Commercial Water Source Heat Pump Water Heater Operations and Installation Manual

Similar documents
Commercial Air Source Heat Pump Water Heater Operations and Installation Manual

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS

Trouble Shooting Guide PWA, 3-phase (D10571)

Rev. E 2013 Pentair Technical Products P/N Distributed by: McLean Parts

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

T-Series Air Conditioner T15 Model

OPERATION & INSTALLATION MANUAL

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

Installation and Operations Manual

Surna 25-Ton Chiller Operating & Maintenance Manual

RPI Industries, Inc.

INSTALLATION & MAINTENANCE MANUAL FOR QuickDraw

Trouble Shooting Guide RAA, 1-phase (D3627)

PROAIR Air Conditioner. CR23 Model INSTRUCTION MANUAL nvent Rev. D P/N

Trouble Shooting Guide PAA, 1-phase (D3731)

AQUA LOGIC S MULTI-TEMP Water-Cooled Marine Duty Series chiller

Trouble Shooting Guide FAA, 3-phase (D3631)

T-Series Air Conditioner T20 Model

Read and save these instructions

POLAR TEMP FARM MORTALITY UNIT OPERATION MANUAL

CELDEK Evaporative Cooler Module Installation, Operation, and Maintenance Manual. CELDEK Evaporative Cooler

Condensing Unit Installation and Operating Instructions

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

T-SERIES Air Conditioner. T50 Model INSTRUCTION MANUAL nvent Rev. F P/N

T-Series Air Conditioner T53 Model

PROAIR Air Conditioner. CR29 Model INSTRUCTION MANUAL nvent Rev. I P/N

WATLOW IND. WATROD Circulation Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date: 6/11/2008 Rev: 2.00

OWNER S MANUAL. Vintage Classic HEAT COOL models. Proudly Made in the USA

T-SERIES Air Conditioner. T20 Model INSTRUCTION MANUAL nvent Rev. C P/N

InstructIon Manual KrEs EQuIPMEnt stands

T-SERIES Air Conditioner. T29 Model INSTRUCTION MANUAL nvent Rev. I P/N

WATLOW IND. WATROD Flange Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date:6/11/2008 Rev: 2.00

Flow Factor ~

SPECTRACOOL Air Conditioner. N21 Model INSTRUCTION MANUAL nvent Rev. G P/N

KPHE24 SERIES WATER-TO-AIR HEAT EXCHANGER

OWNER S MANUAL. Models: AC110, AC125, AC150 made from 2003 through Proudly Made in the USA

Horizontal/Side Discharge Condensing Units

T-SERIES Air Conditioner. T43 Model INSTRUCTION MANUAL nvent Rev. I P/N

PROAIR Air Conditioner. CR43 Model INSTRUCTION MANUAL nvent Rev. H P/N

User s Information and Installation Instructions

1025, BOUL. MARCEL-LAURIN INSTRUCTION MANUAL FOR WATER COOLED ENVIROCHILL CHILLER. Prepared par Claude Gadoury, P. Eng MTL TECHNOLOGIES INC.

M52 3-Phase INSTRUCTION MANUAL FOR: McLean Thermal Business Park Blvd. N Champlin, MN Tel: Fax:

Model R060 Installation - Operation Manual

INSTALLATION INSTRUCTIONS & HOME OWNERS MANUAL ECO 18 ECO 24 ECO 27 IMPORTANT SAFETY INFORMATION

WATLOW IND. FIREBAR Flange Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date: 6/11/2008 Rev: 2.00

RPI Industries, Inc.

OWNER S MANUAL. Vintage Signature Series models: AC750, AC1050, AC1100, AC1250, AC1500, AC1750. Proudly Made in the USA.

Split Floor-Mounted Cooling System Operation Care Installation Manual

ProAir CR43 INSTRUCTION MANUAL FOR: McLean Thermal Business Park Blvd. N Champlin, MN Tel: Fax:

A910.8A Remote Water Chiller, 8 GPH A A / A A-220V TECHNICAL ASSISTANCE TOLL FREE TELEPHONE NUMBER:

! The Caution Symbol (exclamation point) alerts you to a "CAUTION", a safety or

HOMEADVANTAGE II IMPORTANT SAFETY INFORMATION

Installation and Operation Guide

WATLOW ELECTRIC MFG CO. FIREBAR Screw Plug Installation & Maintenance Manual I&M NUMBER: Page: 1 Date: 11/25/2013 Rev: 4.

