Design and Development of Combined Direct and Indirect Evaporative Cooling System

Similar documents
Effect of Operating Parameters on the Performance of Direct Evaporative Cooler

INTERNATIONAL JOURNAL OF APPLIED ENGINEERING RESEARCH, DINDIGUL Volume 1, No 4, 2011

PERFORMANCE EVALUATION OF TWO STAGE AIR COOLER IN DIFFERENT SPEED

EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER

Theoretical Performance Analysis Of Direct Evaporative Cooler In Hot And Dry Climates

Two Stage Indirect/Direct Evaporative Cooling

A Review on Potential of Indirect Evaporative Cooling System

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance

Keywords : Evaporative cooling, Saturation efficiency, Cooling capacity, Cooling pad, Cellulose, Aspen, Coconut coir. IJSER

PERFORMANCE IMPROVEMENT OF SPLIT AIR CONDITIONER USING EVAPORATIVE COOLING METHOD IN THE CLIMATIC CONDITION OF GUWAHATI, ASSAM

Scientific Principals and Analytical Model. Charcoal Cooler. Lisa Crofoot MECH 425, Queens University

Modified Air Cooler with Split Cooling Unit

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22

Air Conditioning System with Modified Condenser Ducts and Evaporative Cooling

Reducing energy consumption of airconditioning systems in moderate climates by applying indirect evaporative cooling

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Numerical Simulation of Window Air Conditioner

A Review on Analysis of Vapour Compression Refrigeration System Using Matrix Heat Exchanger

Performance Optimization of the Evaporative Condenser Design

SIDDHARTH GROUP OF INSTITUTIONS :: PUTTUR Siddharth Nagar, Narayanavanam Road AUTONOMOUS QUESTION BANK (DESCRIPTIVE) UNIT I

A review on Efficient Technique of Air-Conditioning Rajesh Kumar, Pravesh Mishra, Ram Raja

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec REFRIGERATION & AIR-CONDITIONING (Mechanical Engineering)

Review on Waste Heat Recovery Techniques in Air Conditioning Application

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Enhancement of COP in Vapour Compression Refrigeration System

AN ENVIRONMENT FRIENDLY COOLING OPTION

Analysis of Evaporative Cooler and Tube in Tube Heat Exchanger in Intercooling of Gas Turbine

CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

A Generalized Correlation for Pressure Drop of Refrigerant R-134a through Helical Capillary Tubes

Hot Water Making Potential Using of a Conventional Air- Conditioner as an Air-Water Heat Pump

Performance investigation of Air-conditioning system using ejector as expansion device

ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY

Energy Consumption Reduction of AHU using Heat Pipe as Dehumidifier

UNIT 1 AIR CONDITIONING 1. Write the various psychometric processes? Explain any four processes with neat sketches?

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

ENERGY SAVING IN A DOMESTIC SPLIT-TYPE AIR CONDITIONER WITH EVAPORATIVE COOLING SYSTEMS

Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System

Performance Analysis of Domestic Refrigeration System with Thermoelectric Module

Enhancement of COP using Nanoadditives in Domestic Refrigerator

Experimental Study of Direct Contact Condensation of Steam on Water Droplets

Dynamic performance of a novel dew point air conditioning for the UK buildings

Performance analysis of ejector refrigeration system with environment friendly refrigerant driven by exhaust emission of automobile

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System

Pressure drop analysis of evaporator using refrigerants R-22, R-404A and R-407C

ABSTRACT I. INTRODUCTION

Comparative Study of Transcritical CO 2 Cycle with and Without Suction Line Heat Exchanger at High Ambienttemperature

Performance Study of Triple Concentric Pipe Heat Exchanger

Theoretical Performance Analysis of a Liquid Desiccant Air- Conditioning System for Air Heating and Cooling

Performance Evaluation of Evaporated Water In Cooling Towers

II. OBJECTIVE OF RESEARCH

R07. Answer any FIVE Questions All Questions carry equal marks *****

EXPERIMENTAL INVESTIGATION OF WATER COOLER SYSTEM BY USING ECO-FRIENDLY REFRIGERANT (R-134a)

