet (5) Yellow (8) reen (70) Orange (7) Yellow (2) Blue (72) ray (65) Orange (66) Orange/White (67) Note Blue (2) ES OS Black/Red (64) LP DF/FP Note 4 Red () ap T2 T Airflow Settings L L2 ray (65) Black (4) Brown () Yellow (5) Violet (5) Yellow/White (52) Note 7 Yellow/Red (5) Orange (66) Orange/White (67) J0 42 24VA om P ray/white (4) 4 DI2 Black (5) 44 DI reen (70) 45 DI0 Orange (7) 46 DI9 Blue (72) 47 DI8 Yellow (2) 48 DI7 J9 Black (22) 49 DI /4/5/6/ om Violet (2) 50 DI6 Red (24) 5 DI5 ray (26) 52 DI4 Blue (27) 5 DI Pink (25) 54 DI2 Black/White (29) 55 9VD Orange (0) 56 DI Yellow (8) Note Black (F20) 20 Black (F9) 9 Black (F8) 8 Black (F7) 7 Black (F6) 6 Black (F5) Notes: 5 Black (F4) 4 Note 2 Isolation Valve Black (F) Black (F2) 2 Black (F) Black (F0) 0 Black (F9) Black (F8) Black (F7) Black (F6) Black (F5) Black (F4) Black (F) Black (F2) Black (F) Black Red 208V Blue 20 V 265V Yellow (20) ray (9) Yellow (8) Yellow (7) Yellow (J2) Violet (5) Brown () Yellow (2) 2 Disconnect for 5 degree freeze detection limit 2 Acc output is cycled with the compressor Acc 2 output is cycled with the blower. 4 R,, Y, Y2, and inputs are for use with a wall mount thermostat. TO, S, RS, AI, and SS are for use with a TAXXJ02 zone sensor 5 Network controllable 24VA output. 6 Network controllable PWM output. 7 Wire #52 can be used to connect a field supplied and installed 0-5 VD humidity transmitter. 8 Not Used Bundle in the air handler 9 Optional, factory installed unit mounted disconnect 2 Optional, factory installed internal isolation valve Swap blue and red leads for 208V operation 4 Network configurable input Red (87) reen (86) White (88) Black (R) reen/yellow (8) Note 4 TB Terminal Board 24VA (R) Black () 24V OM () Black (L) Alarm (L) Black (X) Note 2 Acc (X) Black (X2) Note Acc 2 (X2) Black () Blower () Black (O) Rev Valve (O) Black (Y) omp (Y) Black (Y2) omp (Y2) Setpoint Shift (SS) Zone Sensor Terminal Black () Black (SS) Black (44) Black (AI) AI OM (AI) Room Sensor (RS) Sensor OM (S) Temp Occ (TO) Alarm irc A (L) Zone Sensor Terminal Zone Sensor Terminal 2 Zone Sensor Terminal 5 Zone Sensor Terminal 6 Black (RS) Alarm irc B (L2) ray () Note 5 Blue (0) Yellow (J2) Yellow (J) Orange (7) Black (6) Black (5) White (4) Violet () Yellow (J) Black () HP Black/White Yellow Red () Black (4) PB Yellow (5) Yellow (20) Yellow (7) Black/White (6) Note 5 Yellow (2) RV Orange (40) Black/White (4) RB Black (74) Violet (28) Black/ White (4) reen /Yellow (57) Note 8 2 5 0 P2 Black (L) Black (L2) Yellow (50) Black (74) 2 B 6 5 2 9 4 7 T T A 9 8 7 6 5 4 2 2 Legend Factory Low voltage wiring Factory Line voltage wiring Field low voltage wiring Field line voltage wiring Relay coil Optional block D Voltage PB traces Field Zone Sensor Wiring apacitor w/ bleed resistor Switch - ondensate overflow Internal junction Switch - High pressure Quick connect terminal Switch - Low pressure L Field wire lug Polarized connector 2 round Open Jumper Relay ontacts- N.O., N.. Rectified ompressor RP Solenoid Plug losed Jumper ompressor Solenoid - ompressor ontactor OS - Occupied Switch O - ondensate Overflow Sensor PB, PB2 - Power blocks P - ompressor Proving PR- Pump Relay S - ompressor Solenoid RB- Blower Relay DA - Discharge Air Temperature Sensor RP - Rectified Solenoid ompressor Plug DF/FP Dirty Filter or Blower Proving RV - Reversing Valve coil DH - Dehumidification Switch or Humidistat TB - Terminal Board ES - Emergency Shutdown FD - Freeze Detection HP - High Pressure Switch PM - Phase uard Module LP - Low Pressure Switch Blue (0) 97P80-02 //09 0

P VERSATE ULTRA SERIES INSTALLATION MANUAL Wiring Schematics cont. FX0 ontrol 460/60/ Variable Speed EM ompressor 2 T T 24 T2 25 26 27 28 29 0 2 4 5 6 7 8 Note 0 Red Yellow Black T Phase uard Monitor (PM) L L2 L T2 T Black (7) White (8) Red (9) Note 9 reen (9) round ray (94) Neutral Disconnect Black (54) L Black (95) L L Blue (55) L2 Yellow (96) L2 L2 Red (56) L Red (97) L L L - + - L2 L + - + - + ROUND 24VA om Johnson FX-0 24VA 9 40 4 42 4 44 45 46 47 48 49 50 5 52 5 54 55 56 20 9 8 7 6 5 4 2 0 6 9 8 7 6 5 4 2 Transformer Red () Black (4) Brown () Violet (5) Yellow (8) Yellow (5) Black/White (6) reen/yellow (7) D09 D08 A4 D07 D0 A A5 A A2 D05 D04 A5 D0 D02 D0 Orange Brown 5VD AI - AI5 + - AI4 + AI6 A24 A4 AI2 5VD A25 A2 AI A22 A2 LED 5VD A A A2 PWM2 PWM2 om PWM 24VA om Note 2 Isolation Valve 2 Red (87) reen (86) White (88) 2 0 4 5 Blue (0) Red () Black (4) Brown () Violet (5) Yellow (8) reen (70) Orange (7) Yellow (2) Blue (72) ray (65) DI2 Orange (66) DI DI0 Orange/White (67) ray (26) DI9 Black (76) Black (76) DI8 DI7 DI /4/5/6/ om PB2 Note Blue (2) ES OS LP DF/BP P O Brown (60) Brown (6) FD DA White (62) White/Blue (62) Black (6) Black/Red (64) ray (65) Note 7 Yellow (5) Yellow/White (52) Yellow/Red (5) Orange (66) Orange/White (67) Yellow (50) DI6 Note 6 ray (68) Black (5) reen (70) Orange (7) Blue (72) DI5 DI4 DI DI2 9VD DI J7 Yellow (2) Black (22) Violet (2) Red (24) ray (26) Blue (27) Pink (25) Black/White (29) Orange (0) K K J8 J2 J0 J9 Black (F20) Black (F9) Black (F8) Black (F7) Black (F6) Black (F5) Black (F4) Black (F) Black (F2) Black (F) Black (F0) Black (F9) Black (F8) Black (F7) Black (F6) Black (5) Black (F5) Black (F4) Black (F) Black (F2) Black (F) Yellow (50) 20 9 8 7 Blue (0) Blue EM Blower Motor 2 6 5 4 2 5 4 Notes: 0 Unit Power Supply 460/60/ w/neutral Orange Brown PB Black Blue 460V Black/White Yellow - Disconnect for 5 degree freeze detection limit. 2 - Acc output is cycled with the compressor. - Acc 2 output is cycled with the blower. 4 - R,, Y, Y2, and inputs are for use with a wall mount thermostat. TO, S, RS, AI, and SS are for use with a TAXXJ02 zone sensor. 5 - Network controllable 24VA output. 6 - Network controllable PWM output. 7 - Wire #52 can be used to connect a field supplied and installed 0-5 VD humidity transmitter. 