OPERATION MANUAL Dated: 04/09/2018 Document Name: SHV _OM Page 1 of 8. Ion Technologies SHV40, 75 & 100 Sewage Ejector Pump SAFETY WARNINGS

WHYNTER Compressor Cooling Beverage Refrigerator - Stainless Steel

SWIMMING POOL HEAT PUMP UNIT ECO - series. Installation & Instruction manual

Installation and Operation Guide

Operation and Maintenance Manual

RecoverX Oil-Filled Hermetic Refrigerant Recovery System. Operation and Maintenance Manual

INSTALLATION & OPERATING INSTRUCTIONS FOR CEILING MOUNT AIR HANDLERS AC SERIES

INSTALLATION AND OPERATING MANUAL

T-SERIES Air Conditioner. T62 Model INSTRUCTION MANUAL nvent Rev. F P/N

BLG-HGP Model Bottom Mounted Full-Length Swing Glass Door Freezer Merchandisers

KPHE32 SERIES WATER-TO-AIR HEAT EXCHANGER

KNHE30 SERIES WATER-TO-AIR HEAT EXCHANGER

OPERATION & INSTALLATION MANUAL IR-30, IR-234, IR-245, IR-260, IR-288, IR-14K220, IR-18K220. Electric Tankless Hot Water Heater

PROAIR Water-Cooled Air Conditioner. CR43WC Model INSTRUCTION MANUAL

SPA BLOWER OWNER'S MANUAL XXXX, XXXX, XXXX, XXXX, XXXX, XXXX fax

Operator s Manual. IP-100 Immersion Probe Cooler

Installation & Operations Manual for R-290 SERIES. BMG-HGP Model Bottom Mounted Full-Length Swing Glass Door Refrigerator Merchandisers 2/

V-SERIES Air Conditioner. VA08 Model INSTRUCTION MANUAL nvent Rev. F P/N

- 1 - Updated on 18 March, 2010

INSTALLATION AND OPERATING MANUAL

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 350 SERIES CIRCULATION HEATERS

Installation & Operations Manual for. BMG-HGP Model Bottom Mounted Full-Length Swing Glass Door Refrigerator Merchandisers. 4/17 Rev.

Installation Instructions

OPERATING AND INSTALLATION MANUAL

INSTALLATION INSTRUCTIONS

KNHE48 SERIES WATER-TO-AIR HEAT EXCHANGER

Condensing Unit and Refrigeration System Installation & Operations Manual R448A/R449A

CLIMAGUARD Air-to-Air Outdoor Heat Exchangers INSTRUCTION MANUAL. Rev. H 2015 Pentair Equipment Protection P/N

GENESIS Air Conditioners. All Models INSTRUCTION MANUAL nvent Rev. K P/N

OPERATION AND MAINTENANCE INSTRUCTIONS FOR ROOF TOP HEAT PUMPS AND CEILING PLENUMS

Read and save these instructions

OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER. Electric Heater Company Base Model "BWXP"

4201 Lien Rd Madison, WI Owner s Manual Therma-Stor III Heat Recovery System. Installation, Operation & Service Instructions

DISPOSER CONTROL CENTER

OPERATOR'S MANUAL. IMPORTANT: READ OPERATOR'S MANUAL CAREFULLY Please fill out & return your warranty card! DP80405

38ASB/CCARS240~600 (036~060) AIR-COOLED CONDENSING UNIT

4.5 CU.FT. REFRIGERATOR INSTRUCTION MANUAL

Read and save these instructions

Installation Instructions

WATLOW IND. Thermostat Control Installation & Maintenance Manual I&M NUMBER

BMG-HGP & BMG-SLP Model Bottom Mounted Full-Length Glass Door Refrigerator Merchandisers

