DEPARTMENTAL GUIDELINES CHAPTER 6 TACTICAL OPERATIONS

Similar documents
Structural Firefighting Policy

I. It shall be the responsibility of the department officers to implement this operating guideline.

Table OUT OF SERVICE. Building Fire Video 1/15/ Inspection, testing and maintenance. Standards Further Referenced by FCNYS

FIREFIGHTER II MANIPULATIVE SKILL OBJECTIVES

Chapter 4: Fire Protection Systems

INTERIOR FIRE BRIGADE MEMBER MANIPULATIVE SKILL OBJECTIVES GENERAL

Fire Service Considerations A Primer for Building and System Designers. Society of Fire Protection Engineers Fire Service Committee

ADVANCED EXTERIOR FIRE BRIGADE MEMBER MANIPULATIVE SKILL OBJECTIVES GENERAL

Understanding, Applying and Enforcing NFPA 25. James D. Lake NFSA Director of Training

SKILL VERIFICATION BOOK FIREFIGHTER I MODULE II FIRE PROTECTION BUREAU. Assigned to: Name:

Vacant Building Loss Prevention Best Practices


Essentials of Fire Fighting, Fourth Edition Transition Guide. Chapter 1: The History of the Fire Service (Essentials, Chapter 1)

Table EXIT ACCESS TRAVEL DISTANCE a OCCUPANCY SYSTEM SYSTEM. A, E, F-1, I-1, M, b,d R, S-1. B c. F-2, S-2, U c

Westbury Fire Department: Hose Company 2 Drill 7/24/14 Thinking Beyond the Obvious or the Norm

Chapter 17 Test. Directions: Write the correct letter on the blank before each question.

Oxnard Fire Department 360 W. Second Street Oxnard, CA (805) Fax (805)

FIRE FIGHTER II APPLICATION PENNSYLVANIA VOLUNTARY FIRE SERVICE CERTIFICATION PROGRAM NFPA Edition

Wilson County Emergency Management Agency 110 Oak Street Lebanon, Tennessee 37087

EASTERN ARIZONA COLLEGE Fire Department Operations II

Annual Report of Inspection, Testing & Maintenance of Automatic Sprinkler System

SUBJECT FIRE OPERATIONS GUIDELINE (F.O.G.) #F510 Issued: 1/2014 Last Revision: 1/2014 Pages: 9 By Order Of: J.S. Thompson, Fire Chief

Module 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements

Detection, and Suppression Systems

Cumru Township Fire Department 4/27/10 Standard Operating Guidelines Page: 1 of 6 Section 15.07

DIVISION 21 FIRE SUPPRESSION

COUNTY OF BERGEN DEPARTMENT OF PUBLIC SAFETY LAW AND PUBLIC SAFETY INSTITUTE POLICE, FIRE & EMS ACADEMIES 281 Campgaw Road Mahwah, N.J.

CENTRAL CALAVERAS FIRE AND RESCUE TRAINING DIVISION CAREER TRAINING AND DEVELOPMENT FIREFIGHTER II STANDARDS

Second Revision No. 1-NFPA [ Section No. 2.2 ] Submitter Information Verification. Committee Statement

Whitestown Fire Department Standard Operating Procedure

Talking about NFPA History of NFPA NFPA Standard 1710: Organization and Deployment of Fire Suppression Operations, EMS

Required Materials For complete material(s) information, refer to

Based on NFPA 1003: Standard for Airport Fire Fighter Professional Qualifications 2015 Edition

Chapter 2: Identification, water and access

CHAPTER 05 - OFFICE OF STATE FIRE MARSHAL SUBCHAPTER 05A - FIRE AND RESCUE SECTION.0900 PUBLIC PROTECTION CLASSIFICATIONS FOR FIRE DISTRICTS

New Construction Fire Inspection Process

Interim Life Safety Measures. Healthcare Construction Certificate - Level 1

The 2012 Fire Suppression Rating Schedule (FSRS)

4/13/2015. Everything a firefighter wants to tell a design professional or building code official, in one hour.

Western Michigan University Facilities Management Engineering Division

ADDISON COUNTY FIREFIGHTERS ASSOCIATION MUTUAL AID SYSTEM STANDARD OPERATING GUIDELINES

FIREFIGHTER II: FIRE DEPARTMENT COMMUNICATIONS COMMUNICATIONS: SKILL SHEET #2 Define and Demonstrate Fire Department Radio Procedure

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures

1.1.0 Protocols for the response to fires involving MRI Machines

Fire System Impairment Policy

NFPA 13E Recommended Practice for Fire Department Operations in Properties Protected by Sprinkler and Standpipe Systems

TRI-LAKES MONUMENT FIRE PROTECTION DISTRICT

Risk Management Services

Building Emergency Response Scenario

Prereq: FOD 131 or Instructor Permission

Program of Instruction Course Syllabus

INCIPIENT FIRE BRIGADE MEMBER MANIPULATIVE SKILL OBJECTIVES GENERAL

A GUIDE FOR CONDUCTING FACILITY PRE-FIRE PLANS

Pro Board Assessment Methodology Matrices for NFPA 1001

FIRE PROTECTION PROGRAM

ATTIC FIRES. Part 3 HEAVY SMOKE SHOWING

Field Operations Guide (FOG) Effective Date: December 1, 2003 Last Revision Date: November 1, 2015

I. INTRODUCTION. A. Purpose: To provide procedures and guidelines for personnel responding to and operating at working structure fire incidents.

