Common Building Code Misinterpretations

Similar documents
Preview of the MA Building Code (780 CMR) 9 th edition

Open to Below: A Discussion of Allowed Floor Openings. Jay A. Ierardi, Ph.D., P.E., LEED AP. Kevin S. Hastings, P.E., LEED AP

Richard B. Alpert, P.E. Senior FPE, Clark Nexsen

Building & Fire Code Academy. Building Better With Our Greatest Resource Education. Welcome!

3/6/2018. Design Tips For Fire and Smoke Barriers. Professional Development Hours (PDH) Certificates. Copyright Materials

Taming the Health Care Building Codes NFPA vs. The International and Chicago Building Codes JENSEN & HALSTEAD LTD.

BUILDING CODE OF THE CITY OF NEW YORK. New York City Department of Buildings 4 June 2007

Agency for Health Care Administration

Laboratories and Hazardous Materials. Company Overview

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

January 1, 2014 Mandatory Effective Date

Agency for Health Care Administration

Questions related to specific materials, methods, and services will be addressed at the conclusion of the presentation.

NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES

CHAPTER 7 ALTERATIONS LEVEL

Sprinklers in Wood-Frame Construction:

SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY

INITIAL FIRE SAFETY ASSESSMENT

2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content

FIRE/SMOKE BARRIER FUNDAMENTALS

The project scope work is 90% new construction and 10% remodel in Esslinger Hall.

Fire Protection Coffee Break Training May 2016

WORKSHEET 2-1 THE MANITOBA RESIDENTIAL OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES

Passive House Northwest AIA CEU Provider. Aubrey Gewehr March 27, 2015

SPRINKLER PROTECTION OF COMBUSTIBLE CONCEALLED SPACES WITH LESS THAN 6 BETWEEN OPPOSITE FACES IN CAVITY.

2015 IRC Significant Changes For Mechanical and Fuel Gas with LSUCCC Amendments

PERFORMANCE COMPLIANCE METHODS

SECTION 907 FIRE ALARM AND DETECTION SYSTEMS

Life Safety Damper Installation ASHRAE St Louis Chapter Feb. 9,2015. Peter McDonnell, PE, LEED AP BD+C McClure Engineering

PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE

Agency for Health Care Administration

Recommended Amendments to the 2015 International Existing Building Code North Central Texas Council of Governments Region

2012 B.C. Building Code Compliance Review (Division B Part 3)

Date: February 22, 2005 Kimbalton DUSEL, Pre-S-2 Submittal CNA0402 PRELIMINARY CODE REVIEW. International Plumbing Code Edition

PERFORMANCE COMPLIANCE METHODS

SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY

PERFORMANCE COMPLIANCE METHODS

FIRE PROTECTION KEY DESIGN CONCEPTS IN HEALTHCARE FACILITIES Scott Twele, Aman Shah Steven Dannaway. AIA Healthcare Group

THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #6

COMPLIANCE ALTERNATIVES

NFPA 45 NFPA 211 NFPA 1600

COMPLIANCE ALTERNATIVES

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION

For the Florida Building Commission And the Fire Code Advisory Council

The Residences at Christina Landing Wilmington, DE

Fire and Life Safety Committee

NFPA 101 Code Update from 2012 Edition to the 2015 Edition

Nirmal Chandra Sinha. Supposed to complete(dd/ MM/YYYY) Comments after Physical Inspection

FIRE SAFETY INSPECTION REPORT

2009 International Fire Code Errata. SECOND PRINTING (Posted April 6, 2010)

FIRE SAFETY INSPECTION REPORT

IFC Significant Changes from the 2009 to the 2015 Edition Tier 1

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

WHITE PLAINS SMOKE CONTROL CODE PART 1. GENERAL REQUIREMENTS

FIRE SAFETY INSPECTION REPORT

FIRE-RESISTANCE-RATED CONSTRUCTION A Primer on IBC Chapter 7

FIRE SAFETY INSPECTION REPORT

LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2006 EDITION

HIGH-RISE RETROFIT ORDINANCES - NO and NO

Welcome to the AccessibilityOnline Webinar Series. Listening to the Webinar. Listening to the Webinar, continued

PLAN REVIEW SUBMITTAL GUIDE

Life Safety - Means of Egress/Exits NFPA 101

FIRE SAFETY REQUIREMENTS FOR PRE RESIDENTIAL BUILDINGS OF THREE OR MORE STORIES (DOROTHY MAE ORDINANCE - NO. 158,963)

