RHEEM Split Systems Condensers All submitted condensers meet the 15 SEER minimum All submitted condensers meet the 208/230V specification All submitted condensers contain enhanced mufflers to help dissipate vibration energy for quieter unit operation All submitted condensers are powder coated for a long lasting professional finish AHU s 1.5 ton AHU has a volumetric flow rate of 600 CFM, 2-ton AHU has a volumetric flow rate of 800 CFM, and 2.5-ton AHU has a volumetric flow rate of 1000 CFM, which meet and exceed the design specifications All submitted AHU s have factory installed 5KW electric heating kits with pullouts All submitted AHU s contain molded polymer corrosion resistant condensate drain pans All submitted AHU s DO NOT exceed the maximum dimensions: 18 in W, 50 in H, and 23 in D All submitted AHU s are Upflow, and have high efficient fan motors and drain connections All submitted AHU s meet the 208/230V specification Warranty All submitted Split Systems have registered a 10 years parts warranty
Date: Mar 11 2015 Job: U.C.F Customer: ADVANCE MECHANICAL Address: ORLANDO, FL Submitted By: SHINE LOVE
Equipment List for Project: U.C.F - Dated: Mar 11 2015 Units Tag No Model No Description HP - 1 AH - 1 HP - 2 AH - 2 HP - 3 AH - 3 RP1518AJ1 RH1T2417STANJC RP1524AJ1 RH1T2417STANJC RP1530AJ1 RH1T3617STANJC RP15: Classic 1 1/2 ton 15 SEER Single Stage Heat Pump RH1T: Constant Torque Motor Single Stage Airflow with Aluminum Evaporator Coil Voltage: 208-230/60/1 Factory Options: None RP15: Classic 2 ton 15 SEER Single Stage Heat Pump RH1T: Constant Torque Motor Single Stage Airflow with Aluminum Evaporator Coil Voltage: 208-230/60/1 Factory Options: None RP15: Classic 2 1/2 ton 15 SEER Single Stage Heat Pump RH1T: Constant Torque Motor Single Stage Airflow with Aluminum Evaporator Coil Voltage: 208-230/60/1 Factory Options: None Accessories For Tag No Field Model Description Notes For Tag No Heat Input(kW) Heater Field Model HP - 1 4.8 RXBH-1724?05J HP - 2 4.8 RXBH-1724?05J HP - 3 4.8 RXBH-1724?05J
Product Submittal Mar 11 2015 Project - U.C.F ORLANDO, FL Date: Mar 11 2015 Performance Summary Tag: HP - 1 Model No: RP1518AJ1 / RH1T2417STANJC Project: U.C.F City: ORLANDO State: FL Altitude: 95 Cooling Performance Air Discharge: Upflow/Downflow/Horizontal AHRI Ref: 7508987 AHRI Rating - Capacity: 18,800 EER: 12.5 SEER: 15 Ambient Air (F) - Dry Bulb: 92.5 Wet Bulb: 76.3 Airflow (CFM) - CFM: 600 SCFM: 600 System Entering Air (F) - Dry Bulb: 80 Wet Bulb: 67 % RH: 51.1 System Leaving Air (F) - Dry Bulb: 57.8 Wet Bulb: 56.9 Air Enthalpy (btu/lb) - Entering: 31.4 Leaving: 24.3 Design Net Cooling Capacity (btuh) - Total: 19,200 Sensible: 14,400 Latent: 4800 Total Power - Watts: 1336.8 KW: 1.3 Heating Performance AHRI Rating @ High Heating - Capacity: 17000 COP: 3.6 HSPF: 8.5 Electric Heat Input - KW: 4.8 @ 230 Volts Heating Airflow (CFM) - CFM: 600 Air Dry Bulb (F) - Outdoor: 41.7 Entering Air: 70 Leaving Air: 118.2 Air Temperature Rise (F) - Rise: 48.2 Capacity (btuh) - Total: 16,378 Total Heating Power - Watts: 5407.4 KW: 5.4 Air Moving System Characteristics External Static Pressure (inches WG) ESP: 0.1 - Blower Speed or Speed Tap - Tap: Low Motor Characteristic (watts & BHP) - Power: 0 Drive: Direct Electrical Supply Outdoor Unit Power Supply Volt/Hz/Ph: 208-230/60/1 (Volt/Hz/Ph) - Outdoor Unit Min Ampacity (amps) - Ampacity: 12 Max Overcurrent Protection (amps) - Fuse: 20 HACR Breaker: 20 Field Installed Electric Heater Kit - RXBH-1724?05J Power Supply (Voltage/Hz/Ph) - 230/60/1 Minimum Ampacity (amps) - 32 Max Overcurrent Protection (amps) - Fuse: 35 (Single circuit power supply for air handlers & heaters)