Shortcut Model for Predicting Refrigeration Cycle Performance

International Journal of Scientific & Engineering Research, Volume 5, Issue 7, July-2014 ISSN

Investigation of an evaporative air cooler using solar energy under Algerian climate

Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area

Available online Journal of Scientific and Engineering Research, 2018, 5(11): Research Article

HEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1

Scholars Research Library

PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS

EXPERIMENTAL STUDY OF CENTRIFUGAL HUMIDIFIER FITTED IN AN INDUSTRIAL SHED LOCATED IN TROPICAL CLIMATES

COMPARING AIR COOLER RATINGS PART 1: Not All Rating Methods are Created Equal

Experimental Investigations of Different Types of Condensers on the Performance of Household Refrigerators

Vapour Compression-Absorption Cascade Refrigeration System- Thermodynamic Analysis

Performance analysis of a vapour compression refrigeration system with a diffuser for theeco-friendly refrigerants R-134a, R-600a and R-152a

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants

Review of Energy Efficient Cooling Techniques Based on Various Evaporative Cooling Systems

Experimental Investigation of Elliptical Tube Bank Cross Flow Heat Exchanger with Inline Arrangement & 45 Angle of Attack

COMPARATIVE ANALYSIS OF SINGLE AND DOUBLE EFFECT LiBr-WATER ABSORPTION SYSTEM


Thermodynamic analysis of air cycle refrigeration system for Chinese train air conditioning

Improving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants R134a and R600a

USE OF DOE-2 TO EVALUATE EVAPORATIVE COOLING IN TEXAS CORRECTIONAL FACILITIES

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

Scientific Journal Impact Factor: (ISRA), Impact Factor: Methodology. [Yadav, 3(9): September, 2014] ISSN:

Oxyvap Evaporative Cooling Applications

s. Properties for R134a are as follows : Saturated R-134a Superheated R-134a

PERFORMANCE OF VCRS SYSTEM WITH HEAT EXCHANGER AND PHASE CHANGE MATERIAL

Dhulapally, Secunderabad Subject: REFRIGERATION AND AIR CONDITIONING QUESTION BANK

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

"COP Enhancement Of Domestic Refrigerator By Sub cooling And Superheating Using Shell &Tube Type Heat Exchanger"

DESIGN AND FABRICATION OF AN EVAPORATIVE COOLING SYSTEM. Md. Rakibuzzaman 1,* and M. A. Wazed 2. Chittagong-4349, Bangladesh 1,*

Design, Development and Experimental Investigation of Volumetric Air Receiver

3. (a) Explain the working of a rotary screw compressor. [10] (b) How the capacity control is achieved in refrigerant compressor?

Design and development of vapor absorption refrigeration system for rural dwellers. Adekeye, T. Oyedepo, S.O and Oyebanji, J.A

Chapter 14, Problem 27.

Regenerator Design for Open Cycle Liquid Desiccant Systems Theoretical and Experimental Investigations

Seyedeh Sepideh Ghaffari 1 & Seyed Ali Jazayeri 2

ICMIEE-PI Design and Construction of a portable air cooler

Heat Transfer Enhancement using Herringbone wavy & Smooth Wavy fin Heat Exchanger for Hydraulic Oil Cooling

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

Green Practices Of Air Conditioning For Major Capital Cities Of India Using Advanced Evaporative Cooling

Waste Heat Utilization of Vapor Compression Cycle for Operation of Vapor Absorption System

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

EXPERIMENTAL INVESTIGATION OF DIRECT EVAPORATIVE COOLER WITH HEMP AND ABACA COOLING PAD MATERIAL

International Research Journal of Engineering and Technology (IRJET) e-issn: Volume: 04 Issue: 05 May p-issn:

Transcription:

