Heat Pump Water Heaters: Laboratory and Field Evaluation of New Residential Products

Similar documents
Energy Efficiency Demonstration Residential Ductless Heat Pumps (DHP) Overview. Ammi Amarnath Chris Trueblood

Energy Efficiency Potential of Heat Pump Water Heaters in Commercial Buildings

Effect Of Setup Thermostat Schedule On Heat Pump Water Heater Energy Consumption, Coefficient Of Performance And Peak Load

NAECA Water Heaters. Tankless (Instantaneous) < 2 gallons Natural Gas 75,000 Btu 200,000 Btu Oil 105,000 Btu 210,000 Btu Electric

Development Of A Low-Cost Heat Pump Water Heater For Residential Applications

Heat Pump Water Heaters: A Key Energy Technology for California

Demonstration of 2nd Generation Ducted GE "Brillion" Hybrid Water Heater in the PNNL Lab Homes

Evaluating Peak Load Shifting Abilities and Regulation Service Potential of a Grid Connected Residential Water Heater

NEEA Report: Laboratory Assessment of AirGenerate ATI80 Heat Pump Water Heater

Interim Report for the Period thru February 15, 2018 Submitted to Department of Business and Professional Regulations Office of Codes and Standards

Shell-and-Tube Heat Exchanger (Four Passes) - Optional

How to Heat Water in All-Electric Homes & Apartments?

Field Evaluation of Pre-Commercial Residential Gas Heat Pump Water Heaters

Performance Assessment of an Advanced Hydronic Heat Pump

Heat Pump Water Heaters

Heat Pump Water Heater

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

Saying Mahalo to Solar Savings: A Billing Analysis of Solar Water Heaters in Hawaii

Food Service Technology Center

Demand-Response Performance of Sanden Unitary/Split-System Heat Pump Water Heaters

New Construction Builders Challenge: Sealed Attic and High Efficiency HVAC in Central Florida: A Year in Review

The Revised Method of Test for Residential Water Heating and Its Impact on Incentive Programs

Food Service Technology Center

Product Offering for 2017

Accelera Heat Pump Water Heaters HEAT PUMP WATER HEATERS

Submittal Data Performance Data Electrical Data

<<Date>> <<Recipient>> <<Address>>

Pack Calculation Pro. Users guide. Version Morten Juel Skovrup

Field Testing Results for Residential Gas-Fired Heat Pump Water Heaters

Hot Food Holding Cabinets Test for FWE HLC

Metcraft Power Soak Performance Test

CT398 Heaterstat TM Temperature Controller. Technical User Guide

Energy Efficient Options for Residential Water Heating

Transcritical CO2 Bottle Cooler Development

Drying Laboratory Methods Drying Parameter Characterization from Small Size Samples

CONVECTION OVENS FOR FOOD SERVICE APPLICATIONS BLODGETT SHO-E

Daikin Blueprint: Delivering Hot Water with a Chiller

Residential Water Conservation Research Brief On-Demand Hot Water Systems

Flow Research, Inc. (781) Water Street (781) (fax) Dear Marketing Manager:

Evaluation of the Incon TS-LLD Line Leak Detection System

Small Commercial Business Energy Audits. Recognizing and addressing the special requirements of the small business market segment.

Hot Water Distribution System Losses in a Net-Zero Home

Executive Summary. Number of Low Number of High Number of Faults , Number of OK

Union County Vocational - Technical Schools Scotch Plains, New Jersey

Operation Guide CT80 ENGLISH

Energy-Efficiency Options for Residential Water Heating

Redesign of Bennett Hall HVAC System

Hot Water System Performance Testing at PG&E s Applied Technology Services: Mimicking a Full-Service Restaurant in the Laboratory

THERMAL ICE STORAGE: Application & Design Guide

GROUND COOLING OF VENTILATION AIR FOR ENERGY EFFICIENT HOUSE IN MALAYSIA: A CASE STUDY OF THE COOLTEK HOUSE

ENERGY SAVING IN A DOMESTIC SPLIT-TYPE AIR CONDITIONER WITH EVAPORATIVE COOLING SYSTEMS

Heat Pump Water Heater Technology Development. EEBA High Performance Home Summit Ed Vineyard Oak Ridge National Laboratory

Savings Without Sacrifice

TECHNOLOGY GUIDE. :: the dawn of a new era in commercial HVAC technology. The all-new Rheem Commercial Renaissance Line featuring:

A Technical Introduction to Cool Thermal Energy Storage Commercial Applications

Nest Learning Thermostat Summer 2012 Savings

Introduction ABSTRACT

The house has 4 inches of exterior foam board (in two layers) and 2 inches closed cell spray foam with cellulose in the wall cavities.

