Residual current monitor RCM470LY/RCM475LY. for TN and TT systems (AC and pulsating DC currents)

Similar documents
LINETRAXX RCMA420. Residual current monitor for monitoring AC, DC and pulsed DC currents in TN and TT systems

ISOMETER IR1575. Insulation monitoring device for unearthed AC/3(N)AC systems up to 480 V and DC systems up to 480 V

ISOMETER IRDH375. Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems)

ISOMETER IR425. Insulation monitoring device for unearthed AC/DC control circuits (IT systems)

ISOMETER IR425. Insulation monitoring device for unearthed AC/DC control circuits (IT systems)

LINETRAXX VME420. Multi-functional relay for overvoltage, undervoltage and frequency monitoring in AC/DC systems with external supply voltage

ISOSCAN EDS460-DG. Insulation fault locator for DC IT systems with high system leakage capacitances

ISOSCAN EDS460/490 EDS461/491. Insulation fault locators with control and display function for EDS systems (insulation fault location systems)

ISOMETER IRDH275BM-7 with coupling device AGH675-7 and AGH675-7MV15

Insulation fault evaluator EDS460-DG

LINETRAXX VMD420. Multi-functional voltage relay for 3(N)AC systems, frequency/overvoltage/undervoltage, phase, phase failure, asymmetry

LINETRAXX RCMS460-D/-L RCMS490-D/-L

1.7. Insulation fault evaluators EDS460/490 EDS461/491

Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Tel.: Fax:

1.7. Insulation fault evaluators EDS460/490 EDS461/491

1.7 A-ISOMETER IRDH575. RoHS. Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Tel.: Fax:

Operating Manual RCM420

ISOMETER isomed427p. Application Medical IT system in accordance with IEC , IEC , IEC and DIN VDE

isopv425 and AGH420 Ground Fault Detector for Ungrounded Solar Arrays < 100 kw And Isolation Tester Prior to Array Startup (Grounded and Ungrounded)

GM420. Digital Ground Continuity Relay For AC Systems. Technical Bulletin NAE /

RCMA423-DM RCMA423-DM1C RCMA423-DM2C RCMA423-DM3C. Operating Manual

IT system floor-standing distribution

Remote alarm indicator and test combination MK2430

Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Phone: Fax:

RCMA423-DM1C Residual current monitor

DEB71. Earth Leakage Monitoring Relay. Benefits. Description

RCMA423. Residual current monitor for monitoring AC-, DC- and pulsed DC currents in TN- and TT systems Software-Version: D330 V1.0x.

isopv and AGH-PV Ground Fault Detector for Ungrounded Solar Arrays up to 1100 V And Isolation Tester Prior to Array Startup (Grounded and Ungrounded)

CMD420 / CMD421 Series

Manual CME420. Multi-functional current relay, AC, overcurrent/undercurrent/ window discriminator function CME420_D00034_02_M_XXEN/05.

Operating Manual VMD420

ISOMETER IRDH265 IRDH365

VME421H Voltage and frequency monitor

VME420 Voltage and frequency monitor

LINETRAXX RCMS150. Residual current monitor type B with integrated measuring current transformers for earthed AC/DC systems (TN and TT systems)

Bender GmbH & Co. KG. All rights reserved. Reprinting only with permission of the publisher. Subject to change! Photos: Bender archives

TM800. Remote alarm indicator and operator panels

BENDER A-ISOMETER IRDH265 IRDH365

Line Isolation Monitor (LIM) LIM2000plus

Operating Manual MS220KA and MSR220KA

Connection. e. g. Pt100. reference limit. yellow Output I. Composition

Operating Manual MSF220V(VU)

Operating Manual MS220DA

T M LIM2010. Line Isolation Monitor (LIM) Technical Bulletin NAE /

VAMP 120 & 121. Arc flash detection units. Product picture

PolyGard 2-channel Gas Controller MGC-03

Universal fault annunciator for panel mounting

enproteko.com Specifications Ratings Item voltage to 24 VAC 5/6 Hz 24 VAC 5/6 Hz or 24 VDC Allowable voltage Characteristics 85% to 11% of power suppl

AO Annunciator Module

Monitoring Devices 11/1

Cat. N. Cat. N (s) 1. DESCRIPTION - USE 3. OVERALL DIMENSIONS. Technology : 4. PREPARATION - CONNECTION 2. PRODUCT RANGE

Process Alarm Module RTA 421

PHOTOELECTRIC AMPLIFIER SERIES

Parameterisable compact fault annunciator with permanent display

7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for Infrastructure & Cities.