Chapter 2: Definitions

Overview of Fire Alarm Provisions Based on the 2012 IBC, IFC and NFPA 72, 2013 Edition

IBC Committee Responsibility Matrix January 2017

Emergency Planning for Institutional Facilities

Welcome to the AccessibilityOnline Webinar Series. Listening to the Webinar

Human Factors - Egress Analysis for High Hazard Occupancies. Presented by: Michael J. Klemenz, PE, SFPE

WORKSHEET 3-1 THE MANITOBA OFFICE OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES

FIRE SAFETY INSPECTION REPORT

INITIAL FIRE SAFETY ASSESSMENT

LIFE SAFETY COMPLIANCE: ADAPTING TO THE 2012 LIFE SAFETY CODE

9/23/ :47 AM. Second Revision No NFPA [ New Section after ] Submitter Information Verification. Committee Statement

Presented by: Bill Lauzon, PE Lauzon Life Safety Consulting, LLC Web: Lauzon-LSC.com

SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY

THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #5

SP07: Coordinating New Door Assembly Installation with Access Control Systems

COURSE SYLLABUS HVAC AND MECHANICAL CONSIDERATIONS FOR PART 3 BUILDINGS CORRESPONDENCE COURSE

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

Chapter Nursing Homes

FIRE SAFETY INSPECTION REPORT

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST

Building Codes & Standards for Healthcare. Healthcare Construction Certificate - Level 1

PROJECT: CIVIC ADDRESS:... PERMIT APPLICATION NO.: DATE:... CRP:. Certified Professional:.

American Fire Sprinkler Association. An Introduction to the IBC and IFC

Code Technologies Committee Report Elevator Lobby Group A changes: Elevator Lobby

WORKSHEET 4-1 THE MANITOBA FIRE RISK INDEX FOR THE RESIDENTIAL OCCUPANCY OF HERITAGE BUILDINGS FIRE SAFETY PARAMETERS

FIRE SAFETY INSPECTION REPORT

FIRE ALARM SYSTEMS & 780 CMR. Dave LeBlanc, PE, FSFPE March 17, 2015

FIRE INSPECTORS GUIDELINES FOR PLAN REVIEWS AND INSPECTIONS OF NEW CONSTRUCTION / ADDITIONS AND CHANGE OF OCCUPANCY

BCAC Egress Work Group

2012 International Fire Code Significant Changes. IFC Background. Purpose IBC and 2012 NFPA 101 Significant Means of Egress Changes

FIRE SAFETY INSPECTION REPORT

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE ASSESSMENT REPORT (FAR)

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course

GROUP SR SPECIAL (ASSISTED SELF-PRESERVATION) OCCUPANCIES

Fire Rated Door Assemblies: Compliant Designs

Transcription:

Common Building Code Misinterpretations Presented by: Ron Melucci, P.E. Technical Manager, FP Division Engineering Planning and Management, Inc. rbm@epm inc.com www.epm inc.com 508 875 2121

Engineering Planning and Management, Inc. is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned on completion of this program will be reported to CES Records for AIA members. Certificates of Completion for non-aia members available on request. This program is registered with the AIA/CES for continuing professional education. As such, it does not include content that may be deemed or construed to be an approval or endorsement by the AIA of any material of construction or any method or manner of handling, using, distributing, or dealing in any material or product. Questions related to specific materials, methods, and services will be addressed at the conclusion of this presentation. 2

Copyright Materials This presentation is protected by US and International copyright laws. Reproduction, distribution, display and use of the presentation without written permission of the speaker is prohibited. Engineering Planning and Management (EPM) 2012 3

Who is EPM? Engineering consulting and strategic technology firm specializing in fire protection Incorporated 1980 HQ Framingham MA 24 FP engineering staff

Presentation Content Primarily 8 th MSBC (based on IBC 2009) Code Sections that are: Misinterpreted Confusing Overlooked 5

403.6.1 Fire service access Two (2) fire service access elevators are now required in high rise buildings greater than 120 ft. in height (403.6.1) elevators Intended for rescue, staging, etc. 6

Fire Service Access Elevator MSBC 403.6.1 requirements in compliance with IBC 3007 Direct access from stair Elevator lobby minimum 150 s.f. s/e power and 1 hour FRR for all el. & lobby circuits 7