Chapter 18 Test. Directions: Write the correct letter on the blank before each question.

DCN: ENGINE COMPANY OPERATIONS CHAPTER 4 March 15, 1997 FIRE SCENE OPERATIONS

FIREFIGHTER 1 COMPETENCY EVALUATION

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions:

FIRE PROTECTION BUREAU ACCREDITATION AND CERTIFICATION PO Box Olympia WA (360) FAX: (360) AIRPORT FIREFIGHTER

Subject: Fire Protection Impairment Program Reference: NFPA (see bottom of page 5) Effective Date: August 2014 Distribution All YC Employees

FIRE INSPECTION CHECKLIST

9S / 9E Inspection Worksheets. The fire department should complete the following sheets prior to inspection date

FIVE YEAR AUTOMATIC FIRE EXTINGUISHING SYSTEMS CERTIFICATION REPORT

Travis County Emergency Services District #1 Standard Operating Guidelines

STATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT

Design & Construction Standards, Revised January

SEPTEMBER-NEWSLETTER-ELEVATOR DANGERS

False Sense of Security???

PLAN REVIEW CHECKLIST

Steven Craft, PhD, P.Eng. FIRE SAFETY DURING THE COURSE OF CONSTRUCTION

Objective 1: Describe fire alarm systems.

Centers for Regional Excellence. Downriver Fire Authority. Organization Committee Objective. Operations Committee Report 2007

ICC CODE CORNER 2012 IFC Code & Commentary

DEPARTMENTAL GUIDELINES CHAPTER 6 TACTICAL OPERATIONS

SURREY FIRE SERVICE. Construction Fire Safety Plan Bulletin

SUMMARY. Building receiving sprinkler credit: SPRINKLERED. Grade: 68. Percent of Building Sprinklered: 100% Sprinkler Demand Met: 91%

Travis County Emergency Services District #1 Standard Operating Guidelines

D. The work addressed in this section consists of a fire protection system, which may include coordination with one or more of the following:

UC Irvine Environmental Health & Safety TITLE: FIRE WATCH AND OUT OF SERVICE NOTIFICATION

WASHINGTON SURVEYING AND RATING BUREAU

MASTER COURSE OUTLINE

Equipment: PowerPoint Presentation: Sprinkler Systems: Review and Response Considerations

Fire Department Orientation / Organization

Standardized Curriculum Form Ontario, Canada

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST

By: Russell Bainbridge March 18th, 2016 FPE 596

Minimum Standards for Engineers Practicing Fire Protection Engineering in the State of Oklahoma September 14, 2016

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry

San Ramon Valley Fire Protection District GREEN SHEET

A Comprehensive Community Risk Reduction Initiative A COMPREHENSIVE COMMUNITY RISK REDUCTION INITIATIVE

TAMARAC FIRE RESCUE DEPARTMENT FIRE PREVENTION BUREAU 6000 North Hiatus Road Tamarac, Florida Telephone: (954) , Fax: (954)

Managing Fire Protection System Impairment

Additional Materials: Instructor s PowerPoint, Question Files

Written Fire Safety Plans

DIVISION 21 FIRE SUPPRESSION FIRE SUPRESSION

Summary. firefighter training in Since that time the firefighter had attended semi-annual

Transcription:

Section 400.000 Suppression Systems The purpose of this guide is to assist the Incident Commander (IC), Fire Officers and Firefighters with the planning of effective operations for supporting water-based suppression systems and the use of water-based suppression systems in buildings or facilities where fire can or has occurred. 401.000 General Water-based suppression systems technology has been very successful in the past and continues to be a proven, effective extinguishing system. However, in spite of the exceedingly successful performance record of water-based suppression systems, failures have occurred and have significant potential of future failures. Since 1897, reported fires in protected structures to the National Fire Protection Association (NFPA) the successful operation rate of water-based suppression systems is about 96%. Analysis of the remaining 4% of system failures provides significant insight into the mechanics of system failure. Reasons for system failure relates to 1) closed valves or premature closure of valves, 2) inadequate system design, installation or maintenance, 3) changes in hazard or commodity configuration and, 4) degradation of water supply. Effectiveness of water-based suppression systems is consistent over their history. The majority of system activation produces favorable results with the operation of one or two sprinkler heads, according to NFPA and Factory Mutual statistics. Systems are designed to control fires of 1500 to 5000 square feet in size. Early Suppression Fast Response (ESFR) technology exceeds its predecessor s performance and achieves fire extinguishment as a design parameter with an area of not more than 1200 square feet. Fire companies should be alert to changes or conditions that will affect the operation, effectiveness, and access to water-based suppression systems. It shall be the responsibility of the fire officer to refer these changes or conditions to the Fire Marshal s Office for determination of whether the water-based suppression system requires upgrading. Fire companies should recognize the following conditions as essential to successful waterbased suppression system operation: A. Systems must be properly designed, installed and maintained. B. Systems are not equally effective in their performance. 1

C. Water supply conditions change over time. D. New commodity/storage methods place greater emphasis on FD support of system. E. Design parameters of systems are based on system application, i.e. life safety, fire control, extinguishment. 402.000 First Due Fire Officer Should Know A. Occupancy(ies). B. Hazard classification(s) within area protected by water-base suppression system(s). C. Building construction and floor plan. D. Extent of protection. E. Type of water-based suppression system(s) protecting structure. F. Identify duration and type(s) of water supply(ies). G. Location of control valve(s). H. Function of each control valve. Consequences of shutting off valves. I. Location of Fire Department Connection (FDC). J. Specific company assignments have primary responsibility for charging the FDC. K. Location of water supply(ies) for handlines. (standpipes, fire hydrants). L. Alternate means for supplying water to the System in the event the FDC is inoperative. M. Location of spare or replacement sprinkler heads. N. Location of waterflow indicators and annunciator panels. O. Name of person responsible for the water-based suppression system. 2

403.000 Fire Ground Operations in Properties Protected with Water- Based Suppression Systems 403.001 Size Up Accurate size-up can be hindered by low visibility from smoke resulting from downward air currents due to operating sprinkler heads. Do not shut down system to improve visibility. 403.002 FDC Operations A minimum, or equivalent, of two-(2) sprinkler supply lines should be connected to the FDC and should be supplemented according to fire conditions. The supply line should be pumped and the line charged to a pressure of 150 psi, unless the system is posted for a different pressure. Combination systems (sprinkler/standpipe) shall be calculated on the basis of the most demanding system. Once all water supply connections have been completed and the fire department connection has been charged, the Incident Commander should verify immediately that water is flowing into the sprinkler system. If no water is flowing, the IC should take action to verify that all accessible control valves are open. Large-Volume Fire Sprinkler Systems, e.g. large orifice sprinklers, Early Suppression Fast Response (ESFR), have system demands of 1200 1500 gpm. FDC manifolds to these systems will have more than the standard two-(2) inlets or multiple FDC connections. Large-volume systems will require the maximum water delivery capacity of both the water supply and the pump apparatus. 403.003 Valves If a valve is found closed, IC should be informed immediately and the valve should be opened fully at the direction of the IC, unless the valve is tagged "Closed for Repairs". Valves found closed should be reported to the fire investigator after the incident. 403.004 Fire Pump If the system is supplied or augmented by a fire pump, the IC should assign a firefighter to verify that the pump is in operation. The IC should be aware of the system demand for Large-volume fire sprinkler systems and the FD s capacity to support the system. Early FD operation with Large-volume fire sprinkler systems must be of sufficient pressure and capacity to ensure that the designed performance parameters of the system are met. REMEMBER, Early Suppression Fast Response (ESFR) is designed to extinguish the fire, as compared to other systems that rely on FD support to extinguish the fire. Inappropriate intervention by the FD on ESFR systems may prevent fire extinguishment. Structures protected by ESFR systems that present a rapidly growing fire on arrival of FD suggest the system has failed to meet its performance parameter. It is unlikely that pump apparatus would have sufficient capacity to improve the performance of a failed 3