INSTALLATION AND OPERATING INSTRUCTIONS

Model TWBS.EW.H Tempered Water Blending System

Installation Instructions

ProAir CR29 INSTRUCTION MANUAL FOR: McLean Thermal Business Park Blvd. N Champlin, MN Tel: Fax:

Transcription:

GEYSER C-250W Commercial Water Source Heat Pump Water Heater Operations and Installation Manual Geyser 250W Manual Version 2.2 Nyle Systems 12 Stevens Rd Brewer, ME 04412 www.nyle.com info@nyle.com 800-777-6953

GEYSER C-250W Read through entire manual before installing, operating, or servicing this unit. Failure to follow any steps or guidelines could result in personal injury, death, destruction of property or may cause the unit to become inoperable. This manual must be kept with the unit at all times. PRECAUTIONS Do not operate unit if it or any of its parts: Have been exposed to fire. Have been submerged in water or exposed to flooding. Have been exposed to extreme temperatures. Have significant interior or exterior damage. Have been running without water. In the case of any of the above, have the unit serviced by a qualified professional before continuing operation. Explosion Hazard! DO NOT purge or pressurize this system with oxygen to test for leakage. Using oxygen may cause dangerous explosive reaction. Overheating water in the tank can cause explosion. Be sure to install correct temperature and pressure relief valves on storage tanks. Failure to do so may result in excessive pressure in the tank which can cause an explosion. GROUNDING Heat pump water heater must be grounded. Failure to ground will result in unreliable performance or an inoperative unit. You may chose to: Ground by connecting unit to a grounded metal, permanent wiring system. or Ground by running an equipment grounding conductor with the circuit conductors and connecting those to the equipment grounding terminal or lead on the water heater. Grounding must be in accordance with national and local electrical codes. Please contact your municipal offices for more information on building codes. Refrigerant! Unit contains R-134a refrigerant under high pressure. Refrigerant must be recovered to relieve pressure before servicing. DO NOT use unapproved refrigerants, substitutes or additives. Failure to abide by these guidelines can result in death, injury and property damages. Contact Nyle s service department for more information on refrigerant options. Burn Risk! Water temperatures over 125 F (52 C) can cause severe burns. Children, elderly and disabled peoples are at high risk of injury and require assistance. Test water for safe temperature before use. Water heater must have temperature limiting devices installed according to local building codes. Electrical Shock! Turn off power to unit before service. Make sure wires are labeled before disconnecting. Test unit after reconnecting wires. Failure to do the above could result in death or injury.

TABLE OF CONTENTS GENERAL INFO & SAFETY...1 INTRODUCTION...1 SAFETY INFORMATION...1 PHYSICAL DIMENSIONS... 2-3 SPECIFICATIONS...4 UNIT SPECIFICATIONS...4 PROGRAMMABLE LOGIC CONTROLS...5 PLC CONTROLLER...5 TEMPERATURE & SETPOINTS...5 CONTROL SCREENS... 6-7 INFO SCREEN...6 SETUP SCREEN...6 ALARM SCREEN...7 RECEIVING, STORAGE & PLACEMENT...8 RECEIVING UNIT...8 PLACEMENT & STORAGE...8 INSTALLATION...9 INSTALLATION...9 SYSTEM USAGE...9 SAMPLE PLUMBING DIAGRAM...10 MAINTENANCE & TROUBLESHOOTING...11 TROUBLE SHOOTING...11 MAINTENANCE...11 SAFETY SETTINGS & WARRANTY...12 SAFETY SETTINGS...12 LIMITED WARRANTY...12 NOTES... 12-13

