FDM221, FDM223, FDM224, FDM223H, FDM224H Manual call points

Similar documents
FDCL221 Line separator

Manual call points. Sinteso / Cerberus PRO FDM225, FDM226

Manual call point. Sinteso Cerberus PRO FDM223H, FDM224H. 'Heavy Duty' manual call point addressed (FDnet/C-NET)

FDM273 Radio manual call point Mounting

DM1101 / DM1103 / DM1104 DM1103-L / DM1103-S Manual call points Manual release button and emergency stop button

XC1003-A Extinguishing control unit

DM1131 / DM1133 / DM1134 Manual call points

FDCL221-M Multi line separator module

Input module, input/output modules

FDCI221, FDCIO221 Input module, input/output module Technical Manual

FDCW241 Radio gateway Mounting

FDCW221 / DOW1171 / SMF121 SMF6120 (repair/replacement) Radio fire detection system

Radio fire detection system

DM1153H-Ex / DM1154H-Ex Manual call point 'Heavy Duty'-Ex

FP120-Z1 Power supply kit A (70 W) Technical Manual

Multi line separator module

FDS229-R / FDS229-A Alarm sounder with supplementary optical indication

FDL241-9 Linear smoke detector Mounting Commissioning

Input module, input/output module

FDCIO223 (ES 45) Transponder

SWING radio fire detection system

ASA linear smoke detector

Output module (230 V)

FDOOT221, FDO221, FDT221

Siemens aspirating smoke detector (ASD) for the addressed FDnet/C-NET detector line or for standalone operation

OH720, OP720, HI720, HI722 Automatic fire detectors Technical Manual

FDOOT241-9, FDOOT241-A, FDO241, FDT241

OOH740, OOHC740. Cerberus PRO. Automatic fire detectors

FDBZ290 Air sampling smoke detection kit Technical Manual

FC330A-ECO Auto-addressing analogue 1-Loop fire detection panel

DBS721, DBS729 Sounder interbase, Sounder beacon interbase

FDOOT241-A9-Ex Multisensor fire detector

Synova TM product catalog.

OH720, OP720, HI720, HI722

FT2010 Floor repeater terminal Operation Manual

Fire control panels FC360

DB110xA, DB1131A, SO620A, DB1151A Detector bases and accessories

FT2011 Floor repeater display Operation Manual

OOH740-A9-Ex Multisensor fire detector

Building Technologies. FDUL221 en Line tester operating instructions for electricians

Installation instructions. For the heating engineer. Installation instructions. timeswitch VTS 160 GB, IE

FDOOT241-A3, FDOOT241-A4, FDOOT241-A5, FDOOT241-A9, FDOOT241-8

OOH740, OOHC740 Automatic fire detectors

FDS229 Alarm sounder with supplementary optical indication Technical Manual

OOH740-A9-Ex Multi-sensor fire detector

Interbases. Sinteso FDSB221, FDSB228, FDSB229

MK8000 OPC Server Interface Specification for CS1115 Building Technologies

FD20 Sinteso Detector system

13 tones to choose from, 2 programmable alarm levels Adjustable sound levels up to 93 dba

FDOOT221, FDOOT241-A3, FDOOT241-A4, FDOOT241-8, FDOOT241-9, FDOOT241-A9, FDO241, FDO221, FDT241, FDT221 Automatic fire detectors Technical Manual

DT1101A / DT1102A / DO110xA Automatic fire detectors

FDF Sinteso Cerberus PRO Cerberus FIT. Flame detector. Flame detector addressed or collective, ASAtechnology TM

2CKA001473B System Manual Busch-Infoline. Handicapped toilet signal set 1510 UC

FC330A-ECO1 Auto-addressing analogue 1-Loop fire detection panel

Thermal Reset Limit Thermostats Electromechanical TW according to DIN EN 14597

DC1192 Input /Output module

QAF63.2-J QAF63.6-J. Frost detectors. for use on the air side

Instructions for the heat exchanger control system SILVER C RX, RECOnomic, sizes 100/120, RECOsorptic, sizes

DC1154 / DC1154-AA / DC1156-AA / DC1157-AA Input / Output modules

Instruction Manual. Alarm Unit For Low Gas Level # Read manual before use! Observe all safety information! Keep manual for future use!