Mixed Occupancy Buildings Code compliance approaches: Accessory Occupancy Incidental Accessory Occupancy (next slide) Non Separated Mixed Occupancy Separated Mixed Occupancy Special Provisions (MSBC 509) Separate Buildings Upgrade Construction Type 8

9

Incidental Accessory Example Multifamily building (R 2), 4 stories, Type (2B) construction with laundry room (F 1) in Basement Allowable height for R 2 is 5 stories, F 1 is only 3 stories Options to comply with building height requirements: Call accessory area if < 10%, still need smoke partitions and sprinklers per Table 508.2.5 (2012 edition clarifies this) If > 10%, also need rated slab separation (separated mixed occupancy) to address height limitation R 2 R 2 R 2 R 2 F 1

Exterior wall opening protection Section 705.8.6 states that openings can be unprotected in the wall above the roof of a lower adjacent building if the lower roof is rated 1 hr. What is misleading about this? 11

Exterior wall opening protection Only considers fire spread from lower roof, not from exterior wall. Table 705.8 requirements still apply. 12

Fire Wall Penetrations IBC Interpretation No. 31 07 2006 Edition 705.2 Structural stability Penetrations are required to be designed for compliance with the provisions of Section 705.2 for structural stability. I.e. must be designed and installed so as to not damage wall if either side collapses. Some NFPA Standards (NFPA 91) prohibit through penetrations of fire walls 13

707.5.1 Supporting Construction Fire barriers must be supported by construction with equivalent FRR. Caution fire barriers on upper floors in non rated buildings: Shafts Atrium or sprinkler zone separation Incidental accessory rooms Other rooms requiring FRR 14

707.5.1 Supporting Construction IBC Interpretation No. 06 06 2003 Edition Issued: 05 31 06 Only the building elements within the load path of that portion of the building construction where the shaft enclosure is located are subject to the provisions of Section 706.4 with regard to supporting construction. 15

Sprinkler Systems Pop quiz, hot shot: If you are creating a 400 sf addition to your 7,200 sf building, are you required to retrofit sprinklers? 16

Sprinkler Systems MGL 26G required in all new buildings > 7,500 sq. ft. with sufficient water flow and pressure. [903.2 Note] also see building code Addition greater than 7,500 sq.ft. MGL 26G same requirement regardless of fire walls Retrofit triggered by major alterations (nature, extent, cost) more guidelines on 10/04/09 memorandum by MA ASAB 17

NFPA 13 vs 13R systems In adddition to height restriction, NFPA 13R systems limited to < 12,000 ft 2 in MA Many tradeoffs for fully sprinklered buildings apply to NFPA 13 systems but not NFPA 13R systems. Key code verbage in accordance with 903.3.1.1 (or 903.3.1.2). 18

Sprinkler trade offs (903.3.1.1 ) Atrium use 404.2 Underground Buildings 405.3 Control area FRR 414.2.4 Building area increase 506.3 Protected Openings Table 705.8 Elevator lobbies 708.14.1 Shaft enclosure exceptions 708.2 FRR of dwelling/sleeping unit sep 709.3 Draftstopping 717.3, 717.4 Delayed Egress 1008.1.9.7 Common POT 1014.3 Dead ends 1018.4 19

Smoke Control Systems Third Party Review is required for all smoke control system designs. Smoke Control Special Inspections are required to be performed by a registered FPE 20

Smoke Control Systems MSBC 909.12.13 The following boundaries must coincide: Atrium separation/ smoke zone Fire alarm zones Sprinkler system zones 21

Fire Pump Room Fire pump rooms require 2 hour fire resistant separation [913] Need FD direct access to exterior or through a fire rated passageway. 22

Emergency Responder Radio Coverage Emergency responder radio coverage now required in all buildings [915.1] unless otherwise approved by FD. Issue: difficult to predict radio performance before building construction is complete. 23

Egress Dimensions 8 th MSBC: egress width factors for new sprinklered buildings: emergency voice/alarm system provided 0.2 / occupant for stairs 0.15 / occupant for doors emergency voice/alarm system not provided 0.3 / occupant for stairs 0.2 / occupant for doors 24

Occupant Load Factors Pop quiz, hot shot True or False: The occupant load factor of a university classroom OL<49 (Group B) is 100 sf/occ The occupant load factor of an office tenant meeting room OL<49 (Group B) is 100 sf/occ The occupant load factor of a usable office building roof terrace is 15 sf/occ 25