LOW COST HEAT PUMP WATER HEATER (HPWH)

SYSTEM DESIGN REQUIREMENTS

Demand Response Potential of Residential Appliances Clothes Washer (LG)

J. R. Qualey III, L. Desmarais, J. Pratt Simplex Time Recorder Co., 100 Simplex Drive, Westminster, MA 01441

Electric radiator test

Submitted to. Texas A&M University-Corpus Christi The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge

Residential Water Heating

Combination unit to support instruction in Thermodunamics, Fluid Mechanics, and Heat Transfer

Solar Air Heating Metal Roofs for Re-Roofing and New Construction

3. (a) Explain the working of a rotary screw compressor. [10] (b) How the capacity control is achieved in refrigerant compressor?

KE2 EvaporatorEfficiency Theory of Operation

The Importance of Integrated Design, Commissioning, and Building Tuning: A Grocery Store Case Study

Southern California Gas Company Customer Programs Department

Benefits Offered by Passive Dehumidification Wheel Speed Control

VIQUA is an ISO9001:2008 registered company specializing in the design, manufacture and sale of ultraviolet systems for:

Energy Saving of Inverter Air Conditioner and R32 Refrigerant DAIKIN VIETNAM. 13 th May 2017

Case Study of an Innovative HVAC System with Integral Dehumidifier. Florida Solar Energy Center Cocoa, Florida

Update Dedicated Heat Recovery Chiller Technology. Don Frye. Gulf South

Effect of the Use Pattern on Performance of Heat Pump Water Heater

Reduction Of Energy Consumption in Airconditioning Systems employing direct evaporative pre-cooling of Condenser air

Evaluation of the Red Jacket Fx1, Fx2, Fx1V and Fx2V Line Leak Detectors For Hourly Monitoring on Rigid Pipelines. Final Report

Link loss measurement uncertainties: OTDR vs. light source power meter By EXFO s Systems Engineering and Research Team

Performance of Solar Water Heating Systems in the United States

Application of Air Source Variable Refrigerant Flow in Cold Climates

Natural geothermal energy

Field Trial of Residential Ammonia-Water Absorption Heat Pump Water Heaters

In Search of the Magic Box: A Review of Crossover Conditioning/Ventilation/Dehumidification Devices on the US Market

Measuring And Understanding Energy Efficiency

Daikin Altherma/Viessmann Integration Notes (used with schematics M1 thru M5)

Dual-Purpose Air Conditioner

Final Report Polymer Bead Laundry

Emerging Technologies: VFDs for Condensers. Douglas T. Reindl Director, IRC University of Wisconsin-Madison. University of Wisconsin-Madison

ENCLOSURE COOLING. Glossary

Advanced Installation and Configuration Instructions

Farm Energy Audit Workshop

Exercise 2-4. Heat Exchangers (Optional Exercise) EXERCISE OBJECTIVE DISCUSSION OUTLINE. Description of a brazed plate heat exchanger DISCUSSION

CARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection.

Laboratory Assessment of Sanden GAU Heat Pump Water Heater Lab

Application of a hybrid control of expansion valves to a 3-ton large room cooling system

PG&E s Applied Technology Services Hot Water Technology Performance Laboratory

Jetstream Series HPLC - PELTIER COLUMN-THERMOSTATS 1. GENERALITIES

Air & Water Heat Pump R832

Transcription:

Heat Pump Water Heaters: Laboratory and Field Evaluation of New Residential Products K.R. (Ammi) Amarnath and Chris Trueblood, Electric Power Research Institute ABSTRACT The Electric Power Research Institute (EPRI) conducted laboratory evaluations of several heat pump water heaters to assess their performance and energy efficiency. Among U.S. heat pump water heaters evaluated were new products from A. O. Smith, General Electric (GE), and Rheem. These units are designed to be integral, drop-in replacements for standard electric water heaters. EPRI conducted a series of draw tests and 24-hour tests under conditions that were somewhat different from the prescribed bounds articulated in the U.S. Federal Code of Regulations water-heating test protocol. The lab tests were conducted using each water heater s default operating mode, a 120 F water temperature setting and other targeted testing conditions. In addition to lab evaluations, EPRI recently launched a medium-scale energy efficiency technology demonstration project that includes installing and monitoring up to 200 new residential heat pump water heaters. Working with sponsoring utility companies, EPRI is providing heat pump water heaters, monitoring equipment, and data analysis for nationwide installations. This paper provides some highlights of the lab tests. Background Heat pump water heaters (HPWHs) are typically more than twice as efficient as standard electric water heaters, and can result in lower annual water heating bills for the consumer, as well as reductions in peak electric power demand. Heat pump water heating technology relies on using electricity to power a vapor-compression cycle to transfer heat from the surrounding air into a water storage tank. All major U.S. water heater manufacturers are introducing heat pump water heater products in 2009 and 2010, marketed as energy-efficient alternatives to standard electric water heaters. With improved product designs and promises of 3 6 year payback periods, new heat pump water heaters have the potential to overcome previous barriers and a moribund U.S. heat pump water heater market. For the past two decades, less than 0.1% of about 9 million water heaters sold annually in the United States have been heat pump units, a legacy of early models that suffered from reliability problems, excessive noise levels, high initial costs, and lack of consumer awareness. Heat pump water heaters differ from standard water heaters in that their performance and efficiency varies significantly under varying conditions, including inlet and outlet water temperature, ambient conditions, and user settings. Laboratory testing is required to characterize how varying conditions affect heat pump water heaters and to provide performance data beyond product nameplate ratings. Additionally, field demonstrations are necessary to provide insight into heat pump water heaters energy use and performance over a wide range of diverse environments. 1-12

EPRI, through its End-Use Energy Efficiency and Demand Response Program, is assessing and demonstrating heat pump water heaters by conducting comprehensive lab and field tests of new products, extensively engaging water heater manufacturers and electric utilities in the process. Laboratory and field evaluations began in 2009 and are continuing through 2010 and 2011. Figure 1 shows the types of HPWHs tested at the EPRI lab in Knoxville, TN. Figure 1. HPWHs Tested at the EPRI lab in Knoxville, TN Laboratory Evaluation Product Specifications Electric power specifications are listed in Table 1 for three HPWH units from the following manufacturers (and rated storage volumes): A. O. Smith (80-gal), GE (50-gal), and Rheem (50-gal). Heat pump power values were obtained from EPRI s lab testing and were the observed power drawn by the heat pump system at two operating conditions: high at approximately 120 F water tank temperature and low at approximately 58 F water tank temperature. Generally, heat pump power will increase as the water tank temperature increases. Table 1. Power Specifications Manufacturer A. O. Smith GE Rheem Heat pump power, high (W) 1, 2 970 540 1170 Heat pump power, low (W) 1, 3 680 410 780 Upper element, rated power (W) 4500 4500 2000 Lower element, rated power (W) 2000 4500 2000 1 Values obtained from 2009 EPRI lab tests 2 Heat pump power, high, is at 120 F water tank temperature and 68 F air temperature 3 Heat pump power, low, is at 58 F water tank temperature and 68 F air temperature 1-13