ISSN 2395-1621 Design and Development of Combined Direct and Indirect Evaporative Cooling System #1 Pallavi B. Bedre, #2 H.U.Tiwari 1 pallavi.bedre@gmail.com 2 sharvay12 @rediffmail.com #12 Pimpri-Chinchwad College of Engineering, Pune, Maharashtra, India ABSTRACT Cooling is an essential part of air conditioning in hot climates. The issues of global warming, the natural resources depletion, and demand for environmentally-friendly systems have led to a growth in use of natural green resources instead of conventional systems. Two methods of evaporative cooling are normally used that is direct evaporative cooling & indirect evaporative cooling. Indirect evaporative cooling can be utilized to cool the air or other fluid with wet surface heat exchangers. This paper theoretically&experimental analyses the performance of combined direct and indirect evaporative cooling in hot and dry climate of Pune, India. Indirect cooling stage consisting of platefin type wet surface heat exchanger followed by direct cooling evaporative consisting of paper cellulose cooling pad is considered. Based on summer weather data of Pune, most frequently occurring condition of 35 C DBT and 50 % RH is selected for the analysis. Minimum temperature of direct evaporative cooling is 26.5 c achieved. 1KW of cooling capacity is achieved with COP of system 6.5. Experimentation of air temperature, relative humidity, cooling capacity, COP changes done at different air flow. ARTICLE INFO Article History Received :18 th November 2015 Received in revised form : 19 th November 2015 Accepted : 21 st November, 2015 Published online : 22 nd November 2015 Keywords- Indirect Evaporative, Direct Evaporative, Cooling Capacity, Cellulose pad. I. INTRODUCTION Cooling is an essential part of air conditioning in hot climates. The issues of global warming, the natural resources depletion, and demand for environmentallyfriendly systems have led to a growth in use of natural green resources instead of conventional systems. Two methods of evaporative cooling are normally used. Direct evaporative cooling (DEC) is the oldest, and the most widespread form of cooling systems. The principle of DEC is the conversion of sensible heat to latent heat. Indirect evaporative cooling can be utilized to cool the air or other fluid with wet surface heat exchangers. The surface of the cooling air passages is wetted by spray water, so that water film evaporates into the cooling air and decreases the temperature of the wetted surface. The primary air or other process fluid flows in the alternative passages and is cooled by indirect contact with the spray water film through the separating wall of the heat exchangers. Several research papers reviewed in the direction of indirect evaporative cooling, characteristic and effectiveness of indirect evaporative cooling. Evaporative cooling is a process of heat and mass transfer based on the transformation of sensible heat into latent heat. If the process develops in ideal adiabatic conditions, the dry bulb air temperature decreases as this transformation develops, increasing its humidity [1,2]. Evaporative cooling is classified as direct evaporative cooling and indirect evaporative cooling. A. Direct evaporative cooling system Direct evaporative systems, water evaporates directly in the air stream, producing an adiabatic process of heat exchange in which the air dry bulb temperature decreases as its humidity increases. Thus, the amount of heat transferred from the air to the water is the same as the one employed in the evaporation of the water [3]. B. Indirect evaporative cooing system Indirect evaporative coolers take advantage of evaporative cooling effects, but cool without raising indoor humidity and develop the indirect evaporative cooling prototype. Indirect evaporative air cooler passes the primary (product) air over the dry side of a heat/mass 2015, IERJ All Rights Reserved Page 1