9 - Optional, factory installed unit mounted disconnect 0 - Optional, factory installed phase guard - Optional, factory installed phase guard. The yellow transformer wire shall be connected directly to the PB- board, if this option is not installed. 2 - Optional, factory installed internal isolation valve. reen/yellow (8) Note 4 TB Terminal Board 24VA (R) Black (R) Note PM Y-OUT Yellow (9) Red () Black/ White (92) Black (4) Black () 24V OM () Black (L) Alarm (L) Black (X) Note 2 Acc (X) Black (X2) PB Yellow (5) Yellow (20) Yellow (7) Black/White (6) Note Acc 2 (X2) Black () Blower () Black (O) Rev Valve (O) Black (Y) omp (Y) Black (Y2) omp (Y2) Setpoint Shift (SS) Zone Sensor Terminal AI OM (AI) Zone Sensor Terminal Room Sensor (RS) Zone Sensor Terminal 2 Black () Sensor OM (S) Black (SS) Zone Sensor Terminal 5 Black (44) Temp Occ (TO) Zone Sensor Terminal 6 Black (AI) Alarm irc A (L) Reheat Enable Black (RS) Alarm irc B (L2) (Dehumidistat) Black (L) Violet (28) Violet () Black/ White Yellow (20) (4) Yellow (2) ray (9) RH ray (75) Blue Yellow (8) Yellow (7) Yellow (J2) Dual Violet (5) apacity Units Only Brown () Yellow (2) Black (L2) ray () Note 5 Blue (0) Yellow (J2) Yellow (J) Orange (7) RV Black (6) Orange (40) Note 0 Black/ Black (5) White (92) White (4) Black/White (4) Violet () Yellow (J) Black () HP reen/yellow (57) Variable Speed 2 EM Blower 5 Motor 0 P2 Yellow (50) B 6 5 2 9 4 7 2 T T A 9 8 7 6 5 4 2 N Y 2 P ray/white (4) Black (54) Blue (55) Red (56) RP reen S Legend Factory Low voltage wiring Factory Line voltage wiring Field low voltage wiring Field line voltage wiring Relay coil Optional block D Voltage PB traces apacitor w/ bleed resistor Field Zone Sensor Wiring Switch - ondensate overflow Internal junction Switch - High pressure Quick connect terminal Switch - Low pressure L Field wire lug Polarized connector 2 round Open Jumper Relay ontacts- N.O., N.. Rectified ompressor RP Solenoid Plug losed Jumper ompressor Solenoid - ompressor ontactor OS - Occupied Switch O - ondensate Overflow Sensor PB, PB2 - Power blocks P - ompressor Proving PR- Pump Relay S - ompressor Solenoid RB- Blower Relay DA - Discharge Air Temperature Sensor RP - Rectified Solenoid ompressor Plug DF/BP Dirty Filter or Blower Proving RV - Reversing Valve coil DH - Dehumidification Switch or Humidistat TB - Terminal Board ES - Emergency Shutdown FD - Freeze Detection Sensor HP - High Pressure Switch PM - Phase uard Module LP - Low Pressure Switch RH - Reheat Valve oil 97P802-09 /9/2

P VERSATE ULTRA SERIES INSTALLATION MANUAL reen/yellow (57) L T Phase uard Monitor (PM) L L2 L D09 D08 D07 D0 D05 D04 D0 D02 D0 20 9 Note 8 8 7 6 5 4 2 2 0 reen (9) Black (95) Yellow (96) Red (97) Note 9 round Neutral Disconnect L L L2 L2 L L Black PB - 5 0 P2 + - + - + - + 6 Yellow (50) 9 8 7 6 5 4 2 2 Page Transformer Note 0 Black (7) White (8) Red (9) Yellow (5) Black/White (6) reen/yellow (7) ROUND 24VA om A4 A A5 A A2 A5 Johnson FX-0 Black (5) ompressor T T T2 Red Yellow Black T T2 L L2 J8 2 5VD 24VA AI 24 25 - AI5 + 26 27 - AI4 + 28 29 0 AI6 A24 A4 2 AI2 5VD 4 A25 A2 5 AI 6 A22 A2 LED 7 5VD 8 A A A2 2 0 4 5 Red () Black (4) Brown () Violet (5) Yellow (8) reen (70) Orange (7) Yellow (2) Blue (72) ray (65) Orange (66) O K Brown (60) J2 9 PWM2 40 PWM2 om 4 PWM Orange/White (67) Brown (6) FD DA White (62) White/Blue (42) Black (6) Black/Red (64) ray (65) Note 7 Yellow (5) Yellow/White (52) Yellow/Red (5) Orange (66) Orange/White (67) Yellow (50) K J0 42 24VA om 4 DI2 44 DI 45 DI0 46 DI9 47 DI8 48 DI7 Note 6 ray (68) P ray/white (4) Black (5) reen (70) Orange (7) Blue (72) Yellow (2) Tan Blue (0) PB2 Black (22) DF/BP Violet (2) Note Red (24) Note 4 Blue (2) ray (26) LP Blue (27) ES Pink (25) Black/White (29) OS Orange (0) Red () Yellow (50) Black (4) Brown () Violet (5) Yellow (8) Black (F20) Black (F9) Black (F8) Black (F7) Black (F6) Black (F5) Black (F4) Black (F) Black (F2) Black (F) Black (F0) Black (F9) Black (F8) Black (F7) Black (F6) Black (F5) Black (F4) Black (F) J9 49 DI /4/5/6/ om 50 DI6 5 DI5 52 DI4 5 DI 54 DI2 55 9VD 56 DI J7 Black (F2) Black (F) 20 9 8 7 6 5 4 2 0 Yellow (20) ray (9) Yellow (8) Yellow (7) Yellow (J2) Violet (5) Brown () Yellow (2) ray () Note 5 Blue (0) Yellow (J2) Yellow (J) Orange (7) Black (6) Black (5) White (4) Violet () Yellow (J) Black () Yellow Red () Black (4) Yellow (5) Yellow (20) Yellow (7) Black/White (6) RV Orange (40) Note 0 Black/ White (92) Black/White (4) Blue (0) Violet (28) Yellow (2) Notes: Disconnect for 5 degree freeze detection limit. 2 Acc output is cycled with the compressor. Acc 2 output is cycled with the blower. 4 R,, Y, Y2, and inputs are for use with a wall mount thermostat. TO, S, RS, AI, and SS are for use with a TAXXJ02 zone sensor. 5 Network controllable 24VA output. 6 Network controllable PWM output. 7 Wire #52 can be used to connect a field supplied and installed 0-5 VD humidity transmitter. Note 2 8 Not Used Bundle in the air handler. Isolation 9 Optional, factory installed unit mounted disconnect Valve 0 Optional, factory installed phase guard Optional, factory installed phase guard. The yellow transformer wire 2 shall be connected directly to the PB-, if this option is not installed. 