GENERAL INFO & SAFETY GENERAL INFORMATION HOW IT WORKS INTRODUCTION Nyle Systems water source heat pumps offer commercial and industrial users an energy efficient means of heating water to temperatures as high as 150 F. Nyle water source heat pumps work by gathering heat from the water source and through a refrigeration cycle, depositing the extracted heat into sanitary water at a usable temperature. Through this cycle both hot sanitary water and cooler source water is made available. Nyle Systems C-250W water source heat pump is a single-package horizontally mounted unit with builtin digital thermostats and manual controls. This unit is built specifically for use in large scale commercial applications where a large amount of sanitary water is needed at usable temperatures. The Geyser C-250W is water sourced, meaning heat is extracted from the source water and, utilizing heat pump technology, is used to heat sanitary water to the desired temperature. As a by-product of heating water, the Geyser C-250W unit will also cool whatever water is being used as the source Performance for heat pumps is expressed in terms of Coefficient of Performance (COP). In typical installations the Geyser C-250W unit achieves COPs ranging from 3-5, depending on source and heated water temperatures. This means it creates 3-5 units of renewable heat from the source water for every 1 unit of electricity required to run the unit. This 300% to 500% efficiency offers significant savings over gas, oil, or electric water heaters with efficiencies for these technologies typically in the range of 70% to 95%. ABOUT THE GEYSER C-250W The Geyser C-250W has a nominal heating capacity of 250,000BTUH, generating up to 567 gallons of hot water per hour. The C-250W also has a nominal cooling capacity of 180,100 BTUH. These units can heat water efficiently up to 150 F and are ideally suited for restaurants, hotels/motels, apartment buildings, laundry facilities, health care facilities, schools, sports arenas, gyms, institutions such as prisons, military barracks, specific manufacturing plants, and more. SAFETY INFORMATION SAFETY CONSIDERATIONS Installation and servicing of heat pump equipment can be hazardous due to system pressure and electrical components. Please note that only trained and qualified service personnel should preform installation, repairs, or service on the Geyser C-250W. When preforming installation, repair, or service on the unit, observe precautions in the manual, tags, and labels attached to the unit. Follow all other safety precautions that may apply. Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock or other hazardous conditions which may cause personal injury or property damage. Always consult a qualified installer, service agency, or your distributor for information or assistance. Do not stand or sit on the unit Disconnect all power before opening the control panel. There is no need to open the control panel unless there is a malfunction internally. Only a licensed technician is to open the control panel. Disconnect all power before installing or servicing the Geyser C-250W. Ensure the power receptacle is rated for the appropriate load. See Data Sticker on the unit. Ensure that the electrical supply has proper overload fuse or breaker protection rated for at least the appropriate amperage. See Data Sticker on the unit. All lifting of the Geyser C-250W heat pump water heater should be done with a fork lift or pallet jack to prevent back injuries. Never move the unit alone. If the pressure relief valve on the existing water heater tank is leaking or dripping, call a licensed plumber for repair. Do not plug or remove valve as this could result in an explosion. Water temperature over 125 F can cause severe burns resulting in scalding. Follow all safety instructions provided by the manufacturer of the existing water heater. Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for brazing operations and have a fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions attached to the unit. Consult local building codes and the National Electrical Code (NEC) for special installation requirements. 1 GENERAL INFO & SAFETY

PHYSICAL DIMENSIONS PHYSICAL DIMENSIONS 2

PHYSICAL DIMENSIONS 3 PHYSICAL DIMENSIONS

SPECIFICATIONS UNIT SPECIFICATIONS Model Number Recovery Rate* C-250W 567 Gal/Hr Heat Capacity* 250,500 BTUH Power Input* Cooling Capacity* Compressor Type Refrigerant 21 KW 180,100 BTUH Semi Hermetic Reciprocating R-134a Water Temp. 150 F Water Corrections Water Flow Rate Condenser ** Condenser Pressure Drop** Water Flow Rate Evaporator** Evaporator Pressure Drop** 2 FNPT 50 Gal/Min 7.5 PSI 36 Gal/Min 4.8 PSI Dimensions (LxWxH) 42 x 61 x 48 1/2 Weight 1,300 LB SPECIFICATIONS 4