EARTH LEAKAGE RELAY. User Manual - Issue 1.0

DPB52. True RMS 3-Phase, Multifunction monitoring relay. Benefits. Description

RTA421. Technical Information. Limit alarm switch Alarm switch and power supply for monitoring current or voltage signals

KHA6-GT*-Ex1. Thermocouple trip amplifiers. Composition. Hazardous area. Safe area. Function. 230 V AC 1-channel. Input EEx ia IIC

Electronic Standard Devices. Annunciator Relay. MR 11 and MRE 11 MR 21 and MRE 21

Operating Manual TR600

Operation and use. Functions and characteristics

DICTATOR Hold-Open Systems for Hazardous Areas

Annunciator Relay MR 11 and MRE 11 MR 21 and MRE 21. Automation Equipment. Power Station Control Systems. Control Room Technology

REA 105 Arc Protection Module. Operator s Manual

Safety Temperature Limiter STL 50 Certified to DIN EN (replaces DIN 3440)

BU: EPBP GPG: DIN Rail Products Devices for the permanent control of insulation on 24 V supply lines for medical locations SELVTESTER-24

Gas cylinder scale Model GCS-1

RSWT. Three phase AC pumps and ventilators soft starter. Benefits. Description

Interface and EOL Modules 8

GMA 301. Operation Manual. Worldwide Supplier of Safety Solutions. Part Number

Operating instructions Safety-monitoring module SRB 302X3. 1 About this document

PolyGard Single Point Controller SPC-X3-20XX for refrigerant gases and vapours

DTA. Motor thermistor relay. Benefits. Description

VAMP 120 & 121. Arc Flash Protection Units. Arc Protection. Customer benefits

Analog Annunciator Unit SACO 16 A3. Product Guide

QFM21... Siemens Building Technologies HVAC Products. Symaro Duct Sensors. for relative humidity and temperature

Wind Alarm Instrument x.x0x

4 Ó â. Contactor RTA421. Contactor with loop power supply for monitoring currentorvoltagesignals. Technical information TI074R/09/en

Operating instructions Safety-monitoring module SRB 302X3. 1. About this document. Content

for relative humidity and temperature

LC1350 Level Controller

Digital Panel Meter K3TL. Ordering Information. Low-cost, High-quality Digital Thermometer with Built-in Microcomputer. Accessories (Order Separately)

7XG3120 ReyArc20 Arc Fault Monitor Relay Energy Management

ACS-30-EU-EMDR- 10-MOD

Instruction Manual August sitrans CU 02

02/11/2015

MK Series. Remote Indicators For Line Isolation Monitors and Fault Location. Technical Bulletin NAE /

DEIF A/S. Technical Manual. Type EC-2 Engine Control Unit D. Technical Manual

OilSET-1000 (12 VDC)

Room Sensors. Building Technologies HVAC Products ... Symaro. for relative humidity (high accuracy) and temperature

Ordering Key. Dielectric strength

Duct Sensors. Siemens Building Technologies HVAC Products. Symaro. for relative humitidy (high accuracy) and temperature

THERMASREG TR 040 THERMASREG TR 060

02/11/2015

PolyGard Single Point Controller SPC-X3-11XX for Toxic Gases and Oxygen

DTA04. Motor thermistor relay. Benefits. Description

RE-PR3-E-27 3-Phase Panel Mount 27kW

SCHMIDT LED Measured Value Display MD Instructions for Use

ABB MEASUREMENT & ANALYTICS DATA SHEET. C50 1/16 DIN controller / alarm unit

Transcription:

Residual current monitor RCM470LY/RCM475LY for TN and TT systems (AC and pulsating DC currents) TDB401003en/03.2010

Residual current monitor RCM470LY Residual current monitor for TN and TT systems (AC and pulsating DC currents) Product description The residual current monitor RCM470LY is designed for fault and residual current monitoring in earthed power supply systems (TN and TT systems) where an alarm is to be activated in the event of a fault, but disconnection must be prevented. In addition, the device can be used to monitor single conductors, such as PE conductors, N-PE connections and PE-PAS connections. Since the values are measured with measuring current transformers, the device is nearly independent of the load current and the nominal voltage of the system. The device can also be used for busbar systems. RCM470LY Device features External measuring current transformer Response values adjustable 10 ma 10 A/100 A 40 400 Hz Response delay, adjustable 0 10 s Alarm relay with two potential-free changeover contacts N/O or N/C operation, selectable Fault memory behaviour, selectable Combined test/reset button Connection external test and reset button LED bar graph indicator I Δn 0 100 % Connection external measuring instrument I Δn 0 100 % CT connection monitoring Sealable transparent cover External supply voltage Type A acc. to IEC/TR 60755 Approvals Application Residual current monitoring in earthed two, three or four conductor systems (TN and TT systems) Current monitoring of single conductors de-energised under normal conditions Socket-outlet circuits for devices which are operated unattended for a long time and which may not fail Alarm systems, safety devices Air conditioning systems, EDP systems Cooling equipment with valuable frozen goods Canteen kitchens Monitoring of earthed power supplies for stray currents, impact on N conductors Function Residual current monitoring takes place via an external measuring current transformer. When the residual current respectively the current exceeds the set response value, the alarm LED lights and the alarm relay switches after the expiry of the set response delay. The fault messages can be stored. The fault memory can be reset by pressing the reset button. The device function can be tested using the test button. The currently measured value in per cent related to the set response value is indicated on the LED bar graph indicator. The CT circuit is continuously monitored. In case of wire breakage, the alarm relay switches and the alarm LED flashes. Standards The RCM470LY series complies with the requirements of the device standards: DIN EN 62020 (VDE 0663) und IEC 62020. 2 TDB401003en/03.2010

Residual current monitor RCM470LY Wiring diagram system connection, external connections Wiring diagram front plate 2 1 1 2 3 4 5 6 9 7 8 10 A B C D E F 3 1 - Supply voltage U S, see ordering information, 6 A fuse recommended. 4 2 - External measuring current transformer (refer to table "External measuring current transformers") 3 - External measuring instrument 4 - External test and reset button "T/R" 5 - Alarm relay: switches when the fault current exceeds the response value and in case of interruption of the CT connection. Note! Do not route the PE conductor through the measuring current transformer! 5 1 - Combined test/reset button "T/R": short-time pressing (< 1s) = RESET; long-time pressing (> 2s) = TEST 2 - Power On LED "ON" 3 - Alarm LED "ALARM": lights when the fault current exceeds the response value and flashes in case of interruption of the CT connection. 4 - LED bar graph indicator: shows the measuring value in per cent related to the preset response value. 5 - Potentiometer for setting the response delay (0 1 s). 6 - Potentiometer for setting the response value (x 1 10 ma). Setting of the DIP switches (white = switch position) 7 - Operating principle of the alarm relay A - N/O operation B - N/C operation 8 - Fault memory behaviour relay + LED A - Fault memory ON B - Fault memory OFF 9 - Setting the response range RCM470LY RCM470LY-72 A - 10 ma A - 100 ma B - 30 ma B - 300 ma C - 100 ma x 1 10 C - 1 A x 1 10 D - 300 ma D - 3 A E - 500 ma E - 5 A F - 1000 ma F - 10 A 10 - Setting the response delay A - x 1 0 1 s B - x 10 TDB401003en/03.2010 3