Occupant Load Factor Table 1004.1.1 Based on Floor Area and Function of the Space Not based on Occupancy Classification How is the owner or tenant truly intending to use the space? 26

Group B Occupant Load Factors 27

Outdoor Areas MSBC 1004.8 OL is assigned by the building official in accordance with the anticipated use. What is the occupant load? What is the intended use? Outdoor area for service of building 1 means of egress (roof). 28

Number of Means of Egress Doors Based on occupancy, occupant load and common path of travel Two doors required where one of 3 conditions exist 29

Number of Means of Egress Is single egress from office tenant C acceptable? If OL < 49? If red line distance is less than 100 ft? 30

Exit discharge capacity Pop quiz, hot shot True or false: The exit discharge should always be sized to accommodate largest occupant load of any single floor served by the stair. 31

Exit discharge capacity False: largest occupant load of any single floor OR from converging floors above and below, whichever is greater. 32

Travel distance Minimum distance to reach any ONE exit Therefore must find the most remote point of occupiable floor space between the exits 33

Horizontal Exits Not the same as exit passageways! Horizontal exit subdivides a space into two(2) areas of refuge. Often used to solve compliance challenges related to exit and exit. An exit passageway is a horizontal extension of the stair shaft enclosure. Often used to solve compliance challenges related to exit and exit. 34

Use Group R # exits Two exits for R 2 unit OL of 21 in fully sprinklered buildings. Multifamily units 200 s.f/occ < 4,000 sf. one exit. Caution: Dormitory OLF still 50 s.f/occ therefore need 2 nd exit above 1,000 s.f. 35

Delayed Egress MSBC 1008.1.9.7 Requires many control functions for unlocking May only be used for one door in means of egress May not be used in Use Groups A, E or H 36

Delayed Egress 37

Access Controlled Egress Doors MSBC 1008.1.4.4 Also requires many control functions for unlocking Intended only for building or tenant entrance doors in means of egress. Auto unlocking features always required from tenant (building) side. 38

Stair enclosures IBC Pop quiz, hot shot What kind of door openings are allowed in a stair shaft or exit passageway enclosure? Offices Storage rooms Bathrooms Mechanical interstitial space Elevators Elevator lobbies 39

Stair opening exceptions in NFPA 101 40

Stair penetrations Pop quiz, hot shot Are the following penetrations acceptable in a stair shaft or exit passageway enclosure? Sprinkler piping Fire alarm conduit Electric heater Structural steel Ductwork 41

Stair enclosures IBC 1022.4 Penetrations. Penetrations into and openings through an exit enclosure are prohibited except for required exit doors equipment and ductwork necessary for independent ventilation or pressurization sprinkler piping standpipes electrical raceway for fire department communication systems electrical raceway serving the exit enclosure and terminating at a steel box not exceeding 16 square inches (0.010 m2) 42

Stair Penetrations NFPA 101 43

Laboratory Requirements Hazardous exhaust systems, IMC vs. NFPA 45 no fire dampers Exhaust ducts may be manifolded in common shaft if hoods are in same fire area and not considered IMC hazardous exhaust system

IMC Hazardous Exhaust IMC SECTION 510.4 2009 Edition IMC Interpretation 14 11 Issued 4 16 12 There is no justification to permit manifolding from separate fire areas even when within a rated shaft. Ducts form different fire areas could act as a direct link between such areas allowing contaminants and/or fire to spread, especially considering that such ducts cannot have fire or smoke dampers.

Laboratories Fire Dampers NFPA 45 fire dampers not allowed in lab hood exhaust Options in lieu of fire dampers: NFPA 45 sub duct exception (shaft only) continuous exhaust NFPA 91 approach (variance) enclose duct in 2 hour construction (wrap) on either side of barrier Route differently to avoid penetrating fire barrier 46

Laboratories Ventilation Codes do not clearly address shutdown of laboratory make up air upon detection of smoke. Could result in negative pressures and excessive door opening forces. Evaluate caseby case. Variance makeup air is extension of exhaust system.

Other Laboratory requirements Lab equipment accessibility employee vs. student (public?) New MAAB requirements for employees Occupant load (egress and plumbing fixtures)

Questions? www.epm inc.com 508 532 7151 Ron Melucci, P.E., Technical Manager, FP Division rbm@epm inc.com 49