Frost Protection Thermostat

FDL241-9 Linear smoke detector Technical Manual

AM1 alarm module. RESOL AM1 alarm module * * Mounting Connection Function. Manual

Mimic display driver, LED ribbon cable

Fire control panels FC726 FC726-XA

Test units and accessories

Flameproof Manual Call Points

Operating instructions Safety-monitoring module SRB 302X3. 1 About this document

Accessories for SMA Inverters Fan Retrofit Kit FANKIT02-10

Instructions for the fan motor control system, SILVER C

Original operating instructions Safety switch with guard locking AC901S AC902S

SCHMIDT LED Measured Value Display MD Instructions for Use

3-way switching valve

Operating instructions Safety-monitoring module SRB 302X3. 1. About this document. Content

Duct Temperature Sensors

SMART EVO 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS

FT2080 Fire terminal (Touch) Mounting Installation

Room thermostat with 24-hour time switch and large LCD

FDCL221-Ex Line adapter (Ex)

FT2080 Fire terminal (Touch) Mounting Installation

CoMo-Control. Operating Manual. English (translation of original instructions) Documentation no.: a

1592P01. for liquids in piping DN

GMA Panels with double busbar

MANUAL Oil Level Sensor

FDA241, FDA221 Aspirating Smoke Detector Technical Manual

Operating instructions V-ZUG-Home

HR 601 C A AUS. ENGLISH Instructions for use Page 2

Thank you for buying a DEVI product. With this purchase you have obtained a product of the highest quality, designed to give long lasting comfort at

DOW1171 / DCW1151 Radio fire detection system

SERVICE-MANUAL INDUCTION COOKER BASE-LINE/FAJITA HEATER SH/BA 3500 FH

FC724 Fire control panel

Test units and accessories

XC10 Extinguishing control panels

FC724 Fire control panel

FDA241, FDA221 Siemens ASD

Installation instructions. For the competent person. Installation instructions VRT 350 VRT 350 GB, IE

VR 90 Remote control unit

FDA241, FDA221 Siemens ASD

FC722 Fire control panel

Semi flush-mount room thermostats

Transcription:

FDM221, FDM223, FDM224, FDM223H, FDM224H Manual call points Technical manual Building Technologies Fire Safety & Security Products

Liefermöglichkeiten und technische Änderungen vorbehalten. Data and design subject to change without notice. / Supply subject to availability. Sous réserve de modifications techniques et de la disponibilité. Siemens Switzerland Ltd 2004-2007 We reserve all rights in this document and in the subject thereof. By acceptance of the document the recipient acknowledges these rights and undertakes not to publish the document nor the subject thereof in full or in part, nor to make them available to any third party without our prior express written authorization, nor to use it for any purpose other than for which it was delivered to him. We reserve all rights in this document and in the subject thereof. By acceptance of the document the recipient acknowledges these rights and undertakes not to publish the document nor the subject thereof in full or in part, nor to make them available to any third party without our prior express written authorization, nor to use it for any purpose other than for which it was delivered to him. Nous nous réservons tous les droits sur ce document, ainsi que sur l'objet y figurant. La partie recevant ce document reconnaît ces droits et elle s'engage à ne pas le rendre accessible à des tiers, même partiellement, sans notre autorisation écrite préalable et à ne pas l'employer à des fins autres que celles pour lesquelles il lui a été remis.

1 About this document...5 2 Safety notes...7 2.1 Signal words and symbols...7 2.1.1 Classification and meaning of signal words...7 2.1.2 Symbols and their meaning...7 2.1.3 Classification and meaning of additional symbols...7 2.2 Safety-relevant working instructions...8 3 Overview...9 4 Setup and function...10 4.1 Manual call point FDM221...10 4.2 Manual call point FDM223...11 4.3 Manual call point FDM224...12 4.4 Diagnosis levels...13 4.5 Accessories...14 5 Project planning...15 6 Installation...16 6.1 Preparation...16 6.2 Installation...17 6.2.1 Fixation...17 6.2.2 Inserting the protective cover...18 6.2.3 Electric connection...19 7 Commissioning...21 7.1 Localization and device test...21 7.2 Performance check...21 8 Maintenance / Troubleshooting...23 8.1 Status retrieval...23 8.2 General maintenance work...23 8.3 Resetting...23 8.4 Replacing the glass pane...25 8.5 Spare parts...27 9 Specifications...28 9.1 Technical data...28 9.2 Dimensional drawings...30 9.2.1 Dimensions...30 9.2.2 Master gauge for recesses...30 9.3 Environmental compatibility...30 3 Building Technologies

