Substation Monitoring System

Similar documents
Substation Monitoring System

i-con Switchgear Condition Monitoring HV Switchgear Integrated Substation Condition Monitoring ISCM Answers for Infrastructure & Cities.

Continuous, real-time detection, alarming and analysis of partial discharge events

Assetguard GDM. Gas density Monitoring for Gas Insulated Switchgears

DeltaV Analyze. Introduction. Benefits. Continuous automated DeltaV System alarm system performance monitoring

Specification for On-Line UPS Battery Monitoring and Data Management System

Architectural and Engineering Specification for a Fence-Mounted Perimeter Intrusion Detection System. FlexZone

MINERVA. Marine. Fire Detection. MX T2000 Panel Range. Features: MINERVA Marine Panel Range

ProStar 325 UV-Vis Detector

APPLICATION DATA SHEET

Adaptive CyCLO Technical and HMI User Guide. CyCLO User Guide. Version th December 2017 REV

Installer Certification Expiration. Terms

ICS Regent. Fire Detector Input Modules PD-6032 (T3419)

Instruction manual MTL process alarm equipment. October 2016 CSM 725B rev 2 MTL RTK 725B. Configuration Software Manual

Operations Manual TS400. Test Station for G450/G460 Gas Detector

QUALITY ASSURANCE/QUALITY CONTROL DOCUMENTATION SERIES OPTICAL DATA REDUCTION AND VALIDATION (IMPROVE PROTOCOL) STANDARD OPERATING PROCEDURE

Important Supplementary Manual to the main Ezeio manual. 5. Section 2a: Introducing the 2400 input and output expansion field stations.

725B Configuration Software Manual

RLDS - Remote LEAK DETECTION SYSTEM

Laptop / PC Programming Manual

FlexPS. Architectural & Engineering. Specification for FlexPS. Architectural/Engineering Specification for a

Section PERIMETER SECURITY SYSTEMS

Architectural and Engineering Specification for a Real-Time Locating System Flare

HERCULES 6 GRAPHICS SYSTEM

Weigh In Motion (WIM) Wheel Impact Load Detector (WILD)

RF SCOUT PLUS INSTRUCTION MANUAL. Dielectric, LLC 22 Tower Rd. Raymond, ME Phone: January 2015, Rev B 1

Panel Mounted Fault Annunciator Series

Equipment Required. WaveRunner Zi series Oscilloscope 10:1 High impedance passive probe. 3. Turn off channel 2.

Universal modular MWD platform adapted for your needs

Analog Input Module IC670ALG630

Architectural and Engineering Specification for a. Flash / Flare

PORTABLE ISOTOPE IDENTIFIER Search Tool / Sample Counting System

Connections, displays and operating elements C D E G H. Installing the control unit

INTREPID Perimeter Intrusion Detection System

D3 Wireless temperature alarm & monitoring system family. tek-troniks

THX-DL Data Logger USER & INSTALLATION MANUAL V

PROPOINTPLUS ASPIRATING SMOKE DETECTION SYSTEM

Procidia iware AlarmWorX32. AlarmWorX32 Viewer January 2010

AirTest Technologies Inc.

Complex alarming made simple

SCAN200E USER S MANUAL

Alarms and Events. Defining Alarm Conditions. Database-Generated Alarms

Enhanced FOUNDATION Fieldbus Physical Layer Diagnostics with the DeltaV System

Fire Operator Workstation (Fire OWS) User s Guide

Annunciator Unit SACO 16 D1. Product Guide

OVEN INDUSTRIES, INC.

Batt-Safe Battery String Monitoring System

CELLTROL II BIOREACTOR CONTROL SYSTEM OPERATIONS MANUAL

Technical Paper. Functional Safety Update IEC Edition 2 Standards Update

Fiber Optic Cable Fence Disturbance Sensor

DATAssure. Laboratory wireless alarm & monitoring system

PACSystems* RX3i. Thermocouple Input Module, 12 Channels, IC695ALG412. GFK-2578B October 2011

Module Features are-configurable, no module jumpers to set

ION Meter Alerts TECHNICAL NOTE NOVEMBER In This Document

Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase

DigiAir QUICK GUIDE & INSTRUCTION MANUAL

Innovative protection that combines power and flexibility

Added password for IP setup page : Password must be in IP format!