exchanging wall, and the secondary (working) air over its opposite wet side. The wet side absorbs heat from the dry side by evaporating water and therefore cooling the dry side, while the latent heat of vaporizing water is given to the wet side air. Under the ideal operating condition, i.e., the product air travelling in a counter-flow manner to the working air and the two airstreams having a good balance of flow rates and an infinite contact area, the product air temperature on the dry side of the sheet will reach the wet bulb temperature of the incoming working air and the temperature of the working air on the wet side of the sheet will increase from its incoming dry bulb temperature to the incoming product air dry bulb temperature and be saturated [4]. However, practical systems are far from this ideal. It has been suggested that only 50% of the incoming working air wet bulb temperature can be achieved for a typical indirect evaporative cooling system. The indirect evaporative cooling systems can be considered as energy recovering systems if a return air stream from the room cooled is used as a secondary air stream in the process, taking advantage of either its lower temperature or humidity. It can also be used a mixed stream of outside and return air [1]. I. LITERATURE REVIEW AND OBJECTIVES E. Velasco Gómez et al. [1] describes the phenomenon of evaporative cooling is a common process in nature, whose applications for cooling air are being used since the ancient years. In fact, it meets this objective with low energy consumption, being compared to the primary energy consumption of other alternatives for cooling, as it is simply based in the phenomenon of reducing the air temperature by evaporating water on it. Chengqin Ren et. al. [2] describes developing an analytical model for the coupled heat and mass transfer processes in indirect evaporative cooling under real operating conditions with parallel/counter flow configurations. Conventionally, one-dimensional differential equations were used to describe the heat and mass transfer processes. In modelling, values of Lewis factor and surface wet ability were not necessarily specified as unity.shahramdelfani et al. [3] the performance of indirect evaporative cooling system (IEC) to pre-cool air for a conventional mechanical cooling system has been investigated for four cities of Iran. For this purpose, a combined experimental setup consisting of an IEC unit followed by a packaged unit air conditioner (PUA) was designed, constructed and tested. Two air simulators were designed and used to simulate indoor heating load and outdoor design conditions. The results indicate IEC can reduce cooling load up to 75% during cooling seasons. Also, 55% reduction in electrical energy consumption of PUA can be obtained. Aftab Ahmad et al. [4] investigated the performance of a 5-ton capacity indirect evaporative cooler under controlled environmental conditions (43.9 C dry-bulb temperature and 19.9% relative humidity) but for different air flow rates (631 to 2388 m3/h). The experimental results showed that the intake air energy efficiency ratio of the cooler varied from 7.1 to 55.1 depending on test conditions and air flow rate. The power consumption of indirect evaporative cooler was found to vary from 68.3 to 746 watts. Water consumption was found to vary between 0.0160 and 0.0598 m 3 /h. At full fan speed, an average of 58.7% of the total water consumed by indirect evaporative cooler was evaporated. Direct evaporative cooling systems can lower the temperature of air using the latent heat of evaporation. As a result, warm dry air is changed into cool moist air, but the energy in the air remains the same [5]. Existing direct evaporative cooling systems are 70 95% effective in terms of the incoming air s wet bulb temperature and only suitable for use in dry, hot climates, or rooms needing both cooling and humidification. Therefore increase humidity and decrease in temperature is occurs in direct evaporative cooling. Because of increase in humidity thermal comfort is not satisfy to control that parameter we use indirect evaporative cooling system. The objectives of the research are to investigate direct&indirect evaporative cooling systems. This system design and development for 1 kw output. The different variation of airflow to be considered for effective cooling system. II. METHODOLOGY AND DESIGN CONSIDERATIONS The objective of this work is to investigate the performance of direct &indirect evaporative cooling for the output temperatureof human thermal comfort [4].This system is focus on heat exchanger, material, flow direction at incoming working air wet bulb temperature can be achieved for a typical indirect evaporative cooling system. The study will be conducted using design and experimental apparatus. The schematic of indirect evaporative cooling is shown in figure Fig.1 in which ambient air is forced on Cellulose pad followed by tube and fin heat exchanger is new design consideration.. Fig.1 indirect evaporative cooling This process is called indirect and is mainly used in those applications where no humidity addition is allowed in the supply air, as well as no risks of contamination, as no mass exchange is permitted between the two air streams. A. Assumptions The following assumptions are made in IEC analysis. 1) Surface wetting in DEC is complete. 2) Miscellaneous load such as make up water addition, pump heat gain and heat gain from ambient are neglected. 3) Heat and mass transfer coefficients are constant. 2015, IERJ All Rights Reserved Page 2