4 Siemens Building Technologies Fire & Security Products 11.2007

0BAbout this document 1 About this document Purpose of the document This document contains all information on the manual call points FDM221, FDM223 and FDM224. The consistent observance of the instructions ensures a trouble-free and safe application. Target group This documentation and the instructions contained therein are intended for the following groups of persons, who perform tasks and have the necessary qualification: Group of persons Activity Qualification Product Manager (PM) He is in charge of local product management and is responsible for the interchange of information between the plant supplying the equipment and his DU for his product line. He co-ordinates the flow of information between the individual groups of people for the various projects. Project Manager Project Engineer Installation personnel Maintenance Personnel The project manager is responsible for the local project management. He co-ordinates the schedules of all groups of people working on a project as well as resources. He also continuously obtains the technical information required for project realization. Provides the parameterization of products, devices and systems in the DU for a specific country or customer. He monitors the serviceability of and gives the go-ahead for the commissioning of products, devices and systems at the place of installation. They are also responsible for trouble-shooting. They install product, device or system components on site, and subsequently carry out a general performance check. They carry out all the maintenance work indicated in the product documentation and check equipment for total serviceability. He has had training appropriate to his function and product range and has attended the product manager training course. He has had the technical training appropriate to his function and the size of a project or the product line used in the project and has attended the training courses for project managers at the supplier's works. He has had the training appropriate to his function and to the products, devices and systems to be parameterized and has attended the technical training courses for project engineers at the supply plant. Professional training in the field of building automation or electrical installations. They have had the technical training appropriate to their function and the product. Reference documents Number Name 007904 Installation for FDM221, always enclosed with the detector 007905 Installation for FDM223 and 224, always enclosed with the detector Operational and safety regulations Before groups of persons begin work on the system they must have read and understood the related documents, in particular Chapter "Safety regulations".2 5

0BAbout this document Disregard of the safety regulations Before they are delivered, products are tested to ensure they function correctly when used properly. Siemens disclaims all liability for damage or injuries caused by the incorrect application of the instructions or disregard of warnings of danger contained in the documentation. This applies in particular to: Personal injuries or damage caused by improper use and incorrect use; Personal injuries or damage caused by disregarding safety instructions in the documentation or on the product; Personal injuries or damage caused by poor maintenance or a lack of maintenance. Symbols and their meaning => Result, note 'Text' Quotation, reproduced identically -> see Cross reference Technical terms Term FDnet MC-Link Explanation Addressed detector line Maintenance and Commissioning Link Document identification Position Title page Last page bottom left Last page bottom left Signification System names: e.g. CS1140 System Product type: e.g. compact control unit CI1145 Purpose of the document: e.g. assembly, installation Document number Edition date Manual Register Modification index Version Date Brief description 007002_e_en_-- 11.2007 FDMH292/3-x IP64 -> IP65 007002_d_en_-- 09.2007 Standards added Diagnosis levels changed 007002_c_en_-- 07.2007 'Technical terms' added Corrections in 'Technical data': - Line separator added - Protection categories IP changed - Standard EN54-17 added - VdS and LPCB approvals added 007002_b_en_-- 09.2006 FDM224 included Diagnosis levels added 007002_a_en_-- 01.2004 First edition 6

