Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev

Similar documents
Installation Guide for AL400ULM. Multi-Output Access Control Power Supply Charger

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC.

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC.

AL400ULACM AL600ULACM - 4 amp - 12VDC or 6 amp. - Fused Outputs - Fused Outputs

ACSI Series 1550K-MD and 1550-MD Motor Drive Electric Latch Retraction

Series. Access Power Controllers. Installation Guide

Installation Guide for models:

Installation Guide for models:

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev

AL600ULADA. NAC Power Extender. Installation Guide

For a red enclosure add an R suffix to the part # e.g. eflow4na8r. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

For a red enclosure add an R suffix to the part # e.g. eflow4na8dr. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

AL800ULADA. NAC Power Extender. Installation Guide

ACM8 & ACM8CB. Access Power Controllers Installation Guide. - Fused Outputs - Fused Outputs. - PTC Outputs - PTC Outputs. Models Include: Rev.

AL600ULX Series. Power Supply/Charger. Installation Guide

10-175UL INSTALLATION. Power Supply UL. Access Control Power Supply/Charger. Installation and Specifications Manual

- Four (4) Fused Outputs - Four (4) PTC Outputs. - Eight (8) Fused Outputs - Eight (8) PTC Outputs

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

Rack Mount Series Installation Guide

- 4 12VDC or 24VDC VDC or 24VDC - Eight (8) Fused Outputs - Eight (8) PTC Outputs. Installing Company: Service Rep.

- Four (4) Fused Outputs - Four (4) PTC Outputs. - Eight (8) Fused Outputs - Eight (8) PTC Outputs

Access Power Controllers with Power Supplies

ACM4 Series UL Listed Sub-Assembly Access Power Controllers

ACM8 Series UL Listed Sub-Assembly Access Power Controllers. Installation Guide. ACM8 - Eight (8) Fuse Protected Outputs

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information)

1 Description. 2 Specifications. HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN

APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES

RPSMLR2 RPSMLR2BB. Panic Device Power Controller Installation Guide LISTED. Rev

SP-1000X. Panic Device Power Controller Installation Guide. Rev

AL1002ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev X

AL1042ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev X

TECHNICAL DATA OBSOLETE

AL1042ULADA. NAC Power Extender. Installation Guide (See Application Guide for additional information) Rev

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option

more than just power! Altronix is the professional security industry s leading manufacturer

IP Access FACP Adapters. Installation Guide. Entrada2DMK - IP Access FACP Adapter Kit. Kit Includes: Entrada2DMR - IP Access FACP Receiver

Securitron Magnalock Corporation S. 51 st St., Ste. 102 Phoenix, AZ Phone: (800) MAGLOCK

POWERPATH PS-8 (105531) PS-8E (100263) PS-6 (105530) PS-6E (100262)

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual

GENERAL STANDARD FEATURES. ISO-9001 Engineering and Manufacturing Quality System Certified to International Standard ISO-9001 PATENT PENDING

4100U City and Relay Cards Installation Instructions

June 10, 2002 DF C S2424

PSN-1000 & PSN 1000(E) Installation Manual

PDD-8PCI. Power Distribution Board With Supervised Interface. Installation and Specifications Manual

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels

Remote NAC Power Supply D7038

July 14, 1999 DF C-100.

Cautions and Warnings. Introduction 4009 NAC POWER EXTENDER

MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL RELEASE DEVICES TEST WEEKLY TO ASSURE PROPER OPERATION OF RELEASE DEVICE/CONTROL PANEL

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

Installation Instructions. PS902 Power Supply. These instructions cover the following parts: PS902 Power Supply Specifi cations:

Booster Power Supply Manual

FIREFORCE 8 NOTIFICATION APPLIANCE CIRCUIT EXPANDER INSTALLATION & OPERATION MANUAL

MR-2602 Two Zone Fire Alarm Control Panel

AL602ULADA AL802ULADA AL1002ULADA

MODEL B2 INSTALLATION MANUAL

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL

FireNET Plus Wiring Instructions

Conventional Releasing Control Panel

Power Supplies. Overview

Specification/ Data Sheet

I TS-12 1 Y K DO WHAT THEY DON T. Model. INSTALLATION lnstrljctlons. FIRE BURGLARY lnstrumentsrn INC.