PROGRAMMABLE LOGIC CONTROLS PLC CONTROLLER Your Geyser C-Series may be equipped with a Programmable Logic Controller (PLC) and Human- Machine Interface (HMI) for controlling the water heating process. Sensors within the system provide operating information to the PLC which uses this information to safely control the heating process. The control comes with a factory water high temperature setpoint of 120 F. The control is limited to a maximum water high temperature setpoint of 150 F. Operating at higher temperatures could void the warranty. TEMPERATURE & SETPOINTS To view and adjust the temperature setpoint, follow these steps. View the HMI mounted on the electrical panel door. Locate the High Temp value on the setup screen. Touch the box representing the current value. A keypad and cursor will appear. Enter the desired temperature setpoint (maximum 150 F) Touch the return, or enter key on the keypad. The display will return to the info screen, and your entered value should be displayed in the high Temp value box. The unit is now set to heat up to the new setpoint temperature. Note: Until the Return key is pressed, the unit will run based upon the previous setpoint temperature. SETPOINT RANGES & SAFETIES SAFETY FACTORY SETTING ACTION Low Flow (heating or cooling side) < 4.4 Gal/Min Shutoff Low water temperature Safety (leaving evaporator) 36 F Shutoff Low Water Temperature Alarm (leaving evaporator) 38 F Alarm High Water Temperature Safety (leaving condenser) 155 F Shutoff Temperature Setpoint Range 100 F - 150 F - High Refrigerant Pressure Cut-out 380 psi Shutoff/Alarm High Refrigerant Pressure Cut-in 340 psi - Low Refrigerant Pressure Cut-out 15 psi Shutoff/Alarm Low Refrigerant Pressure Cut-in 35 psi - Low Refrigerant Pressure Bypass Time Delay 30 sec - Low Oil Pressure Differential Cut-out 9 psi Shutoff/Alarm Low Oil Pressure Differential Cut-in 13 psi - Low Oil Pressure Differential Time Delay 120 sec - Compressor Anti-Short Cycle Delay 180 sec - 5 PROGRAMMABLE LOGIC CONTROLS

CONTROL SCREENS INFO SCREEN SETUP SCREEN START : Starts heat pump STOP : Stops heat pump Low Pressure : indicates current pressure on low side of refrigeration system High Temp : indicates current user-selected high water temperature setpoint Time/Date : press to set time and date on control screen: High Pressure : indicates current pressure on high side of refrigeration system Oil Pressure : indicates status of compressor oil pressure differential (OK, Fault) Solenoid Valve : indicates status of suction line solenoid valve (Open, Closed) Compressor : indicates running status of compressor (On, Off) Flow HOT : indicates water flow status on condenser side of system (True, False) Flow COLD : indicates water flow status on evaporator side of system (True, False) HOT IN/OUT : indicates water temperatures entering and leaving the condenser side of system COLD IN/OUT : indicates water temperatures entering and leaving the evaporator side of system CTD : indicates remaining time in compressor time delay countdown CONTROL SCREENS 6

CONTROL SCREENS ALARM SCREEN LOW TEMP : GREEN indicates that the water temperature leaving the evaporator is above the shutoff value. RED indicates that the water temperature leaving the evaporator is below the shutoff value. OVER TEMP : GREEN indicates that the water temperature leaving the condenser is below the shutoff value. RED indicates that the water temperature leaving the condenser is above the shutoff value. The alarm screen is accessible when the flashing warning symbol is displayed in the screen header. Press the flashing warning symbol to access the alarm screen. Only one alarm will display at a time. If more than one alarm is active, the most recently activated alarm will display. Once the indicated alarm condition is resolved, the next active alarm, if any, will display until all alarm conditions are resolved. EVAP FLOW : GREEN indicates evaporator flow switch is closed, or enough water flow is present. RED indicates evaporator flow switch is open, or not enough water flow is present. COND FLOW : GREEN indicates condenser flow switch is closed, or enough water flow is present. RED indicates condenser flow switch is open, or not enough water flow is present. OIL PRESSURE : GREEN indicates that the compressor differential oil pressure is within the normal operating range. RED indicates that the compressor differential oil pressure is outside of the normal operating range. LOW PRESSURE : GREEN indicates that the refrigeration suction pressure is above the cut-out value. RED indicates that the refrigeration suction pressure is below the cut-out value. HIGH PRESSURE : GREEN indicates that the refrigeration discharge pressure is below the cut-out value. RED indicates that the refrigeration discharge pressure is above the cut-out value. 7 CONTROL SCREENS