Residual current monitor RCM470LY Technical data Insulation coordination acc. to IEC 60664-1: Rated insulation voltage Rated impulse withstand voltage/pollution degree Voltage ranges Supply voltage U S Operating range of U S Frequency range of U S Power consumption AC 250 V 4 kv/3 see ordering information 0.85 1.1 x U S DC/50 400 Hz 3 VA Measuring circuit External measuring current transformers W, WR, WS series Load 180 Ω Load RCM470LY-72 18 Ω Operating characteristics acc. to IEC 62020 and IEC/TR 60755 Type A Rated residual operating current I Δn 10 ma 10 A Rated residual operating current I Δn for -72 100 ma 100 A Response delay t v, adjustable 0 10 s Accuracy of response delay ± 20 % Rated frequency 40 400 Hz Relative uncertainty 40 400 Hz: 0-25 % 400 1000 Hz: 10-25 % Hysteresis approx. 25 % of the response value Response time t an at IΔn = 1 x IΔn (tv = 0 s) < 250 ms Response time t an at IΔn = 5 x IΔn (tv = 0 s) 20 ms Number of measuring channels 1 Displays LED bar graph indicator 0 100 % LEDs Power On, Alarm Inputs/outputs Test and reset button internal/external Cable length external test and reset button 10 m Current source for external measuring instrument DC 0 400 µa Load 12.5 kω Cable lengths for measuring current transformers Single wire 0.75 mm² 0 1 m Single wire, twisted 0.75 mm² 0 10 m Shielded cable 0.5 mm² 0 40 m Recommended cable (shielded, shield on one side connected to terminal l of the RCM470, not connected to earth) J-Y(St)Y min. 2x0.8 Switching elements Number of switching elements 1 x 2 changeover contacts Operating principle, adjustable N/C operation/n/o operation Electrical endurance, number of cycles 12000 Rated contact voltage AC 250 V/DC 300 V Making capacity AC/DC 5 A Breaking capacity 2 A, AC 230 V, cos phi = 0.4 0.2 A, DC 220 V, L/R = 0.04 s Fault memory on/off Environment/EMC EMC immunity EN 61543 EMC immunity EN 61000-6-4 Shock resistance IEC 60068-2-27 (during operation) 15 g/11 ms Bumping IEC 60068-2-29 (during transport) 40 g/6 ms Vibration resistance IEC 60068-2-6 (during operation) 1 g/10 150 Hz Vibration resistance IEC 60068-2-6 (during transport) 2 g/10 150 Hz Ambient temperature (during operation) -10 +55 C Ambient temperature (for storage) -40 +70 C Climatic class acc. to DIN IEC 60721-3-3 3K5 Connection Connection type modular terminals Connection properties rigid/flexible 0.2 40.2 2.5 mm² flexible with ferrules without/with plastic collar 0.25 2.5 mm² Conductor sizes (AWG) 24 12 Other Operating mode continuous operation Mounting any position Degree of protection, internal components (IEC 60529) IP30 Degree of protection, terminals (IEC 60529) IP30 Type of enclosure X470 Enclosure material polycarbonate Screw mounting 2 x M4 DIN rail mounting acc. to IEC 60715 Flammability class UL94V-0 Weight 350 g 4 TDB401003en/03.2010

Residual current monitor RCM470LY Ordering information Rated frequency Response delay Measuring current transformer Displays Fault memory behaviour 40 400 Hz 0 10 s W, WR, WS internal/external selectable Other supply voltages on request / * Absolute values of the operating range 1) For industrial application only / 2) For industrial and household applications Suitable system components Response Supply voltage U S range I Δn AC DC Type Art. No. 230 V RCM470LY B 9401 20172) 90 132 V* RCM470LY-13 B 9401 20192 10 ma 10 A 24 V RCM470LY-11 B 9401 20252) 9,6 84 V* RCM470LY-21 B 9401 20211) 77 286 V* RCM470LY-23 B 9401 20241) 100 ma 100 A 230 V RCM470LY-72 B 9401 20272) Type designation Inside diameter/size (mm) Displays Input Output Type Art. No. External measuring current transformers ø 20 W20 B 9808 0003 ø 35 W35 B 9808 0010 ø 60 W60 B 9808 0018 ø 120 W120 B 9808 0028 ø 210 W210 B 9808 0034 70 x 175 WR70x175 B 9808 0609 115 x 305 WR115x305 B 9808 0610 20 x 30 WS20x30 B 9808 0601 50 x 80 WS50x80 B 9808 0603 80 x 120 WS80x120 B 9808 0606 External measuring instruments 96 x 96 0 100 % 9604-4241 B 986 807 Measuring converter 0 400 µa 0 10 V 0/4 20 ma RK170 B 9804 1500 Other measuring current transformer types on request Dimension diagram X470 Dimensions in mm TDB401003en/03.2010 5