TECHNICAL DATA SHEET CONVENTIONAL FIRE ALARM SYSTEMS Conventional Fire Alarm Control Panel

30.45 Electric Release PDRP-2001

"SS90" SERIES CONTROLS MODEL C INSTALLATION MANUAL

THE "SS90" SERIES RELEASE DEVICES MODEL B2 INSTALLATION MANUAL

WARNING. Installation Tip: Try out this unit before installing onto a fire door system. Test and learn the release INTRODUCTION

TECHNICAL DATA. multi-hazard. model vfr400. Release Control Panel 290a. January 16, 2014

Installation Manual CFP-105. Fire Alarm Control Panel. Version 1.0

RELEASE DEVICE CONTROLS

This wiring diagram describes circuit connections for all models of the Series Quaestor-SZU Releasing Fire Control

ACSI AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1089, REV. F

Duct smoke housings, 4-wire D341/D341P and D342/D342P

M O D E L S F I R E G A R D M C V ADVANCE FIRE CONTROL RELEASE DEVICE

Wiring Instructions for the 2900 Series FIREGUARD Combination Door Closer-Holder and Releasing Device with Integral Smoke Detector

Commercial and Light Industrial Fire Alarm Control Panel

Public Safety DAS Annunciator Panel

Remote Booster Power Supplies

Firefly II Multi Voltage RELEASE DEVICES. Firefly II & IIB-MV INSTALLATION MANUAL

RELEASE DEVICES RELEASE DEVICE-WPS MODELS A/B INSTALLATION MANUAL U.L. LISTED CANADIAN LISTED CSFM: :100 GENERAL DESCRIPTION:

Addressable NAC Output Module D327A

TrueAlert Addressable Notification Appliances

1200-HCM DIN RAIL MOUNTING FIRE SYSTEM MODULE Fire Detection & Extinguishant Control A R T PATOL LIMITED SUPPLY FAULT SOUNDER

Supplement to The PDRP-1001/PDRP-1001A/PDRP-1001E Deluge Preaction Control Panel Manual

Release Control Fire Alarm Systems

RDM LOCK G Series Electromagnetic Lock. Listings. Standard Features. Ordering Information:

PDD-FT-3. Fire Panel Interface With EOL Trigger. Installation and Specifications Manual

Fire Safety. Installation Instructions Model SMB-2 Main Control Board OPERATION INSTALLATION

INSTALLATION GUIDE XR5FC AND XR5SL COMMERCIAL FIRE PANELS

PS1240x Series Dual Voltage Access Control Power Supply Systems Operating and Installation Instructions Rev D.01

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

TrueAlert Addressable Notification

1. POWERPATH Operation

LiftMaster 300 Windsor Drive Oak Brook, IL LiftMaster.com

FireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel

LifeAlarm Fire Alarm Controls

MANUAL RESET ALARM RELEASE

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906

Transcription:

Installation Guide for AL600ULM Multi-Output Access Control Power Supply Charger Rev. 091800 1