RECEIVING, STORAGE & PLACEMENT IMPORTANT: RECEIVING When receiving shipment at the job site, carefully inspect the shipment against the bill of lading. Please make sure that all unit s have been received as ordered. Inspect each units shipping crate/packaging and inspect each unit for damage. If there is a problem, notify the shipping company to make proper notation of any shortages or damage on all copies of the freight bill. Check The Following: 1. 2. 3. 4. RECEIVING UNIT Please read this entire manual before installation. Be sure to follow all installation steps. Failure to conform to these instructions may decrease the heat pump performance and could cause severe injury or death. Only qualified, licensed persons should install the heat pump equipment and electrical supply. Installation must conform to all local, state, and federal applicable codes. Compare the electrical data on the unit data sticker with ordering and shipping information to verify that the correct unit has been delivered. Verify that the unit is the correct model for the entering water temperature of the job. Verify that the refrigerant tubing is free of kinks or dents. Inspect all electrical connections. Be sure connections are clean and tight at the terminals. UNIT LOCATION 1. 2. 3. 4. This unit is designed for indoor use in climates where the outdoor temperature can drop below freezing. Provide sufficient space for water and electrical connections. Locate unit in an area that allows for easy access and removal of access panels. Allow enough space for service personnel to perform maintenance. It is recommended to allow 3ft clearance on all sides. Clearance for electrical should follow all local codes and regulations. CLEANING AND FLUSHING 1. 2. PLACEMENT & STORAGE If the heat pump is to be connected to an existing storage tank, the old tank must be drained and cleaned of sediment before the heat pump is installed. Prior to start-up of any heat pump, the water circulating system must be cleaned and flushed of all dirt and debris. STORAGE If the equipment is not needed for immediate installation upon its arrival at the job site, it should be left in its shipping carton and stored in a clean, dry area of the building. Units must be stored in an upright position at all times. Do not remove any equipment from its shipping package until it is needed for installation. NOTE: It is the responsibility of the purchaser to file all necessary claims with the shipping company. RECEIVING, STORAGE & PLACEMENT 8

INSTALLATION IMPORTANT: INSTALLATION Please read this entire manual before installation. Be sure to follow all installation steps. Failure to conform to these instructions may decrease the heat pump performance and could cause severe injury or death. Only qualified, licensed persons should install the heat pump equipment and electrical supply. Installation must conform to all local, state, and federal applicable codes. CONNECTING WATER PIPING All plumbing should be performed by a licensed professional, and should adhere to all local and state codes. 1. 2. 3. 4. 5. For maximum efficiency, the heat pump should have the coldest water from the hot water supply tank running through the condensing heat exchanger and the warmest possible air passing through the evaporating heat exchanger. This is done to make efficient use of the temperature difference. Therefore, the lowest connection in the hot water supply tank should be used for the condenser supply (Hot Water Inlet) to the heat pump and the condenser return (Hot Water Outlet) from the heat pump should be installed higher up on the tank, but not near the top. Installing the return at the top of the tank can cause cooler water to mix with the hottest water at the top of the tank. Lines to and from the heat pump must be properly sized for the correct flow rate. Too much or too little water flow will decrease efficiency. Water tank ports must also be large enough to ensure peak water demands can be handled. For the Geyser C-250W the line size should be 1. Some municipal codes require installation of temperature and pressure relief valves on plumbing sections. Others may require dielectric plumbing fittings. Use copper or bronze fittings. All hot water pipes must be insulated. All plumbing must be sized for peak water flow demands. Tanks with dip tubes should be used with caution or avoided altogether, because the dip tube can restrict flow and cause heat pump malfunction. CONNECTING WIRING All electrical work should be performed by a licensed professional, and should adhere to all local and state codes. The heat pump control is housed inside the electrical enclosure. Follow the name plate information located on the unit for proper voltage, phase, ampacity, breaker sizing and wire sizing. Locate a fuse disconnect as close as possible to the heat pump. SYSTEM USAGE BEFORE START UP Verify the following: High voltage is correct and matches nameplate Piping is complete and the water system has been cleaned and flushed. Air is purged from closed loop system. Isolation valves are open and water control valves or loop pumps are wired. Service panels are in place. Unit controls are in off position. 9 INSTALLATION