2 Safety notes 1BSafety notes 2.1 Signal words and symbols This chapter describes the danger levels and the relevant safety regulations applicable for the use of the products from Siemens Building Technologies. Please read the work instructions as well as the chapter About this document before beginning any work. 2.1.1 Classification and meaning of signal words The danger level that is, the severity and probability of danger is indicated by the signal words listed below. Non-observance may lead to the consequences indicated: DANGER! WARNING! CAUTION! NOTE! Imminent danger! May cause danger to life or serious bodily injury! Dangerous situation! May cause serious bodily harm. May cause dangerous situations! May cause light injuries! Possibly harmful situation! May cause damage to the product or to objects in the immediate vicinity of the product! 2.1.2 Symbols and their meaning The symbols listed below indicate the nature and origin of the danger. General danger Electrical voltage Example for an indication of danger The example below illustrates the appearance and form of danger warnings in our documents. DANGER! External voltage Disconnect the module from the power supply. 2.1.3 Classification and meaning of additional symbols Tips and information. Refers to extremely important or critical decisions to be taken into account before continuing the work. 7

1BSafety notes 2.2 Safety-relevant working instructions Country-specific standards The products are developed and produced in compliance with the relevant international and European safety standards. Should additional country-specific, local safety standards or regulations concerning project planning, installation, operation and disposal of the product apply in the place of operation, then these standards or regulations must also be taken into account in addition to the safety regulations mentioned in the product documentation. Electrical installations DANGER! Work on electrical installations Work on electrical installations may only be carried out by qualified electricians or by instructed persons working under the guidance and supervision of a qualified electrician, in accordance with the electroctechnical regulations. Assembly, installation, commissioning and inspection work If any tools or accessories such as ladders are required, safe and suitable devices must be used. The activation of fire control installations for test purposes must not cause damage to the system or parts thereof. Fire control installations must only be activated after the test has been completed and the system has been definitely handed over to the customer. Third party systems or devices must only be activated in the presence of the responsible person. Modifications to the system design and the products Modifications to a system or to individual products may cause faults or malfunctioning. Please request written approval from us and the relevant authorities concerning in-tended system modifications and system extensions. Modules and spare parts Locally procured modules and spare parts must comply with the technical specifica-tions laid down by the manufacturer. This compliance is always ensured for original spare parts supplied by us. 8

3 Overview 2BOverview Manual call point FDM221 Housing FDMH291-x Manual call point FDM223 Housing FDMH293-x Manual call point FDM224 Housing FDMH293-x The manual call points consist of a housing and a call point unit. They have the following features: Individual call point addressing Indication of the condition (Alarm, localization or test) by means of a dichromatic LED Integrated line separation function Communication via FDnet 9

3BSetup and function 4 Setup and function 4.1 Manual call point FDM221 The manual call point FDM221 triggers alarm when the glass pane is pushed in (direct operation). The alarm is immediately transmitted to the control panel. 1 2 3 7 8 4 6 5 Legend 1 Housing bottom 2 LED 3 Switching unit 4 Terminals 5 Switching lever for test activation 6 Key with double function: Function test and opening housing 7 Alarm actuator (hammer) 8 Glass 10

4.2 Manual call point FDM223 3BSetup and function The manual call point FDM223 triggers alarm when the glass pane is pushed in and the alarm button is pressed (indirect operation). The alarm is immediately transmitted to the control panel. 1 3 4 2 5 6 7 Legend 1 Housing bottom 2 Switching unit 3 Terminals 4 Stopping lever 5 Alarm button 6 LED 7 Glass 11

3BSetup and function 4.3 Manual call point FDM224 The manual call point FDM224 triggers alarm when the glass pane is pushed in (direct operation). The alarm is immediately transmitted to the control panel. To reset the manual call point FDM224 after an alarm, a new glass pane must be inserted. 1 2 3 6 5 4 Legend 1 Housing bottom 2 Switching unit 3 Terminals 4 Glass 5 LED 6 Alarm button 12

4.4 Diagnosis levels 3BSetup and function The detector largely auto-monitors its function. The following diagnosis levels are derived from the different control measurings: Normal Exchange required Fault Details see table below. When a fatal error occurs, which makes the proper function of the detector impossible, a fault message is signalled. To remedy the cause, additional information is available in the detector. This information may be displayed by e.g. the detector exchanger and tester FDUD29x (details see Operation Detector exchanger and tester, doc. nos. 007227 and 009718). Indication on the detector exchanger and tester 'No Deviation' 'needed excha.' * Any fault message Signification Normal, no fault is present The detector is fully functional Exchange required Button monitoring outside the tolerance Fault is present Alarming is no longer ensured Button monitoring outside the tolerance or impaired by extraneous influences Supply error Software error (Watchdog error) Storage error Communication error between detector and control panel Actions none Replace detector Replace detector Check detector line voltage Replace detector Replace detector Replace detector Remedy cause Note The status 'Any fault message' can be displayed together with another status, e.g. 'needed excha.' (exchange required). * Indication on the detector exchanger and tester always in English; no translation into the country-specific language. 13