A. O. Smith and GE have included interlock mechanisms to prevent concurrent heat pump and resistive element operations. Rheem, however, allows both the heat pump and one 2,000W element to operate concurrently if needed. In Table 2 user-selectable operating modes are described for each water heater. All heat pump water heaters have a vacation mode that will essentially allow the water tank temperature to decrease to around 50-60 F so that standby losses are minimized during extended periods of non-use. Note that A. O. Smith and GE have heat pump only modes available, whereas Rheem does not provide a heat pump only mode. Table 2. Operating Modes and Airflow Pattern Manufacturer A. O. Smith GE Rheem Userselectable operating modes Maximum Efficiency (heat pump only) Hybrid (either heat pump or upper element; algorithm favors heat pump, based on water temp) Conventional Electric (either upper or lower element) eheat (heat pump only) Hybrid (either heat pump or upper element; algorithm favors heat pump, based on water temp) High Demand (either heat pump or upper element; algorithm favors element, based on water temp) Standard Electric (either upper or lower element) Energy Saver (heat pump; time-based algorithm adds upper element after 45 minutes) Normal (heat pump; time-based algorithm adds upper element after 30 minutes) 4 Electric Heat (both upper and lower elements) Airflow pattern Into the left side, out of the right side Into both sides, out of the back Into the top, out of the sides and back Because the Rheem unit requires the user to select a mode upon powering the unit, it does not have a default operating mode. In this case, the Energy Saver mode was chosen to represent the default operating mode because this mode provides the closest resemblance to both the A. O. Smith and GE factory default Hybrid modes. Test Design and Procedure EPRI has established a set of lab test procedures loosely based on the U.S. Code of Federal Regulations water heating test protocol. 5 EPRI used the HPWHs factory default setting conditions; these are not necessarily held within the prescribed bounds articulated in the federal standard. By doing this, EPRI could characterize a water heater s performance and efficiency under other test conditions by performing a series of draw tests and 24-hour tests. For example, EPRI has tested water heaters using a 120 F water temperature setting (typically default settings provided by manufacturers) instead of enforcing the standard 135 F water temperature setting. 4 Rheem has considered renaming Normal mode to High Demand mode for clarity 5 Uniform Test Method for Measuring the Energy Consumption of Water Heaters. Title 10 Code of Federal Regulations, Pt. 430, Subpt. B, App. E. 2009 ed., 176-194. Print. 1-14

The electrical supply for these tests was provided by single-phase 240Vac 60Hz service. The test voltage was targeted to be 240Vac; however, voltage regulation and tolerance was not maintained during these tests. Test area. EPRI s water heater lab test area consists of an indoor water retention barrier located within a semi-controlled environment. Domestic water supply is implemented with a 125-gallon storage tank with a jet pump and pressure tank to provide approximately 40-psi water pressure. The water system is capable of delivering up to 10 gallons per minute (gpm) of water flow. Supply water temperature is regulated manually, by adding multiple bags of ice or warm tap water to the storage tank as needed. The indoor ambient conditions are regulated by two unitary heating and cooling systems. One system is set to cooling mode while the other system is set to heating mode, and both thermostats are set such that a desired ambient temperature can be maintained. Ambient humidity control was not available for these laboratory tests. Sensors and meters. The following sensors and meters were used to obtain measurement data collected in the heat pump water heater tests. Each measurement point is polled at 5-second intervals: Water flow rate and totalization is measured using a turbine-based, high-frequency pulse output water meter (Omega, FTB4607). The water meters are installed in the supply water piping. Accuracy, from 1.1 to 20.0 gpm, is ±1.5% of the measured flow rate. Water temperatures, both inlet and outlet, are both measured using a T-type thermocouple insertion probe assembly (Omega, TTIN-18U-12). Both temperature probes are inserted into the water piping near the hot and cold ports on the water heater, but they do not penetrate into the water heater tank or pass through the heat trap (if present). Measurement accuracy was calibrated to within ±1.0 F, as reported by the data acquisition s thermocouple input module (Advantech, ADAM-4118). Electric power and energy is measured using an ac power meter (Continental Control Systems, WattNode WNC-3D-240-MB) with two 30A solid-core current transformers (Continental Control Systems, CTT-0300-030). The power meters and current transformers are installed adjacent to a nearby circuit breaker panel, approximately 10-20 feet away from the water heater test locations. Accuracy, at nominal line voltages and current draws between 3.0A and 39.0A, is ±1.5% of the reading. Ambient temperature is measured using a T-type thermocouple (Omega, 5SRTC-TT-T- 24-36), and ambient relative humidity is measured using a humidity transmitter (Vaisala, HMP233). These ambient sensors are placed such that they are not in the direct path of a heat pump water heater s exhaust air stream. Test procedure summary. Each HPWH is subjected to an initial reheat cycle to ensure that a full tank of hot water is available just prior to testing. Additionally, the domestic water supply tank and ambient conditions are established and maintained to within EPRI s lab capabilities throughout the duration of each test. The draw test consists of a single, continuous water draw event that is terminated when the tank is nearly depleted of hot water (i.e. water outlet temperature decreases by 25 F). The HPWH is then allowed to fully reheat undisturbed. A flow rate of 3.0 gpm is maintained during 1-15