PowerWizard. Level 1.0 & Level 2.0 Control Systems Training

Ammonia Leak Detector Manual

Oxygen & Carbon Dioxide Analyser. Model 1737 Operators Manual

APPLICATION DATA SHEET

Analog Annunciator Unit SACO 16 A3. Product Guide

Architectural and Engineering Specification for a Fiber Optic Pipeline Integrity Monitoring System. FiberPatrol FP7000

Index Arc Guard Systems. Arc Guard Systems. Arc Guard Systems Industrial Automation Supply - Tel:

FIRECLASS Networking. Addressable Fire Alarm Control Panels From Software version 21. Product Application and Design Information FC-A-FCNET-A

Operations Manual TS400. Test Station for G450/G460 Gas Detector

AUTOMATION. Operator s Manual RST Series Web Enabled Input Module. Rev. A2, 1/12

3D_ISS. Integrated Software System. User Guide Manual

RAMSES: THE LHC RADIATION MONITORING SYSTEM FOR THE ENVIRONMENT AND SAFETY

SUPREMATouch Modular Fire & Gas Detection System

KELTRON LS 7000 ALARM MANAGEMENT SYSTEM Keltron Alarm Monitoring, Dispatch, and Reporting Software

SECTION 1 (Page 2) Introduction, standard accessories and mounting specifications.

Network Hardware and wiring (quiz)...

Optical Preemption & Priority Control Systems

WeatherLink for Alarm Output Addendum

D-TECT 3 IP. GJD260 IP Motion Detector

Annunciator unit. Application

PotterNet Fire & Facility Supervising Station

iotdr Series Portable OTDR Test Set iotdr Series OTDR Tester is entirely new portable product released by OPWILL.

FCD-wire Contents. List of Figures

SAMPLE SPECIFICATIONS CONTINUOUS MONITORING SYSTEM (Insitu)

ISIS USERS MANUAL I.S.I.S. 550B

E N G L I S H FIRE ALARM ASPIRATION SENSING TECHNOLOGY QUICK INSTALLATION GUIDE STAND-ALONE FAAST LT MODELS FL0111E FL0112E FL0122E. 367 mm.

Product Guide Low Voltage Switchboard & Switchgear

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2

IntelliPack : 800 Series

Architectural and Engineering Specification for a Personal Alarm System System (PAS)

SECTION : CAMPUS CENTRAL METERING SYSTEM DESIGN

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA

Panel Mounted Fault Annunciator Series

ENSC 388: Engineering Thermodynamics and Heat Transfer

Alarm Monitoring and Management

SD Storage Cabinet. Outstanding performance

Perimeter security using Fibre optics

Spectron LSN (Life Safety Network) Suggested Specifications

FTS500 Series. Handheld OTDR Test Set.

PWM. Solar Charge controller with Ethernet. Solar Smart PWM 20Amp. Hardware Description : Release : 19 June 2014

C&K Software What s New. Commander II Version 3.0 Monitor II Version 3.0 Satellite II Version 1.0

Process Gas Chromatograph

Transcription:

Substation Monitoring System UHF Partial Discharge Monitoring

System Description Introduction The UHF PDM System is the third generation, spanning 20 years, of monitoring systems developed for GIS partial discharge monitoring. It utilises well proven technology used from the former systems but the data acquisition system has been modified to conform to the one-platform approach as used for GDM and CBM systems. The IEC requirement for High Voltage on-site testing using partial discharge monitoring can be met by this system where an on-line system is required. A portable PDM system can also be applied - see the Dialoc System in Appendix1. The system is modular and designed to facilitate measurements using internal or external UHF sensors. In order to simplify the signal cabling, a Node Unit Cubicle containing the monitoring equipment is located in the GIS switchgear hall where the signals for each CB bay can be concentrated. This wall mount Node Unit Cubicle also allows for a very simple communications connection to transmit all of the bay data along a single fibre cable. The UHF transducer head provides the signal input to the specially designed signal conditioning modules and comprises:- UHF Sensor [Internal or External type] with UHF Cable [typically 5m, to 10m] UHF Signal Filtering and Optical Processor The optical signal conditioning modules provide the data input to the data acquisition system. The Node unit has been developed to process data for 27 UHF inputs [i.e. 9 conditioning modules for 9 three-phase sets of sensors for 275kV to 800kV GIS] Typically this allows one Node unit to concentrate and process data for three circuit breaker bays The Node Units are connected via fibre optic communications cable to a central PDM control cubicle where an HMI is available to provide access to the data and where alarm data is automatically generated. Multiple Node Units can be connected to the central CBM Control Cubicle to provide adequate coverage for every size of GIS substation.