Dimensions, Weight & Clearances Dimensions - Length: 29-3/4 Width: 29-3/4 Height: 25 Outdoor Unit Weight (lb) (lb) - Weight: 133 Air Handler Dimensions (inches) - Length: 21 11/16 Width: 17 1/2 Height: 42 1/2 Air Handler Weight (lb) - Weight: 92 Outdoor Unit Clearances (inches) - Sides: 24 Top: 36 Product Submittal #: 76611873-0328-486f-9112-668553d88689 Submittal Printed on: 3/11/2015 1:04:44 PM For Model: RP1518AJ1 In keeping with its policy of continous progress and product improvement, reserves the right to make changes without notice. Gross capacity does not include the effect of motor heat. AHRI rating is net capacity and includes the effect of fan motor heat. All net capacities also accounts for the effect of motor heat. ASHRAE Weather Data 2009 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc., Atlanta, GA, USA. www.ashrae.org All rights reserved. Used by permission in this program.
Unit Drawings for HP - 1 - RP1518AJ1
Air Handler Unit Drawings for AH - 1 - RH1T2417STANJC
Feature List for HP - 1 - RP1518AJ1
Air Handler Feature List for AH - 1 - RH1T2417STANJC
Product Submittal Mar 11 2015 Project - U.C.F ORLANDO, FL Date: Mar 11 2015 Performance Summary Tag: HP - 2 Model No: RP1524AJ1 / RH1T2417STANJC Project: U.C.F City: ORLANDO State: FL Altitude: 95 Cooling Performance Air Discharge: Upflow/Downflow/Horizontal AHRI Ref: 7509020 AHRI Rating - Capacity: 24,000 EER: 12.5 SEER: 15 Ambient Air (F) - Dry Bulb: 92.5 Wet Bulb: 76.3 Airflow (CFM) - CFM: 800 SCFM: 800 System Entering Air (F) - Dry Bulb: 80 Wet Bulb: 67 % RH: 51.1 System Leaving Air (F) - Dry Bulb: 57.8 Wet Bulb: 56.6 Air Enthalpy (btu/lb) - Entering: 31.4 Leaving: 24.2 Design Net Cooling Capacity (btuh) - Total: 26,100 Sensible: 19,100 Latent: 7000 Total Power - Watts: 1838 KW: 1.8 Heating Performance AHRI Rating @ High Heating - Capacity: 22200 COP: 3.6 HSPF: 9 Electric Heat Input - KW: 4.8 @ 230 Volts Heating Airflow (CFM) - CFM: 800 Air Dry Bulb (F) - Outdoor: 41.7 Entering Air: 70 Leaving Air: 112.6 Air Temperature Rise (F) - Rise: 42.6 Capacity (btuh) - Total: 16,378 Total Heating Power - Watts: 5696.7 KW: 5.7 Air Moving System Characteristics External Static Pressure (inches WG) ESP: 0.1 - Blower Speed or Speed Tap - Tap: High Motor Characteristic (watts & BHP) - Power: 0 Drive: Direct Electrical Supply Outdoor Unit Power Supply Volt/Hz/Ph: 208-230/60/1 (Volt/Hz/Ph) - Outdoor Unit Min Ampacity (amps) - Ampacity: 14 Max Overcurrent Protection (amps) - Fuse: 20 HACR Breaker: 20 Field Installed Electric Heater Kit - RXBH-1724?05J Power Supply (Voltage/Hz/Ph) - 230/60/1 Minimum Ampacity (amps) - 32 Max Overcurrent Protection (amps) - Fuse: 35 (Single circuit power supply for air handlers & heaters)
Dimensions, Weight & Clearances Dimensions - Length: 29-3/4 Width: 29-3/4 Height: 25 Outdoor Unit Weight (lb) (lb) - Weight: 131 Air Handler Dimensions (inches) - Length: 21 11/16 Width: 17 1/2 Height: 42 1/2 Air Handler Weight (lb) - Weight: 92 Outdoor Unit Clearances (inches) - Sides: 24 Top: 36 Product Submittal #: 76611873-0328-486f-9112-668553d88689 Submittal Printed on: 3/11/2015 1:04:48 PM For Model: RP1524AJ1 In keeping with its policy of continous progress and product improvement, reserves the right to make changes without notice. Gross capacity does not include the effect of motor heat. AHRI rating is net capacity and includes the effect of fan motor heat. All net capacities also accounts for the effect of motor heat. ASHRAE Weather Data 2009 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc., Atlanta, GA, USA. www.ashrae.org All rights reserved. Used by permission in this program.