the draw, and the cutoff temperature is obtained by subtracting 25 F from the maximum recorded water outlet temperature. The 24-hour test subjects the HPWH to a simulated usage pattern. During the first six hours of the 24-hour test, a standard volume of water (10.7 gallons) is drawn from the tank at hourly intervals for a total of 64.3 gallons drawn. The remaining 18 hours are then allowed to elapse with no water draw events. Draw Test Results A summary of the draw test results are shown in Table 3 for the A. O. Smith, GE, and Rheem heat pump water heaters. Draw tests were performed at target conditions of 67.5±2.0 F ambient temperature, 50% ambient relative humidity, 58.0±2.0 F supply water temperature, and a 120 F water temperature setting. The summary includes each water heater s settings, measured conditions, calculated process variables, and overall efficiency (coefficient of performance). Table 3. Summary of the Draw Test Results A. O. Test Condition or Measurement Smith GE Rheem Operating Mode Hybrid Hybrid Energy Saver Water Temp Setting ( F) 120 120 120 Test Duration & [Recovery Time] (hours) 3.4 [3.3] 3.1 [2.8] 1.4 [1.4] Ambient Temp, Avg ( F) 68.6 68.8 69.0 Ambient Humidity, Avg (%RH) 52.4 48.5 34.4 Water Draw Flow Rate, Avg (gpm) 3.0 3.0 2.9 Water Draw Inlet Temp, Weighted Avg ( F) 58.9 58.1 59.2 Water Draw Outlet Temp, Weighted Avg ( F) 119.6 113.6 114.6 Water Draw Volume & [Actual Tank Volume] (gal) 64.9 [80] 36.4 [45] 39.7 [50] Water Draw Energy (ton-h) 2.7 1.4 1.5 Electric Power Reheat, Avg (kw) 1.3 0.8 1.9 Electric Power Reheat, Max (kw) 4.2 4.5 3.2 Electric Energy Reheat (kwh) 4.3 2.3 2.6 2.2 2.1 2.0 Draw test results observations. When studying the draw test results presented in Table 3, several observations can be made. First, the testing conditions for each water heater were maintained within the specified desired ranges except for the ambient relative humidity, which was not controllable in the lab test area. Second, one of the most significant differences in the results is the volume of water drawn from each water heater. As expected, a larger water draw volume occurs with a larger tank size and necessitates more electrical energy to recover. In an effort to normalize the draw test results for varying water draw volumes, one may study the average power, maximum power, and overall coefficient of performance (COP) for each water heater, as charted in Figure 2. 1-16

Figure 2. Draw Test Average and Maximum Power, and Overall COP Power (kw) 5 4 3 2 1 1.3 4.2 2.2 0.8 4.5 3.2 2.1 1.9 2.0 4.5 4.5 0.9 0 A. O. Smith GE Rheem (Typcial Standard Electric Power Reheat, Avg (kw) Electric Unit) Electric Power Reheat, Max (kw) Manufacturer The overall COPs (quotient when dividing energy output by energy input ) for each water heater are within about 10% of each other (2.0 to 2.2), even though the average and maximum power values vary quite largely. The Rheem unit has the highest average power (1.9kW), but it recovers in less than half of the time required by the A. O. Smith and GE units. While the A. O. Smith unit achieves the highest overall COP from this draw test, it took the longest time to recover. As expected, a trade-off must be made between average power consumption and recovery time for heat pump water heaters. The Rheem unit maximum power is the lowest of the three water heaters because Rheem utilizes a 2.0kW resistive element, whereas A. O. Smith and GE utilize a 4.5kW resistive element during a portion of the recovery period. As listed in Table 3, the A. O. Smith unit maximum power was 4.2kW instead of 4.5kW. The maximum power was observed when the supplied ac voltage was 235Vac. Heat pump water heaters twice as efficient. The estimated results from a standard electric water heater (without heat pump technology) are also shown in Figure 2 to serve as baseline data. Typical standard electric units would likely utilize 4.5kW upper and lower resistive elements, which would draw relatively constant power during the reheat period. The overall COP for a standard electric water heater must be less than 1.0 (the theoretical efficiency of a resistive electric heating element is 100%), and in general such water heaters are typically at least 90% efficient in recovering from a water draw event. Based on the results from this draw test, the U.S. heat pump water heaters are more than twice as efficient as a typical standard electric water heater. 24-Hour Test Results The summary of the 24-hour test results is provided in Table 4 for A. O. Smith, GE, and Rheem heat pump water heaters. These tests were performed at target conditions of 67.5±2.0 F ambient temperature, 50% ambient relative humidity, 58.0±2.0 F supply water temperature, and a 120 F water temperature setting. 1-17