Node Unit Configuration The PDM Node Unit is modular in design and can house up to 9 UHF Optical transducer interface modules. Each module contains 3 optical input channels, and an optical output control channel. This allows 9 sets of three-phase UHF transducers to be monitored giving a maximum of 27 UHF optical transducers per node. Processing at the node is carried out using an integrated measurement system built on industrial PC technology. Access to the measurement system to configure the node is provided by an Ethernet connection. Each Node Unit is configured independently via software installed on the Node Unit s industrial PC. The software has been designed so that even the very largest of systems can be configured very quickly and easily. The first defining parameter of the Node is the number of UHF transducers that the Node is required to monitor for a particular installation. Figure 1 below provides an illustration of this. Figure 1 Substation PDM Node Unit Configuration The name of the substation is entered along with the Node Unit number which identifies the particular Node to the central GDM Control Cubicle. The number of UHF transducers connected to the Node Unit (maximum 27) is also entered.

On entering these details and saving the changes, the software will automatically provide access to a second interface screen which is used to configure the individual channels. Figure 2 below provides an illustration of this. Figure 2 Channel Assignment and PDM Sensor Details From Figure 2, it can be seen that the channels are assigned to PDM sensors on a module by module basis. The number of modules activated to allow data to be input is determined by the screen shown in Figure 1. Since many of the PDM sensors have identical parameters in terms of CB Bay reference, Detection [Sensitivity] Level and alarm levels, the software allows the user to copy the settings to multiple lines to aid the configuration process. The following parameters are assigned to each channel: Circuit Breaker Bay. Phase. PDM Sensor Reference. Detection Level. 1 st Stage Alarm Level 2 nd Stage Alarm Level 3 rd Stage Alarm Level

Once the Node Units channels have been configured, and the settings saved, the main Node Unit monitoring screen will be displayed. This can be seen overleaf in Figure 3. Figure 3 Main Node Unit Monitoring Screen Calibration The main Node Unit monitoring screen displays the settings from all 27 transducer inputs, divided into three tabs. The readings are displayed in dbm values. On selecting the Start button, real time Peak PD Levels will be displayed for each of the sensors. Prior to performing this action however, the channels are required to be calibrated. Although all of the channels are identical in terms of components, the components will inevitably have slightly different values (within their quoted tolerance window) which need to be normalised across the channels. Figure 4 overleaf provides an illustration of the Calibration screen. Calibration is carried out with the transducer disconnected from the Node Unit inputs. In most situations this will be the default situation since the Node Unit will be configured in the factory in the absence of the actual installed sensors themselves. If calibration is to be carried out in service with the transducer already connected then the

transducer input terminal links within the Node Unit will need to be opened (see Drawings section for terminal link identification). The channels are calibrated on a module by module basis (maximum of 9 modules per Node Unit and 3 channels per module). Each module is selected by clicking on the appropriate tab. Figure 4 Calibration Screen By selecting the Start Calibrate button the real-time signal volts at the input to the data acquisition card for the 3 channels shown will be displayed. This is effectively the offset value which is required to be made zero. For each channel input the negative value of the signal volts into the Offset box for each channel. All channels should then read zero i.e. base setting of -80dBm. Connect the -50dBm calibrator or use the internal -50dBm Self test calibrator to each of the three inputs in turn. Note the dbm value for each channel. In the Gain box insert the value determined by the following equation: 1-(Measured Value/-50)