2 Optional, factory installed internal isolation valve. Red 4 Network configurable input. (87) 5 Refer to the 5-Speed EM Motor Low Voltage onnection Table. reen (86) White reen/yellow (8) (88) Note 4 TB Terminal Board 24VA (R) Black (R) Black () 24V OM () Black (L) Alarm (L) Black (X) Note 2 Acc (X) Black (X2) Note Acc 2 (X2) Black () Blower () Black (O) Rev Valve (O) Black (Y) omp (Y) Black (Y2) omp (Y2) Setpoint Shift (SS) Zone Sensor Terminal AI OM (AI) Zone Sensor Terminal Room Sensor (RS) Zone Sensor Terminal 2 Black () Sensor OM (S) Black (SS) Zone Sensor Terminal 5 Black (44) Temp Occ (TO) Zone Sensor Terminal 6 Black (AI) Alarm irc A (L) Black (RS) Alarm irc B (L2) Black (L) HP Black/White Note 5 Note PM Y-OUT Yellow (9) Black/ White (92) Violet () Black/ White (4) B 5-Speed EM Blower Motor 6 5 2 9 4 7 2 T T A 9 8 7 6 5 4 2 Y 5 4 2 Wiring Schematics cont. FX0 ontrol 460/60/ 5-Speed EM Red Tan N L 5-Speed EM Low Voltage onnections Model TAP- TAP-2 TAP- TAP-4 TAP-5 05 Blue Red ray 08 Blue Red ray 02 Blue Red ray 024 Blue Red ray 00 Blue Red ray 06 Blue Red ray 04 Blue Red ray 042 Blue Red ray 048 Blue Red ray 060 Blue Red ray 070 Blue Red ray Tan Blue 460V Unit Power Supply 460/60/ Note 5 Blue Brown Black Black (L2) Orange Red reen Legend Factory Low voltage wiring Factory Line voltage wiring Field low voltage wiring Field line voltage wiring Relay coil Optional block D Voltage PB traces apacitor w/ bleed resistor Field Zone Sensor Wiring Switch - ondensate overflow Internal junction Switch - High pressure Quick connect terminal Switch - Low pressure L Field wire lug Polarized connector 2 round Open Jumper Relay ontacts- N.O., N.. Rectified ompressor RP Solenoid Plug losed Jumper ompressor Solenoid - ompressor ontactor OS - Occupied Switch O - ondensate Overflow Sensor PB, PB2 - Power blocks P - ompressor Proving PR- Pump Relay S - ompressor Solenoid RB- Blower Relay DA - Discharge Air Temperature Sensor RP - Rectified Solenoid ompressor Plug DF/BP Dirty Filter or Blower Proving RV - Reversing Valve coil DH - Dehumidification Switch or Humidistat TB - Terminal Board ES - Emergency Shutdown FD - Freeze Detection Sensor HP - High Pressure Switch PM - Phase uard Module LP - Low Pressure Switch RH - Reheat Valve oil 97P822-04 /8/2 2

Wiring Schematics cont. Hot as Reheat Humidity Sensor Terminal Block Io Vin nd Vo onnect to on the Low Volt Terminal Board onnect to R on the Low Volt Terminal Board NOTE: Reversing these two wires will cause the transformer breaker to trip Dehumidistat Wiring (NOT USED) Yellow (5) Yellow /Wht (52) J8 2 24 25 26 27 28 29 0 2 4 5 6 7 8 5VD - AI + - AI5 + - AI4 + - AI6 + - AI2 + 5VD - AI + LED 5VD A2 A2 24VA A24 A4 A25 A22 24VA om A2 ROUND A4 A5 A A D09 D08 D07 D0 6 20 9 8 7 6 5 4 2 Low Voltage Terminal Board O/B J2 9 40 4 PWM2 PWM2 om PWM A A A2 D05 D04 0 L Y2 X R Y L2 L X2 SS J0 42 4 44 45 46 47 48 24VA om DI2 DI DI0 DI9 DI8 DI7 A5 Johnson FX-0 D0 D02 9 8 7 6 5 AI RS S TO Dehumidistat J9 49 50 5 52 5 54 55 56 DI /4/5/6/ om DI6 DI5 DI4 DI DI2 9VD DI D0 4 2 J7

ontrols - Aurora Base ontrol Aurora Base ontrol NOTE: Refer to the Aurora Base ontrol Application and Troubleshooting uide and the Instruction uide: Aurora Interface and Diagnostics (AID) Tool for additional information. ontrol Features Software AB Standard Version 2.0 Single or Dual apacity ompressors Either single or dual capacity compressors can be operated. EM Blower Motor Option An EM blower motor can be driven directly using the onboard PWM output. Four blower speeds are available based upon the, Y, Y2, and W input signals to the board. The blower speeds can be changed either by the EM manual configurations mode method or by using the Aurora AID Tool directly. All four blower speeds can be set to the same speed if desired. 5-Speed EM Blower Motor Option A 5-Speed EM blower motor will be driven directly using the thermostat connections. Any of the, Y, or Y2/W signals can drive any of the 5 available pre-programmed blower speeds on the motor. All 5 Series "" vintage units will be wired this way at the factory. Other ontrol Features Random start at power up Anti-short cycle protection High and low pressure cutouts Loss of charge Water coil freeze detection Air coil freeze detection Over/under voltage protection ondensate overflow sensor Load shed Dehumidification (where applicable) Emergency shutdown Hot gas reheat operation (where applicable) Diagnostic LED Test mode push button switch Two auxiliary electric heat outputs Alarm output Accessory output with N.O. and N.. Modbus communication (master) Modbus communication (slave) Field Selectable Options via Hardware DIP Switch (SW) Test/onfiguration Button (See SW Operation Table) Test Mode The control is placed in the test mode by holding the push button switch SW for 2-5 seconds. In test mode most of the control timings will be shortened by a factor of sixteen (6). LED (green) will flash at second on and second off. Additionally, when entering test mode LED (red) will flash the last lockout one time. Test mode will automatically time out after 0 minutes. Test mode can be exited by pressing and holding the SW button for 2 to 5 seconds or by cycling the power. NOTE: Test mode will automatically be exited after 0 minutes. EM onfiguration Mode The control is placed in the EM configuration mode by holding the pushbutton switch SW for 5 to 0 seconds, the high, low, and EM speeds can be selected by following the LED display lights. LED2 (yellow) will fast flash when entering the EM configuration. When setting speed LED (green) will be continuously lit, for low speed LED (red) will be continuously lit, and for high speed both LED (green) and LED (red) will be continuously lit. During the EM configuration mode LED2 (yellow) will flash each of the 2 possible blower speeds times. When the desired speed is flashed press SW, LED2 will fast flash until SW is released. speed has now been selected. Next select low speed, and high speed blower selections following the same process above. After third selection has been made, the control will exit the EM configuration mode. Aux fan speed will remain at default or current setting and requires the AID Tool for adjustment. Reset onfiguration Mode The control is placed in reset configuration mode by holding the push button switch SW for 50 to 60 seconds. This will reset all configuration settings and the EEPROM back to the factory default settings. LED (green) will turn off when entering reset configuration mode. Once LED (green) turns off, release SW and the control will reset. DIP Switch (SW2) SW2- FP Selection Low water coil temperature limit setting for freeze detection. On = 0 F; Off = 5 F. SW2-2 FP2 Selection On = 0 F; Off = N/A SW2- RV O/B - thermostat type. Heat pump thermostats with O output in cooling or B output in Heating can be selected. On = O; Off = B. SW2-4 Access Relay Operation (P2) and 2-5 Access Relay Operation SW2-4 SW2-5 ycle with Blower ON ON ycle with ompressor OFF OFF Water Valve Slow Opening ON OFF ycle with omm. T-stat Hum md OFF ON 4