3BSetup and function 4.5 Accessories Module Designation Application DMZ1197-AD Sealing For zones where there is danger of spray water. Note: Thanks to the additional seal, which is placed over the call point unit, the manual call points FDM223H and FDM224H are in compliance with protection category IP65. DMZ1197-AC Protective cover Protection against unintended alarm activation with FDM223 and FDM224 FDMC291 Protective cover Protection against unintended alarm activation with FDM221 Cable gripper Cable gripper with 2 cable entries max. cable diameter 7.8 mm for FDM223 or FDM224 14

5 Project planning 4BProject planning Compatibility Compatible with all control panel types that support the FDnet detector line. Refer to 'List of compatibility' (doc. no. 008331) for details. Range of application The manual call points are intended for use in places where a fire can be detected by people who can manually trigger an alarm. Place of installation The manual call points must be installed in easily accessible places at a height of 1.3 1.6 m. Environmental influences If the manual call points are used in industry, this must be precisely clarified with the person responsible for the project, since plastics cannot withstand some environmental conditions. The following factors must be taken into account: Chemicals Temperature Moisture 15

5BInstallation 6 Installation 6.1 Preparation Depending on the cabling (recessed or surface cabling), the housing must be prepared for inserting the cables. FDM221 1. Break out the key from the housing cover. 2. Press the two key knobs into the recesses (see figure below). 3. Pull the lid forwards. Keep the key in a safe place. 4. Determine the entry opening(s) in the housing: Recess cabling: Breakout point at the back of the housing base Surface cabling: Markings on the top and bottom of the housing for the drill hole(s), with a diameter of max. 25 mm 5. Clamp the housing in a bench vice. 6. Drill the entry opening(s). Danger of injury Observe the tool manufacturer's safety notes! FDM223/FDM224 1. Pull the cover of the keyhole to the right. 2. Open the housing with the key enclosed in the delivery. Keep the key in a safe place. 3. Determine the entry openings in the housing and break them out from the bottom, top or rear panel. 16

5BInstallation 6.2 Installation 6.2.1 Fixation FDM221 1. Install the housing at a height of 1.3 1.6 m on an even surface. 2. Pull the cables through the entry opening(s) into the housing. 3. For surface mounting, use screwed cable glands (max. M20 with nut). FDM223/FDM224 1. Install the housing at a height of 1.3 1.6 m on an even surface. In wet areas, only use the screw holes marked by arrows (see figure below). 2. Pull the cables through the entry opening into the housing. 3. For surface mounting, use screwed cable glands (max. M20). 17

5BInstallation 6.2.2 Inserting the protective cover When a protective cover is used, proceed as follows: 1. Open the housing. 2. Place the protective cover (1) in the lid (2) (see figure below). 3. Close the housing (3) with the lid (2). FDM221 1 2 3 FDM223/FDM224 3 2 1 18

5BInstallation 6.2.3 Electric connection Notes on work on electrical installations Caution Consider the positive and negative poles! As long as a manual call point is out of service, it must be provided with a note "OUT OF SERVICE! Only one wire may be connected to each terminal point; only this way is it possible to guarantee a faultless connection over the complete life cycle. FDM221 Connection diagrams FDM223/FDM224 FDnet FDnet FDnet FDnet + + FDM221 1. Connect the feeding line to the terminals in the call point unit (1), in accordance with the connection diagram. 2. When inserting the call point unit (1) into the housing (2), pay attention to the feeding line. 3. Place the call point unit (1) with the inscription TOP pointing to the top (terminals on the right) into the housing (2) until the locking device snaps in. 4. Close the housing (2) with the lid (3). 3 1 2 19