ESFR system, compared to a conventional sprinkler system. Full-scale fire testing of ESFR systems has achieved extinguishment in high-piled storage arrangements in times that would give the IC the expectation that the fire will be extinguished before FD arrival. Real time scenarios would suggest the ESFR protected fire will be extinguished before fire units are dispatched. Therefore, fire conditions on arrival may suggest system failure and the large-volume nature of the system may present water supply deficiencies. The IC may seek to terminate the fire pump and the system s water supply connection in favor of effective master stream operations. 403.005 Ladder Company Operations Ladder company functions should provide ventilation and salvage, as needed to avoid delay in advancing hose lines. Salvage covers should be spread over those items or areas likely to be affected by operating sprinklers or hose lines. Special attention should be given to areas on levels below the area of sprinkler operation. 403.006 Post-Fire Operations Water-based suppression systems should not be shut-off until the fire has been extinguished. The IC should assign a firefighter to remain at the valve until overhaul is completed. The firefighter shall remain there until given proper directions by the Incident Commander. The firefighter may be directed to open or close valves as needed. Orders should also be given to the fire apparatus operator to shut down the lines connected to the FDC as these by-pass the main sprinkler valve, water will flow until pump discharge gates are closed. 403.007 Limited Sprinkler Operation Where only a few sprinkler heads are operating, sprinkler tongs, tapered wooden wedges or dowels can be used to immediately stop the flow from the opened heads without shutting off the entire system. When overhauling is completed, the lines from the fire apparatus pump to the waterbased suppression system FDC should be ordered disconnected. 403.008 System Restoration When possible, the system should be restored to full operation as soon as possible. The owner/manager of the facility is responsible for ensuring the system is properly restored. The Fire Marshal s Office should be notified, by the Incident Commander, of ALL system activation or impairments, activated or impaired notification should be done through Communications. Fire Inspectors will assess the system s condition and will take enforcement action, in accordance with local code. 4

404.000 Fire Department Operations in Properties Protected with Outside Exposure Sprinklers Buildings or properties having a severe exposure problem are equipped with outside or external sprinkler system designed to provide a water curtain capable of shielding the property from fires in other buildings or in storage areas. Many of these systems are manually operated, some are thermostatically operated. 404.001 Pre-Planning Properties that are equipped with outside exposure sprinklers should have the following information included in pre-planning documents: A. Occupancy(ies). B. Hazard classification(s) within area protected by water-base suppression system(s). C. Building construction and floor plan. D. Extent of protection. E. Type of water-based suppression system(s) protecting structure. F. Identify duration and type(s) of water supply(ies). G. Location of control valve(s). H. Function of each control valve. Consequences of shutting off valves. I. Location of Fire Department Connection (FDC). J. The Incident Commander will assign a company with the primary responsibility for charging the FDC. K. Location of water supply(ies) for handlines. (standpipes, fire hydrants). L. Alternate means for supplying water to the System in the event the FDC is inoperative. M. Location of spare or replacement sprinkler heads. N. Location of water flow indicators and annunciator panels. O. Name of person responsible for the water-based suppression system. 5

404.002 The Incident Commander Should Consider Maintenance of the exterior integrity of exposure building(s) on each side of fire. Insure that all windows are closed and that fire has not extended into the exposure buildings. A. Severe exposures, attack lines should be set up in exposure buildings using standpipe system, if available B. The roof of exposure building(s) should be checked to make certain no part of the roof structure is in danger of ignition. C. Initiate salvage operations on exposure building(s). D. Termination of outside sprinklers is appropriate when the fire threat is no longer present. E. Initiate fire sprinkler system restoration procedures. 405.000 Fire Department Operations in Properties Protected with Standpipe Systems Buildings equipped with standpipe systems have areas because of remoteness or height which would make quick placement of fire streams untimely or impractical. The procedures to use a standpipe system are the same as for a fire sprinkler system. 405.001 Pre-Planning Properties that are equipped with standpipe systems should have the following information included in pre-planning documents: A. Occupancy(ies) B. Hazard classification(s) within area protected by standpipe system(s). C. Building construction and floor plan. D. Extent of protection E. Type of standpipe system(s) protecting structure. F. Identification of pressure-regulating devices (PRD). G. Identify duration and type(s) of water supply(ies). H. Location of standpipe outlets and control valve(s). 6

I. Function of each control valve. Consequences of shutting off valves. J. Location of Fire Department Connection (FDC). K. The Incident Commander will assign a company with the primary responsibility for charging the FDC. L. Location of water supply(ies). M. Alternate means for supplying water to the System in the event the FDC is inoperative. N. Name of person responsible for the standpipe system. 405.002 Fire Department Operations When pumping into the FDC the pump operator should consider the following when calculating the Pump Discharge Pressure (PDP): A. Friction loss in hose lines between pump and standpipe connection. B. Friction loss in the standpipe system C. Elevation of the nozzle(s) D. Number and size of attack lines operating from standpipe. E. Required nozzle pressure. PDP in excess of 200 psi should not be used unless the standpipe system has been designed and posted for higher pressures. A minimum, or equivalent, of two-(2) supply lines should be connected to the FDC and should be supplemented according to fire conditions. The supply line should be charged to a pressure as calculated above or if the system is posted for a specific pressure. Combination systems (sprinkler/standpipe) shall be calculated on the basis of the most demanding system. Fire attack is generally performed by connecting the attack line to the standpipe outlet a floor below the fire floor and advance the line up one flight of stairs. Private hose or house lines attached to Class II or III (occupant use hose) standpipe outlets are NOT to be used except in the case of extreme emergency. 7