Unit Drawings for HP - 2 - RP1524AJ1
Air Handler Unit Drawings for AH - 2 - RH1T2417STANJC
Feature List for HP - 2 - RP1524AJ1
Air Handler Feature List for AH - 2 - RH1T2417STANJC
Product Submittal Mar 11 2015 Project - U.C.F ORLANDO, FL Date: Mar 11 2015 Performance Summary Tag: HP - 3 Model No: RP1530AJ1 / RH1T3617STANJC Project: U.C.F City: ORLANDO State: FL Altitude: 95 Cooling Performance Air Discharge: Upflow/Downflow/Horizontal AHRI Ref: 7509100 AHRI Rating - Capacity: 30,200 EER: 13 SEER: 15.5 Ambient Air (F) - Dry Bulb: 92.5 Wet Bulb: 76.3 Airflow (CFM) - CFM: 1000 SCFM: 1000 System Entering Air (F) - Dry Bulb: 80 Wet Bulb: 67 % RH: 51.1 System Leaving Air (F) - Dry Bulb: 58.6 Wet Bulb: 57.3 Air Enthalpy (btu/lb) - Entering: 31.4 Leaving: 24.6 Design Net Cooling Capacity (btuh) - Total: 30,700 Sensible: 23,100 Latent: 7600 Total Power - Watts: 2034.1 KW: 2.0 Heating Performance AHRI Rating @ High Heating - Capacity: 28200 COP: 3.54 HSPF: 8.2 Electric Heat Input - KW: 4.8 @ 230 Volts Heating Airflow (CFM) - CFM: 1000 Air Dry Bulb (F) - Outdoor: 41.7 Entering Air: 70 Leaving Air: 108.9 Air Temperature Rise (F) - Rise: 38.9 Capacity (btuh) - Total: 16,378 Total Heating Power - Watts: 6352.8 KW: 6.4 Air Moving System Characteristics External Static Pressure (inches WG) ESP: 0.1 - Blower Speed or Speed Tap - Tap: Low Motor Characteristic (watts & BHP) - Power: 0 Drive: Direct Electrical Supply Outdoor Unit Power Supply Volt/Hz/Ph: 208-230/60/1 (Volt/Hz/Ph) - Outdoor Unit Min Ampacity (amps) - Ampacity: 19 Max Overcurrent Protection (amps) - Fuse: 30 HACR Breaker: 30 Field Installed Electric Heater Kit - RXBH-1724?05J Power Supply (Voltage/Hz/Ph) - 230/60/1 Minimum Ampacity (amps) - 32 Max Overcurrent Protection (amps) - Fuse: 35 (Single circuit power supply for air handlers & heaters)
Dimensions, Weight & Clearances Dimensions - Length: 33-3/4 Width: 33-3/4 Height: 31 Outdoor Unit Weight (lb) (lb) - Weight: 160 Air Handler Dimensions (inches) - Length: 21 11/16 Width: 17 1/2 Height: 42 1/2 Air Handler Weight (lb) - Weight: 99 Outdoor Unit Clearances (inches) - Sides: 24 Top: 36 Product Submittal #: 76611873-0328-486f-9112-668553d88689 Submittal Printed on: 3/11/2015 1:04:51 PM For Model: RP1530AJ1 In keeping with its policy of continous progress and product improvement, reserves the right to make changes without notice. Gross capacity does not include the effect of motor heat. AHRI rating is net capacity and includes the effect of fan motor heat. All net capacities also accounts for the effect of motor heat. ASHRAE Weather Data 2009 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc., Atlanta, GA, USA. www.ashrae.org All rights reserved. Used by permission in this program.
Unit Drawings for HP - 3 - RP1530AJ1
Air Handler Unit Drawings for AH - 3 - RH1T3617STANJC
Feature List for HP - 3 - RP1530AJ1
Air Handler Feature List for AH - 3 - RH1T3617STANJC