ontrols - Aurora Base ontrol cont. ycle with Blower - The accessory relay will cycle with the blower output. ycle with ompressor - The accessory relay will cycle with the compressor output. Water Valve Slow Opening - The accessory relay will cycle and delay both the blower and compressor output for 90 seconds. SW2-6 Operation selection of single or dual capacity compressor. On = Single Stage; Off = Dual apacity SW2-7 Lockout and Alarm Outputs (P2) selection of a continuous or pulsed output for both the LO and ALM Outputs. On = ontinuous; Off = Pulsed SW2-8 Future Use Alarm Jumper lip Selection From the factory, ALM is connected to 24 VA via JW2. By cutting JW2, ALM becomes a dry contact connected to AL. EM Blower Speeds The blower speeds can be changed either by using the EM manual configurations mode method or by using the Aurora AID Tool directly (see Instruction uide: Aurora Interface and Diagnostics (AID) Tool topic). Field Selectable Options via Software (Selectable via the Aurora AID Tool) EM Blower Speeds An EM blower motor can be driven directly using the onboard PWM output. Four blower speeds are available, based upon the, Y (low), Y2 (high), and Aux input signals to the board. The blower speeds can be changed either by the EM manual configurations mode method (see EM onfiguration Mode topic) or by using the Aurora AID Tool directly. All four blower speeds can be set to the same speed if desired. Aux blower speed will remain at default or current setting and requires the AID Tool for adjustment. Safety Features The following safety features are provided to protect the compressor, heat exchangers, wiring and other components from damage caused by operation outside of design conditions. Fuse a amp automotive type plug-in fuse provides protection against short circuit or overload conditions. Anti-Short ycle Protection 4 minute anti-short cycle protection for the compressor. Random Start 5 to 80 second random start upon power up. Fault Retry in the fault condition, the control will stage off the outputs and then try again to satisfy the thermostat Y input call. Once the thermostat input calls are satisfied, the control will continue on as if no fault occurred. If consecutive faults occur without satisfying the thermostat Y input call, then the control will go to Lockout mode. Lockout when locked out, the blower will operate continuously in speed, and PS blower motor output will remain on. The Alarm output (ALM) and Lockout output (L) will be turned on. The fault type identification display LED (Red) shall flash the fault code. To reset lockout conditions with SW2-8 On, thermostat inputs Y, Y2, and W must be removed for at least seconds. To reset lockout conditions with SW2-8 Off, thermostat inputs Y, Y2, W, and DH must be removed for at least seconds. Lockout may also be reset by turning power off for at least 0 seconds or by enabling the emergency shutdown input for at least seconds. Lockout With Emergency Heat - if the control is locked out in the heating mode, and a Y2 or W input is received, the control will operate in the emergency heat mode while the compressor is locked out. The first emergency heat output will be energized 0 seconds after the W input is received, and the blower will shift to high speed. If the control remains locked out, and the W input is present, additional stage of emergency heat will stage on after 2 minutes. When the W input is removed, all of the emergency heat outputs will turn off, and the EM blower will shift to speed and PS blower motor output will remain on. High Pressure fault is recognized when the Normally losed High Pressure Switch, P4-9/0 opens, no matter how momentarily. The High Pressure Switch is electrically in series with the ompressor ontactor and serves as a hardwired limit switch if an overpressure condition should occur. Low Pressure - fault is recognized when the Normally losed Low Pressure Switch, P4-7/8 is continuously open for 0 seconds. losure of the LPS any time during the 0 second recognition time restarts the 0 second continuous open requirement. A continuously open LPS shall not be recognized during the 2 minute startup bypass time. Loss of harge fault is recognized when the Normally losed Low Pressure Switch, P4-7/8 is open prior to the compressor starting. ondensate Overflow - fault is recognized when the impedance between this line and 24 VA common or chassis ground drops below 00K ohms for 0 seconds continuously. Freeze Detection (oax) - set points shall be either 0 F or 5 F. When the thermistor temperature drops below the selected set point, the control shall begin counting down the 0 seconds delay. If the thermistor value rises above the selected set point, then the count should reset. The resistance value must remain below the selected set point for the entire length of the appropriate delay to be recognized as a fault. This fault will be ignored for the initial 2 minutes of the compressor run time. Freeze Detection (Air oil) - uses the FP2 input to protect against ice formation on the air coil. The FP2 input will operate exactly like FP except that the set point is 0 degrees and is not field adjustable. 5