All channels should then read -50dBm. Calibration is then completed for that module. Select the remaining modules in turn within the Node Unit and repeat the procedure to calibrate the respective input channels. When completed press the Stop Calibrate button and Save the settings. The values will remain stored until the next calibration procedure is carried out. By selecting Stop Calibrate followed by Exit, the user will be returned to the main Node Unit monitoring screen as shown in Figure 3. Data Collection Once calibration has been completed and the transducers connected to the input channels, the Start button will initialise data collection from all of the transducers connected to the Node Unit. Readings every second are acquired from every transducer connected to the Node Unit. The readings are displayed as real-time values in their respective position on the main Node Unit monitoring screen. If any of the alarm criteria is met for any of the channels then that particular channel will be highlighted in red for clarity. Should any areas of the substation be undergoing maintenance or any channels of the PD system being tested or maintained, then the maintenance box for that particular zone can be checked if required. Any noise or test pulses etc that occur within the maintenance period can then go unrecorded (if required see Maintenance section) for as long as the maintenance box is checked. All data will be saved on the hard drive of the Node Unit. To provide a backup of this data, periodically, the PDM Control Cubicle will poll the Node Units and transfer any new data to its hard drive. This data will then be backed up to an external hard drive located within the PDM Control Cubicle. The data is therefore stored on three separate media devices which will minimise any risk of loss of data.

Diagnostics Should a Node Unit be in a hardware alarm condition at the GDM Control Cubicle, the nature of the alarm can be identified by selecting the Diagnostics button on the main Node Unit monitoring screen. Figure 5 overleaf provides an illustration of the Diagnostics screen. The hardware item that is in alarm will be indicted by a red light. The alarms are generated by the following criteria: +12Vdc Supply (Modules 1-5) out of limits. +12Vdc Supply (Modules 6-9) out of limits. -12Vdc Supply (Modules 1-9) out of limits. +48 Vdc Supply out of limits Node temperature transducer fail. Ambient temperature transducer fail. UHF Optical transducer fail (1-27 individually identified).

Figure 5 Diagnostics Screen Failure of one of the power supplies to the input modules will produce an alarm condition for both the relevant power supply and all of the UHF optical transducer inputs connected to the affected modules since they will be inactive and unable to gather data. All alarms are recorded in the Alarm log which can be viewed from this screen. The alarms are listed in chronological order. By selecting Close Diagnostics the user will be returned to the main Node Unit monitoring screen. PDM Summary UHF Sensor Status By selecting Node Status from the main Node Unit monitoring screen the current status for each UHF sensor can be viewed. Figure 6 overleaf provides an illustration of the UHF Sensor Status screen.

Figure 6 Zone Status Screen By selecting a UHF Sensor from the UHF Sensor list, the following information will be displayed: Detection Level (dbm): Displays the nominal detection level in dbm that the PDM system will acknowledge as a signal. If the environment has background noise above this level then the detection level can be increased to avoid noise detection. Level 1 Alarm (dbm): Displays the level value of the 1 st stage alarm level. Level 2 Alarm (dbm): Displays the density value of the 2 nd stage alarm level. Level 3 Alarm (dbm): Displays the density value of the 3 rd stage alarm level. Present PD Level (dbm): Displays the current signal level being detected. Present Alarm Level: Displays the current alarm level for the signal being detected in dbm.

Trending By selecting Trend Plots from the main Node Unit monitoring screen the trending of the PDM data can be viewed. Figure 7 provides an illustration of the Trend Plots screen. Figure 7 Trendplots Screen The trends can be viewed over 24 hours, 1 week and 1 month as required. By selecting PD activity point on the Trendplot, the PD diagnostic data can be displayed as amplitude, pulse counts in relation the point-on-wave [POW] of power frequency voltage. Also a sequential POW display shows the PD behaviour over 50 cycles of power frequency voltage

Data Archiving and Displays The data is archived in monthly files and can be used as a database for diagnostic information. The archived data can be viewed, as show in Figure 8, using a range of data visualisations and can be copied for reports directly into Microsoft Word files. Figure 8 Archived Data Screen Remote Access Remote access to the PDM Control Cubicle is very much dependent on the infrastructure available at the substation. The most common form of access is via a modem but it is possible to also use a Local or Wide Area Network to gain access to the data. The remote access options are explored with each individual customer to define the best possible solution to implement in each case.