4) Temperature and enthalpy at air-water interface is represented by a constant average temperature over the entire surface. B. Material for Direct Evaporative cooling Material Selected for evaporative pads: Cellulose pad: Sheet thickness 0.2mm Manufacturer: M/S Munters Aw=Vp.As Where, As=wetted surface area of pad per unit volume (m 2 /m 3 ) = 70 m 2 /m 3 for selected cellulose pad Vp = Volume of the pad Aw= 70 x (0.3x0.3x0.3) =1.89 m 2 Fig. 3 Cellulose pad area Fig. 2CELdek 7090-15 evaporative cooling pad manufactured by Munters CELdek 7090-15 evaporative cooling pad is used in systems where high efficiency cooling is required & shown in fig. 2. It can be used for many different cooling purposes but is particularly suitable for cooling of livestock buildings and greenhouses. The Green stripe pad consists of specially impregnated and corrugated cellulose paper sheets with different flute angles, one steep (60 deg) and one flat (30 deg) that have been bonded together. This unique design yields a cooling pad with high evaporation efficiency while still operating with a very low pressure drop. In addition scaling is kept to a minimum and no water carryover occurs due to the fact that the water is directed to the air inlet side of the pad. This is where most of the evaporation takes place. For better efficiency of DEC, we select the 300mm thickness of pad at average velocity of 4m/s, which derives 93% efficiency of cooling. C. Design Considerations For Pune, Frequent ambient condition is DBT =35ºC and 50% RH.This is used as inlet condition for design of IEC system. The properties of air based on this condition are as below; DBT-35ºC, RH-50% WBT-23ºCEnthalpy of intake air h in =81 KJ/kg of dry air Temperature reduction achievable in DEC is given by= (DBT-WBT) X Efficiency of pad = (35-23)x0.93=11.96ºC Thus achievable temperature=35-11.16=23.84ºc Corresponding values of RH from Psychometric chart is 92% and enthalpy as 69 KJ/Kg of dry air. So air condition before and after the evaporative cooling pad is: Before DBT as 35ºC and WBT as 23ºC After DBT as 23.84ºC WBT as 23ºC, Enthalpy at the outlet of evaporating pad is h out =69 KJ/kg of dry air D. Pad Material and geometry Total wetted surface area(m 2 ) of pad is given by, E. Airflow requirement: The maximum cooling load is obtained with the equation as: Qc=m(h in -h out ) -------Qc in KW 1=m(81-69) m=0.083kg/s F. Amount of Water Evaporated in system: Evaporation heat of water=2270 KJ/kg Amount of water evaporated per second (M evap ) during cooling process is given by equation, Qc=2270x M evap 1 = 2270x M evap M evap = 0.00044 kg/s Which is equivalent to 26 ml of water per minutes, So while selecting feed water pump this additional quantity need to be considered. To get comfortable RH value lesser, 50% of fresh ambient air & DEC output air mixture is used. m 1 h 1 +m 2 h 2 =m 3 h 3 Where, m 1 = Ambient air m 2 =outlet of DEC air m 3 =Mixture air (m 1+ m 2 ) (0.5x81)+ (0.5x65.5) = (0.5+0.5) h 3 h 3 =73.25KJ/Kgof dry air RH=69%, T 3 =28.8 ºC III. EXPERIMENTAL SETUP AND TESTING To evaluate performance of DEC/IEC system in defined ambient conditions and in order to investigate effect of operational parameters, an experimental setup was designed, constructed & tested as shown in Fig. 4. Fig. 4 Experimental Setup of DEC/IEC system 2015, IERJ All Rights Reserved Page 3