ontrols - Aurora Base ontrol cont. Over/Under Voltage Shutdown - An over/under voltage condition exists when the control voltage is outside the range of 8 VA to 0 VA. If the over/under voltage shutdown lasts for 5 minutes, the lockout and alarm relay will be energized. Over/under voltage shutdown is selfresetting in that if the voltage comes back within range of 8 VA to 0 VA for at least 0.5 seconds, then normal operation is restored. Operation Description Power Up - The unit will not operate until all the inputs and safety controls are checked for normal conditions. The unit has a 5 to 80 second random start delay at power up. Then the compressor has a 4 minute anti-short cycle delay after the random start delay. Standby In standby mode, Y, Y2, W, DH, and are not active. Input O may be active. The blower and compressor will be off. Heating Operation Heating, st Stage (Y) - The blower is started on speed immediately and the compressor is energized 0 seconds after the Y input is received. The EM blower motor is switched to low speed 5 seconds after the Y input. Heating, 2nd Stage (Y, Y2) - The compressor will be staged to full capacity 20 seconds after Y2 input is received. The EM blower will shift to high speed 5 seconds after the Y2 input is received. Heating, rd Stage (Y, Y2, W) - The hot water pump is deenergized and the first stage of electric heat is energized 0 seconds after the W command is received. If the demand continues the second stage of electric heat will be energized after 5 minutes. Emergency Heat (W) - The blower will be started on speed, 0 seconds later the first stage of electric heat will be turned on. 5 seconds after the first stage of electric heat is energized the blower will shift to Aux speed. If the emergency heat demand is not satisfied after 2 minutes the second electric heat stage will be energized. Blower () - The blower will start immediately upon receiving a thermostat command. If there are no other commands from the thermostat the EM will run on speed until the command is removed. Regardless of blower input () from the thermostat, the blower will remain on for 0 seconds at the end of each heating cycle. ooling Operation In all cooling operations, the reversing valve directly tracks the O input. Thus, anytime the O input is present, the reversing valve will be energized. ooling, st Stage (Y, O) - The blower is started on speed immediately and the compressor is energized 0 seconds after the Y input is received. The EM blower motor is switched to low speed 5 seconds after the Y input. ooling, 2nd Stage (Y, Y2, O) - The compressor will be staged to full capacity 20 seconds after Y2 input is received. The EM blower will shift to high speed 5 seconds after the Y2 input is received. Blower () - The blower will start immediately upon receiving a thermostat command. If there are no other commands from the thermostat the EM will run on speed until the command is removed. Regardless of blower input () from the thermostat, the blower will remain on for 0 seconds at the end of each heating, cooling, and emergency heat cycle. Dehumidification (Y, O, DH or Y, Y2, O, DH) - When a DH command is received from the thermostat during a compressor call for cooling the EM blower speed will be reduced by 5% to increase dehumidification. Emergency Shutdown - Four (4) seconds after a valid ES input, P2-7 is present, all control outputs will be turned off and remain off until the emergency shutdown input is no longer present. The first time that the compressor is started after the control exits the emergency shutdown mode, there will be an anti-short cycle delay followed by a random start delay. Input must be tied to common to activate. ontinuous Blower Operation - The blower output will be energized any time the control has a input present, unless the control has an emergency shutdown input present. The blower output will be turned off when input is removed. Load Shed - The LS input disables all outputs with the exception of the blower output. When the LS input has been cleared, the anti-short cycle timer and random start timer will be initiated. Input must be tied to common to activate. 6

ontrols - Aurora Base ontrol cont. Aurora Base ontrol LED Displays These three LEDs display the status, configuration, and fault codes for the control. These can also be read in plain English via the Aurora AID Tool. Status LED (LED, reen) Description of Operation Fault LED, reen Normal Mode ON ontrol is Non-functional OFF Test Mode Slow Flash Lockout Active Fast Flash Dehumidification Mode Flash ode 2 (Future Use) Flash ode (Future Use) Flash ode 4 Load Shed Flash ode 5 ESD Flash ode 6 (Future Use) Flash ode 7 onfiguration LED (LED2, Yellow) Description of Operation No Software Overwritten DIP Switch was Overwritten EM onfiguration Mode Fault LED (LED, Red) Red Fault LED onfiguration LED, Yellow Flashing EM Setting Slow Flash Fast Flash LED Flash ode* Lockout Reset/ Remove Normal - No Faults OFF Fault - Input No Auto Fault - High Pressure 2 Yes Hard or Soft Fault - Low Pressure Yes Hard or Soft Fault - Freeze Detection FP2 4 Yes Hard or Soft Fault - Freeze Detection FP 5 Yes Hard or Soft Fault - ondensate Overflow 7 Yes Hard or Soft Fault - Over/Under Voltage 8 No Auto Fault - FP & FP2 Sensor Error Yes Hard or Soft NOTE: All codes > use long flash for tens digit and short flash for the ones digit. 20, 0, 40, 50, etc. are skipped. AB Basic Faults Aurora Interface and Diagnostics (AID) Tool The Aurora Interface and Diagnostics (AID) Tool is a device that is a member of the Aurora network. The AID Tool is used to troubleshoot equipment which uses the Aurora control via Modbus RTU communication. The AID Tool provides diagnostics, fault management, EM setup, and system configuration capabilities to the Aurora family of controls. An AID Tool is recommended, although not required, for EM airflow settings. The AID Tool simply plugs into the exterior of the cabinet in the AID Tool port. AB ontrol Board Layout 6.25 in. 2 2 F Y HP HP LP LP FP2 FP2 FP FP REV REV LO HI F F R Factory P5 Factory JW2 - Alarm P2 P4 PWM FM EM PWM P SW Test RV K K2 Hi K Fan K4 Alarm K5 Acc K6 Field onnections Off LED FP 5 o F/0 o F R FP2 5 o F/0 o F Fault RV B/O A Dip A Dip 2 LED Dual/Single L Pulse/ontinuous Status Reheat/Normal P9 LO P P Factory Use 5.0 in. Aurora TM Base ontrol Factory Fan onnection R O/B Field onnections SW2 On LED 2 2 Y onfig 4 5 6 7 8 Y Y2 W DH om om2 A-Fuse Factory P6 P RS485 Exp LED 5 P7 RS 485 P8 LED 4 RS485 NET EH EH2 EH O N/A (+) (-) R (+) (-) R 5.75 in. ES LS ALM AL A c A no A nc LO R O/B Y Y2 W DH R R 5.5 in. 7