SAMPLE PLUMBING DIAGRAM SAMPLE PLUMBING DIAGRAM 10

MAINTENANCE & TROUBLESHOOTING MAINTENANCE UNIT HEAT EXCHANGER MAINTENANCE 1. 2. Keep all air out of the water or solution. Keep the system under pressure at all times. Closed loop systems must have positive static pressure. REPLACEMENT PROCEDURES When contacting Nyle for service or replacement parts, refer to the model number and serial number of the unit as stamped on the serial plate attached to the unit. If replacement parts are required, mention the date of installation of the unit and the date of failure, along with an explanation of the malfunctions and a description of the replacement parts required. TROUBLE SHOOTING COMPRESSOR WILL NOT RUN 1. 2. 3. 4. 5. The breaker may be open or the circuit breaker is tripped. Check electrical circuits and motor windings for shorts or grounds. Investigate for possible overloading. Replace fuse or reset circuit breakers after fault is corrected. Supply voltage may be too low. Verify supply voltage matches name plate voltage listed. Control system may be faulty. Check control for correct wiring and check the transformer for proper voltage. Wires may be loose or broken. Replace or tighten. The low pressure switch may have tripped due to one or more of the following: a) Heating 1) Source temperature too low 2) Low Refrigerant b) Cooling 1) Heated water flow too low 2) Low refrigerant 6. 7. The high pressure switch may have tripped due to one or more of the following: INSUFFICIENT COOLING OR HEATING 1. 2. a) Heating 1) Condenser heat exchanger clogged 2) Heated water flow too low 3) Heated water too hot b) Cooling 1) Condenser heat exchanger clogged 2) Heated water flow too low Water temperatures are outside of their acceptable ranges. UNIT OPERATION IS NOISY 1. 2. 3. 4. 5. 6. Check for restriction in water flow. Check refrigerant subcooling and superheat for proper refrigerant charge and expansion valve operation. Check compressor for loosened mounting bolts. Make sure compressor is floating free on its isolator mounts. Check for tubing contact with the compressor or other surfaces. Check screws on all panels for tightness. Check for chattering or humming in the contactors or relays due to low voltage or a defective holding coil. Replace the component. Check for proper installation of vibration absorbing material under the unit. Check for abnormally high discharge pressures. Check for any loose panels or parts that may be in contact with each other; vibrations from the compressor may cause them to chatter against one another. 11 MAINTENANCE & TROUBLESHOOTING

SAFETY SETTINGS & WARRANTY SAFETY SETTINGS Safety Factory Setting Action Temperature Setpoint 120 F - High Refrigerant Pressure Cut-out 400 psi Shutoff High Refrigerant Pressure Cut-in 300 psi Restart Low Refrigerant Pressure Cut-out 5 psi Shutoff Low Refrigerant Pressure Cut-in 20 psi Restart Defrost Temperature Setpoint (Refrigerant) 28 F Defrost Compressor Anti-short Cycle Delay 300 sec - LIMITED WARRANTY The equipment supplied by Nyle is warranted to be free from defects in workmanship and materials for a period of one year from the date of the original installation or 15 months from the date of delivery, whichever comes first. A new or remanufactured part will be supplied by Nyle providing the defective part is first returned to Nyle for inspection. The replacement part assumes the unused portion of the warranty. The warranty does not include labor or other costs incurred for diagnosis, repairing or removing, installing or shipping the defective or replacement parts. Nyle makes no warranty as to the fitness of the equipment for a particular use and shall not be liable for any direct, indirect or consequential damages in conjunction with this contract and/or the use of its equipment. Buyer agrees to indemnify and save harmless Nyle from any claims or demands against Nyle for injuries or damages to third parties resulting from buyer's use or ownership of the equipment. No other warranties, expressed or implied, will be honored unless in writing by an officer of Nyle Systems. SAFETY SETTINGS & WARRANTY 12

NOTES 13 NOTES

NOTES NOTES 14