Residual current monitor RCM475LY Residual current monitor for TN and TT systems (AC and pulsating DC currents) Product description The residual current monitor RCM475LY is designed for fault and residual current monitoring in earthed power supply systems (TN and TT systems) where an alarm is to be activated in the event of a fault, but disconnection must be prevented. In addition, the device can be used to monitor single conductors, such as PE conductors, N-PE connections and PE-PAS connections. Since the values are measured with measuring current transformers, the device is nearly independent of the load current and the nominal voltage of the system. RCM475LY Device features Internal measuring current transformer ø 18 mm Response values, adjustable 10 ma 10 A 50 60 Hz Response delay, adjustable 0 10 s Alarm relay with two potential-free changeover contacts N/O or N/C operation, selectable Fault memory behaviour, selectable Combined test/reset button Connection external test and reset button LED bar graph indicator I Δn 0 100 % Connection external measuring instrument I Δn 0 100 % Sealable transparent cover External supply voltage Type A acc. to IEC/TR 60755 Approvals Application Residual current monitoring in earthed two, three or four conductor systems (TN and TT systems) Current monitoring of single conductors de-energised under normal conditions Socket-outlet circuits for devices which are operated unattended for a long time and which may not fail Alarm systems, safety devices Air conditioning systems, EDP systems Cooling equipment with valuable frozen goods Canteen kitchens Monitoring of earthed power supplies for stray currents, impact on N conductors Function Residual current monitoring takes place via an internal measuring current transformer. When the residual current respectively the current exceeds the set response value, the alarm LED lights and the alarm relay switches after the expiry of the set response delay. The fault messages can be stored. The fault memory can be reset by pressing the reset button. The device function can be tested using the test button. The currently measured value in per cent related to the set response value is indicated on the LED bar graph indicator. Standards The RCM475LY series complies with the requirements of the device standards: DIN EN 62020 (VDE 0663) und IEC 62020. 6 TDB401003en/03.2010

Residual current monitor RCM475LY Wiring diagram system connection, external connections Wiring diagram front plate 1 5 1 2 3 4 5 6 7 A B C D 8 9 10 2 3 4 E F 1 - Supply voltage US, see ordering information, 6 A fuse recommended. 2 - External measuring instrument 3 - External test and reset button "T/R" 4 - Alarm relay: switches when the fault current exceeds the response value. 5 - Internal measuring current transformer Note! Do not route the PE conductor through the measuring current transformer! 1 - Combined test/reset button "T/R": short-time pressing (< 1s) = RESET; long-time pressing (> 2s) = TEST. 2 - Power On LED "ON" 3 - Alarm LED "ALARM": lights when the fault current exceeds the response value. 4 - LED bar graph indicator: shows the measuring value in per cent related to the preset response value. 5 - Potentiometer for setting the response delay (0 1 s). 6 - Potentiometer for setting the response value (x 1 10 ma). Setting of the DIP switches (white = switch position) 7 - Operating principle of the alarm relay A - N/O operation B - N/C operation 8 - Fault memory behaviour relay + LED A - Fault memory ON B - Fault memory OFF 9 - Setting of the response range A - 10 ma B - 30 ma C - 100 ma D - 300 ma E - 500 ma F - 1000 ma x 1 10 10 - Setting of the response delay A - x 1 0 1 s B - x 10 TDB401003en/03.2010 7