ontrols - FX0 (optional) Optional FX0 Microprocessor and BAS Interface temperature, O 2 or current status switches. The control has unused binary and PWM outputs that can be commanded over the BAS for field use. An optional Medium User Interface (MUI) for control setup and advanced diagnostics is available with some mounting kits, MUIK - Panel mount version and the MUIK4-Wall mount version. Main FX 0 Board The FX0 is a microprocessor based control that not only monitors and controls the heat pump but also can communicate any of this information back to the building automation system (BAS). This means that not only does the control monitor the heat pump at the unit you can also monitor and control many the features over the BAS. This clearly puts the FX0 in a class of its own. The control will enumerate all fault conditions (HP, LP, O, LO, and Freeze Detection) over a BAS as well as display them on a medium user interface (MUI). HP, LP, O and Freeze Detection faults can all be reset over a BAS. A Loss Of harge fault can not be reset or bypassed until the problem has been corrected. A MUI is invaluable as a service tool for the building service team. The unit can be commanded to run by a typical heat pump thermostat or run based on heating and cooling set points supplied by a BAS. The control board is wired with quick connect harnesses for easy field change out of a bad control board. All variable speed EM blower speed settings can be changed over a BAS or with a MUI. The control has an input programmed to enable field installed emergency heat in the event that the compressor is locked out. This input can also be commanded on from a BAS as needed. An alarm history can be viewed through the MUI and will be held in memory until the unit is power cycled. Relative humidity can be read by a 0-5VD humidity sensor that is displayed over the network. If you are using a variable speed EM blower motor the control can enable dehumidification mode based on a set point in the control. The dehumidification set point itself can also be changed over a BAS or with a MUI. Dehumidification mode can also be enabled by the BAS. Because the FX0 is not factory configured to read O 2 levels, contact the factory for application assistance. The FX0 control has unused analog and digital inputs for field installed items such as air temperature, water Zone Sensors There are two options for zone sensors that can be used with the FX0 control. Both sensors use a Johnson controls A99 positive temperature coefficient type sensor. The TAXXJ02 has a set point adjustment now which will give the end user a +/- 5 F adjustment from the set point as well as a push button that can be used for temporary occupancy. The control leaves the factory set to operate with a TAXXJ02 sensor, the TAXXA04 sensor through a building automation system, or with a user interface. Standard Features Anti Short ycle High Pressure Protection Low Pressure Protection Freeze Detection Loss Of harge Detection Random Start Display for diagnostics Reset Lockout at disconnect or through BAS 2 Accessory outputs Optional BAS add-on controls DD Operation and onnection Other optional network protocol boards that can be added to the FX0 are: Johnson ontrol N2 LonWorks BAnet - MS/TP @ 9,200 Baud rate - Limit devices to 0 on a single trunk line ontrol and Safety Feature Details Emergency Shutdown The emergency shutdown mode can be activated by a command from a facility management system or a closed contact on BI-2. The default state for the emergency shutdown data point is off. When the emergency shutdown mode is activated, all outputs will be turned off immediately and will remain off until the emergency shutdown mode is de-activated. The first time the compressor starts after the emergency shutdown mode has been de-activated, there will be a random start delay present. 8

ontrols - FX0 (optional) cont. Lockout Mode Lockout mode can be activated by any of the following fault signals: refrigerant system high pressure, refrigerant system low pressure, freeze detection, and condensate overflow. When any valid fault signal remains continuously active for the length of its recognition delay, the controller will go into fault retry mode, which will turn off the compressor. After the ompressor short cycle delay, the compressor will attempt to operate once again. If three consecutive faults occur in 60 minutes during a single heating or cooling demand, the unit will go into lockout mode, turning off the compressor, enabling the alarm output, and setting the blower back to low speed operation until the controller is reset. If the control faults due to the low pressure input (BI-) being open during the pre-compressor startup check, the control will go into lockout mode immediately, disabling the compressor from starting and enabling the alarm output (BO-6). The lockout condition can be reset by powering down the controller, by a command from the BAS, or by the holding the ES and