5BInstallation FDM223/FDM224 1. Connect the feeding line to the terminals in the call point unit (1), in accordance with the connection diagram. 2. When inserting the call point unit (1) into the housing (2), pay attention to the feeding line. 3. Place the call point unit (1) into the housing (2) with the terminals pointing upwards; then fix it with two screws. 4. In wet zones, use a seal (3) (DMZ1197-AD). 5. Close the housing (2) with the lid (4). 4 3 2 1 20

6BCommissioning 7 Commissioning 7.1 Localization and device test The manual call points are equipped with an internal alarm indicator. This alarm indicator may as well be activated from the control panel for localization and device testing. The table shows the LED indication for the different control panel commands. Command Device test Localization LED indication green, flashing red, flashing 7.2 Performance check FDM221 1. Set the detector line to Test. 2. Insert the key from below into the housing. The glass pane falls down, actuating the switch. The LED flashes. 3. Pull off the key. The glass is pushed back into its initial position and the detector is again ready for operation. 4. Set the detector line back to normal operation. FDM223 1. Set the detector line to Test. 2. Pull the cover of the keyhole to the right. 3. Open the door with the key. 4. Push the button. The alarm signal is transmitted. 5. Set the detector in operational availability again. 6. Close the door of the detector. 7. Set the detector line back to normal operation. 21

6BCommissioning FDM224 1. Set the detector line to Test. 2. Pull the cover of the keyhole to the right. 3. Open the door with the key. The alarm signal is transmitted. 4. Close the door of the detector. The detector is ready for operation again. 5. Set the detector line back to normal operation. 22

8 Maintenance / Troubleshooting 7BMaintenance / Troubleshooting 8.1 Status retrieval The manual call points are provided with an MC-Link. With this link, proximity exchange of data is possible over short distances between the manual call point and the detector exchanger and tester. The following actions can be performed from the control panel: Commissioning Read error list / status register 8.2 General maintenance work The following maintenance work must be performed on an annual basis: Check all detectors for mechanical damage. Replace defective detectors.carry out a performance check. 8.3 Resetting After alarm activation the manual call point must be set in operational availability again. This procedure is different for each of the two detector types. FDM221 To set the detector back to operational availability, proceed as follows: 1. Open the housing. 2. Remove the glass pane. 3. Insert a new glass pane. 4. Close the housing. 5. Carry out a performance check. 1 23

7BMaintenance / Troubleshooting FDM223 To set the detector back to operational availability, proceed as follows: 1. Open the housing. 2. Remove the glass pane. 3. Insert a new glass pane. 4. Push the black locking lever (2) in the upper right corner to the right until you hear it clicking. The alarm button is now protruding by approx. 5 mm. 5. Close the housing. 6. Carry out a performance check. 2 FDM224 To set the detector back to operational availability, proceed as follows: 1. Open the housing. 2. Remove the glass pane. 3. Insert a new glass pane. 4. Close the housing. 5. Carry out a performance check. 24

7BMaintenance / Troubleshooting 8.4 Replacing the glass pane FDM221 The glass pane is provided with a number. It is covered by a foil layer. This foil holds the glass splinters together when the glass pane is pushed in, enabling trouble-free removal of the glass. Proceed as follows: 1. Press the two key knobs in the recesses. 2. Pull the lid forwards. 3. Insert the glass pane so that the number is pointing to the bottom and can be read from the front. 4. Insert the glass on the guiding (1) and push it towards the alarm actuator (2). 5. Push the retainer (3) to the right until the glass is below the retainer. 6. Close the housing with the lid. 1 2 1 3 25

7BMaintenance / Troubleshooting FDM223/FDM224 The glass pane is square-shaped and can be inserted in any direction. Proceed as follows: 1. Pull the cover of the keyhole to the right. 2. Open the housing with the key enclosed in the delivery. Keep the key in a safe place. 3. Push the retainer (1) to the right. 4. Place the glass pane on the guiding (2) and below the retainer (1). 5. Release the retainer. 6. Set the detector in operational availability by resetting it. 7. Close the door. 2 1 26

8.5 Spare parts 7BMaintenance / Troubleshooting Designation FDM221 FDM223/FDM224 Application Cover with key FDMK291 To open the housing and for the performance check of FDM221. Key DMZ1195 Glass pane FDMG291 DMZ1196-AC A part of the actuation mechanism, protects the switch from soiling. 27