Table 4. Summary of the 24-Hour Test Results Test Condition or Measurement A. O. Smith GE Rheem Operating Mode Hybrid Hybrid Energy Saver Water Temp Setting ( F) 120 120 120 Ambient Temp, Avg ( F) 69.2 68.4 68.0 Ambient Humidity, Avg (%RH) 40.7 39.6 38.6 Water Draw Flow Rate, Avg (gpm) 3.0 3.0 3.0 Water Draw Inlet Temp, Weighted Avg ( F) 58.1 58.2 58.7 Water Draw Outlet Temp, Weighted Avg ( F) 121.2 117.5 121.6 Water Draw Volume (gal) 64.3 64.4 64.2 Water Draw Energy (ton-h) 2.7 2.6 2.7 Electric Power Reheat, Avg (kw) 0.9 0.5 1.1 Electric Power Reheat, Max (kw) 1.0 0.5 1.2 Electric Energy Reheat (kwh) 3.8 3.4 4.0 2.5 2.7 2.4 24-hour test results observations. When studying the 24-hour test results presented in Table 4, several observations can be made. The conditions in which each water heater is tested were maintained within the specified desired ranges except for ambient relative humidity, which cannot be controlled in the lab test area. The total water draw volume for each water heater is within 0.1 gallons of the required 64.3 gallons water draw. One noticeable difference on the water measurements is that the GE unit s average water outlet temperature is approximately 4 F lower than the other units average water outlet temperatures. This difference occurs because the GE unit does not fully reheat its water tank between any of the hourly water draw periods. The most significant differences in the results are seen in comparing the reheat power levels and overall COPs for the 24-hour test (COP is the quotient when dividing energy output by energy input ). The average power, maximum power, and overall COP for each water heater are charted in Figure 3. In all cases, the heat pump water heaters did not engage any resistive elements during the 24-hour test period. If a similar 24-hour test was to be conducted using another operating mode that favors faster reheat times (such as High Demand or Normal modes) then the resistive elements are expected to be engaged during a portion of the reheat period. 1-18

Figure 3. 24-Hour Test Average and Maximum Power, and Overall COP 5 4.5 4.5 Power (kw) 4 3 2 1 0.9 1.0 2.5 0.5 0.5 2.7 1.1 1.2 2.4 0.9 0 A. O. Smith GE Rheem (Typical Standard Electric Unit) Electric Power Reheat, Avg (kw) Electric Power Reheat, Max (kw) Manufacturer As depicted in Figure 3, the GE unit s average and maximum power levels (measured during the reheat periods) are about 50% lower than the comparable power levels for the A. O. Smith and Rheem units. This difference should be expected because the GE unit s heat pump power ratings are roughly half of the power ratings shown for the A. O. Smith and Rheem units (see Table 1). All three U.S. water heaters exhibited relatively stable power profiles, where the maximum power was observed to be within 10% of the average power during each water heater s reheat period. Heat pump water heaters more than twice as efficient and draw a quarter of the power. The estimated results from a standard electric water heater (without heat pump technology) are also shown in Figure 3 to serve as baseline data. Typical standard electric units would likely utilize 4.5kW upper and lower resistive elements, which would draw relatively constant power during the reheat periods. The overall COP for a standard electric water heater must be less than 1.0 (the theoretical efficiency of a resistive electric heating element is 100%), and in general such water heaters are typically about 90% efficient after subjected to a 24-hour test. Based on the results from this 24-hour test (at 120 F water temperature setting), these heat pump water heaters are at least 2.5-times more efficient than a typical standard electric water heater. Additionally, these heat pump water heaters draw less than 25% of the power drawn by a typical standard electric water heater (1.1kW or lower, compared to 4.5kW). Performance Characterization As heat pump technologies involve moving heat from one medium to another, the primary drivers that affect a heat pump s performance and efficiency are source and sink temperatures over which the heat transfer takes place. In the case of heat pump water heaters, the ambient air temperature acts as the source, and the water tank temperature acts as the sink. Effects of water inlet temperature. Assuming a constant ambient air temperature and a constant water outlet temperature, the theoretical maximum COP will be higher for lower water tank temperatures. While lower supply water temperatures may yield higher system efficiencies, more electrical energy input is required to reheat the water tank. This may appear contradictory, 1-19