Return keys on the MUI for 5 seconds. Low Pressure (BI-) The low-pressure switch shall be a normally closed (N) switch that monitors the systems refrigerant pressure. The input shall be checked 5 seconds before compressor start up to be sure the pressure switch is closed and then ignored for the first 2 minutes after the compressor output (BO-2) is enabled. If the switch is open continuously for (0) seconds during compressor operation the compressor output (BO-2) will be disabled. The compressor will not restart until the compressor short cycle time delay has been satisfied. ondensate Overflow The condensate overflow sensing circuit will monitor the condensate level as a resistance input to AI-. If the condensate water level rises resulting in the input resistance rising above the set point for the recognition delay period, the condition will be recognized as a fault. The condensate will be subjected to a (0) second lockout delay which requires that the fault be sensed for a continuous (0) seconds before suspending unit operation. Alarm Output (BO-6) The alarm output will be enabled when the control is in the lockout mode and will be disabled when the lockout is reset. Freeze Detection (AI-5) The freeze detection sensor will monitor the liquid refrigerant temperature entering the water coil in the heating mode. If the temperature drops below the freeze detection trip point for the recognition delay period, the condition will be recognized as a fault. The freeze detection trip point will be factory set for 0 F (- ) and will be field selectable for 5 F (-9 ) by removing a jumper wire on BI-5. The freeze detection fault condition will be bypassed 2 minutes at normal compressor startup, to allow the refrigeration circuit to stabilize. If the freeze detection sensor becomes unreliable at any time compressor operation will immediately be suspended until the problem is corrected. This should be displayed as an alarm on the BAS and the MUI. This alarm will be reported as a Water Low Temp Limit fault. High Pressure (BI-) The high-pressure switch shall be a normally closed (N) switch that monitors the systems refrigerant pressure. If the input senses the high-pressure switch is open it must disable the compressor output immediately and count the fault. The compressor minimum on time does not apply if the highpressure switch opens. The compressor will not restart until the compressor short cycle time delay has been satisfied. Test Mode Raising the zone temperature input (AI-) reading to 80 220 F or by holding the ES and down arrow keys on the MUI for 5 seconds will put the control into test mode. In test mode the random start delay and the compressor fixed on delay time will both be shortened to 5 seconds and the reversing valve will be allowed to cycle with out shutting down the compressor. If an MUI is connected to the control LED 8 will flash and the words Test Mode Enabled will be shown on the LD display when the control is in test mode. Test mode will be disabled after a power cycle, 0 minute timeout, or by holding the ES and Up arrow keys on the MUI. Sequence of Operation Power Fail Restart When the controller is first powered up, the outputs will be disabled for a random start delay. The delay is provided to prevent simultaneous starting of multiple heat pumps. Once the timer expires, the controller will operate normally. Random Start Delay This delay will be used after every power failure, as well as the first time the compressor is started after the control exits the unoccupied mode or the emergency shutdown mode. The delay should not be less than second and not longer than 20 seconds. If the control is in test mode the random start delay will be shortened to 5 seconds. 9

ontrols - FX0 (optional) cont. ompressor Fixed On Delay Time The ompressor Fixed On Delay Time will ensure that the compressor output (B02) is not enabled for 90 seconds after the control receives a call to start the compressor. This delay is adjustable from 0 00 seconds over a BAS or a MUI. If the control is in test mode the ompressor Fixed On Delay Timer will be shortened to 5 seconds. ompressor Minimum On Delay The compressor minimum on delay will ensure that the compressor output is enabled for a minimum of two (2) minute each time the compressor output is enabled. This will apply in every instance except in the event the high pressure switch is tripped or emergency shutdown then the compressor output will be disable immediately. ompressor Short ycle Delay Time The compressor short cycle time delay will ensure that the compressor output will not be enabled for a minimum of five (5) minutes after it is disabled. This allows for the system refrigerant pressures to equalize after the compressor is disabled. Heating ycle On a call for heating, the blower enable output and accessory output 2 will turn on immediately after the random start delay timer has been satisfied. If the compressor short cycle time delay has been satisfied, the compressor will turn on after the blower enable and accessory output 2 are on and the fixed compressor start delay timers have been satisfied. NOTE: Auxiliary heat output can be controlled over the BAS. Set Point ontrol Mode In set point control mode the reversing valve output will be disabled. As the temperature drops below the heating set point and begins to operate in the heating proportional band, the compressor (low capacity for two-stage compressors) output (BO-2) will be enabled. For units with two-stage compressors, a PI loop in the programming of the control will determine when the full capacity compressor output (BO-4) is to be enabled. The compressor must be operating in low capacity for a minimum of 0 seconds before the full capacity compressor output can be enabled. During low capacity compressor operation