8BSpecifications 9 Specifications 9.1 Technical data Detector line Operating voltage 12 33 VDC Operating current (quiescent) 200 μa Maximum current connection factor 1 Quiescent current connection factor 1 Address connection factor 1 Separator connector factor 1 Protocol FDnet System compatibility see doc. no. 008331 'List of compatibility'. Line separator Line voltage: nominal minimum maximum Voltage at which the separator opens: minimum maximum Permanent current when switches are closed Switching current (e.g. in case of short circuit) Leakage current when switches are open Serial impedance when switches are closed 32 VDC (= V nom ) 12 VDC (= V min ) 33 VDC (= V max ) 7.5 VDC (= V SO min ) 10.5 VDC (= V SO max ) max. 0.5 A (= I C max ) max. 1 A (= I S max ) max. 1 ma (= I L max ) max. 0.5 Ω (= Z C max ) External alarm indicator connectable ext. AI 2 (only with FDM223 and FDM224) Electric current 9 15 ma Voltage 10 17 VDC Length of line max. 30 m with unshielded cables, or when the shielding is connected to the detector's positive pole max. 5 m, if the shielding is connected with the earth Connections Detector line and ext. AI Design Conductor cross-section MC-Link Spring clips 0.2 1.5 mm² proximity interface 28

8BSpecifications Ambient conditions Operating temperature -25 +70 C Storage temperature -30 +75 C Air humidity 95 % rel. Protection category EN60529/IEC529: FDM221, housing FDMH291-x FDM223/FDM224, housing FDMH293-x without sealing DMZ1197-AD FDM223/FDM224 housing FDMH293-x with sealing DMZ1197-AD FDM223H/FDM224H, housing FDMH292-x without sealing DMZ1197-AD FDM223H/FDM224H housing FDMH292-x with sealing DMZ1197-AD Electromagnetic compatibility at: 1 MHz 1 GHz 1 GHz 2 GHz IP44 IP44 IP65 IP44 IP65 50 V/m 30 V/m Mechanical data Dimensions (W x D x H) FDM221 FDM223/FDM224 Housing material: FDM221 FDM223/FDM224 Colours: FDMxxx-R FDMxxx-B FDMxxx-Y FDMxxx-G 87 x 87 x 47 mm 134 x 139 x 43 mm ABS PC red (RAL 3000) blue (RAL 5005); House alarm yellow (RAL 1023); Extinguishing green (RAL 6024); Control Standards Standards: FDM221 FDM223 FDM223H FDM224 FDM224H VdS approvals: FDM221 FDM223 FDM223H FDM224 FDM224H LPCB approvals: FDM221 FDM223 FDM223H EN54-11, CEA GEI-052: Draft 2.0, 11/06/97 EN54-11, CEA GEI-052: Draft 2.0, 11/06/97 EN54-11, CEA GEI-052: Draft 2.0, 11/06/97 EN54-11, EN54-17 EN54-11, EN54-17 G203059 G204002 G205014 G206123 G206124 126ac/01 126ac/02 126ac/03 Protection categories IEC 60529 QS standards Siemens Standard SN 36350 ISO9001 ISO9004 CE conformity mark yes 29

8BSpecifications 9.2 Dimensional drawings 9.2.1 Dimensions FDM221, housing FDMH291-x FDM223/FDM224, housing FDMH293-x 9.2.2 Master gauge for recesses FDM221, housing FDMH291-x FDM223/FDM224, housing FDMH293-x 9.3 Environmental compatibility Electronic components and synthetic materials can be separated. The synthetic material parts are identified and can be disposed of accordingly. 30

8BSpecifications 31

Siemens Switzerland Ltd Siemens Switzerland Ltd 2004-2007 Building Technologies Group Data and design subject to change without notice. International Headquarters Supply subject to availability. Gubelstrasse 22 CH-6301 Zug Tel. +41 41-724 24 24 Fax +41 41-724 35 22 www.siemens.com/buildingtechnologies Document no. 007002_e_en_-- Manual FD20 Edition 11.2007 Section 4