but it is indeed a phenomenon of heat pump water heating technology. The matrix shown in Table 5 provides a general representation of how a heat pump water heater s efficiency and energy use will change based on varying water inlet temperatures, assuming all other conditions are held constant. Table 5. General Effects of Water Inlet Temperature on Efficiency and Energy Use Water Inlet Temperature Cooler Warmer Heat Pump Efficiency Higher Lower Electrical Energy Used More Less To demonstrate how lower water temperatures affect efficiency and energy use, the A. O. Smith heat pump water heater was subjected to three different draw tests. For each draw test, the average water inlet temperature was changed, but all other conditions and settings were held constant (to within EPRI s lab testing capabilities). The graph shown in Figure 4 contains a plot of overall COP and electrical energy for the set of draw tests conducted at these average water inlet temperatures: 52 F, 59 F, and 67 F. Figure 4. Overall COP and Electrical Energy for Varying Water Inlet Temperatures (Draw Tests) 2.6 Electric Energy Reheat (kwh) 6.0 2.5 5.0 2.4 2.3 2.2 4.69 2.30 4.32 2.23 3.90 4.0 3.0 2.0 Electric Energy (kwh) 2.12 2.1 50 55 60 65 70 Draw Test: Average Water Inlet Temp ( F) 1.0 As shown in Figure 4, a 15 F decrease in water inlet temperature (67 F to 52 F) results in an 8% increase in overall COP (2.1 to 2.3) but requires 20% more electrical energy (3.9kWh to 4.7kWh) to reheat the water tank. Effects of water outlet temperature. Assuming a constant ambient air temperature and a constant water inlet temperature, the theoretical maximum COP will be higher for lower water outlet temperatures. When lower water outlet temperature yields higher system efficiencies, less electrical energy input is required to reheat the water tank. The matrix shown in Table 6 provides a general representation of how a heat pump water heater s efficiency and energy use will change based on varying water outlet temperatures, assuming all other conditions are held 1-20

constant. Please note that the effect of varying water outlet temperature results in the electrical energy decreasing with increasing efficiency, which is inverse from the effect caused by varying water inlet temperature as explained in the previous section. Table 6. General Effects of Water Outlet Temperature on Efficiency and Energy Use Water Outlet Temperature Hot Hotter Heat Pump Efficiency Higher Lower Electrical Energy Used Less More To demonstrate this effect, the A. O. Smith heat pump water heater was subjected to two different 24-hour tests. For each 24-hour test, the water temperature setting was changed, but all other conditions and settings were held constant (to within EPRI s lab testing capabilities). The graph shown in Figure 5 contains a plot of overall COP and electrical energy for the pair of 24- hour tests conducted when the average water outlet temperatures were measured at 121 F and 135 F. Figure 5. Overall COP and Electrical Energy for Varying Water Outlet Temperatures (24-Hour Tests) 2.6 Overall Electric Energy (kwh) 6.0 2.51 2.5 5.27 5.0 2.4 2.3 2.2 3.77 2.22 4.0 3.0 2.0 Electric Energy (kwh) 2.1 1.0 120 125 130 135 140 24-Hour Test: Average Water Outlet Temp ( F) As shown in Figure 5, a 14 F decrease in average water outlet temperature (135 F to 121 F) results in a 13% increase in overall COP (2.2 to 2.5) and results in 28% less electrical energy required (5.3kWh to 3.8kWh) to reheat the water tank over the 24-hour test period. Implications/Conclusions from Lab Evaluation The lab evaluations show that heat pump water heaters could be more than twice as efficient as standard electric water heaters. Additionally, the heat pump component of the water heaters can operate while drawing less than 25% of the average power required of standard electric water heaters. While the energy efficiency and power consumption figures are favorable for heat pump water heating technologies tested by EPRI, longer reheat periods are required to recover a tank of 1-21