the variable speed EM blower will operate in medium speed and will operate in high speed when the compressor is operating at full capacity. Thermostat ontrol Mode In thermostat mode the compressor will be cycled based on Y and Y2 calls from a room thermostat. When the control receives a Y command (BI-7) from the thermostat the low capacity compressor output (BO2) will be enabled and the variable speed EM blower will operate in medium speed. When the control receives a Y2 command (BI-8) from the thermostat the variable speed EM blower will operate in high speed. During the heating cycle the reversing valve will be commanded into the off position. ooling ycle On a call for cooling, the blower enable output and accessory output 2 will turn on immediately after the random start delay timer has been satisfied. If the compressor short cycle time delay has been satisfied, the compressor will turn on after the blower enable and accessory output 2 are on and the fixed compressor start delay timers have been satisfied. Set Point ontrol Mode In set point control mode the reversing valve output will be enabled. As the temperature rises above the cooling set point and begins to operate in the cooling proportional band, the low capacity compressor output (BO-2) will be enabled. A PI loop in the programming of the control will determine when the full capacity compressor output (BO-4) is to be enabled. The compressor must be operating in low capacity for a minimum of 0 seconds before the full capacity compressor output can be enabled. During low capacity compressor operation the variable speed EM blower will operate in medium speed and will operate in high speed when the compressor is operating at full capacity. Thermostat ontrol Mode In thermostat mode the compressor will be cycled based on Y and Y2 calls from a room thermostat. When the control receives a Y command (BI-7) from the thermostat the low capacity compressor output (BO2) will be enabled and the variable speed EM blower will operate in medium speed. When the control receives a Y2 command (BI-8) from the thermostat the full capacity compressor output will be enabled and the variable speed EM blower will operate in high speed. During the cooling cycle the reversing valve will be commanded into the ON position. Variable Speed EM Blower Operation Blower speeds will be selected through the user interface or the facility management system. There will be a total of 2 speeds selectable with only three being selected at any one time. The lowest numbered speed selection set to ON will select the low-speed blower setting, the middle selection set to ON will select the medium-speed blower setting and the highest selection set to ON will select the high-speed blower setting. If all selections are set to OFF 40

ontrols - FX0 (optional) cont. the software shall select speed setting 0 for low-speed, for medium-speed, and will select speed setting 2 for high speed. If only one selection is set to ON, that selection will set the low-speed blower setting, the medium-speed setting will be, and the high-speed setting will be speed 2. The maximum low-speed setting will be speed 0 and the minimum high-speed setting will be speed. In addition there is a low limit setting in the software to prevent the variable speed EM blower speed from being set below acceptable limits for each unit size. Emergency Heat/Network Enabled Output (BO-5) This output is set from the factory to enable/disable emergency heat. If a problem occurs with the unit resulting in the compressor being locked out in heating mode, the control will automatically enable this output to turn on field installed electric heat. This output is interlocked with the blower proving input BI-6 (Blower proving sensors must be field supplied and installed). BI-6 must be connected to PB2 position (see unit schematic) in the field if no blower proving sensor is desired. There is a configurable parameter available through a BAS network that must be enabled if this output is to be commanded over the BAS network. NOTE: For auto switch over, BO-5 must be set to "Emergency" using the MUI. MUI Alarm History Reporting If a fault occurs the fault will be recorded in history for display on the medium user interface in the History Menu. Each fault type will be displayed in the history menu with a number between 0 and. A reading of + will mean that fault has occurred more than three times in the past. The history menu can be cleared with a power cycle only. Alarm date and time are not included in the history. Inputs and Outputs onfiguration Field Selectable Options Freeze Detection Set Point (BI-5) The freeze detection set point input allows you to adjust the freeze detection set point (AI-5). When the jumper is installed on BI-5 (Wire #24) the freeze detection set point is factory set for 0 F (- ). When the jumper on BI-5 (Wire #24) is removed the freeze detection set point will be 5 F (-9 ). Accessory Outputs (BO-7 and BO-8) Accessory Output will be energized 90 seconds prior to the compressor output being energized. Accessory Output 2 will be energized with the blower output (BO-). When the corresponding compressor output is turned off the accessory output will be deactivated immediately. These outputs are selectable for normally open or normally closed operation through the MUI or through the BAS. FX0 User Interface (MUI) Physical Layout Power LED Alarm LED Up Arrow Right Arrow LED LED 4 Escape (ES) Button Return Button LED 8 Left Arrow Down Arrow Alarm LED - Indicates a Lock-Out or a bad Freeze Sensor Power LED - Shows FX processor is operational LED - Flashing shows ompressor running LED 2 - Flashing shows Full apacity ompressor running LED - On shows Fan running LED 4 - On shows Reversing Valve in cool LED 8 - Flashing shows unit in Test Mode 4