AL600ULM - Multi-Output Access Control Power Supply/Charger Overview: The AL600ULM multi-output access control power supply/charger is specifically designed for use with access control systems and accessories. The AL600ULM converts a 115 VAC / 60Hz input into five individually regulated 12VDC or 24VDC power limited outputs (see specifications). Each output will route power to a variety of access control hardware devices including Mag Locks, Electric Strikes, Magnetic Door Holders, etc. These outputs will operate in both fail-safe and fail-secure modes. Controlled trigger input is achieved through normally open (N.O.) or normally closed (N.C.) supervised input or the polarity reversal from an FACP (Fire Alarm Control Panel). A form C dry output relay enables HVAC Shutdown, Elevator Recall or may be used to trigger auxiliary devices. Specifications: UL Listed Fire and Access Control Power Supply (UL1481, UL294). CSFM - California State Fire Marshal Approved. MEA - NYC Department of Buildings Approved. NFPA 72 compliant. Class 2 rated. Input 115VAC / 60Hz, 1.9 amps. Field selectable 12VDC or 24VDC. 6 amps continuous supply current at 12VDC / 24VDC. Five (5) individual power limited outputs. Current limit is 2.5 amps @ 12VDC or 24VDC per output. Filtered and electronically regulated outputs, 100mV peak output voltage ripple. Maximum charge current.7 amps. Built-in charger for sealed lead acid or gel type batteries. Automatic switch over to stand-by battery when AC fails. Thermal and short circuit protection with auto reset. AC input and DC output indicators. s indicate condition of power outputs. Power & input trigger s. AC fail supervision (form "C" contact). DC output supervision (form C contact). Battery fail and battery presence supervision (form "C" contact). Fire Alarm Panel or Access Control System trigger inputs. (N.O. or N.C. supervised trigger input and polarity reversal trigger input (4mA draw from FACP). Power fail supervision relay (form C contact rated 1amp @ 28VDC/115VAC). Output relay energizes when unit is triggered (form C contact rated 1amp @ 28VDC/115VAC). Power supply is complete with enclosure, cam lock, transformer and battery leads. Enclosure accommodates up to two (2) 12AH batteries. Enclosure dimensions: 15.5"H x 12"W x 4.5"D Voltage Output Settings: Output 12VDC 24VDC Switch Position SW 1 Closed, SW 2 Open SW 1 Open, SW 2 Closed 2 IIAL600ULM-Rev. 091800 Altronix is not responsible for any typographical errors. Product specifications are subject to change without notice.

Stand-by Specifications: Output 4 hr. of Stand-by & 24 hr. of Stand-by & 60 hr. of Stand-by & 5 Minutes of Alarm 5 Minutes of Alarm 5 Minutes of Alarm 12VDC / 40 AH Battery Stand-by = 6.0 amps Stand-by = 1.0 amps Stand-by = 300mA Alarm = 6.0 amps Alarm = 6.0 amps Alarm = 6.0 amps 24VDC / 12 AH Battery Stand-by = 200mA Alarm = 6.0 amps 24VDC / 40 AH Battery Stand-by = 6.0 amps Stand-by = 1.0 amps Stand-by = 300mA Alarm = 6.0 amps Alarm = 6.0 amps Alarm = 6.0 amps Installation Instructions: The AL600ULM should be installed in accordance with The National Electrical Code and all applicable Local Regulations. 1. Mount the AL600ULM in desired location. It is recommended to first review the following tables for screw terminals, switch selection and status indications. This will greatly facilitate installation hook-up. Carefully review: Voltage Output Settings (pg. 2) Terminal Identification Table (pg. 5) Stand-by Specifications (pg. 3) Typical Application Diagrams (pgs. 6-7) Diagnostics (pgs. 4-5) Fig. 1 CAUTION: De-energize unit prior to servicing. For continued protection against fire hazard replace fuse with the same type and rating 3.5A, 250V. Replace fuse cover before energizing. Door AL600ULXB Switch Position: 24VDC = SW1 OPEN 12VDC = SW1 CLOSED + DC --- BKLYN, N.Y. 11220 24V - OPEN 12V - CLOSED AC BAT + BAT --- DC OFF ON L G N BAT FAIL AC FAIL 115 power mains (non-power limited) Battery and AC Supervision Circuit (power limited). Use separate knockout. Keep 1/4" away from non power limited wiring NEG1 NEG2 NEG3 NEG4 NEG5 Wire Strap (from Enclosure to Door) DC Output to devices (power limited) Fire Alarm Interface 1 2 3 4 5 POS DC OUTPUT (ALARM) 6 7 8 9 10 POS DC OUTPUT (STANDBY) DRY OUTPUT FAIL Battery connection (non power limited) Battery 1 Battery 2 3