hot water. The recovery time could last over 3 hours for reheating a cold tank, but this will vary based on the water heater model, operating mode, and usage characteristics. Technical application issues. Technically, each water heater tested at EPRI exhibited reliable performance during its relatively short time undergoing laboratory tests. Practical application issues may arise with the adoption of heat pump water heating technology. For example, the following issues must be addressed when installing a heat pump water heater in a residence: Adequate physical space: Heat pump water heaters are generally larger (height, width, and/or depth) compared to standard water heaters. Having limited physical space may prevent the water heater from being installed in a desired location within a residence. Adequate air volume and circulation: Heat pump water heaters have specific air volume and circulation requirements that can degrade a heat pump water heater s performance if installed in a confined sealed space, such as a closet or a small room. Condensate removal: Access to a drain or to the outdoors is required for removing the heat pump water heater s condensate. Typically, existing water heaters will have a drain pan, but additional piping may be required for handling condensate removal. Noise: Heat pump water heaters generate a humming or whirring noise when the heat pump system operates. Depending on the heat pump water heater model and location within a residence, occupants may take notice of potentially undesirable noise levels. Exhaust air: Heat pump water heaters exhaust cool, dehumidified air into their surroundings, which may or may not be desirable to the occupants. The U.S. heat pump water heaters reviewed in this report each have a means to disable the heat pump operation to stop the exhaust air. Field Evaluation Overview In 2009, EPRI launched a medium-scale energy efficiency technology demonstration project that includes installing and monitoring up to 200 new residential heat pump water heaters. Working with sponsoring utility companies, EPRI is providing heat pump water heaters, monitoring equipment, and data analysis for nationwide installations. The objectives of the demonstration are to assess heat pump water heater technology by measuring efficiency, to provide credible data on the performance and reliability of heat pump water heaters, and to assess user satisfaction in a residential setting. The heat pump water heaters slated for field installations include the latest Underwriters Laboratories (UL) approved models from A. O. Smith, GE, Rheem, Stiebel-Eltron, and Daikin (Note: The last two will be evaluated at field sites only). Demonstrations sites must be owned by the occupants, have standard utility rates, and be served by no more than l water heater. Treatment sites (those receiving a new HPWH) require adequate physical space and air circulation for proper installation, as well as access to a condensate drain line and electrical service. Control sites will have existing water heaters (standard electric or natural gas) monitored in parallel with treatment sites over the 2-year demonstration period. Occupants are requested to operate the water heaters normally, year-round, and are allowed to adjust the water temperature setting and operating modes as desired. 1-22

Instrumentation. Both treatment and control sites will be provided with appropriate instrumentation for collecting usage data. The data collection efforts allow multiple sensors and meters to capture the performance and operational characteristics of a field-installed HPWH. EPRI offers two types of instrumentation packages for field installations: a Full package and a Lite package. Both packages provide water heater and whole house energy and power consumption plus hot water usage volume. A photograph showing of the contents of a Full package is provided in Figure 6. Figure 6. Instrumentation for Field Data Collection (Full Package) Data acquisition panel (data logger, ambient temp/humidity, and WiFi repeater), 24 x14 3 CTs (2 for whole house, 1 for water heater) WiFi base station (plugs into home router) 2 thermistor immersion probes (for water inlet and outlet temps) Water meter Power meter (measures both whole house and water heater electricity) The Full package adds measurements of basic power quality data (voltage, current, reactive power, and frequency), ambient temperature and relative humidity, water inlet and outlet temperatures. Data is recorded every minute for the Full package and every 5 minutes for the Lite package. Both packages have on-board memory for data storage and will periodically upload data logs to EPRI via the internet. Initial findings. As of this writing, field data are just being collected and analyzed. Interim data will be made available (first to the funders, and subsequently to the public), as and when analyses are being completed. References Residential Heat Pump Water Heaters, EPRI Technical Brief 1015428, 2007 Heat Pump Water Heaters - Laboratory Tests, EPRI Technical Update 1017889, 2009 Energy Efficiency Demonstration Update, EPRI Technical Update 1019345, 2009 1-23