Test setup consists of IEC/DEC unit including a 300 mm thick cellulose pad as DEC unit, a heat exchanger in which water as cooling media as IEC unit, a water circulating pump. Water is distributed over Cellulose DEC pads using proper perforated plate which allows uniform and continuous water flow to wet. Specifications of this heat indirect exchanger have been presented in Table 1. TABLE I HEAT EXCHANGER SPECIFICATION 1 Heat Exchanger type Tube and Fin 2 Size(mm) 210X200X40 3 Fin density(per 100mm) 75 fins 4 Effective frontal Area (mm 2 ) 356 Fig. 6 Cooling capacity of IEC system Temperature and relative humidity (RH) are measured in the following positions: Air temperature and RH after the DEC unit Air temperature after the IEC unit in primary flow. Water temperature of DEC water tank (above DEC pad) Water temperature of Heat Exchanger inlet and outlet pipes. The relative humidity was measured by the sensors in the range of 10% to 95% and the accuracy and resolution were 3% and 0.01% respectively.also air flow, current was measured at the outlet of IEC heat exchangers. IV. RESULT & CONCLUSIONS Results show that the air temperature drops to 26.5ºC from 35ºC. Relative humidity at the outside of indirect heat exchanger is increased to 73.8% from 50% of ambient air.from observations,rh value is reduced by 23.8% in IEC than DEC outlet at 450m 3 /hr of airflow. This is achieved with 50% of ambient air mixing at IEC heat exchanger. Study also reveals the air temperature and relative humidity are less at less air flow. The output cooling capacity is achieved is close 1KW with air flow at 350 m 3 /hr. The graph represent the mass flow rate Vs Temperature. Fig. 7 COP of IEC system Fig. 8 relative humidity changes in DEC & IEC Fig.5 Mass flow rate changes with temperature outlet of IEC. The fig.5 shows that as the mass flow rate increases the temperature drop is also increases. After IEC the temperature dropped by 1 ºC as water temperature is below than air temperature. Fig. 6 shows that mass flow rate increases the cooling capacity of IEC is increases. Fig. 7 shows that the mass flow rate increases the COP of that system is increases. The fig. 8 shows that as the mass flow rate increases the RH of DEC & IEC increases.the effectiveness values of DEC and IEC varies with increase in air flow form 100 m 3 /hr to 450 m 3 /hr. Combined indirectdirect evaporative cooling systems can be beneficial in hot and dry climates and the inlet temperature of air can be reduced below its wet bulb temperature. Thus the normal operation of DEC can be extended into humid atmosphere and can provide comfort in most of the summer season. 2015, IERJ All Rights Reserved Page 4

ACKNOWLEDGMENT Thanks to H.U.Tiwari for his valuable guidance and inspiration throughout this work. Sincere thanks to Mr. Parthasarthi G. and Mr.K. Parmeshwar for his support in experimental evaluation. REFERENCES [1] E. Velasco Gómez, F.C. Rey Martínez, A. Tejero González The phenomenon of evaporative cooling from a humid surface as an alternative method for air-conditioning, INTERNATIONAL JOURNAL OF Volume 1, Issue 1, 2010 pp.69-96. [2] Chengqin Ren, Hongxing Yang, An analytical model for the heat and mass transfer processes in indirect evaporative cooling with parallel/counter flow configurations, International Journal of Heat and Mass Transfer 49 (2006) 617 627. [3] ShahramDelfani, JafarEsmaeelian, HadiPasdarshahri, Maryam Karami, Energy saving potential of an indirect evaporative cooler as a precooling unit for mechanical cooling systems in Iran, Energy and Buildings 42 (2010) 2169 2176.Aftab Ahmad, ShafiqurRehman, Luai M. Al-Hadhrami, Performance evaluation of an indirect evaporative cooler under controlled environmental conditions, Energy and Buildings 62 (2013) 278 285. [4] Eloy Velasco Gómez, Ana Tejero González, Francisco Javier Rey Martínez Experimental characterisation of an indirect evaporative cooling prototype in two operating modes, Applied Energy 97 (2012) 340 346. [5] X. Zhao, Shuli Liu, S.B. Riffat Comparative study of heat and mass exchanging materials for indirect evaporative cooling systems, Building and Environment 43 (2008) 1902 1911. [6] Ana Tejero-González, Manuel Andrés-Chicote, Eloy Velasco-Gómez, Francisco Javier Rey-Martínez Influence of constructive parameters on the performance of two indirect evaporative cooler prototypes, Applied Thermal Engineering 51 (2013) 1017-1025. [7] GhassemHeidarinejad, MojtabaBozorgmehr, ShahramDelfani, JafarEsmaeelian Experimental investigation of two-stage indirect/direct evaporative cooling system in various climatic conditions, Building and Environment 44 (2009) 2073 2079. [8] Ala Hasan, Indirect evaporative cooling of air to a sub-wet bulb temperature, Applied Thermal Engineering 30 (2010) 2460-2468. [9] M. Shariaty-Niassar, N. Gilani, An Investigation of Indirect Evaporative Coolers, IEC With Respect to Thermal Comfort Criteria, Iranian Journal of Chemical Engineering Vol. 6, No. 2 (Spring), 2009. 2015, IERJ All Rights Reserved Page 5