2. Set AL600ULM to the desired DC output voltage by setting the switches to the appropriate positions (refer to voltage output settings). Note: It is good operating practice to measure and verify output voltage before connecting devices to ensure proper operation of equipment. 3. Connect AC power (115VAC 50/60Hz to terminals marked [L, G, N]. Use 18 AWG or larger for all power connections. Secure green wire lead to earth ground (Fig. 1, pg. 3). Use 18 AWG or larger for all power connections (Battery, AC input). Keep power limited wiring separate from non-power limited wiring (115VAC / 60Hz Input, Battery Wires). Minimum.25 spacing must be provided. 4. Connect fail-secure type locking hardware (e.g. door strikes and electronic dead bolts) positive leads to terminals marked [1 thru 5 POS DC OUTPUT (ALARM)] (Fig. 1, pg. 3) and the negative leads to terminals marked [NEG 1 thru NEG 5] (Fig. 1, pg. 3). 5. Connect fail-safe type locking hardware (e.g. mag locks, door strikes and door holders) positive leads to terminals marked [6 thru 10 POS DC OUTPUT (STAND-BY)](Fig. 1, pg. 3) and negative leads to terminals marked [NEG 1 thru NEG 5] (Fig. 1, pg. 3). 6. To trigger the AL600ULM from a FACP connect signaling circuit of FACP to inputs marked [NEG ] and [POS ] input (Fig. 1, pg. 3). Polarity is shown in alarm condition. For latching fire alarm interface (Fig. 5, 6, 7, pg. 7). Note: A 2.2K EOL must be installed across terminals marked [] or MOM5 will remain in an alarm condition. 7. To trigger the AL600ULM using a supervised dry contact connect the 2.2K resistor in series for a N.C. trigger input and in parallel for N.O. trigger input (Fig. 2, pg. 6). 8. Connect auxiliary devices triggered by the AL600ULM to the terminals marked [DRY OUTPUT N.O. & C] for normally open output or terminals marked [DRY OUTPUT N.C. & C] for normally closed output (Fig. 1, pg. 3). Note: This relay will energize when the AL600ULM is triggered. 9. For Access Control applications batteries are optional. When batteries are not used a loss of AC will result in the loss of output voltage. Batteries must be lead acid or gel type if used. Connect one (1) 12VDC battery to terminals marked [+ BAT -] (Fig. 1, pg. 3) for 12VDC operation. Use two (2) 12VDC batteries connected in series for 24VDC operation. (Battery leads included). 10. It is required to connect supervisory trouble reporting devices to outputs marked [AC FAIL, BAT FAIL] (Fig. 1, pg. 3) and [Power Fail] (Fig. 1, pg. 3) supervisory relay outputs marked [N.C., C, N.O.] to appropriate notification devices. Use 22 AWG to 18 AWG for AC Fail & Low/No Battery reporting. Cut AC delay jumper to delay report 6 hours (Fig. 1, pg. 3). Maintenance: Unit should be tested at least once a year for the proper operation as follows: Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper voltage level (see power supply output specifications table). Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage at the battery terminals and at the board terminals marked [- BAT +] to insure that there is no break in the battery connection wires. Note: Maximum charge current under discharge is 1.25 amps. Note: Expected battery life is 5 years, however it is recommended changing batteries in 4 years or less if necessary. Diagnostics: AL600ULB - Power Supply Red (DC) Green (AC) Power Supply Status ON ON Normal operating condition. ON OFF Loss of AC, Stand-by battery supplying power. OFF ON No DC output. Short circuit or thermal overload condition. OFF OFF No DC output. Loss of AC. Discharged battery. 4