Residual current monitor RCM475LY Technical data Insulation coordination acc. to IEC 60664-1 Rated insulation voltage Rated impulse withstand voltage/pollution degree Voltage ranges Supply voltage U S Operating range of U S Frequency range of US Power consumption AC 250 V 4 kv/3 see ordering information 0.85 1.1 x U S DC 50 400 Hz 3 VA Measuring circuit/response values Internal measuring current transformer ø 18 mm Load 180 Ω Operating characteristics acc. to IEC/TR 60755 Type A Rated residual operating current I Δn 10 ma 10 A Response delay t v, adjustable 0 10 s Accuracy of response delay ± 20 % Rated frequency 50 60 Hz Relative uncertainty 0-20 % of the response value Hysteresis approx. 25% of the response value Response time t an at IΔn = 1 x IΔn (tv = 0 s) < 250 ms Response time t an at IΔn = 5 x IΔn (tv = 0 s) 20 ms Number of measuring channels 1 Displays LED bar graph indicator 0 100 % LEDs Power On, Alarm Inputs/outputs Test and reset button, potential free Maximum cable length for external measuring instrument Current source for external measuring isntrument/max. load internal/external 10 m DC 0 400 µa/12.5 kω Switching elements Number of switching elements 1 x 2 changeover contacts Operating principle, adjustable N/C operation/n/o operation Electrical endurance, number of cycles 12000 Rated contact voltage AC 250 V/DC 300 V Making capacity AC/DC 5 A Breaking capacity 2 A, AC 230 V, cos phi = 0.4 0.2 A, DC 220 V, L/R = 0.04 s Fault memory on/off Environment/EMC EMC immunity EN 61543 EMC immunity EN 61000-6-4 Shock resistance IEC 60068-2-27 (during operation) 15 g/11 ms Bumping IEC 60068-2-29 (during transport) 40 g/6 ms Vibration resistance IEC 60068-2-6 (during operation) 1 g/10 150 Hz Vibration resistance IEC 60068-2-6 (during transport) 2 g/10 150 Hz Ambient temperature, during operation -10 +55 C Ambient temperature for storage -40 +70 C Climatic class acc. to DIN IEC 60721-3-3 3K5 Connection Connection type modular terminals Connection properties rigid/flexible 0.2 4/0.2 2.5 mm² flexible with ferrules without/with plastic collar 0.25 2.5 mm² Conductor sizes (AWG) 24 12 Other Operating mode continuous operation Mounting any position Degree of protection, internal components (IEC 60529) IP30 Degree of protection, terminals (IEC 60529) IP30 Type of enclosure X475 Enclosure material polycarbonate Screw mounting 2 x M4 DIN rail mounting acc. to IEC 60715 Installation into standard distribution panels acc. to DIN 43871 Flammability class UL94V-0 Weight 350 g 8 TDB401003en/03.2010

Residual current monitor RCM475LY Ordering information Measuring current Rated Time Fault memory Response Supply voltage U S transformer Displays frequency delay behaviour range I inside diameter Δn AC DC Type Art. N0. 230 V RCM475LY B 9401 2018 50 60 Hz 0 10 s ø 18 mm internal/external selectable 10 ma 10 A 90 132 V* RCM475LY-13 B 9401 2035 77 286 V* RCM475LY-23** B 9401 2069 Other supply voltages on request / * Absolute values of the operating range / ** no GL approval Suitable system components Type designation Size (mm) Displays Input Output Type Art. No. External measuring instruments 96 x 96 0 100 % 9604-4241 B 986 807 Measuring converter 0 400 µa 0 10 V 0/4 20 ma RK170 B 9804 1500 Other measuring current transformer types on request Dimension diagram X470 Dimensions in mm TDB401003en/03.2010 9

Bender GmbH & Co. KG P.O. Box 1161 35301 Gruenberg Germany Londorfer Strasse 65 35305 Gruenberg Germany Tel.: +49 6401 807-0 Fax: +49 6401 807-259 E-Mail: info@bender.de www.bender.de BENDER Group TDB401003en / 03.2010 / pdf / Schw / Bender GmbH & Co. KG, Germany Subject to change! The specified standards take into account the version that was valid at the time of printing.