MOM5 - Output Module ON OFF Power (Green) Normal operation. Power failure. Trigger (Green) Input is triggered (alarm condition). No input trigger (non-alarm condition). Outputs (Red) Output tripped due to a short circuit or overload condition. Normal operation. Terminal Identification: AL600ULB - Power Supply Terminal Function/Description Legend L, G, N Connect 115 VAC to these terminals: L to hot, N to neutral, G to ground. + DC - 12VDC / 24VDC @ 6 amps continuous non-power limited output. AC FAIL Used to notify loss of AC power, e.g. connect to audible device or alarm panel. Relay C, N.C., N.O. normally energized when AC power is present. Contact rating 1 amp @ 28VDC. AC or brownout fail is reported within 1 minute of event. To delay reporting of up to 6 hrs., cut AC delay jumper and reset power to unit. BAT FAIL Used to indicate low battery condition, e.g. connect to alarm panel. Relay normally N.O., N.C., C energized when DC power is present. Contact rating 1 amp @ 28VDC. A removed battery is reported within 5 minutes. Battery reconnection is reported within 1 minute. Low battery threshold: 12VDC output threshold set @ approximately 10.5VDC, 24VDC output threshold set @ approximately 21VDC. - BAT + Stand-by battery connections. Maximum charge rate.7 amp. MOM5 - Output Module Terminal Legend Function/Description - DC INPUT + 12 or 24VDC from power supply. Dry normally open (N.O.) or normally closed (N.C.) supervised (2.2K EOL resistor) input trigger. A short or open circuit will transfer power from terminals marked [POS. DC OUTPUT (STAND-BY)] to terminals marked [POS DC OUTPUT (ALARM)]. - INPUT + Wet (5-30VDC) input trigger. Applying voltage to these terminals in the polarity shown will transfer power from terminals marked [POS. DC OUTPUT (STAND-BY)] to terminals marked [POS DC OUTPUT (ALARM)] (e.g. fire alarm control panel indications circuit).. NEG 1 THRU NEG 5 Supplies constant negative voltage. POS DC OUTPUT Supplies positive voltage when dry trigger input or fire (ALARM) 1-5 alarm wet trigger input is applied. POS DC OUTPUT Supplies positive voltage in normal condition. (STAND-BY) 6-10 Power is removed when dry trigger input or fire alarm wet trigger input is applied. N.C., C., N.O. When the MOM5 is triggered the C and N.O. terminals will close and the DRY OUTPUT C and N.C. terminals will open. This output is used to trigger auxiliary devices. (e.g. HVAC Shutdown, Elevator Recall etc.) N.C., C, N.O. Form C contacts used for reporting no voltage is present at [-- DC input +] FAIL terminals. Under normal conditions, terminals N.O. and C are open, N.C. and C are closed. A loss of power causes N.O. and C to close and N.C. and C to open. 5

Typical Application Diagrams: Fig. 2 AL600ULM module shown with wet and/or dry normally closed trigger inputs (Non-Latching): AL600ULM module shown with wet and/or dry normally open trigger inputs (Non-Latching): N.C. INPUT FROM FACP OR ACCESS N.O. INPUT FROM FACP OR ACCESS Fig. 3 - Two (2) or more AL600ULM modules shown with wet and/or dry normally closed trigger inputs (Non-Latching): (--) N.C. INPUT FROM FACP OR ACCESS MOM5 MULTI-OUTPUT MODULE DRY OUTPUT FAIL DRY OUTPUT FAIL TO INPUT OF NEXT MOM5 Fig. 4 - Two (2) or more AL600ULM modules shown with wet and/or dry normally open trigger inputs (Non-Latching): (--) N.O. INPUT FROM FACP OR ACCESS DRY OUTPUT FAIL DRY OUTPUT FAIL TO INPUT OF NEXT MOM5 6

Fig. 5 AL600ULM module shown with with wet and/or dry normally closed fire alarm trigger inputs (Latching with Manual Reset): Typical Application Diagrams: AL600ULM module shown with with wet and/or dry normally open fire alarm trigger inputs (Latching with Manual Reset): OUTPUT OUTPUT DRY OUTPUT FAIL N.C. INPUT OUTPUT DRY OUTPUT FAIL N.O. INPUT OUTPUT N.O. RESET N.C. RESET Fig. 6 - Two (2) AL600ULM modules shown with wet and/or dry normally closed fire alarm trigger inputs (Latching with Manual Reset): N.C. INPUT DRY OUTPUT FAIL DRY OUTPUT FAIL N.O. RESET Fig. 7 - Two (2) AL600ULM modules shown with wet and/or dry normally open fire alarm trigger inputs (Latching with Manual Reset): N.O. INPUT DRY OUTPUT FAIL DRY OUTPUT FAIL N.C. RESET 7

Enclosure Dimensions: 15.5 H x 12 W x 4.5 D 2.25" 3.68" 4.56" 12" 1.22" 1.22" 4.5".875" 9.97" 1.3" 1.22" 1" 1" 2" 6.625" 13.25" 13.53" 3.5" 2.2" 1.25" 1" 15.5" 1.22" 2.25" 3.68" 4.56" MEMBER 8 Altronix Corp. 140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056 web site: www.altronix.com, e-mail: info@altronix.com, Lifetime Warranty, Made in U.S.A.